Online Detection of Hydrogen Fluoride under Corona Discharge in Gas-Insulated Switchgear Based on Photoacoustic Spectroscopy

1
School of Cable Engineering, Henan Institute of Technology, Xinxiang 453003, China
2
Henan Key Laboratory of Cable Structure and Materials, Xinxiang 453003, China
3
School of Electrical Engineering and Automation, Henan Institute of Technology, Xinxiang 453003, China
4
Institute of Electrical Engineering, Chinese Academy of Sciences, Beijing 100190, China
*
Author to whom correspondence should be addressed.
Sensors 2024, 24(9), 2806; https://doi.org/10.3390/s24092806
Submission received: 1 April 2024 / Revised: 24 April 2024 / Accepted: 26 April 2024 / Published: 27 April 2024
(This article belongs to the Special Issue Photoacoustic Sensors and Devices for Gas Detection)

Abstract

:
Internal discharge and overheating faults in sulfur hexafluoride (SF6) gas-insulated electrical equipment will generate a series of characteristic gas products. Hydrogen fluoride (HF) is one of the main decomposition gases under discharge failure. Because of its extremely corrosive nature, it can react with other materials in gas-insulated switchgear (GIS), resulting in a short existence time, so it needs to be detected online. Resonant gas photoacoustic spectroscopy has the advantage of high sensitivity, fast response, and no sample gas consumption, and can be used for the online detection of flowing gas. In this paper, a simulated GIS corona discharge experimental platform was built, and the HF generated in the discharge was detected online by gas photoacoustic spectroscopy. The absorption peak of HF molecule near 1312.59 nm was selected as the absorption spectral line, and a resonant photoacoustic cell was designed. To improve the detection sensitivity of HF, wavelength modulation and second-harmonic detection technology were used. The online monitoring of HF in the simulated GIS corona discharge fault was successfully realized. The experimental results show that the sensitivity of the designed photoacoustic spectroscopy detection system for HF is 0.445 μV/(μL/L), and the limit of detection (LOD) is 0.611 μL/L.

