Next Article in Journal
Evaluation of the Spot Shape on the Target for Flat Heliostats
Next Article in Special Issue
Induction Motor Drive Direct Torque Control and Predictive Torque Control Comparison Based on Switching Pattern Analysis
Previous Article in Journal
Jatropha curcas, L. Pruning Residues for Energy: Characteristics of an Untapped By-Product
Previous Article in Special Issue
3-Leg Inverter Control for 2-Phase Outer Rotor Coreless Torque Actuator in Hybrid Multi-D.O.F System
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Gain Scheduled Torque Compensation of PMSG-Based Wind Turbine for Frequency Regulation in an Isolated Grid

1
School of Electrical Engineering, Shenyang University of Technology, Shenyang 110870, China
2
Department of Energy Technology, Aalborg University, 9100 Aalborg, Denmark
3
Liaoning Province Electric Power Company, Shenyang 110006, China
4
Department of Electrical and Computer Engineering, Michigan Technological University, Houghton, MI 49931, USA
5
School of Information Science and Engineering, Shenyang University of Technology, Shenyang 110870, China
*
Author to whom correspondence should be addressed.
Energies 2018, 11(7), 1623; https://doi.org/10.3390/en11071623
Submission received: 23 May 2018 / Revised: 17 June 2018 / Accepted: 18 June 2018 / Published: 21 June 2018

Abstract

:
Frequency stability in an isolated grid can be easily impacted by sudden load or wind speed changes. Many frequency regulation techniques are utilized to solve this problem. However, there are only few studies designing torque compensation controllers based on power performances in different Speed Parts. It is a major challenge for a wind turbine generator (WTG) to achieve the satisfactory compensation performance in different Speed Parts. To tackle this challenge, this paper proposes a gain scheduled torque compensation strategy for permanent magnet synchronous generator (PMSG) based wind turbines. Our main idea is to improve the anti-disturbance ability for frequency regulation by compensating torque based on WTG speed Parts. To achieve higher power reserve in each Speed Part, an enhanced deloading method of WTG is proposed. We develop a new small-signal dynamic model through analyzing the steady-state performances of deloaded WTG in the whole range of wind speed. Subsequently, H theory is leveraged in designing the gain scheduled torque compensation controller to effectively suppress frequency fluctuation. Moreover, since torque compensation brings about untimely power adjustment in over-rated wind speed condition, the conventional speed reference of pitch control system is improved. Our simulation and experimental results demonstrate that the proposed strategy can significantly improve frequency stability and smoothen power fluctuation resulting from wind speed variations. The minimum of frequency deviation with the proposed strategy is improved by up to 0.16 Hz at over-rated wind speed. Our technique can also improve anti-disturbance ability in frequency domain and achieve power balance.

1. Introduction

At present, wind turbine generators (WTGs) are widely applied. However, its variability and fluctuation increase the difficulty of grid frequency stability and power balance. Especially in an isolated grid, WTGs bring a serious challenge to frequency stability. In addition, sudden load change may lead to power imbalance. In an isolated grid with a high proportion of wind power penetration, the frequency stability of isolated grid needs to be improved by adjusting WTGs output power [1,2,3,4].
WTG needs some power reserves to regulate frequency and balance power [5,6,7,8,9]. WTGs can obtain power reserves mainly in three ways: external energy storage system (ESS), pitch system and converter system [10,11,12,13,14]. Although utilizing many ESS devices can improve frequency stability, there are a few limitations such as the significant increase in economic cost [15]. Therefore, researchers developed model predictive control (MPC) to adjust pitch system for frequency regulation [16]. Some power reserve can be obtained by adjusting the pitch angle to non-zero. However, due to the delay characteristics and a long control period of pitch actuator, pitch system may lead to untimely power adjustment. Therefore, WTGs cannot fully contribute to frequency regulation when relying only on pitch system.
In contrast to ESS and pitch system, converter system has advantages of simple application and fast response to frequency variations [17,18]. Two schemes are commonly used to regulate frequency with converter control. One scheme is that WTG runs with maximum power point tracking (MPPT) control mode, and the power response to frequency variation is achieved by inertia and kinetic energy for a short time [19,20]. The other scheme is that WTG does not track the maximum power point, and the power reserve of WTG is achieved by under-speeding or over-speeding control methods. The work in [21] shows that over-speeding control method is more appropriate to gain power reserves for deloaded WTG. However, at a low wind speed, if frequency regulation is entirely achieved by power reserves of deloaded WTG, the regulation ability is weak, and severe instability may be caused by rapid change of WTG speed. If only inertial characteristic is considered, severe instability may be caused [22]. In terms of frequency regulation method applied to WTG, the most commonly used control strategy is the variable droop control [23]. Wu et al. [24] investigated which droop factor of individual deloaded WTGs can be controlled to improve the primary frequency contribution. Together with [21,25,26], they reach the following consensus. (1) At a low wind speed, there is a possibility of instability when deloaded WTG contributes more energy. Although this could be avoided by limiting the WTG power contribution with a relatively high droop value, the dynamic inertia response capability of WTG cannot be fully utilized; (2) Since utilizing wind speed as a control variable is not appropriate for actual application, variable droop parameters are computed by deloading power and effective droop factor [27]. Despite its effectiveness, the different power compensation capabilities of deloaded WTG in the whole speed range are not considered, which is important.
In summary, the above approaches cannot handle issues such as enhancing power reserve and different power compensation capabilities in each Speed Part. This paper aims to tackle them, through leveraging a new strategy in converter and pitch system for frequency regulation without external ESS. The contributions with respect to the proposed control algorithms are as follows.
  • To optimize the primary frequency contribution of WTG, this paper presents a gain scheduled control strategy based on H theory which combines the advantages of steady-state power reserves and inertia and enhances the torque compensation gain at whole range of wind speed.
  • In the deloading method, different deloading factors are designed to smoothen WTG output power and to ensure more power reserve.
  • The WTG speed reference of pitch control system is changed to avoid decay or even power oscillation between different Speed Parts caused by torque compensation.
  • Comparing with the state-of-the-art MPPT and Droop methods, the frequency deviation with the proposed strategy is reduced by 0.16 Hz and 0.04 Hz, respectively, at over-rated wind speed, and 0.38 Hz and 0.06 Hz, respectively, when wind speed changes.
The rest of the paper is organized as follows. The isolated grid configuration is analyzed in Section 2. An improved deloading torque method of WTG is developed in Section 3. Characteristics of the deloaded WTG with torque compensation are studied in Section 4. Section 5 builds linearized model and designs H controller. Simulation and experiment results are shown in Section 6. Finally, the conclusion is given in Section 7.

2. Isolated Grid Configuration

In an isolated grid, load is supplied by a permanent magnet synchronous generator (PMSG) based wind turbine and a diesel generator. The PMSG is connected to the isolated grid by a converter. This work is based on the following wind turbine model in [28]. Some details of this model are included for completeness.
{ P m = 0.5 ρ C p ( λ , β ) A r V w 3 , C p ( λ , β ) = c 1 ( c 2 / λ i c 3 β c 4 ) e c 5 / λ i + c 6 λ , 1 λ i = 1 λ + 0.08 β 0.035 β 3 + 1 ,
where Pm is mechanical power, ρ is air density, Cp is the power coefficient, λ is the tip speed ratio, β is the pitch angle, Ar is effective area covered by turbine blades, Vw is wind speed, and c1, c2, c3, c4, c5 and c6 are coefficients. The values of relevant parameters in equations and block diagrams of this paper can be seen in Appendix A. The rotor motion equation of PMSG is expressed as:
d d t ω r = ( T m T e ) 1 2 H ,
where ωr is the generator angular speed, Tm is mechanical torque, Te is electric magnetic torque, and H is inertia coefficient. To regulate WTG output power when isolated frequency is unstable, the torque compensation is adopted by Equation (3).
T e = T e , d e l + T e , c o m ,
where Te is electric magnetic torque, Te,del is deloading torque, and Te,com is torque compensation.
The block diagram of the isolated grid is shown in Figure 1. In the pitch system, τβ is mechanical time constant of pitch actuator, the classical PI controller is to stabilize the WTG speed at the reference ω r * , and the speed reference is changed. Pe is output power of WTG, Pd is diesel generator output power, Pl is load power, and Pdev is power deviation. Frequency deviation fdev is obtained by an average aggregate frequency response model Hg(s), while M is inertia coefficient and D is damping coefficient. Diesel generator is controlled to balance power flow [29]. The governor and engine dynamics of diesel generator are modeled as in [23]. Td and Tg are mechanical time constants of engine and governor, respectively. KI is an integral coefficient and R is a droop factor. The proposed deloading torque method can be described in Equation (4). Te,com is obtained by the proposed gain scheduled torque compensation strategy.
Frequency regulation strategy depends on load characteristics, and power–frequency regulation of generators can be set by adjusting control systems [30]. Thus, to reduce frequency regulation difficulty and enhance anti-disturbance ability of the isolated grid, WTG is deloaded based on over-speeding control. On the one hand, WTG could adjust output timely according to power demand of isolated grid and reduce pressure of balancing power for diesel generator. On the other hand, WTG output power could be smoothed when wind speed changes. Thus, deloaded WTG has evident advantages for enhancing grid frequency stability.

3. Deloading Method for WTG

Deloading method enables WTG to possess affluent power reserves. Two deloading factors kf1 and kf2 (0 < kf1 < kf2 < 1) are applied. Corresponding relationships between torque and speed of WTG with deloading factors are shown in Figure 2. The power reserve of WTG can be obtained with deloading factor. The power reserve of WTG increases with decreasing deloading factor. It can be seen that the power reserve with kf2 is between those with kf1 and MPPT. The capacity of power reserve of WTG depends on the selection of deloading factors. When wind speed is higher than its rated value, kf2 is selected as 0.9 to obtain 0.1 pu power reserve of WTG. If kf1 is selected, higher power reserves can be presented but causes more wind energy loss. When wind speed is lower than its rated value, kf2 may not be able to provide WTG sufficient power reserve to regulate frequency. Therefore, kf1 may be selected as 0.8 to possess more power reserve for WTG to regulate frequency. The deloading factors may vary theoretically from 1 (no power reserve) to 0 (total curtailment). The selection of deloading factors is related to capacity of a WTG and power requirement of grid [31].
To obtain appropriate power reserve in each Speed Part and expand speed range in Part 2, three Speed Parts are defined as follows.
Part 1: ω 0 < ω r ω 1 . In this Part, to provide WTG more power reserves, kf1 is selected. ω0 is the cut-in angular speed and ω1 is the initial angular speed.
Part 2: ω 1 < ω r < ω 2 , ( ω 2 > ω r , nom ) . This Part is the transition of Parts 1 and 3. ωr,nom is the rated speed of WTG. The electromagnetic torque reference is proportional to WTG speed, and the red transition curve as shown in Figure 2 is applied for smoothening its output power. The purpose of expanding speed range is to reduce power variation when wind speed changes.
Part 3: ω 2 ω r < ω r , max . kf2 is chosen in this Part. WTG output power is the highest among all Parts. The power reserve in this Part is also the largest. ωr,max is the speed up limit. When WTG speed decreases, more energy would be obtained by adjusting pitch angle, and WTG speed reference of pitch control system is changed to be ω2 naturally.
Based on the above description, an improved torque control method is proposed to ensure more reserve. The red transition curve as shown in Figure 2 is adopted in Part 2. The proposed deloading torque in this paper is expressed by Equation (4).
T e , d e l = { k f 1 k o p t ω r 2 , ω 0 < ω r ω 1 k f 2 P e , nom ω 2 k f 1 k o p t ω 1 2 ω 2 ω 1 ( ω r ω 2 ) + k f 2 P e , nom ω 2 , ω 1 < ω r < ω 2 k f 2 P e , nom ω r , ω 2 ω r < ω r , max
where kopt is the optimal factor, and Pe,nom is the rated power. Furthermore, steady-state simulation is conducted with kf1 and kf2. The relationship between power and speed is obtained as shown in Figure 3. The shaded part is the area of adjustable power of deloaded WTG for frequency regulation.
Control laws of the proposed deloading method are further analyzed by steady-state simulation. Simulation results in the whole range of wind speed are shown in Figure 4. When wind speed approaches the rated value, WTG with deloading method would reach the rated angular speed. Thus, the action of pitch angle with deloading method is earlier than that with MPPT control. Correspondingly, Cp with deloading method is also smaller than the value with MPPT control. In other words, the rated wind speed of deloaded WTG is derated by keeping certain power reserve.

4. Analysis of Deloaded WTG

At under-rated wind speed, the deloaded WTG operates at Point A in Figure 3, and certain power reserve of WTG is obtained. When frequency drops, WTG increases output power to isolated grid. Due to rapid change of increasing output power, WTG’s operation point moves to Point B. Furthermore, increasing output power of WTG leads to overload; thus, its speed decreases, and WTG’s operation point moves to Point C. When frequency deviation becomes stable at almost zero or within the dead band, the WTG will return to Point A. However, at over-rated wind speed, the deloaded WTG operates at speed ω2. When isolated grid requires power, the deloaded WTG would increase torque to supply power by torque compensation controller. Since adjustment of pitch angle is not timely, the WTG speed would be decreased from speed ω2, which leads to decrease of Te,del of deloading torque controller. At this point, WTG speed is influenced by torque compensation controller, pitch controller and deloading torque controller. Speed decreasing leads to deloading torque reduction and untimely power adjustment. Since untimely power adjustment can be induced, angular speed reference ω2 of pitch control system is not suitable when WTG participates in frequency regulation. However, when torque compensation component of WTG is added to support frequency, with a reasonable and higher speed reference ω3 of pitch control system, pitch angle would begin operation timely, and more power can be absorbed by wind turbine. Thus, this paper adopts ω3 (ω3 > ω2) as a new speed reference of pitch control system to avoid decay or even power oscillation caused by torque compensation. ω3 is designed in pitch control system. This new speed reference increases adjustment range of WTG speed and regulation time for pitch system. The selection of ω2 and ω3 is related to capacity and inertia of WTG. The selection purpose of ω2 is to expand speed range for reducing power variation when wind speed changes. The selection purpose of ω3 is to ensure regulating power effectively and extend regulation time for pitch control system response.
Simulation above rated wind speed is performed, and results are shown in Figure 5. ω2 and ω3 are set at 1.02 pu and 1.05 pu, respectively. Torque compensation demand is added by 0.06 pu. With traditional deloading method in [23,26], deloaded WTG increases output power to 0.96 pu rapidly. However, when a constant torque compensation component demand 0.06 pu is added, the rotational speed is decreased from angular speed reference ω2, which leads to decreases of Te and Pe. In this period, speed decreasing leads to deloading torque decreasing and power drops. When deloading method in Equation (4) with ω2 is applied, the output power is also not adequate. When deloading method in Equation (4) with ω3 is applied, a higher rotational speed with a reasonable torque creates a higher power. Deloaded WTG increases output power to 0.96 pu rapidly, and some speed jitter is caused by torque compensation. Simulation results show the necessity of resetting speed reference of pitch control system.
Moreover, steady-state performances of the deloaded WTG are simulated at different wind speeds. The steady-state simulation results are shown in Table 1 and Table 2. In Table 1, wind speed is set at 10 m/s, and WTG is deloaded by Equation (4). Torque and power of WTG increase with the increasing torque compensation component Te,com, and then corresponding speed of WTG decreases. In Table 2, wind speed is set at 13.5 m/s, and WTG speed is adjusted at 1.05 pu of its rated speed by pitch control. It can be seen that the greater the absolute value of Te,com is, the more output power Pe can be compensated. The steady-state power reserve in Part 1 is less than that in Part 3, and the inertial characteristic would be utilized to possess more available power reserve in Part 1 for short-time frequency regulation. The gap of power reserve between different Speed Parts is narrowed, which states the rationality of using different reasonable deloading factors based on Speed Parts.

5. Design of Torque Compensation Controller

5.1. Linearized Models of the Deloaded WTG

According to the motion equation and mechanical power of WTG in [28], linearized equation can be expressed by Equation (5).
{ Δ P m Δ P e = H ω r 0 d Δ ω r d t , Δ P m = a 1 Δ β + a 2 Δ ω r + a 3 Δ V w ,
where “Δ” indicates a small-signal value around the operating point, subscript “0” indicates steady-state value around the operating point, and a1, a2 and a3 depending on the variables at stable operating point are calculated by Equation (6) [32].
{ a 1 = P m β = 0.5 ρ A r V w 0 3 C p β , a 2 = P m ω r = 0.5 ρ A r V w 0 3 C p λ λ ω r , a 3 = P m V w = 0.5 ρ A r ( 3 C p 0 V w 0 2 + V w 0 3 C p λ λ V w ) .
According to Equations (4)–(6), linearized models of deloaded WTG can be written as
Δ ω ˙ r = { a 1 Δ β + ( a 2 3 k f 1 k o p t ω r 0 2 T e , c o m 0 ) Δ ω r + a 3 Δ V w ω r 0 Δ T e , c o m H ω r 0 , ω 0 < ω r ω 1 a 1 Δ β + [ a 2 k f 2 P e , nom ω 2 k f 1 k o p t ω 1 2 ω 2 ω 1 ( 2 ω r 0 ω 2 ) k f 2 P e , nom ω 2 T e , c o m 0 ] Δ ω r + a 3 Δ V w ω r 0 Δ T e , c o m H ω r 0 , ω 1 < ω r < ω 2 a 1 Δ β + ( a 2 T e , c o m 0 ) Δ ω r + a 3 Δ V w ω r 0 Δ T e , c o m H ω r 0 , ω r ω 2 .
The linearized models take deloading factors and torque compensation value into account. In Parts 1 and 2, kf1 and kf2 are introduced, WTG speed is mainly affected by wind speed and torque compensation. In Part 3, the output power is constant without power compensation, and a1, a2, a3 and relevant variables are related to kf2. Pitch angle needs to be considered, and the linearized model of pitch control system as [33]:
{ Δ β * = ( K β p + K β i / s ) Δ ω r , Δ β = 1 τ β s + 1 Δ β * ,
where Kβp and Kβi are proportional and integral coefficients.
Based on the above analysis, the linearized models in Parts 1 and 2 could not reflect operation characteristics in Part 3. Therefore, it is necessary to study compensation ability of deloaded WTG in different Speed Parts. Considering the complexity and small speed range of the dynamic model in Part 2, one torque compensation controller is commonly applied to Parts 1 and 2, another one is adopted in Part 3.

5.2. Design of Gain Scheduled Torque Compensation Controller

The purpose of torque compensation controller is to complement power shortage and ensure stable operation of WTG. H control can overcome the influences of wind speed or sudden load changes, and achieve optimal operation of WTG [34,35]. Thus, H controller is more suitable for frequency regulation in the deloaded WTG. The overall block diagram of H control is shown in Figure 6. Specific designs of the controller are as follows.
According to linearized models in Equation (8), [x1 x2]T are chosen as state variables. Small-signal of WTG speed Δωr is added to the state variables x = [x1 x2 Δωr]T. The external input is w = [ΔVw ΔPloss]T. Ploss is the sum of Pd and Pl. The input signal is u = ΔTe,com. The output signal of plant P tracks deviation ΔPdev = ΔPe − ΔPloss. The plant P is described by state equation:
x ˙ = A 1 x + B 11 w + B 12 u
with A 1 = [ 1 τ β 0 1 1 0 0 a 1 q 1 H ω r 0 a 1 q 2 H ω r 0 a 2 q 3 H ω r 0 ] , B 11 = [ 0 0 0 0 a 3 H ω r 0 0 ] , B 12 = [ 0 0 1 H ] , and output equation:
y = C 1 x + D 11 w + D 12 u ,
with C 1 = [ 0 0 q 3 ] , D 11 = [ 0 1 ] , D 12 = ω r 0 , where q 1 = K β p τ β , q 2 = K β i τ β , q 3 = { 3 k f 1 k o p t ω r 0 2 + T e , c o m 0 , Parts   1 , 2 T e , c o m 0 , Part   3 .
Subsequently, the corresponding plant transfer function is:
P = [ A 1 B 11 B 12 C 1 D 11 D 12 ] .
In Figure 6, Hg(s) is given by Equation (12).
H g = [ A g B g C g D g ] ,
where Ag = −D/M, Bg = 1, Cg = 1/M, and Dg = 0. Weighting function W2(s) is chosen as W2(s) = µ, and weighting function W1(s) is chosen as:
W 1 = [ A 2 B 2 C 2 D 2 ] .
Thus, frequency regulation issues for the deloaded WTG are transferred into H norm minimization of the transfer function T z ˜ w ˜ from input w ˜ = [ Δ f d e v * Δ V w Δ P l o s s ] T to output signal z ˜ = [ z 1 z 2 ] T . The closed loop system is expressed as:
[ z ˜ y ˜ ] = P ˜ [ w ˜ u ] ,
where P ˜ of the system transfer function can be expressed as:
P ˜ = [ A 1 O O O B 11 B 12 B g C 1 A g 0 0 B g D 11 B g D 12 B 2 D g C 1 B 2 C g A 2 B 2 B 2 D g D 11 B 2 D g D 12 D 2 D g C 1 D 2 C g C 2 D 2 D 2 D g D 11 D 2 D g D 12 O 0 0 0 0 μ D g C 1 C g 0 1 D g D 11 D g D 12 ] .
W1(s) is a tracking performance weighting function of frequency deviation. To improve the sensitivity of frequency deviation response, W1(s) has the characteristics of high gain and low pass. W2(s) is the upper bound of the uncertainty for model parameters. W1(s) and W2(s) are designed by testing repeatedly in this paper as follows:
{ W 1 ( s ) = 4.2 s + 100 , W 2 ( s ) = 0.03 ( Parts   1 , 2 ) W 1 ( s ) = 1.4 s + 100 , W 2 ( s ) = 0.03 ( Part   3 ) .
According to the augmented matrix P ˜ , K1(s) and K2(s) are obtained by using a MATLAB (7.13) function hinfsyn and reduced as:
{ K 1 ( s ) = 9002 s 2 + 1.093 × 10 6 s + 1.931 × 10 7 s 3 + 2.021 × 10 4 s 2 + 4.119 × 10 6 s + 2.109 × 10 8 , K 2 ( s ) = 1097 s 2 + 1.097 × 10 5 s + 421.2 s 3 + 1.424 × 10 4 s 2 + 1.414 × 10 6 s + 5429 .
The K1(s) has a steady-state gain of 0.0916, two zeros at −21.4599 and −99.9576, and three poles at −101, −104 and −2 × 104. K1(s) is simplified to K1(s) = 0.0916(s + 21.4599)/(s + 104). The K2(s) has a steady-state gain of 0.0776, two zeros at −0.0038 and −100, and three poles at −0.00384, −100 and −14,140. Subsequently, K2(s) is simplified to K2(s) = 0.0776/(s + p), where p is a sufficiently large pole.
The purposes of gain scheduled torque compensation controller are to improve anti-disturbance ability for frequency and ensure power balance. The proposed H control has mainly two merits as follows: (1) Different power reserves in each Speed Part are considered in the piecewise controller. In this way, the proposed strategy could support power shortage based on frequency deviation and WTG Speed Part. If the same gain is applied, the generated power compensation in Part 3 is more than that in Parts 1 and 2. To improve the frequency regulation ability in Parts 1 and 2, the steady-state gain of K1(s) is bigger than that of K2(s); (2) The H controller has another advantage of making full use of power reserve and inertia characteristic for frequency regulation. In Parts 1 and 2, the power compensation of WTG is mainly dependent on less power reserve and inertial characteristic for a short time. When the frequency change behavior is slow, it is not suitable to use the inertia characteristic for a long time. The overload and instability of WTG are easily induced, and the gain of K1(s) is required to be smaller. When the frequency change is more rapid, it is available to use the inertia characteristic. Here, the gain of K1(s) is expected to be bigger. The power reserve in Part 3 is larger and constant. Thus, the gain of K2(s) is almost constant at low frequency and attenuates rapidly for noise immunity in higher frequencies. K1(s) and K2(s) are consistent with the expected design. It is also clear that the anti-disturbance ability in Part 3 is stronger than that in Parts 1 and 2.

6. Simulation and Experiment

6.1. Simulation Setup

To verify the effectiveness and validity of the proposed H controller, it is compared with MPPT controller and variable droop controller (Droop for short) in simulation and experiment. H controller and Droop controller are based on the deloading method in Equation (4). Droop controller is introduced in Equation (18) [23]. Parameters of isolated grid are shown in Table 3.
T e = T e , d e l + K P ( f r a t e d f ) ,
where KP is variable droop factor, and frated is the rated frequency of isolated grid. When KP is small, frequency regulation ability of WTG will be weakened. When KP is great, unreasonable torque compensation component may worsen system stability.

6.2. Simulation Results

To compare the effectiveness of the presented strategy when load changes, simulation is conducted. Simulation period is 10 s, and wind speeds are set as constants. At the instant of 4 s, load demand is increased by 1.5 kW. The simulation results are shown in Figure 7 and Figure 8.

6.2.1. Case 1: At Over-Rated Wind Speed

Wind speed is set to 13.5 m/s. In Figure 7a, due to lack of wind power contribution, Pd with MPPT control is less than those with deloading method. From 4.02 s to 4.15 s, Pd with H control is 100 W which is less than that with Droop control. The variation of Pd is smoothened by power reserve of deloaded WTG, the more WTG output power is, means that the less Pd is. As shown in Figure 7b, Pe with MPPT is constant and the power reserve with deloading method is 1 kW for regulating frequency. Compared with Droop control, the power compensation is increased up to 120 W with H control. The frequency curves are shown in Figure 7c. With MPPT control, the frequency drops to 49.31 Hz when load is increased. The frequency variation with H control is the smallest. The torque compensation responses to frequency deviation are shown in Figure 7d. In this case, controller K2(s) is applied, the maximum possible torque compensation is 0.1 pu. When frequency drops rapidly, due to the use of inertia characteristic and power reserve, the peak torque compensation value with H control is 0.057 pu. The peak torque compensation value with Droop control is 0.045 pu. The torque compensation of H control is up to 1.27 times of that of Droop control. It can be seen that the torque compensation gain of H control is higher than Droop control. The pitch angle curves of WTG with different methods are shown in Figure 7e. At a same over-rated wind speed, since the obtained wind power with deloading method is always less than its rated value, the pitch angles with deloading method are 6.7° bigger than that (3.4°) with MPPT control. When the deloaded WTG increases output power to regulate frequency, more energy is obtained by adjustment of pitch angle.

6.2.2. Case 2: At Under-Rated Wind Speed

Wind speed is set to 10 m/s. In Figure 8a, when load demand is increased at 4 s, Pd is lowered. Meantime, the WTG with deloading method participates in balancing power. Due to the WTG’s power contribution since 4 s, compared to MPPT control, diesel generator outputs with deloading methods are reduced. In Figure 8b, the initial outputs of WTG with MPPT and deloading method are 5.79 kW and 5.66 kW, respectively, and the steady-state power reserve of deloaded WTG is 130 W. When load increases, the instantaneous power compensation of WTG with H control is about 400 W which is larger than that (340 W) with Droop control. Due to the inertia characteristic, the power compensations of deloaded WTG are more than the steady-state power reserve of 130 W. The frequency curves are shown in Figure 8c. When the frequency is disturbed by a load change at 4 s, the frequency variation with H control is the smallest. In Figure 8d, Te,com with Droop control is weaker than that with H control. The torque compensation response gain is enhanced by H control.

6.3. Experimental Setup

Experimental platform is shown in Figure 9. The platform in laboratory contains diesel generator, constant load, electronic load, indoor WTG and RTLAB real-time simulator. The task of diesel generator is to support voltage and frequency. The constant load is utilized to imitate conventional load. The load change is realized by the electronic load. The indoor WTG is simulated by operating cabinet, grid connected cabinet, main control cabinet, motor and PMSG. The driving system of wind turbine simulation is composed of inverter and motor. The output power of motor is adjusted by inverter. The wind turbine simulation algorithm is applied to PLC. According to wind speed, pitch angle and real-time generator speed, wind turbine mechanical power is calculated by Equation (1). Wind speed is obtained by look-up table or external input. The pitch angle control system is also simulated in PLC, and its specific strategy is included in Figure 1. In this way, the mechanical torque is calculated. WTG speed reference is obtained by Equation (1) which is sent to the inverter. PMSG is driven by the motor. Subsequently, the generated power is output to the isolated grid through the converter. The simulation of indoor WTG is implemented. Voltage signals of isolated grid are transmitted to RTLAB real-time simulator for calculating frequency. Torque compensation controllers are programmed in the RTLAB. Torque compensation component is sent to the PLC through analog interfaces. The operation condition of isolated grid is monitored by HMI. The key data are recorded by measurement instrument.
The dead zone of frequency regulation is set at 0.18 Hz. When frequency deviation is outside the dead zone, the signal of torque compensation component is enabled. Once frequency deviation inside the dead zone, the present compensation component is held in the compensation controller. To verify the effectiveness of the proposed strategy, experiments for different cases were carried out.

6.4. Experimental Results

6.4.1. Case 1: At Over-Rated Wind Speed

Wind speed is set at 13.5 m/s, load demand is added by 1.5 kW at 4 s, and experimental period is 10 s. Experimental results with different control methods are shown in Figure 10a,b. When MPPT control is adopted, at 4 s, since the load is increased, frequency deviation of isolated grid dips to −0.64 Hz. WTG output power is 10 kW, and its torque is constant. With Droop control, initial output power of deloaded WTG is 9 kW. The output power of deloaded WTG is increased by Droop control according to frequency deviation. The output power of WTG is up to 9.34 kW, and the minimum frequency deviation is −0.52 Hz. With H control, the maximum output power is about 9.40 kW, the minimum frequency deviation is −0.48 Hz. It can be seen that the variation of frequency deviation with H control is smaller than the other control methods.

6.4.2. Case 2: At Under-Rated Wind Speed

Wind speed is set to 10 m/s, load demand is added by 1.5 kW at 4 s, and the experimental results with different control methods are shown in Figure 10a,b. The WTG output power with MPPT control is 5.7 kW. When load is increased, the frequency deviation dips to −0.66 Hz. With Droop control, the output power of WTG is compensated by 0.2 kW, and the minimum of frequency deviation is reduced to −0.6 Hz. With the proposed H control, frequency deviation variation is suppressed, and restores to dead zone. The maximum power compensation of WTG is nearby 0.3 kW, the minimum frequency deviation is −0.56 Hz. It can be seen that the frequency regulation capability is further enhanced by H control.

6.4.3. Summary of Results

To quantify the comparison between the MPPT, droop and H control algorithms for simulations and experiments, the important values are shown in Table 4. Pe,commax indicates the maximum of power compensation of WTG. The minimum of frequency deviation fdev,min is also shown. It can be seen that, at different cases, Pe,commax with H control is larger than those with the other control methods, and fdev,min with H control is the largest. The power compensations of WTG at over-rated wind speed is larger than that those at under-rated speed. With MPPT control, WTG has no power compensation. At over-rated wind speed, comparing the other methods, the minimum of frequency deviation with H control is enhanced by 0.16 Hz and 0.04 Hz, respectively. The primary frequency regulation contribution of WTG is further enhanced by H control. Compared with simulation results, there are oscillations in the experimental results. The oscillations could be caused by the weak mechanical system of diesel generator. In addition, according to the simulation and experimental curves shown in Figure 7, Figure 8, Figure 10 and Figure 11, the overall trend is consistent.

6.4.4. Case 3: Wind Speed Change

In this case, wind speed is variable, as shown in Figure 12; load capacity is constant; and experimental period is 100 s. Wind speed change leads to output power variation of WTG. To suppress frequency fluctuation caused by WTG output power, deloaded WTG provides power compensation to isolated grid when wind speed changes. Experimental results are shown in Figure 13a,b. When MPPT control is applied, WTG has no power compensation, the minimum Pe is 6.2 kW, and the minimum frequency deviation is −0.9 Hz. When Droop control is adopted, the minimum Pe is 6.0 kW, and the minimum frequency deviation is −0.58 Hz. With the proposed H control, change of Pe is smaller than those with other control methods. The minimum Pe is 6.2 kW, and the minimum frequency deviation is reduced to −0.52 Hz. The torque compensation controller provides a damping to the power variation of WTG. The capability of torque compensation with H control is stronger than that with droop control. The change of frequency with H control is the smallest. The pitch angle curves are shown in Figure 13b. At over-rated speed, the pitch angles with deloading method are greater than that with MPPT control. At under-rated speed, the pitch angles go to zero to obtain the maximum wind energy. Due to the delay characteristic of pitch control system, the pitch angle curve with H control is roughly the same as the curve with Droop control. The specific data comparison is shown in Table 5. Comparing the other methods, the minimum of frequency with H control is enhanced by 0.38 Hz and 0.06 Hz, respectively, which shows that the H control enhances the ability of WTG to suppress frequency variation.

7. Conclusions

The gain scheduled control strategy based on H theory strategy in this paper enhances the frequency stability of isolated grid. Compared with other control methods, the torque compensation gain is further enhanced by the proposed strategy for the whole range of wind speeds. The proposed strategy nicely integrates the advantages of steady-state power reserves and inertia for regulating frequency, which enables achieving more power reserves with different deloading factors. The speed reference of pitch system is also improved to avoid decay of power compensation at over-rated wind speed. Various H control performance metrics including inhibiting frequency fluctuation, minimization of active power change, and smoothing power are confirmed by experiments. Comparing with the state-of-the-art MPPT and Droop methods, the frequency deviation with the proposed strategy is reduced by 0.16 Hz and 0.04 Hz, respectively, at over-rated wind speed, and 0.38 Hz and 0.06 Hz, respectively, when wind speed changes.

Author Contributions

All authors conceived and designed the study. H.W., Y.L. and Y.M. performed the simulation and wrote the manuscript with guidance from J.Y., Z.C. and S.H., W.G., G.Z. and L.Y. collaborated in the experiment verification and the analysis of results.

Funding

This research is supported by “Application Technology Research and Engineering Demonstration Program of National Energy” of China (NY20150303).

Conflicts of Interest

The authors declare no conflict of interest.

Appendix A

Table A1. Parameters of wind turbine.
Table A1. Parameters of wind turbine.
c10.5176c2116c30.4c45
c521c60.0068Ar20.1 m2kopt0.1767
kf10.9kf20.8ω00.4ω10.97
ωr,nom1ω21.02ω31.05ωr,max1.2
Table A2. Parameters of diesel generator.
Table A2. Parameters of diesel generator.
R0.08KI7
Td0.005 sTg0.1 s
Table A3. Parameters of system.
Table A3. Parameters of system.
M0.5D0.01
Table A4. Parameters at the operating point (Vw = 10 m/s).
Table A4. Parameters at the operating point (Vw = 10 m/s).
ωr034.2927 rad/sa10
a278.4096a31979.1
Table A5. Parameters at the operating point (Vw = 13.5 m/s).
Table A5. Parameters at the operating point (Vw = 13.5 m/s).
ωr040.32 rad/sa1−437.7964
a2101.5045a31696.9

References

  1. Attya, A.B.; Dominguez-Garcia, J.L.; Anaya-Lara, O. A review on frequency support provision by wind power plants: Current and future challenges. Renew. Sustain. Energy Rev. 2018, 81, 2071–2087. [Google Scholar] [CrossRef]
  2. Pradhan, C.; Bhende, C.N.; Samanta, A.K. Adaptive virtual inertia-based frequency regulation in wind power systems. Renew. Energy 2018, 115, 558–574. [Google Scholar] [CrossRef]
  3. Attya, A.B.; Hartkopf, T. Wind turbine contribution in frequency drop mitigation—Modified operation and estimating released supportive energy. IET Gener. Trans. Distrib. 2014, 8, 862–872. [Google Scholar] [CrossRef]
  4. Wu, Z.; Gao, W.; Gao, T.; Yan, W.; Zhang, H.; Yan, S.; Wang, X. State-of-the-art review on frequency response of wind power plants in power systems. J. Mod. Power Syst. Clean Energy 2018, 6, 1–16. [Google Scholar] [CrossRef]
  5. Krpan, M.; Kuzle, I. Introducing low-order system frequency response modelling of a future power system with high penetration of wind power plants with frequency support capabilities. IET Renew. Power Gener. 2018, in press. [Google Scholar] [CrossRef]
  6. Bevrani, H.; Feizi, M.R.; Ataee, S. Robust frequency control in an islanded microgrid: H and μ-synthesis approaches. IEEE Trans. Smart Grid 2016, 7, 706–717. [Google Scholar] [CrossRef]
  7. Wilches-Bernal, F.; Chow, J.H.; Sanchez-Gasca, J.J. A fundamental study of applying wind turbines for power system frequency control. IEEE Trans. Power Syst. 2016, 31, 1496–1505. [Google Scholar] [CrossRef]
  8. Nguyen, N.; Mitra, J. An analysis of the effects and dependency of wind power penetration on system frequency regulation. IEEE Trans. Sustain. Energy 2016, 7, 354–363. [Google Scholar] [CrossRef]
  9. Mitra, A.; Chatterjee, D. Active power control of DFIG-based wind farm for improvement of transient stability of power systems. IEEE Trans. Power Syst. 2016, 31, 82–93. [Google Scholar] [CrossRef]
  10. Zoghlami, M.; Kadri, A.; Bacha, F. Analysis and application of the sliding mode control approach in the variable-wind speed conversion system for the utility of grid connection. Energies 2018, 11, 720. [Google Scholar] [CrossRef]
  11. Martínez-Lucas, G.; Sarasúa, J.I.; Sánchez-Fernández, J.A. Frequency regulation of a hybrid wind–hydro power plant in an isolated power system. Energies 2018, 11. [Google Scholar] [CrossRef]
  12. Rocabert, J.; Luna, A.; Blaabjerg, F.; Rodríguez, P. Control of power converters in AC microgrids. IEEE Trans. Power Electron. 2012, 27, 4734–4749. [Google Scholar] [CrossRef]
  13. Wang, H.; Chen, Z.; Jiang, Q. Optimal control method for wind farm to support temporary primary frequency control with minimised wind energy cost. IET Renew. Power Gener. 2015, 9, 350–359. [Google Scholar] [CrossRef]
  14. Ghosh, S.; Kamalasadan, S.; Senroy, N.; Enslin, J. Doubly fed induction generator (DFIG)-based wind farm control framework for primary frequency and inertial response application. IEEE Trans. Power Syst. 2016, 31, 1861–1871. [Google Scholar] [CrossRef]
  15. Kamel, R.M.; Chaouachi, A.; Nagasaka, K. Three control strategies to improve the microgrid transient dynamic response during isolated mode: A comparative study. IEEE Trans. Ind. Electron. 2013, 60, 1314–1322. [Google Scholar] [CrossRef]
  16. Pahasa, J.; Ngamroo, I. Coordinated control of wind turbine blade pitch angle and PHEVs using MPCs for load frequency control of microgrid. IEEE Syst. J. 2016, 10, 97–105. [Google Scholar] [CrossRef]
  17. Hoseinzadeh, B.; Chen, Z. Intelligent load-frequency control contribution of wind turbine in power system stability. In Proceedings of the IEEE EUROCON, Zagreb, Croatia, 1–4 July 2013. [Google Scholar]
  18. Asensio, A.P.; Gomez, S.A.; Rodriguez-Amenedo, J.L.; Plaza, M.G.; Carrasco, J.E.G.; de las Morenas, J.M.A.M. A voltage and frequency control strategy for stand-alone full converter wind energy conversion systems. Energies 2018, 11, 474. [Google Scholar] [CrossRef]
  19. Xiong, L.; Li, Y.; Zhu, Y.; Yang, P.; Xu, Z. Coordinated control schemes of super-capacitor and kinetic energy of DFIG for system frequency support. Energies 2017, 11. [Google Scholar] [CrossRef]
  20. Tang, Y.; Dai, J.; Ning, J.; Dang, J.; Li, Y.; Tian, X. An extended system frequency response model considering wind power participation in frequency regulation. Energies 2017, 10. [Google Scholar] [CrossRef]
  21. Li, Y.; Xu, Z.; Wong, K.P. Advanced control strategies of PMSG-based wind turbines for system inertia support. IEEE Trans. Power Syst. 2017, 32, 3027–3037. [Google Scholar] [CrossRef]
  22. Wu, Z.; Gao, W.; Wang, X.; Kang, M.; Hwang, M.; Kang, Y.C.; Gevogian, V.; Muljadi, E. Improved inertial control for permanent magnet synchronous generator wind turbine generators. IET Renew. Power Gener. 2016, 10, 1366–1373. [Google Scholar] [CrossRef]
  23. Arani, M.F.M.; Mohamed, Y.A.R.I. Analysis and mitigation of undesirable impacts of implementing frequency support controllers in wind power generation. IEEE Trans. Energy Convers. 2016, 31, 174–186. [Google Scholar] [CrossRef]
  24. Vidyanandan, K.V.; Senroy, N. Primary frequency regulation by deloaded wind turbines using variable droop. IEEE Trans. Power Syst. 2013, 28, 837–846. [Google Scholar] [CrossRef]
  25. Moutis, P. Discussion on “primary frequency regulation by deloaded wind turbines using variable droop”. IEEE Trans. Power Syst. 2014, 29, 414. [Google Scholar] [CrossRef]
  26. Vidyanandan, K.V.; Senroy, N. Closure to discussion on “primary frequency regulation by deloaded wind turbines using variable droop”. IEEE Trans. Power Syst. 2014, 29, 414–415. [Google Scholar] [CrossRef]
  27. Arani, M.F.M.; Mohamed, Y.A.R.I. Analysis and impacts of implementing droop control in DFIG-based wind turbines on microgrid/weak-grid stability. IEEE Trans. Power Syst. 2015, 30, 385–396. [Google Scholar] [CrossRef]
  28. Qin, Z.; Blaabjerg, F.; Loh, P.C. A rotating speed controller design method for power leveling by means of inertia energy in wind power systems. IEEE Trans. Energy Convers. 2015, 30, 1052–1060. [Google Scholar] [CrossRef]
  29. Chen, Z.; Hu, Y. A hybrid generation system using variable speed wind turbines and diesel units. In Proceedings of the 29th Annual Conference of the IEEE Industrial Electronics Society, Roanoke, VA, USA, 2–6 November 2003. [Google Scholar]
  30. Wang, Y.; Meng, J.; Zhang, X.; Xu, L. Control of PMSG-based wind turbines for system Inertial response and power oscillation damping. IEEE Trans. Sustain. Energy 2015, 6, 565–574. [Google Scholar] [CrossRef]
  31. Wang, Y.; Bayem, H.; Giralt-Devant, M.; Silva, V.; Guillaud, X.; Francois, B. Methods for assessing available wind primary power reserve. IEEE Trans. Sustain. Energy 2015, 6, 272–280. [Google Scholar] [CrossRef]
  32. Van, T.L.; Nguyen, T.H.; Lee, D.C. Advanced pitch angle control based on fuzzy logic for variable-speed wind turbine systems. IEEE Trans. Energy Convers. 2015, 30, 578–587. [Google Scholar] [CrossRef]
  33. Fazeli, M.; Asher, G.M.; Klumpner, C.; Yao, L. Novel integration of DFIG-based wind generators within microgrids. IEEE Trans. Energy Convers. 2011, 26, 840–850. [Google Scholar] [CrossRef]
  34. Zhong, Q.C.; Hornik, T. Cascaded current–voltage control to improve the power quality for a grid-connected inverter with a local load. IEEE Trans. Ind. Electron. 2013, 60, 1344–1355. [Google Scholar] [CrossRef]
  35. Li, Y.W.; Vilathgamuwa, D.M.; Loh, P.C. Robust control scheme for a microgrid with PFC capacitor connected. IEEE Trans. Ind. Appl. 2007, 43, 1172–1182. [Google Scholar] [CrossRef]
Figure 1. Block diagram of isolated grid.
Figure 1. Block diagram of isolated grid.
Energies 11 01623 g001
Figure 2. The torque curves of WTG with different deloading factors.
Figure 2. The torque curves of WTG with different deloading factors.
Energies 11 01623 g002
Figure 3. The output power of deloaded WTG.
Figure 3. The output power of deloaded WTG.
Energies 11 01623 g003
Figure 4. Control laws of the deloaded WTG.
Figure 4. Control laws of the deloaded WTG.
Energies 11 01623 g004
Figure 5. Different responses of deloaded WTG.
Figure 5. Different responses of deloaded WTG.
Energies 11 01623 g005
Figure 6. Block diagram of H control.
Figure 6. Block diagram of H control.
Energies 11 01623 g006
Figure 7. Simulation results when Vw is 13.5 m/s. (a) output power of diesel generator; (b) output power of WTG; (c) isolated grid frequency; (d) torque compensation component; (e) pitch angle.
Figure 7. Simulation results when Vw is 13.5 m/s. (a) output power of diesel generator; (b) output power of WTG; (c) isolated grid frequency; (d) torque compensation component; (e) pitch angle.
Energies 11 01623 g007
Figure 8. Simulation results when Vw is 10 m/s. (a) output power of diesel generator; (b) output power of WTG; (c) isolated grid frequency; (d) torque compensation component.
Figure 8. Simulation results when Vw is 10 m/s. (a) output power of diesel generator; (b) output power of WTG; (c) isolated grid frequency; (d) torque compensation component.
Energies 11 01623 g008
Figure 9. Experimental platform.
Figure 9. Experimental platform.
Energies 11 01623 g009
Figure 10. Experimental results when Vw is 13.5 m/s.
Figure 10. Experimental results when Vw is 13.5 m/s.
Energies 11 01623 g010
Figure 11. Experimental results when Vw is 10 m/s.
Figure 11. Experimental results when Vw is 10 m/s.
Energies 11 01623 g011
Figure 12. Wind speed.
Figure 12. Wind speed.
Energies 11 01623 g012
Figure 13. Experiment results when wind speed changes.
Figure 13. Experiment results when wind speed changes.
Energies 11 01623 g013
Table 1. Output Characteristics of the Deloaded WTG at 10 m/s.
Table 1. Output Characteristics of the Deloaded WTG at 10 m/s.
Te,com (pu)ωr (pu)Te (pu)Pe (pu)Power Reserve (pu)
−0.20.97370.54430.52990~0.0488
−0.10.95910.56230.5393−0.0094~0.0394
00.91950.60880.5598−0.0299~0.0189
0.10.87720.6540.5737−0.0438~0.005
0.20.83060.69670.5787−0.0488~0
Table 2. Output Characteristics of the Deloaded WTG at 13.5 m/s.
Table 2. Output Characteristics of the Deloaded WTG at 13.5 m/s.
Te,com (pu)ωr (pu)Te (pu)Pe (pu)Power Reserve (pu)
−0.21.050.65710.70~0.3
−0.11.050.75710.795−0.095~0.205
01.050.85710.9−0.2~0.1
0.11.050.95711−0.3~0
Table 3. Parameters of Isolated Grid.
Table 3. Parameters of Isolated Grid.
SystemParametersValues
Diesel generatorRated power10 kW
-Rated voltage400 V
-Rated frequency50 Hz
Constant loadRated power5.5 kW
Electronic loadRated power10 kW
Wind turbineRated speed12 m/s
PMSGRated power10 kW
Table 4. Comparison with different control methods in simulation and experiment.
Table 4. Comparison with different control methods in simulation and experiment.
Control StrategyMPPT ControlDroop ControlH Control
SimulationCase 1, Pe,commax0450 W570 W
Case 1, fdev,min−0.69 Hz−0.5 Hz−0.45 Hz
Case 2, Pe,commax0354 W420 W
Case 2, fdev,min−0.71 Hz−0.55 Hz−0.52 Hz
ExperimentCase 1, Pe,commax0340 W400 W
Case 1, fdev,min−0.64 Hz−0.52 Hz−0.48 Hz
Case 2, Pe,commax0200 W300 W
Case 2, fdev,min−0.66 Hz−0.6 Hz−0.56 Hz
Table 5. Comparison with different control methods when wind speed changes.
Table 5. Comparison with different control methods when wind speed changes.
Control StrategyMPPT ControlDroop ControlH Control
Maximum of Pe10 kW9 kW9 kW
Minimum of Pe6.2 kW6.0 kW6.2 kW
Maximum of fdev0.2 Hz0.1 Hz0.1 Hz
Minimum of fdev−0.9 Hz−0.58 Hz−0.52 Hz

Share and Cite

MDPI and ACS Style

Wang, H.; Yang, J.; Chen, Z.; Ge, W.; Hu, S.; Ma, Y.; Li, Y.; Zhang, G.; Yang, L. Gain Scheduled Torque Compensation of PMSG-Based Wind Turbine for Frequency Regulation in an Isolated Grid. Energies 2018, 11, 1623. https://doi.org/10.3390/en11071623

AMA Style

Wang H, Yang J, Chen Z, Ge W, Hu S, Ma Y, Li Y, Zhang G, Yang L. Gain Scheduled Torque Compensation of PMSG-Based Wind Turbine for Frequency Regulation in an Isolated Grid. Energies. 2018; 11(7):1623. https://doi.org/10.3390/en11071623

Chicago/Turabian Style

Wang, Haixin, Junyou Yang, Zhe Chen, Weichun Ge, Shiyan Hu, Yiming Ma, Yunlu Li, Guanfeng Zhang, and Lijian Yang. 2018. "Gain Scheduled Torque Compensation of PMSG-Based Wind Turbine for Frequency Regulation in an Isolated Grid" Energies 11, no. 7: 1623. https://doi.org/10.3390/en11071623

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop