1. Introduction
Line commuted converter-based high voltage direct current (LCC-HVDC) transmission systems have the advantages of long transmission distance and large transmission capacity. Thus, LCC-HVDC is widely used to transmit renewable energy [
1,
2,
3]. Thyristors without self-turn-off capability are used as converter devices in LCC-HVDC. Inverter stations are prone to commutation failures following faults in the receiving-end grid. Commutation failures cause the AC bus voltage of the rectifier station to decrease first, and then increase, which produces AC transient overvoltage in the sending-end grid. The AC transient overvoltage may cause the renewable energy generation to be disconnected from the grid, and even threaten the stable operation of the sending-end grid. Both the sending-end grid and LCC-HVDC are faced with a serious threat due to AC transient overvoltage.
The suppression of AC transient overvoltage has gained a lot of attention. The authors of [
4] pointed out that DC current overshooting in the rectifier station leads to reactive power surplus and AC transient overvoltage in the sending-end grid when commutation failure occurs in the inverter station. The transient reactive power characteristics of the sending-end and receiving-end grid during commutation failures and their effects on the AC transient overvoltage are analyzed [
5]. The authors of [
6] provided an expression for the peak value of AC transient overvoltage. The influencing factors of feeder AC transient overvoltage have been quantitatively analyzed [
7]. The existing studies have focused on the effect of the change in reactive power consumption of the rectifier station due to the change in active power caused by the commutation failure. The direct effect of active power on the AC bus voltage has thus far been neglected in the literature.
There are two main types of methods used for the suppression of AC transient overvoltage. Reactive power compensation is the more effective way. Reactive power compensation can reduce the reactive power compensated by the filter, and mitigate reactive power surplus during low-voltage periods. Additionally, during overvoltage conditions, reactive power compensation devices absorb a portion of the reactive power, providing a significant amount of capacitive reactive power to the grid. Reactive power compensation devices help to mitigate excess reactive power at the rectifier station, thereby suppressing the AC transient overvoltage. Commonly used reactive power compensation devices include the static var compensator (SVC), static synchronous compensator (STATCOM), and phase angle regulators. The regulator capacity is selected according to the size of the transient overvoltage [
8]. Transient overvoltage suppression strategies that coordinate the converter station filter, synchronous compensator, and synchronous generator in the near zone of the converter station have been proposed [
9,
10]. Additionally, an optimization control model has been constructed to reduce the AC transient overvoltage by coordinating a synchronous compensator and a static var compensator [
11,
12]. Dynamic reactive power compensation can suppress the AC transient overvoltage, but the investment cost is high and the coordination between reactive power compensation devices is complicated. The utilization of reactive power compensation to prevent AC transient overvoltage is limited. However, the substantial reactive power consumption of LCC-HVDC incurs high costs when installing dynamic reactive power compensation devices, and it also escalates the coordination complexity between the converter station and dynamic reactive power compensation devices. Therefore, current research often involves optimizing the control system of LCC-HVDC to suppress transient overvoltage at the rectifier station.
Suppressing the AC transient overvoltage by optimizing the control system of LCC-HVDC is a hot spot in current research. A parameter optimization method to suppress the AC transient overvoltage according to the sensitivity relationship between control parameters and the AC transient overvoltage has been proposed [
13]. The parameters of the voltage-dependent current order limiter (VDCOL), commutation failure prevention control, and constant current control (CCC) have been optimized to reduce the reactive power exchanged between the rectifier station and the grid during the fault period [
5,
14]. In one study, the reference value of the trigger angle of the rectifier station was improved to suppress the transient overvoltage according to the relationship between the reactive power consumed by the rectifier station, the DC voltage, and the DC current [
15,
16]. The trigger angle can also be determined according to the load flow of the sending-end grid and the relationship between the reactive power and voltage [
17].
The sending-end grid and rectifier station are connected by the power flow. The variation in the AC bus voltage of the rectifier station changes the active and reactive power of the rectifier station, which further affects the AC bus voltage. The AC-DC system coupling is aggravated in the sending-end grid with a small short-circuit ratio, because the change in the active power has a greater effect on the AC bus voltage of the rectifier station. Coupling AC and DC systems influence each other through line connections. The authors of [
18] analyzed the mutual influence among control parameters of AC and DC systems under normal operation, while the authors of [
19] examined the interaction characteristics of AC and DC systems from the perspectives of large and small disturbances, providing a comprehensive overview of the causes, phenomena, and consequences of various interactions. The authors of [
20] analyzed the coupling characteristics between LCC-HVDC and the weak sending-end grid, indicating that large-scale power transfer resulting from LCC-HVDC faults can lead to voltage instability or even transient instability in power grids. The authors of [
21] established quantitative evaluation indices for the coupling between AC and DC systems in multi-infeed DC transmission systems based on electrical quantities, such as the inter-tie impedance between converter stations, DC power, and short-circuit capacity. The authors of [
22] analyzed the influencing factors of transient overvoltage, clarifying the transient voltage characteristics and dominant influencing factors under AC and DC system faults and categorizing the influencing factors of transient overvoltage in the sending-end grid into three types: LCC-HVDC control parameters, the sending-end grid, and the receiving-end grid faults. The authors of [
23] pointed out that during the generation of transient overvoltage in the sending-end grid, changes occur in variables such as the rectifier station AC bus voltage, the reactive power consumption of the rectifier station, and the DC current. These changes trigger rapid responses from relevant controllers in LCC-HVDC to maintain grid stability. Conversely, the controlled electrical quantities then influence the control process, forming a cyclic relationship. The AC transient overvoltage is suppressed by adjusting the reactive power consumed by the rectifier station in the existing method. Because the active and reactive power of LCC-HVDC is coupled, the adjustment of reactive power inevitably changes the active power. The variation in active power leads to a change in AC bus voltage, which affects the active and reactive powers. Neglecting the AC-DC system coupling at the rectifier station could affect the accuracy of transient overvoltage suppression.
In this study, the AC transient voltage characteristics of the sending-end grid of LCC-HVDC under commutation failure are analyzed with consideration for the joint influence of active and reactive power changes. Additionally, the impact of AC-DC system coupling on the AC transient overvoltage is explored. The expression of the AC bus voltage of the rectifier station is derived to depict the relationship between the AC bus voltage and DC current under the action of AC-DC system coupling. A dynamic model of the AC bus voltage is established considering AC-DC system coupling. Then, an improved suppression method for AC transient overvoltage considering the AC-DC system coupling is proposed, which is realized by setting the command value of the DC current of the rectifier station based on model prediction control. The effectiveness of the proposed method is verified by the standard test model of the LCC-HVDC.
2. Transient Voltage Characteristics of Sending-End Grid
The structure of LCC-HVDC, which mainly includes converter stations and a DC transmission line, is shown in
Figure 1. The converter station includes a rectifier station and an inverter station. The rectifier and inverter stations are connected through DC transmission lines. Filters are equipped in the DC and AC sides of converter stations. A hierarchical control structure is adopted in LCC-HVDC. The main control level sends the commands from the dispatching center to the pole control level after calculating and processing. The pole control level sends the control signal to the control units of the converter valves. Then, the normal phase change is realized through controlling the conductance of the converter valves. The minimum trigger angle control and CCC are deployed in the rectifier station. The constant current control, current error control (CEC), and constant extinction angle control (CEAC) are deployed in the inverter station. Both rectifier and inverter stations are configured with VDCOL [
24]. During the steady-state operation of LCC-HVDC, the rectifier station is generally controlled by CCC, and the inverter station is controlled by CEAC [
25]. During commutation failures of the inverter station, the rectifier station typically utilizes CCC and VDCOL to maintain the DC current.
A commutation failure occurs when a valve expected to turn off fails to regain the blocking ability under reverse voltage or cannot complete the turn-off process, which causes an inverse commutating phase from the valve expected to turn off to the valve expected to turn on. The DC current changes under the combined action of the control of the inverter and rectifier stations, which results in fluctuations in active power and reactive power consumption at the rectifier station. The power fluctuations change the AC bus voltage of the rectifier station, as shown in
Figure 2. The transient of LCC-HVDC after commutation failure can be divided into four stages.
Stage 1: Both valves of the upper and lower bridge arms conduct simultaneously after a commutation failure. The commutation failure leads to a short circuit on the DC side. The DC voltage at the inverter station reduces, thus resulting in a rapid surge in DC current. The sudden surge in DC current causes a slight uptick in the AC bus voltage of the rectifier station because of the delayed response of the rectifier station controllers.
Stage 2: The command value of the DC current decreases as the DC voltage decreases under the action of VDCOL. While the CCC of the rectifier station controls the trigger angle to increase briefly to reduce the DC current, the DC current gradually approaches the command value. However, because the DC current is still larger than the steady-state value and the trigger angle of the rectifier station increases, the reactive power consumed by the rectifier station increases. The rectifier station absorbs more reactive power from the sending-end grid. At the same time, the active power transmission is blocked due to the drop in DC voltage at the inverter station [
26]. Therefore, the AC bus voltage drops.
Stage 3: Normal commutation is recovered. The DC voltage of the inverter station gradually increases. The trigger angle of the rectifier station reduces, but also maintains a considerable value. Concurrently, the DC current of the rectifier station continues to decrease to the commanded value of the VDCOL. As the DC current stabilizes, the transmission power remains relatively constant. However, the decrease in the DC current prompts a notable reduction in the consumed reactive power. Because of the constraints of the response speed of the AC filter and the communication delay, the reactive power compensation at the rectifier station cannot be decreased in a timely manner. The surplus reactive power is delivered to the sending-side grid, thus resulting in a rise in the AC bus voltage of the rectifier station.
Stage 4: The DC voltage at the inverter station gradually rises and returns to the rated value under the influence of the control system after the fault clearance. Simultaneously, the DC current gradually returns to the normal value. The trigger angle of the rectifier station decreases gradually, restoring the active power to the pre-fault level. The reactive power consumed by the rectifier station gradually resumes. The sending-end grid supplies more active power to the rectifier station, leading to a balance in the exchange of reactive power between the rectifier station and the sending-end grid. Consequently, the AC bus voltage of the rectifier station gradually returns to the steady-state value.
After a commutation failure of the inverter station, the active power of the rectifier station decreases initially, then gradually increases due to the intervention of the control system. The reactive power consumed by the rectifier station initially rises before subsequently decreasing. Under the influence of active and reactive power, the AC bus voltage of the rectifier station decreases initially before rising. The increase in AC bus voltage leads to transient overvoltage in the sending-end grid, posing a threat to renewable energy generation.
4. Transient Overvoltage Suppression Method Considering AC-DC System Coupling
After a commutation failure, the rectifier station absorbs a large amount of reactive power due to the rapid rise in DC current. As the DC current falls, the reactive power consumed by rectifier station decreases, which produces a reactive power surplus. Meanwhile, the obstruction of power transmission results in a decline in the active power fed to the rectifier station. The reactive power imbalance and active power variations jointly result in AC transient overvoltage. Therefore, by substituting Equations (11) and (14) into Equation (7), the dynamic model of the AC bus voltage can be built as:
The trigger angle of the rectifier station varies according to the command value under CCC. The trigger angle can be written as:
The trigger angle is related to the DC current, so the dynamic model of the AC bus voltage reflects the relationship between the AC bus voltage and the DC current, which depicts the feasible range of the AC bus voltage of the rectifier station under the coupling effect of the sending-end grid and the rectifier station. The feasible range is related to the DC current. The AC transient overvoltage can be suppressed by controlling the DC current. According to the dynamic model, the improved suppression method of AC transient overvoltage is proposed based on the model of predictive control, as shown in
Figure 5.
The model of predictive control takes the output of the previous moment as the input of the next moment until the convergence condition is satisfied, and finally obtains the optimal control command value. The DC current of the rectifier station is used as the control quantity. The command value of the DC current, to prevent the AC bus voltage from exceeding the limit, is determined through continuous iteration. The smaller the AC bus voltage, the larger the DC current variation. A large DC current is not conducive to DC voltage stabilization, nor the commutation recovery of the inverter station. Therefore, controlling the AC bus voltage within the allowable voltage threshold is taken as the control target. The DC current first rises and then decreases after a commutation failure. As the DC current decreases, the AC bus voltage rises. Therefore, VDCOL is switched to overvoltage suppression control when a decrease in the DC current is detected.
Step 1: According to the relationship between AC bus voltage and DC current, the DC current at moment
k is calculated by the AC bus voltage at moment
k, which can be written as:
where
and
are the AC bus voltage and DC current at moment
k;
and
are the firing angle and overlap angle of commutation at moment
k.
Step 2: Equation (15) is used as a prediction model, and the predicted AC bus voltage at the moment
k + 1 can be obtained according to the DC current at the moment
k:
Step 3: The predicted AC bus voltage is compared with the allowable voltage threshold. If the predicted AC bus voltage is greater than the allowable voltage threshold, the feedback correction should be implemented. The AC bus voltage after feedback correction is written as:
where
, which is the deviation between the voltage at the moment
k + 1 and the allowable voltage threshold.
The AC bus voltage at moment k is replaced by . Then, step 1 is repeated. If the predicted AC bus voltage is less than or equal to the allowable voltage threshold, continue to step 4.
Step 4: The AC voltage difference between the
k and
k + 1 moments is judged according to the following convergence criterion:
where
is a sufficiently small constant.
If the convergence criterion is not satisfied, the AC bus voltage at moment k is replaced by that at the moment of k + 1. Then, step 1 is repeated. The iteration repeats until the convergence criterion is satisfied. The DC current that makes the AC bus voltage satisfy the convergence criterion is adopted as the command value. The command value of the trigger angle is generated by the CCC for trigger control. The command value of the DC current takes into account the influence of the AC-DC system coupling on the transient overvoltage, thereby enhancing the accuracy of the control of AC transient overvoltage.
The transient AC overvoltage suppression method proposed in this paper achieves control by dynamically computing the DC current command value in real-time and utilizing the existing CCC to determine the rectifier station’s trigger angle command value. This approach requires no additional hardware, only the inclusion of a calculation module for the DC current command value, making it practical in a real system.