1. Introduction

SF6 gas possesses many excellent characteristics, such as high dielectric strength, strong chemical inertness, and low toxicity, which significantly improve the reliability and stability of equipment and reduce the labor intensity of the routine inspection and operation maintenance of equipment, and thus, SF6 has been widely used in GIS [1,2].
Few decomposition products are generated during the normal operation of GIS. In the case of a discharge or overheating fault in GIS, SF6 will decompose and produce a series of low-fluorine sulfides (SxF6−x, 1 ≤ x ≤ 5). These low-fluorine sulfides will repolymerize into SF6 after the faults disappear. However, when trace amounts of water or oxygen are present in SF6, these low-fluorine sulfides will react with the impurities to produce more compounds, such as HF, SO2, H2S, CO, CF4, CS2, SO2F2, SOF2, etc. [3].
Van Brunt [4] from the National Bureau of Standards of the United States proposed a three-region model to explain the SF6 decomposition mechanism during discharge, which is widely recognized. In his theory, the SF6 discharge region can be divided into three zones, as shown in Figure 1: the glow zone, ion migration zone, and main gas chamber zone. In the presence of water and oxygen, SF6, water, and oxygen are dissociated under electron collision in the glow region to form low-fluorine sulfide, O, OH, and F particles. These particles will react in the glow region, and the reaction processes are shown in Formulas (1)–(8) [3].
S F 5 + O = S O F 4 + F
S F 5 + O H = S O F 4 + H F
S F 4 + O = S O F 4
S F 4 + O H = S O F 4 + H F
S F 3 + O = S O F 2 + F
S F 3 + O H = S O F 2 + H F
S F 2 + O H = S O F 2 + H F
S F + O + F = S O F 2
In the ion migration zone, some ions react with the compounds produced in the glow zone, and the reaction in this zone has little influence on the final product. The main reaction process is shown in Formulas (9)–(11).
S F 6 + S O F 4 = · S O F 5 + S F 5
S F 6 + S O 2 = · S O 2 F + 2 H F
S + · O 2 = S + O 2
When the stable products produced in the glow zone are diffused to the main gas chamber zone, they will react with the water and oxygen in the main gas chamber region to generate more stable products. The main reaction process is shown in Formulas (12)–(15).
S F 2 + O 2 = S O 2 F 2
S F 4 + H 2 O = S O F 2 + 2 H F
S O F 2 · + H 2 O = S O 2 + 2 H F
S O F 4 + · H 2 O = S O 2 F 2 + 2 H F
According to the discharge mechanism of SF6, HF is one of the main decomposition products. HF is very active. It can strongly corrode metal materials, which brings great security risks to the safe operation of GIS. IEC60480-2020 clearly states that SF6 will produce HF under discharge and high-temperature faults, and it stipulates that the maximum allowable concentration of HF in SF6 gas insulation is 25 μL/L [5].
The discharge and overheat faults in GIS will produce HF, so HF is a very important fault characteristic gas in GIS [6]. The chemical properties of HF are very active, which leads to HF’s existence for a short time. Therefore, it is difficult to detect HF in the offline detection of gas in GIS.
The traditional HF gas detection methods mainly include infrared absorption spectroscopy, detection tubes, and carbon nanotube gas sensors. Infrared spectroscopy has wide spectral lines, dense absorption peaks, and poor anti-interference ability, and it is easily affected by environmental gases and makes it difficult to detect trace gases. The detection tube method can realize the detection of HF gas by using the principle of chemical color reaction, but it is easily affected by the environment and there is gas interference. The accuracy of the carbon nanotube method is low, and it makes it difficult to realize online detection. Fourier transform infrared absorption spectroscopy can also be used to detect HF gas, but its volume is large, the sensitivity is low, and it is not suitable for online monitoring [7,8]. Tunable Diode Laser Absorption Spectroscopy (TDLAS) has also been used to detect HF [8,9,10]. In recent years, the detection of HF gas by photoacoustic spectroscopy has been rare. Teemu Tomberg et al. adopted the cantilever beam-enhanced photoacoustic spectroscopy technique based on an optical parametric oscillator to detect the strong absorption of spectral lines of HF at 2475.8836 nm and found that the LOD of HF was below nL/L [11]. All of these studies focused on HF standard gases. At present, there is no research on the online detection of HF gas generated during simulated GIS discharge.
Gas photoacoustic spectroscopy is a non-background gas detection technology with high accuracy, good long-term stability, and high sensitivity. Resonance photoacoustic spectroscopy can detect flowing gas [12,13,14,15,16]. Therefore, resonance photoacoustic spectroscopy was used in this research to monitor the HF generated during a simulated discharge fault. The research results are of great significance for the safe operation of GIS.

2. Principle of Resonant Photoacoustic Spectroscopy Detection Technology

Gas photoacoustic spectroscopy is a kind of detection technology based on the photoacoustic effect, which is caused by the periodic non-radiative relaxation (thermal effect) caused by the absorption of changing light energy by gas molecules. The sound pressure generated by gas molecules in photoacoustic cells can be expressed as the wave formula [17,18,19,20].
2 p c 2 2 p t 2 = γ 1 c 2 H t
In Formula (16), p represents the sound pressure of the gas, and c represents the sound velocity in the gas; γ = CP/CV, which represents the specific heat ratio of the gas; H represents the thermal power density generated by the gas absorption-modulated light energy. If the incident light intensity is I, H = αI, α is the absorption coefficient of the gas molecule.
In a cylindrical coordinate system, considering gas heat conduction loss and viscosity loss, the amplitude Aj(ω) in normal mode j can be expressed as follows:
A j ω = i ω ω j 2   α γ 1 V c p j I d V 1 ω 2 ω J 2 i ω ω j Q j
In Formula (17), ωj represents the resonant angular frequency under normal mode j; VC represents the cavity volume; Qj represents the quality factor under normal mode j; p j represents the conjugate complex number of sound pressure in simple positive mode j. In actual use, ω = ωj is usually used to ensure that the photoacoustic cell works in a simple positive mode, in which case, the sound pressure of the photoacoustic cell can be expressed as follows:
p r M , ω j = ( γ 1 ) Q j ω j L C V C I j p j ( r M ) α P 0
In Formula (18), P0 represents the power of the light source; I j = 1 P 0 C p j I d V , and C represents the concentration of the gas; ( γ 1 ) Q j ω j L C V C I j p j ( r M ) is called the photoacoustic cell constant, expressed as Ccell, which is a parameter related only to the structure, material, and size of the photoacoustic cell.
The sensitivity of the microphone is denoted as Ms, and then, the photoacoustic signal Spas can be denoted as follows:
S p a s = M s · C c e l l · C · α · P 0
According to Formula (19), when Ms, Ccell, α, and P0 are constant, the photoacoustic signal is proportional to the concentration of the gas to be measured, which is the theoretical basis of photoacoustic detection.

3. Construction of Photoacoustic Spectroscopy Experiment System

Figure 2 depicts the schematic structure of the photoacoustic HF gas-sensing system. A tunable distributed feedback (DFB) laser was used as an excitation light source. The DFB laser was driven by the current of modulating sinusoidal and scanning sawtooth waves. The light emitted by the DFB laser passed through the fiber collimator into the resonant photoacoustic cell. The HF gas in the photoacoustic cell absorbed modulated light to produce photoacoustic signals. The second-harmonic signal of HF gas absorption was obtained by using the phase-locked amplifier. An oscilloscope was used to collect the second-harmonic signal detected by the phase-locked amplifier.
A discharge chamber was designed. The actual corona discharge was simulated by the needle–plate electrode. Figure 3 shows the gas path connection and the electrodes in the schematic structure of the test system. To reduce the loss of HF in the gas cycle, each part of the structure was connected by pipes made of polytetrafluoroethylene. To reduce the gas flow noise in the experiment, a circulating pump (KVP04-1.1-24, Kamoer, Shanghai, China) and flowmeter (D07-7B, BEIJING SEVENSTAR FLOW CO., Ltd., Beijing, China) were used to maintain the gas flow rate at 50 mL/min. The pressure in the gas path was 0.3 MPa. The discharge chamber was made of quartz glass and stainless steel. The needle electrode was a high-voltage electrode. The volume of the discharge chamber was 2 L. The maximum discharge voltage was 60 kV. The vacuum pump (RV12, Edwards, Burgess Hill, UK) can reduce the air pressure of the gas path to 2 × 10−3 mbar.

Absorption Lines of HF

The photoacoustic signal depended on the absorption intensity of the HF gas to the incident light. The absorption intensity of HF gas was not only related to the concentration of the gas and the length of the photoacoustic cell, but also to the intensity of the absorption spectral line of the gas. The absorption spectral line of HF was selected by querying the High-Resolution Transmission Molecular Absorption Database (HITRAN) [21].
Figure 4 shows the absorption lines of HF in the near-infrared region. It can be seen from Figure 4a that the absorption lines of HF in the near-infrared region were mainly concentrated in the bands of 1250–1350 nm and 2300–2800 nm. The absorption intensity of HF was greater in the mid-infrared region. Quantum cascade lasers can be used in the mid-infrared region, but they are too expensive. In addition, other gases also have strong absorption in the mid-infrared band, which will lead to interference. Therefore, the absorption line of 1312.59 nm was selected.
According to the HITRAN database, gas absorption lines of HF, H2O, CO, CO2, and H2S were obtained. Figure 5 is a comparison of the absorption intensity of HF and its main interference gases after amplification. As can be seen from Figure 5, HF had a strong absorption coefficient at 1312.59 nm, and there was no obvious interference from other gases. A DFB laser with a central wavelength of 1312.6 nm was selected as the excitation light source. According to the wavelength of the DFB laser, the collimator (50-1310A-APC, Thorlabs, Newton, NJ, USA) with the central wavelength of 1310 nm was selected.
There are two types of photoacoustic cells: non-resonant photoacoustic cells and resonant photoacoustic cells. Compared with non-resonant photoacoustic cells, resonant cells can detect flowing gas [22]. In this research, it was necessary to detect flowing gas, so resonant photoacoustic cells were selected. The choice of photoacoustic cell material is very important. The material is related to the damping, viscosity, and heat loss of the gas, which greatly affects the detection sensitivity of the photoacoustic system. Materials with high heat conductivity and a large Poisson ratio are generally selected for photoacoustic cells [23]. At the same time, the processing difficulty should be considered. Commonly used materials for photoacoustic cell are brass, copper, aluminum alloy, stainless steel, and so on. The characteristic parameters of these materials are shown in Table 1. Red copper has the highest thermal conductivity. However, its characteristic is soft, and it is difficult to ensure the smooth surface of the photoacoustic cell during processing. Among other materials, aluminum alloy has the highest thermal conductivity and Poisson ratio. At the same time, aluminum alloy is easy to process. Therefore, aluminum alloy was selected as the photoacoustic cell material.
The photoacoustic cells designed in this research adopted the first-order longitudinal resonance mode. Increasing the photoacoustic cell constant can improve the intensity of the acoustic signal. The photoacoustic cell constant can be increased by increasing the cavity length or decreasing the cavity radius. However, if the cavity radius is too small or the length is too large, it is easy to make light shine on the cell wall. Theoretical research shows that in order to achieve a better de-noising effect, the length of the buffer cavity should be 1/2 of the length of the resonant cavity, and the diameter of the buffer cavity should be more than 3 times the diameter of the resonant cavity [24]. In this study, the inlet and outlet were placed in the buffer chamber, which could effectively reduce the gas flow noise. The resonant chamber used in the test had a radius of 5 mm and a length of 100 mm. The buffer chamber was 50 mm long and 35 mm in diameter.
A photoacoustic cell window should be made of a material that does not react with HF, and the incident light transmission should be as large as possible. A WG51050 window was selected for use in this test. The material of WG51050 is CaF2, which does not react with HF. Its transmissivity in the near-infrared region is above 92%. According to the data provided by the manufacturer of THORLABS, the light transmission characteristic of WG51050 is shown in Figure 6.
A capacitive microphone has the advantages of high sensitivity, good transient characteristics, wide frequency response, and low cost. An electret microphone is a kind of capacitive microphone. An electret microphone provides polarization voltage by itself, which makes the internal circuit relatively simple, low cost, and small in size. The photoacoustic signal is sensitive to the shape of the photoacoustic cavity, so it is more appropriate to choose a small electret microphone. In this research, the MPA416 microphone made by Beijing Prestige Co., Ltd. (Beijing, China) was selected. The diameter of the microphone was 1/4 inch, the sensitivity was 50 mV/pa, and the frequency response range was 20 Hz~20 kHz. To determine the installation position of the microphone, COMSOL-Multiphysics 5.4 was used to simulate the frequency domain of the photoacoustic cell. The simulation results are shown in Figure 7. According to COMSOL calculation results, the first-order longitudinal resonance frequency of the photoacoustic cell was 650.4 Hz. As can be seen from Figure 7, when the resonant photoacoustic cell worked in the first-order resonance mode, the sound pressure at the middle position of the resonator was the largest. Therefore, the microphone needed to be installed in the middle of the resonator.
Based on the previous analysis, the main sizes of the designed photoacoustic cell are shown in Figure 8.

4. Experiment and Analysis

4.1. The Modulating Sinusoidal Wave Frequency of the DFB Laser

When the frequency of a modulating sinusoidal wave is half of the photoacoustic cell resonance frequency, the photoacoustic second-harmonic signal will be the strongest. Therefore, before the formal experiment, it was necessary to determine the resonance frequency of the photoacoustic cell.
To find the resonance frequency of the photoacoustic cell, the resonant frequency of the photoacoustic cell was tested using the system shown in Figure 2. In the test, H2S/SF6 mixed gas was used as the sample gas. The DFB laser (PL-DFB-1578-AA81-SA, LD-PD INC) had a central wavelength of 1578.12 nm. In order to enhance the photoacoustic signal, the output optical power of the DFB laser was amplified by using an Erbium-Doped Fiber Amplifier (EDFA). The output optical power of the EDFA was 1W. The peak-to-peak value of the modulating sinusoidal wave was 63.4 mV. In order to eliminate the influence of temperature change on the photoacoustic signal, the temperature control system was used to control the temperature of the photoacoustic cell at 30 °C.
The photoacoustic cell was filled with 100 μL/L H2S/SF6 standard gas. The gas pressure in the photoacoustic cell was 1 atmosphere. The amplitude of the modulating sinusoidal wave was 31.7 mV. The output power of the EDFA was set to 1 W. The frequency of the modulating sinusoidal wave was adjusted from 300 Hz to 345 Hz, and the value of the photoacoustic second-harmonic signal was recorded. The photoacoustic second-harmonic signal was fitted using a Lorentz curve. The fitting result is shown in Figure 9. As can be seen from Figure 9, when the frequency of the modulating sinusoidal wave was 321.8 Hz, the signal was the strongest. Therefore, the first-order longitudinal resonance frequency of the photoacoustic cell was 643.6 Hz.

4.2. Calibration of HF Concentration

To calibrate the detection sensitivity of the system, 525 μL/L HF/SF6 standard gas was used. Before the test, the photoacoustic cell was purged 5 times with the standard gas to passivate the aluminum alloy. The standard gas was quickly tested after intake, and the test time was 40 s. The test was repeated 12 times. The test results are shown in Figure 10. Figure 10 shows the mean and standard deviation of each test.
As can be seen from Figure 10, the photoacoustic signal gradually increased and became stable with the increase in the number of test times. This was due to the passivation of aluminum alloy to reduce the loss of HF. After 12 tests, the photoacoustic signal no longer increased. The result of the 12th test was used to calculate the detection sensitivity of the system to HF gas. Figure 11 shows the photoacoustic second-harmonic wave of the 12th test. The mean value of the photoacoustic signal in the 12th test was 233.750 μV. By calculation, the detection sensitivity of the test system was 0.445 μV/(μL/L).
The LOD is a very important parameter used to measure the ability of detection systems. It represents the lowest concentration of gas that can be detected by the system. The LOD can be expressed by Formula (20).
L O D = K σ s S
In Formula (20), K represents the confidence coefficient, σs represents the standard deviation of the signal, and S represents the sensitivity of the detection system. According to the detection result, the standard deviation of the signal was 0.272 μV. When K is 1, LOD is 0.611 μL/L according to Formula (20).

4.3. Online Detection of HF under Simulated GIS Corona Discharge Fault

The gas tightness of the detection system was tested. Vacuum and 0.1 atm (gauge pressure) positive pressure gas tightness tests were carried out on the gas path system. Under both test conditions, there was no change in gas pressure after 12 h. This showed that the gas system was well sealed. Before each experiment, the discharge room and electrodes were scrubbed with anhydrous ethanol. Then, the gas system was connected and the gas system was cleaned five times using the vacuum pump and SF6 standard gas. Finally, the SF6 standard gas was inflated into the discharge electrical room to make the gauge pressure reach 0 atm.
Under the action of the circulating pump, the gas in the discharge room circulated in the gas path. The photoacoustic second-harmonic detection technology and wavelength modulation technology were used to test the HF concentration in the gas path. The peak-to-peak value of the scanning sawtooth wave of the DFB laser was 50 mV, and the frequency was 0.1 Hz. The peak-to-peak value of the modulating sinusoidal wave of the DFB laser was 50 mV and the frequency was 321.8 Hz.
The actual GIS corona discharge fault was simulated by the needle–plate electrode discharge. The photoacoustic spectroscopy test system shown in Figure 2 was used for the online detection of HF generated during discharge. The plate electrode was copper, and the needle electrode material was aluminum alloy. The discharge voltage was 20 kV. The discharge lasted for 372 min. During the discharge, HF was also reduced due to chemical reactions with materials in the gas path. The concentration of HF in the gas path over time during the discharge is shown in Figure 12. As can be seen from Figure 12, from 0 to 150 min, the concentration of HF rose faster. This is because the HF produced by the discharge was much more than that consumed. From 150 min to 264 min, the concentration of HF was saturated. This is because the HF produced by the discharge was approximately equal to that consumed. From 264 min to 372 min, the concentration of HF showed a downward trend. This may have been due to the weakening of the discharge energy caused by the ablation of the aluminum alloy needle electrode in the discharge, resulting in less HF being produced by the discharge than consumed.
When the voltage was reduced to 0, the discharge stopped. The concentration of HF over time is shown in Figure 13. As can be seen from Figure 13, the concentration of HF decreased approximately linearly. This was due to the reaction of HF with materials in the gas path, resulting in a reduction in its concentration. Therefore, offline detection cannot reflect the HF concentration when a GIS fault occurs. In order to accurately measure HF concentrations in GIS, online monitoring technology is necessary.

5. Conclusions

In this research, the concentration of trace HF gas produced by GIS corona discharge was detected. An online detection platform was built, which could realize the real-time online detection of HF gas concentrations. Compared with previous studies, the platform was more consistent with real corona discharge characteristic gas-detection scenarios, which provided an important basis for GIS condition assessment. A detection system for HF gas online monitoring was built. A gas circuit system with good sealing was designed. A corona discharge fault in GIS was simulated by using needle–plate electrode discharge. Gas photoacoustic spectroscopy was used to detect HF generated in discharge in real time. In order to detect flowing gas, a resonant photoacoustic cell was designed. According to the mechanism of photoacoustic signal generation, the material of the photoacoustic cell and the size of the photoacoustic cavity were reasonably designed. By querying the HITRAN database, the absorption intensities of HF and interference gases were compared, and the absorption spectral line of HF in the near-infrared region was determined. Wavelength modulation spectroscopy and second-harmonic detection techniques were used in the detection. The online monitoring of HF generated in a simulated GIS corona discharge fault was successfully realized by using the test system. The test system was calibrated using 525 μL/L standard HF/SF6 mixed gas. The detection sensitivity of the test system for HF gas was 0.445 μV/(μL/L), and the LOD was 0.611 μL/L.
HF was found to be reduced by reacting with materials in the gas path. In the early stage of a discharge fault, the HF concentration increases rapidly. With the ablation of the discharge point, the discharge energy may weaken, resulting in a decrease in the concentration of HF. The research results of this paper have important significance in GIS online monitoring.

Author Contributions

L.W. conceived the idea of this work; L.W. and K.L. proposed the methodology for the measurements; L.W. performed the experimental investigation and data analysis. The manuscript was written by L.W. and X.Z.; edited by X.Z.; and revised by all authors. All authors have read and agreed to the published version of the manuscript.

Funding

The Youth Innovation Promotion Association CAS (2021135), the Henan Institute of Technology High-level Talent Research Fund (KQ2108), the State Power Investment Group coordinated research and development funding support project (KYT C2021SD02), the Henan Province Science and Technology Research Program Project (232102230013), and the Henan Province Natural Science Foundation Project (242300421615).

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

All data underlying this article are available in the article.

Conflicts of Interest

The authors declare no conflicts of interest.

References

  1. Tang, N.; Qiao, S.; Li, L.; Fan, X.; Zhou, W. Validity of HF and H2S as target gases of insulation monitoring in gas insulated switchgear. Trans. China Electrotech. Soc. 2017, 32, 202–211. [Google Scholar]
  2. Chen, K.; Wang, N.; Guo, M.; Zhao, X.; Qi, H.; Li, C.; Zhang, G.; Xu, L. Detection of SF6 gas decomposition component H2S based on fiber-optic photoacoustic sensing. Sens. Actuators B Chem. 2023, 378, 133174. [Google Scholar] [CrossRef]
  3. Ji, S.; Zhong, L.; Liu, K.; Li, J.; Cui, Y.; Wang, Y.; Guo, J.; Ji, G. Research status and development of SF6 decomposition components analysis under discharge and its application. Proc. CSEE 2015, 35, 2318–2332. [Google Scholar]
  4. Van Brunt, R.J.; Herron, J.T. Fundamental processes of SF6 decomposition and oxidation in glow and corona discharges. IEEE Trans. Electr. Insul. 1990, 25, 75–94. [Google Scholar] [CrossRef]
  5. IEC60480; Power Cables with Extruded Insulation and Their Accessories for Rated Voltages above 30 kV (Um = 36 kV) up to 150 kV (Um = 170 kV)-Test Methods and Requirements. International Electrotechnical Commission: Geneva, Switzerland, 2020.
  6. Liu, C.; Palanisamy, S.; Chen, S.; Wu, P.; Yao, L.; Lou, B. Mechanism of Formation of SF6 Decomposition Gas Products and its Identification by GC-MS and Electrochemical methods: A mini Review. Int. J. Electrochem. Sci. 2015, 10, 4223–4231. [Google Scholar] [CrossRef]
  7. Zhang, S.; Yao, Q.; Li, X. On-line Monitoring of HF Gas in High Voltage GIS Based on Flange Optical Fiber Sensing Technology. High Volt. Eng. 2019, 45, 402–409. [Google Scholar]
  8. Tang, F.; Liu, S.; Lv, Q.; Li, X.; He, S.; Zeng, X.; Yue, Y. Design and adsorption experiment of TDLAS sensor for HF detection in GIS. Laser Infred. 2020, 50, 543–550. [Google Scholar]
  9. Liu, Y. Research and Realization of HF Gas Detection Based by Tunable Diode Laser Spectroscopy. Master’s Thesis, Tianjin University, Tianjin, China, 2012. [Google Scholar]
  10. Yao, Q.; Yuan, Z.; Li, X.; Miao, Y.; Qiu, N. Using TDLAS Technology to Detect HF Gas in SF6 High-voltage Switches. Instrum. Tech. Sens. 2013, 5, 70–71+90. [Google Scholar]
  11. Tomberg, T.; Vainio, M.; Hieta, T.; Halonen, L. Sub-Parts-Per-Trillion Level Sensitivity in Trace Gas Detection by Cantilever-Enhanced Photo-Acoustic Spectroscopy. Sci. Rep. 2018, 8, 1848. [Google Scholar] [CrossRef]
  12. Palzer, S. Photoacoustic-Based Gas Sensing: A Review. Sensors 2020, 20, 2745. [Google Scholar] [CrossRef]
  13. Popa, C. Ethylene Measurements from Sweet Fruits Flowers Using Photoacoustic Spectroscopy. Molecules 2019, 24, 1144. [Google Scholar] [CrossRef] [PubMed]
  14. Mikkonen, T.; Luoma, D.; Hakulinen, H.; Genty, G.; Vanninen, P.; Toivonen, J. Detection of gaseous nerve agent simulants with broadband photoacoustic spectroscopy. J. Hazard. Mater. 2022, 440, 129851. [Google Scholar] [CrossRef]
  15. Wu, H.P.; Dong, L.; Yin, X.K.; Sampaolo, A.; Patimisco, P.; Ma, W.G.; Zhang, L.; Yin, W.B.; Xiao, L.T.; Spagnolo, V.; et al. Atmospheric CH4 measurement near a landfill using an ICL-based QEPAS sensor with V-T relaxation self-calibration. Sens. Actuators B Chem. 2019, 297, 126753. [Google Scholar] [CrossRef]
  16. Zhang, X.; Li, X.; Liu, H.; Zheng, C. The quantitative detection of SF6 characteristic decomposition component H2S based on cantilever enhanced photoacoustic spectrometry. Trans. China Electrotech. Soc. 2016, 31, 187–196. [Google Scholar]
  17. Chen, K.; Yu, Q.; Gong, Z.; Guo, M.; Qu, C. Ultra-High Sensitive Fiber-Optic Fabry-Perot Cantilever Enhanced Resonant Photoacoustic Spectroscopy. Sens. Actuators B Chem. 2018, 268, 205–209. [Google Scholar] [CrossRef]
  18. Duquesnoy, M.; Aoust, G.; Melkonian, J.-M.; Lévy, R.; Raybaut, M.; Godard, A. Quartz Enhanced Photoacoustic Spectroscopy Based on a Custom Quartz Tuning Fork. Sensors 2019, 19, 1362. [Google Scholar] [CrossRef] [PubMed]
  19. Li, Z.; Si, G.; Ning, Z.; Liu, J.; Fang, Y.; Si, B.; Cheng, Z.; Yang, C. Highly Sensitive Sphere-Tube Coupled Photoacoustic Cell Suitable for Detection of a Variety of Trace Gases: NO2 as an Example. Sensors 2022, 22, 281. [Google Scholar] [CrossRef] [PubMed]
  20. Rothman, L.S.; Gordon, I.E.; Babikov, Y.; Barbe, A.; Chris Benner, D.; Bernath, P.F.; Birk, M.; Bizzocchi, L.; Boudon, V.; Brown, L.R.; et al. The HITRAN2012 molecular spectroscopic database. J. Quant. Spectrosc. Radiat. Transf. 2013, 130, 4–50. [Google Scholar] [CrossRef]
  21. Liu, B.; Tang, Y.; Chen, W. Analysis on Resonant Photoacoustic Cell in Photoacoustic Spectroscopy Monitoring System for Detecting Trace Gases in Transformer Oil. High Volt. Appar. 2014, 50, 42–47. [Google Scholar]
  22. Bijnen, F.G.C.; Reuss, J.; Harren, F.J.M. Geometrical optimization of a longitudinal resonant photoacoustic cell for sensitive and fast trace gas detection. Rev. Sci. Instrum. 1996, 67, 2914–2923. [Google Scholar] [CrossRef]
  23. Liu, B. First-Order Longitudinal Photoacoustic Cell and Multi-Component Gas Detection Characteristics Based on Photoacoustic Spectroscopy. Master’s Thesis, College of Electrical Engineering of Chongqing University, Chongqing, China, 2011. [Google Scholar]
  24. Schramm, D.U.; Sthel, M.S.; Silva, M.G.D.; Carneiro, L.O.; Junior, A.J.S.; Souza, A.P. Application of laser photoacoustic spectroscopy for the analysis of gas samples emitted by diesel engines. Infrared Phys. Technol. 2003, 44, 263–269. [Google Scholar] [CrossRef]
Figure 1. Three-zone model of gas discharge.
Figure 1. Three-zone model of gas discharge.
Sensors 24 02806 g001
Figure 2. Schematic structure of the test system for the photoacoustic trace HF sensor.
Figure 2. Schematic structure of the test system for the photoacoustic trace HF sensor.
Sensors 24 02806 g002
Figure 3. Schematic structure of the gas path structure of the test platform and electrode. (a) Gas path connection, (b) Electrode.
Figure 3. Schematic structure of the gas path structure of the test platform and electrode. (a) Gas path connection, (b) Electrode.
Sensors 24 02806 g003
Figure 4. Absorption lines of HF in the near-infrared region: (a) 0.78~3 μm, (b) 1.25~1.35 μm.
Figure 4. Absorption lines of HF in the near-infrared region: (a) 0.78~3 μm, (b) 1.25~1.35 μm.
Sensors 24 02806 g004
Figure 5. Absorption lines of HF and its main interfering gases near 1310 nm.
Figure 5. Absorption lines of HF and its main interfering gases near 1310 nm.
Sensors 24 02806 g005
Figure 6. Transmissivity characteristic curve of CaF2 window.
Figure 6. Transmissivity characteristic curve of CaF2 window.
Sensors 24 02806 g006
Figure 7. Simulation results of sound field distribution in photoacoustic cell.
Figure 7. Simulation results of sound field distribution in photoacoustic cell.
Sensors 24 02806 g007
Figure 8. Sizes of the photoacoustic cell.
Figure 8. Sizes of the photoacoustic cell.
Sensors 24 02806 g008
Figure 9. Frequency response curve of photoacoustic cell.
Figure 9. Frequency response curve of photoacoustic cell.
Sensors 24 02806 g009
Figure 10. The test result of the system for the standard gas.
Figure 10. The test result of the system for the standard gas.
Sensors 24 02806 g010
Figure 11. The photoacoustic second-harmonic wave of the 12th test of the system for the standard gas.
Figure 11. The photoacoustic second-harmonic wave of the 12th test of the system for the standard gas.
Sensors 24 02806 g011
Figure 12. HF concentration curve with discharge voltage of 20 kV.
Figure 12. HF concentration curve with discharge voltage of 20 kV.
Sensors 24 02806 g012
Figure 13. Variation in HF concentration with time after the discharge stopped.
Figure 13. Variation in HF concentration with time after the discharge stopped.
Sensors 24 02806 g013
Table 1. Characteristic parameters of materials commonly used in photoacoustic cells.
Table 1. Characteristic parameters of materials commonly used in photoacoustic cells.
MaterialDensity (g·cm−3)Thermal Conductivity (W·m−1·K−1)Poisson Ratio (μ)
Copper8.43108.90.32
Red copper8.92386.40.35
Aluminum alloy2.901670.34
Stainless steel7.9316.20.30
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Wan, L.; Zhao, X.; Li, K. Online Detection of Hydrogen Fluoride under Corona Discharge in Gas-Insulated Switchgear Based on Photoacoustic Spectroscopy. Sensors 2024, 24, 2806. https://doi.org/10.3390/s24092806

AMA Style

Wan L, Zhao X, Li K. Online Detection of Hydrogen Fluoride under Corona Discharge in Gas-Insulated Switchgear Based on Photoacoustic Spectroscopy. Sensors. 2024; 24(9):2806. https://doi.org/10.3390/s24092806

Chicago/Turabian Style

Wan, Liujie, Xiaohe Zhao, and Kang Li. 2024. "Online Detection of Hydrogen Fluoride under Corona Discharge in Gas-Insulated Switchgear Based on Photoacoustic Spectroscopy" Sensors 24, no. 9: 2806. https://doi.org/10.3390/s24092806

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop