A Three-Level Neutral-Point-Clamped Converter Based Standalone Wind Energy Conversion System Controlled with a New Simplified Line-to-Line Space Vector Modulation †

1
Laboratoire d’Electronique de Puissance, UER-ELT, Ecole Militaire Polytechnique (EMP), BP 17 Bordj-El-Bahri, Alger 16111, Algeria
2
Ecole Supérieure des Techniques Aéronautiques et de Construction Automobile (ESTACA), BP 76121, 53061 Laval, France
3
Laboratoire d’Electrotechnique et d’Electronique de Puissance de Lille (L2EP), Centrale Lille, Cité Scientifique, BP 48, 59651 Villeneuve d’Ascq, France
4
Grenoble INP, Université de Grenoble Alpes, CNRS, G2Elab, 38000 Grenoble, France
*
Author to whom correspondence should be addressed.
This paper is an extended version of our paper published in the 21st European Conference on Power Electronics and Applications (EPE’19 Europe), Genova, Italy, 3–5 March 2019.
Energies 2024, 17(9), 2214; https://doi.org/10.3390/en17092214
Submission received: 16 December 2023 / Revised: 12 April 2024 / Accepted: 16 April 2024 / Published: 4 May 2024

Abstract

:
Wind power systems, which are currently being constructed for the electricity worldwide market, are mostly based on Doubly Fed Induction Generators (DFIGs). To control such systems, multilevel converters are increasingly preferred due to the well-known benefits they provide. This paper deals with the control of a standalone DFIG-based Wind Energy Conversion System (WECS) by using a three-level Neutral-Point-Clamped (NPC) converter. The frequency and magnitude of the stator output voltage of the DFIG are controlled and fixed at nominal values despite the variable rotor speed, ensuring a continuous AC supply for three-phase loads. This task is achieved by controlling the DFIG rotor currents via a PI controller combined with a new Simplified Direct Space Vector Modulation strategy (SDSVM), which is applied to the three-level NPC converter. This strategy is based on the use of a line-to-line three-level converter space vector diagram without using Park transformation and then simplifying it to that of a two-level converter. The performance of the proposed SDSVM technique in terms of controlling the three-level NPC-converter-based standalone WECS is demonstrated through simulation results. The whole WECS control and the SDSVM strategy are implemented on a dSPACE DS 1104 board that drives a DFIG-based wind system test bench. The obtained experimental results confirm the validity and performance in terms of control.

1. Introduction

Recently, there has been a strong trend toward wind energy utilization either for grid connection or for household supply [1,2,3]. Hence, new wind generators of several MW have been developed and are currently being installed worldwide for use in high-power wind generation systems [4,5,6]. In these power systems, DFIGs are more commonly used due to their variable speed operating abilities, with four-quadrant active and reactive power capabilities [2,7]. Furthermore, the PWM converters that are in use are designed to flow only the slip power, which is roughly 30% of the nominal generated electricity, thanks to the reduced power flowed by the rotor windings of a DFIG [7,8].
Despite the advantages in terms of reducing the PWM converter rating, the increased power of recent wind turbines requires the use of parallel connections of several back-to-back two-level converter modules to increase the transferred total power [7,9]. Hence, high power is transferred by the current rather than the voltage and, as a result, the high current can be handled and greater power losses in the conversion systems are achieved.
In order to enhance system yield and reduce the power loss in these conversion systems, multilevel PWM converters are increasingly preferred due to the advantages that they provide [10,11]. In fact, they increase the power rating thanks to their increased output-modulated voltages since the blocking voltage of each switch is one-half that of the DC link voltage [9,10,11,12]. Furthermore, their output voltage waveform is improved and, consequently, the voltage harmonic content is reduced compared to that of two-level converters with the same switching frequency [13,14].
To control these converters, many control strategies have been proposed and developed [12,15,16,17,18]. Three-hysteresis comparator control has been considered the simplest control strategy, but it suffers from high-frequency operation and phase current interactions [12]. The Carrier-Based Modulation (CBM) method uses a combination of a triangular carrier and a phase reference signal. Hence, a complex analog circuit is required. Nevertheless, devices have to be added to the CBM to balance the DC link voltage. In addition to this, interference between the three phases can be created since each phase is controlled separately. Contrary to this, Space Vector Modulation (SVM) strategies gather the three phase references in one entity to avoid phase interference, but most of them employ complex dwelling time computation due to the use of complicated transformations, especially for multilevel inverters.
This paper presents a new SDSVM for a three-level NPC-converter-based standalone WECS (Figure 1) to control the frequency and magnitude of DFIG stator output voltages supplying an isolated load. The advantage of this proposed SDSVM compared to the CBM is the fact that it can gather the three phase reference signals into one entity vector without any complex analog circuitry, avoiding interference between the three phases. Similarly, its advantage compared to other conventional SVM strategies is the fact that it enables, on the one hand, the copying of directly modulated waveforms onto output voltages of a three-phase, three-level converter without using a Park transformation. On the other hand, it allows for the simplification of the line-to-line space vector diagram of a three-level converter into that of a two-level one. Therefore, the SDSVM algorithm is implemented more easily and, hence, the execution time is greatly reduced since it uses an easy time calculation based on a simple subtraction rather than a complicated matrix transformation. In addition to this, the feasibility of the SDSVM strategy for the control of the three-level-based standalone WECS is studied and analyzed for a continuous AC supplying a three-phase load.
This paper is organized as follows: in the Section 2, we briefly present the constitution and operation of the WECS. The Section 3 is devoted to the line-to-line modeling of the three-level NPC converter as well as the modeling of the DFIG. The Section 4 presents the macroscopic control of the standalone WECS with a focus on the proposed SDSVM algorithm. Finally, the Section 5 and Section 6 are dedicated, respectively, to proving the validity and efficiency of the proposed scheme through simulations and experimental results.

2. Standalone WECS Presentation

A representation of the standalone WECS when feeding an isolated load is given in Figure 1. It is composed of a small-scale wind turbine coupled to a Permanent Magnet Synchronous Machine (PMSM) and DFIG through a gearbox. The back-to-back three-level NPC converter is connected to the PMSM to provide the appropriate DC link voltage, and it is also linked to an isolated load that provides the required supply of electricity. Thus, the DFIG-side converter controls the frequency and magnitude of the stator output voltage of the DFIG in order to ensure a continuous AC supply for the three-phase load, whereas the PMSM-side converter controls the DC link voltage. This paper deals mainly with DFIG control via a three-level NPC converter, focusing on the application of the proposed SDSVM technique. Thus, the next section concerns the modeling of both the three-level NPC converter and the DFIG.

3. Standalone WECS Modeling

3.1. Line-to-Line Conversion Modeling of the Three-Level NPC Converter

Figure 2 demonstrates the structure of the DFIG-side three-level NPC converter, which consists of three commutation circuits fed by a capacitive voltage divider. The voltage across the two capacitors, us1 and us2, must be controlled to be equal to half the value of the full DC voltage us to ensure the good operation of the NPC converter.
u s 1 = u s 2 = u s 2
Line-to-line voltage (um1, um2) modeling of the DFIG-side three-level NPC converter is now detailed and will be used by the proposed SDSVM rather than voltage coordinates in the αβ reference frame.
The first clamped commutation circuit (Figure 3a) is considered in order to present the operating of the NPC converter.
-
In the case where the switches T1c and T2c are on, the output voltage vm1 is equal to u s .
-
In the case where the switches T2c and T3c are on, the output voltage vm1 is equal to u s 1 = u s / 2 .
-
In the case where the switches T3c and T4c are on, the output voltage vm1 is equal to 0.
Figure 3. The figure shows an equivalent commutation circuit: (a) first clamped commutation circuit; (b) first equivalent commutation circuit.
Figure 3. The figure shows an equivalent commutation circuit: (a) first clamped commutation circuit; (b) first equivalent commutation circuit.
Energies 17 02214 g003
Therefore, this clamped commutation circuit is equivalent to a commutation circuit whose one ideal switch among the three is at any time switched on (Figure 3b).
The switch states are modeled using switching functions (frc). The index r corresponds to a row, and c corresponds to a commutation circuit. If frc = 1, the corresponding ideal switch (and so a corresponding transistor) is closed. Otherwise, if frc = 0, it is open. Thus, switching functions in the equivalent commutation circuit depend on transistor gate signals, as follows:
f 1 c = T 1 c , f 3 c = T 4 c , f 2 c = T 2 c . T 3 c
All of the ideal switches are represented in a matrix containing vertical equivalent commutation circuits (Figure 4).
Only two line-to-line modulated voltages um1 and um2 are considered:
{ u m 1 = v m 1 v m 3 = ( f 11 f 13 ) u s + ( f 21 f 23 ) u s 2 u m 2 = v m 2 v m 3 = ( f 12 f 13 ) u s + ( f 22 f 23 ) u s 2
The modulated currents im1 and im2 are expressed as follows:
{ i m 1 = ( f 11 f 13 ) i r 1 + ( f 21 f 23 ) i r 2 i m 2 = ( f 12 f 13 ) i r 1 + ( f 22 f 23 ) i r 2
We define conversion functions (mrc) as follows [19]:
{ m 11 = f 11 f 13 m 12 = f 12 f 13 m 21 = f 21 f 23 m 22 = f 22 f 23
m r c = f r c f r 3
By replacing (5) in Equations (3) and (4) we find the following:
{ u m 1 = m 11 u s + m 21 u s 2 u m 2 = m 12 u s + m 22 u s 2
{ i m 1 = m 11 i r 1 + m 21 i r 2 i m 2 = m 12 i r 1 + m 22 i r 2

3.2. DFIG Based WECS Modeling

To establish the DFIG model, it is convenient to refer to the electric equations of the rotating Park reference frame that is synchronized with the stator flux (Figure 5) since the DFIG-based WECS presented in this study supplies an isolated load via its stator voltages.
In the Park reference frame, the DFIG stator electric equations are given as follows [8,20,21,22,23]:
{ v s d = R s i s d + d ϕ s d d t ω s ϕ s q v s q = R s i s q + d ϕ s q d t + ω s ϕ s d v r d = R r i r d + d ϕ r d d t ω r ϕ r q v r q = R r i r q + d ϕ r q d t + ω r ϕ r d
The stator and rotor flux are given as follows:
{ ϕ s d = L s i s d + L m i r d ϕ s q = L s i s q + L m i r q ϕ r d = L r i r d + L m i s d ϕ r q = L r i r q + L m i s q
Rs and Ls are, respectively, the resistances and inductances of the stator windings, and Lm is the mutual inductance.
Vsd, vsq, vrd, vrq, isd, isq, ird, irq, ϕsd, ϕsq, ϕrd, and ϕrq are the d and q components of the stator and rotor voltages, currents, and flux. ωr and ωs are, respectively, the electric rotor and stator pulsations in rad/s.
Rotor speed ωr is deduced from stator speed ωs and mechanical speed Ω as follows:
ω r = ω s p Ω
where Ω is the mechanical speed in rad/s, and p is the pole pair number.
The angle θr is obtained by integrating the previous equation
θ r = t 0 t 0 + Δ t ω r d t + θ r 0
Since the stator flux is oriented with d axis, the following conditions can be set:
{ ϕ s q = d ϕ s q d t = 0 ϕ s d = ϕ s
Voltage and flux equations of the stator windings can be simplified in a steady state by assuming that the resistance of the stator winding Rs is neglected:
{ v s d = 0 v s q = v s = ω s ϕ s
{ ϕ s d = ϕ s = L s i s d + L m i r d ϕ s q = 0 = L s i s q + L m i r q
From Equation (15), the equations relating the stator currents to the rotor currents are given as follows:
{ i s d = ϕ s L s L m L s i r d i s q = L m L s i r q
From Equations (10) and (16), the following expressions can be deduced:
{ i r q = L s L m i s q ϕ r q = σ L s L r L m i s q
where σ = 1 L m 2 L s L r
{ v r d = R r i r d + σ L r d i r d d t e q v r q = R r i r q + σ L r d i r q d t + e d + e ϕ
where
{ e q = ω r σ L r i r q e d = ω r σ L r i r d e ϕ = ω r L m L s ϕ s

4. Standalone WECS Control

4.1. Overall WECS Control

Several recent pieces of research on DFIG-based WECS control techniques can be distinguished [24,25,26,27]. In a standalone WECS mode, the frequency and magnitude of the DFIG stator output voltage have to be controlled and should be fixed at nominal values, regardless of the variable rotor speed [28]. Three control stages can be distinguished in the control method (Figure 6): the first control stage is dedicated to regulating the stator voltage magnitude to the desired value Vs_ref, while the second control stage is devoted to rotor current control. The third control stage deals with three-level NPC converter control by using the proposed SDSVM technique.
The measured d and q components of the stator voltage (vsd, vsq) are used to calculate the magnitude of the output voltage vector:
v s = v s d 2 + v s q 2
The rotor frequency fr is adjusted somehow to regulate the stator frequency to its nominal value simply by verifying the following equation:
f r = | f s p Ω 2 π |
Since the control inputs of the DFIG are the rotor currents, it is convenient to express the stator voltage versus the rotor currents, and this is achieved by substituting the stator flux components given in Equation (10) in Equation (9). Thus, the DFIG stator voltages can be rewritten as follows:
{ v s d = R s i s d + L s d i s d d t + L m d i r d d t ω s ϕ s q v s q = R s i s q + L s d i s q d t + L m d i r q d t + ω s ϕ s d
In a steady state, the DFIG stator voltages can be expressed as follows:
{ v s d = R s i s d ω s ϕ s q v s q = R s i s q + ω s ϕ s d
The stator resistance is neglected (Rs = 0), and by replacing the stator flux components with the expressions given in Equation (10) in Equation (23), it yields:
{ v s d = ω s L m ( i r q + A d ) v s q = + ω s L m ( i r d + A q )
where
{ A d = R s ω s L m i s d L s L m i s q A q = R s ω s L m i s q L s L m i s d

4.2. DFIG Rotor Current Control

The second stage is devoted to the rotor current controller. The rotor currents of the DFIG are sensed and transformed to the dq reference frame by using a Park transformation. Then, their control is ensured using two PI controllers (Figure 7) after they are compared to their references. The d and q components of the DFIG rotor voltage reference vrd_ref and vrq_ref are thus evaluated (Figure 7). Thanks to the modeling provided by Equation (19), the emf coupling of d_ref, q_ref, and Φ_ref are estimated from the measured rotor and stator currents of the DFIG, rotor current pulsation ωr and estimated d component of the stator flux ϕ ˜ s d , as follows:
{ e ˜ q _ r e f = L r ω r σ i r q e ˜ d _ r e f = L r ω r σ i r d e ˜ ϕ _ r e f = ω r L m L s ϕ ˜ s d

4.3. Simplified Direct Space Vector Modulation (SDSVM)

After controlling the rotor currents, the voltage references vrd_ref and vrq_ref issued from the DFIG rotor current controller (Figure 7) have to be transformed to vmref1, vmref2 and vmref3 by using Park−1 transformation in equilibrium with the three-phase system.
{ [ v m r e f 1 v m r e f 2 v m r e f 3 ] = [ cos θ r sin θ r cos ( θ r 2 π / 3 ) sin ( θ r 2 π / 3 ) cos ( θ r + 2 π / 3 ) sin ( θ r + 2 π / 3 ) ] [ v r d _ r e f v r q _ r e f ]
The proposed SDSVM strategy has to control the three-level NPC converter in the line-to-line (um1, um2) reference frame. The global schematic of the SDSVM (Figure 8) consists of three blocks: hexagon detection, sector detection, and voltage vector selection and duration calculation.
The main principle of this modulation strategy is to divide the line-to-line space vector diagram of the three-level converter into six small hexagons that are the space vector diagram in the line-to-line reference frame of a conventional two-level inverter (Figure 9). As illustrated, the hexagons (H1, H3, H4, and H6) shift from the center by u s / 2   , whereas the hexagons (H2 and H5) shift by 2 u s / 2 [29]. Two procedures must be completed to transform the three-level space vector frame to the two-level space vector frame:
  • Only one hexagon must be selected among the six, and this is performed according to the location of a given reference voltage.
  • The original reference voltage vector must be subtracted from the amount of the center voltage vector of the selected hexagon (Figure 9).
Hence, the determination of the switching sequence and the calculation of the voltage vector duration are carried out for a two-level direct SVM [30].

4.3.1. Hexagon Detection and Reference Vector Correction

At first, the modulated voltage references vmref1, vmref2 and vmref3, issued from Equation (27) have to be transformed into line-to-line voltages.
{ u m r e f 1 = v m r e f 1 v m r e f 3 u m r e f 2 = v m r e f 2 v m r e f 3
Then, the space vector diagram in the frame (um1, um2) is divided into six hexagons (H1H6) (Figure 9).
Each hexagon is defined according to the angle θ between the um2-axis and the reference voltage vector u m r e f .
θ = a r c t g u m r e f 1 u m r e f 2
Table 1 gives the conditions that must be satisfied for the reference voltage vector u m r e f to belong to each particular hexagon. Once the small hexagon is detected, the correction of the voltage vector should be performed by considering the hexagon number Hi.
  • In the case where the reference voltage vector   u m r e f belongs to one of the following hexagons (H1 or H3 or H4 or H6), then the new corrected reference voltage vector u m r e f _ c is given as follows:
    u m r e f _ c =   u m r e f + u s / 2
  • In the case where the reference voltage vector   u m r e f belongs to one of the following hexagons (H2 or H5), then the new corrected reference voltage vector u m r e f _ c is given as follows:
    u m r e f _ c = u m r e f + 2 u s / 2

4.3.2. Sector Detection

Once the hexagon is identified and the voltage vector corrected, the sector should be identified in the same way, according to the angle θ c between the um2-axis and the new reference voltage vector u m r e f _ c (Figure 10). Thus, six triangular sectors (S1S6) can be distinguished.
θ c = a r c t g u m r e f 1 _ c u m r e f 2 _ c
Table 2 gives the conditions that must be satisfied for the reference voltage vector u m r e f _ c to belong to each particular sector Si.

4.3.3. Voltage Vector Selection and Duration Calculation

In this stage, the proposed SDSVM strategy uses the nearest two voltage vectors. Therefore, the choice of the two selected voltage vectors has to be modified according to hexagon Hi first and then sector Si, where the reference voltage vector is located.
The duration of each vector is determined by the obtained projections onto the frame vectors (um1, um2). For example, for a desired modulation vector located in sector S1 (Figure 11), the three selected vectors are u 5 , u 4 , and   u 0   o r   u 7 . Their respective durations (t1, t2, and t0) and the modulation time Tm are expressed according to the following:
u m r e f _ c = t 1 T m u 5 + t 2 T m u 4 + t 0 T m u 0
In fact, only two durations must be determined because all durations must be equal to the modulation period:
T m = t 1 + t 2 + t 0
In order to obtain parallel projections with vectors u m 1 and u m 2 , the duration of the zero vector will always be determined according to the others. For our example, we achieved the following:
u m r e f _ c = t 1 T m u 5 + t 2 T m u 4 + ( T m t 1 t 2 ) T m u 0
The above equation can be rewritten as follows:
u m r e f _ c = t 1 T m ( u 5 u 0 ) + t 2 T m ( u 4 u 0 ) + u 0
Using the projection already mentioned on the um1-axis and um2-axis, we obtain the following:
On the um1-axis:
{ u 5 u 0 = 0 u 4 u 0 = 2 u s
On the um2-axis:
{ u 5 u 0 = u s u 4 u 0 = 2 u s
Hence, the durations t1 and t2 are obtained using (36)–(38), as follows:
{ t 1 = u m r e f 2 _ c u m r e f 1 _ c u s T m t 2 = 2 u m r e f 1 _ c u s T m
We assume that
{ X = u m r e f 2 _ c u s T m Y = u m r e f 1 _ c u s T m
Therefore, the durations of t1, t2, and t0 are given as follows:
{ t 1 = X Y t 2 = 2 Y t 0 = T m t 1 t 2
The calculation of the durations t1 and t2 in the six sectors are summarized in Table 3 [29].
For the five remaining hexagons (H2H6), the duration calculation can be established in the same way. The use of redundant voltage vectors allows for DC link voltage balancing [12,14,19] according to the sign of Δus (us1us2) and the sign of the three rotor currents of the DFIG.

5. Simulation Results

In order to verify the theoretical study of the three-level NPC-converter-based standalone WECS controlled with the proposed SDSVM strategy, the numerical simulation of the complete standalone DFIG-based WECS and its control has been performed by using MATLAB/Simulink software 2013b. The simulation results were obtained using the following elements: a DFIG with a 6 kVA three-level converter; f = 5 kHz; capacitors C1 = C2 = 750 µF; a three-phase load of Rl = 30 Ω; Ll = 5 mH; and DC link voltage of us = 600 V.
Figure 12a shows that the overall WECS system is well controlled since the measured output voltage is well regulated to its reference despite variations in the rotating speed of the wind turbine, which varies from 1000 rpm to 2000 rpm (Figure 12b). The good regulation is confirmed by the small value of the mean square error of the observed variable Vs with respect to the reference Vs_ref, which is equal to 0.25. The voltages us1 and us2 across the capacitors C1 and C2 are equal (Figure 12c); hence, the DC link voltage is balanced. This result confirms that the proposed SDSVM scheme adheres to the redundant converter switching states. Figure 12d displays the reference-modulated voltages and the voltage vectors used for the three-level NPC converter that are drawn in the plan (um1, um2). Figure 12e,f illustrates the modulated line-to-line output voltage of the three-level NPC converter and its respective single-sided amplitude spectrum. The calculated THD of the modulated line-to-line output voltage is −30.034.
In order to test the robustness of the overall control system, Figure 13 demonstrates the simulation results of standalone WECS control with load variation. In fact, a scenario that simulates the connection and disconnection of a second load at times t = 0.5 s and t = 1.5 s, respectively, is considered. Figure 13a shows that the DFIG stator output voltage is well regulated even during the connection or disconnection of other loads. Figure 13b illustrates the active and reactive powers produced by the DFIG and consumed by the three-phase load during this transient time. The three-phase load currents and also their zoom are displayed in Figure 13c,d. The results presented in this figure prove the robustness of the overall control system, even with load variation.

6. Experimental Results

A laboratory experimental test bench was built (Figure 14) to confirm the validity of the proposed SDSVM technique in controlling a three-level NPC converter supplying a simple three-phase load (Figure 14a). Then, this technique was implemented to control the voltage and frequency of the whole standalone DFIG-based WECS (Figure 14b), which consists of a wind turbine emulator based on a torque-controlled DC machine, a PMSM, a DFIG, and a three-level NPC converter. The last component was designed for 6 kVA drive operation, with 400 V, 50 Hz AC, and a DC voltage of us = 250 V with 1500 µF/350 V capacitors. The power modules were two bridged insulated gate bipolar transistors (IGBTs), which were packed into one module. Hall effect sensors were used to sense the required currents and voltages for the control method. The proposed SDSVM technique, as well as the standalone DFIG-based WECS control strategy, were both implemented on a dSPACE DS1104 board.
Figure 15 displays the experimental results of the three-level NPC controlled by the proposed SDSVM supplying a three-phase load. Figure 15a displays the modulated line-to-line voltages um1, the modulated line-to-neutral voltage vm1, and the load current iL1. Figure 15b shows the evolution of the DC link voltage us as well as voltages us1 and us2 across the upper and lower capacitors during the balancing procedure. It can be clearly seen that after time t1 (the beginning time of the balancing procedure execution), the voltages of both capacitors converged to an equal value after 400 ms. This is due to the capability of the proposed SDSVM to adhere to the redundant NPC converter switching states. The angles θ (between the um2-axis and the reference voltage vector umref) and θc (between the um2-axis and the new reference voltage vector umref_c) are shown in Figure 15c. In addition, Figure 15d shows the hexagon and the sector in which the voltage vector reference tip is located. It is clearly shown that hexagon H and sector S have a staircase shape and, therefore, the reference voltage vector will certainly sweep the six hexagons and the six sectors. Figure 15e illustrates the line-to-line output voltage together with its respective single-sided amplitude spectrum. Figure 15f shows the waveform of the line-to-line voltage, load current, and DC link voltage with a step change in the frequency (from 50 Hz to 100 Hz) of the voltage reference. This result confirms the validity of the SDSVM, even during a transient state.
To confirm the overall control of the standalone WECS when using the proposed SDSVM technique, we provided Figure 16. In fact, Figure 16a displays the steady-state waveforms of the three-level converter line-to-line output voltage, DFIG rotor current, DFIG stator current, and DFIG stator voltage. It is obvious that the rotor current frequency is smaller than that of the stator current. Figure 16b illustrates the used voltage vectors of the three-level NPC converter in the (um1, um2) plan.
From Figure 16c, it is clear that the rms output voltage and frequency have achieved their references even with load variation. This is due to the good control of the DFIG rotor current, and consequently, the output voltage of the NPC converter (Figure 16d). Thus, these results confirm the robustness of the control system even under load variation. It was noted that due to the load change, the voltage establishment time was 50 ms, and the frequency establishment time was 80 ms. Figure 16e,f illustrates the experimental waveforms of system control during step-up and step-down changes in the rms voltage reference, respectively. Moreover, it can be clearly seen that during these changes, the regulated rms voltage follows its reference. It can also be noted that the voltage establishment time due to the step-up change in the reference voltage is 160 ms, whereas, for the step-down change, it is 160 ms.
The results provided in this figure prove the efficiency of the proposed control for both steady and transient states.

7. Conclusions

In this paper, the control of a standalone DFIG-based WECS using a three-level NPC converter has been presented. The main purpose of this work is to regulate the magnitude and frequency of the output voltage when supplying three-phase AC loads. In order to accomplish this task, the rotor currents of the DFIG were controlled by using the proposed SDSVM combined with two PI controllers. This technique provided ease of implementation since it allows us to copy directly modulated waveforms onto the output voltages of a three-phase, three-level converter without using a Park transformation. Furthermore, it also permits the simplification of the line-to-line space vector diagram of a three-level converter to that of a two-level converter. This SDSVM can be easily extended for use in high-order multilevel converters. The validity of the proposed technique for standalone DFIG-based WECS control was verified via simulation and validated with a laboratory experimental test bench of a three-level converter-based standalone WECS. The presented simulation and experimental results have confirmed the validity of the proposed SDSVM and demonstrated the good performance of the standalone DFIG-based WECS when using a three-level NPC converter.

Author Contributions

Methodology, T.G.; Software, T.G.; Validation, T.G.; Formal analysis, L.B., B.F. and S.B.; Resources, L.B. and N.R.; Writing—original draft, T.G.; Writing—review & editing, B.F.; Supervision, B.F. and S.B. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Data Availability Statement

The original contributions presented in the study are included in the article, further inquiries can be directed to the corresponding author.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Zhang, C.; Wang, L.; Wu, X.; Gao, X. Performance analysis and design of a new-type wind-motor hybrid power pumping unit. Electr. Power Syst. Res. 2022, 208, 107931. [Google Scholar] [CrossRef]
  2. Li, Z.L.; Li, P.; Yuan, Z.P.; Xia, J.; Tian, D. Optimized utilization of distributed renewable energies for island microgrid clusters considering solar-wind correlation. Electr. Power Syst. Res. 2022, 206, 107822. [Google Scholar] [CrossRef]
  3. Behabtu, H.A.; Coosemans, T.; Berecibar, M.; Fante, K.A.; Kebede, A.A.; Mierlo, J.V.; Messagie, M. Performance evaluation of grid-connected wind turbine generators. Energies 2021, 14, 6807. [Google Scholar] [CrossRef]
  4. Dannier, A.; Fedele, E.; Spina, I.; Brando, G. Doubly-fed induction generator (DFIG) in connected or weak grids for turbine-based wind energy conversion system. Energies 2022, 15, 6402. [Google Scholar] [CrossRef]
  5. Porte-Agel, F.; Bastankhah, M.; Shamsoddin, S. Wind-turbine and wind-farm flows: A review. Bound.-Layer Meteorol. 2020, 174, 1–59. [Google Scholar] [CrossRef] [PubMed]
  6. Ahmed, S.D.; Al-Ismail, F.S.M.; Shafiullah, M.; Al-Sulaiman, F.A.; El-Amin, I.M. Grid integration challenges of wind energy: A review. IEEE Access 2020, 8, 10857–10878. [Google Scholar] [CrossRef]
  7. Ghennam, T. Supervision d’une Ferme Eolienne Pour son Intégration Dans la Gestion d’un Réseau Electrique, Apports des Convertisseurs Multi-Niveaux au Réglage des Eoliennes à Base de Machine Asynchrone à Double Alimentation. Ph.D. Thesis, École Centrale de Lille, Villeneuve-d’Ascq, France, EMP, Algiers, Algeria, 2010. [Google Scholar]
  8. Ghennam, T.; Berkouk, E.M.; Francois, B. Modeling and Control of a doubly fed induction generator based wind conversion system. In Proceedings of the International Conference on Power Engineering, Energy and Electrical Drives (POWERENG 2009), Lisbon, Portugal, 18–20 March 2009. [Google Scholar]
  9. Yaramasu, V.; Dekka, A.; JDurán, M.; Kouro, S.; Wu, B. PMSG-Based wind energy conversion systems: Survey on power converters and controls. IET Electr. Power Appl. 2017, 11, 956–968. [Google Scholar] [CrossRef]
  10. Karad, S.; Thakur, R. Recent trends of control strategies for doubly fed induction generator based wind turbine systems: A comparative review. Arch. Comput. Methods Eng. 2021, 28, 15–29. [Google Scholar] [CrossRef]
  11. Yaramasu, V.; Dekka, A.; Kourou, S. Multilevel converters for renewable energy systems. In Multilevel Inverters, Control Methods and Advanced Power Electronics; Academic Press: Cambridge, MA, USA, 2021; Volume 6, pp. 155–184. [Google Scholar]
  12. Ghennam, T.; Berkouk, E.M.; Francois, B. A novel space vector current control based on circular hysteresis areas of a three-phase neutral-point-clamped inverter. IEEE Trans. Ind. Electron. 2010, 57, 2669–2678. [Google Scholar] [CrossRef]
  13. Amjad, A.M.; Mehran, K.; Gadoue, S.; Blaabjerg, F. Online harmonic elimination pulse width modulation technique for modular multilevel cascade converter. Int. J. Electr. Power Energy Syst. 2021, 133, 107242. [Google Scholar] [CrossRef]
  14. Ghennam, T.; Berkouk, E.M. Back-to-back three-level converter controlled by a novel space-vector hysteresis current control for wind conversion systems. Electr. Power Syst. Res. 2010, 80, 444–455. [Google Scholar] [CrossRef]
  15. Espinoza, M.; Cárdenas, R.; Diaz, M.; Clare, J.C. An enhanced dq-based vector control system for modular multilevel converters feeding variable speed drives. IEEE Trans. Ind. Electron. 2017, 64, 2620–2630. [Google Scholar] [CrossRef]
  16. Aguilera, R.P.; Acuña, P.; Lezana, P.G.; Konstantinou, G.; Wu, B.; Bernet, S.; Agelidis, V.G. Selective harmonic elimination model predictive control for multilevel power converters. IEEE Trans. Power Electron. 2017, 32, 2416–2426. [Google Scholar] [CrossRef]
  17. Yang, S.; Tang, Y.; Wang, P. Distributed control for a modular multilevel converter. IEEE Trans. Power Electron. 2018, 33, 5578–5591. [Google Scholar] [CrossRef]
  18. Liu, X.; Qiu, L.; Wu, W.; Ma, J.; Fang, Y.; Peng, Z.; Wang, D. Efficient model-free predictive power control for active front-end modular multilevel converter. Int. J. Electr. Power Energy Syst. 2021, 132, 107058. [Google Scholar] [CrossRef]
  19. Francois, B.; Semail, E. Modeling and Control of a Three-Phase Neutral-Point-Clamped Inverter by Means of a Direct Space Vector Control of Line to Line Voltages. In Proceedings of the 10th European Power Electronics and Motion Control Conference (EPE-PEMC 2002), Cavtat & Dubrovnik, Croatia, 9–11 September 2002. [Google Scholar]
  20. Ko, H.S.; Yoon, G.G.; Kyung, N.H.; Hong, W.P. Modeling and control of DFIG-based variable-speed wind-turbine. Electr. Power Syst. Res. 2008, 78, 1841–1849. [Google Scholar] [CrossRef]
  21. Zamanifar, M.; Fani, B.; Golshan, M.E.H.; Karshenas, H.R. Dynamic modeling and optimal control of DFIG wind energy systems using DFT and NSGA-II. Electr. Power Syst. Res. 2014, 108, 50–58. [Google Scholar] [CrossRef]
  22. Somoro, M.A.; Memon, Z.A.; Kumar, M.; Baloch, M.H. Wind energy integration: Dynamic modeling and control of DFIG based on super twisting fractional order terminal sliding mode controller. Energy Rep. 2021, 7, 6031–6043. [Google Scholar] [CrossRef]
  23. Khatounian, F.; Monmasson, E.; Berthereau, F.; Delaleau, E.; Louis, J.P. Control of a doubly fed induction generator for aircraft application. In Proceedings of the IECON’03. 29th Annual Conference of the IEEE Industrial Electronics Society (IEEE Cat. No. 03CH37468), Roanoke, VA, USA, 2–6 November 2003; pp. 2711–2716. [Google Scholar]
  24. Bekiroglu, E.; Yazar, M.D. MPPT Control of grid connected DFIG at variable wind speed. Energies 2022, 15, 3146. [Google Scholar] [CrossRef]
  25. Behara, R.K.; Saha, A.K. neural network predictive control for improved reliability of grid-tied DFIG-based wind energy system under the three-phase fault condition. Energies 2023, 16, 4881. [Google Scholar] [CrossRef]
  26. Chhipą, A.A.; Chakrabarti, P.; Bolshev, V.; Chakrabarti, T.; Alexey, G.S.; Vasilyev, N.; Ghosh, S.; Kudryavtsev, A. modeling and control strategy of wind energy conversion system with grid-connected doubly-fed induction generator. Energies 2022, 15, 6694. [Google Scholar] [CrossRef]
  27. Aljafari, B.; Stephenraj, J.P.; Vairavasundaram, I.; Rassiah, R.S. Steady state modeling and performance analysis of a wind turbine-based doubly fed induction generator system with rotor control. Energies 2022, 15, 3327. [Google Scholar] [CrossRef]
  28. Mesbahi, T.; Ghennam, T.; Berkouk, E.M. A doubly fed induction generator for wind stand-alone power applications (simulation and experimental validation). In Proceedings of the 2012 XXth International Conference on Electrical Machines, Marseille, France, 2–5 September 2012. [Google Scholar]
  29. Ghennam, T.; Belhadji, L.; Francois, B.; Bacha, S. A simplified line-to-line space vector modulation for multilevel converter applied for a standalone wind energy conversion system. In Proceedings of the 21st European Conference on Power Electronics and Applications (EPE’19 ECCE Europe), Geova, Italy, 3–5 September 2019. [Google Scholar]
  30. Akel, F.; Ghennam, T.; Laour, M.; Bendib, D.; Berkouk, E.M.; Chikh, M. Control of single stage grid connected pv-inverter based on direct space vector pwm. Prog. Clean Energy 2015, 2, 755–774. [Google Scholar]
Figure 1. The figure shows the wind conversion system.
Figure 1. The figure shows the wind conversion system.
Energies 17 02214 g001
Figure 2. The figure shows the structure of the used three-level NPC converter.
Figure 2. The figure shows the structure of the used three-level NPC converter.
Energies 17 02214 g002
Figure 4. The figure shows a diagram of a matrix converter structure with three commutation cells of three switches.
Figure 4. The figure shows a diagram of a matrix converter structure with three commutation cells of three switches.
Energies 17 02214 g004
Figure 5. The figure shows the orientation of the d, q frame.
Figure 5. The figure shows the orientation of the d, q frame.
Energies 17 02214 g005
Figure 6. The figure shows a block diagram of standalone DFIG-based WECS control.
Figure 6. The figure shows a block diagram of standalone DFIG-based WECS control.
Energies 17 02214 g006
Figure 7. The figure shows the DFIG current controller.
Figure 7. The figure shows the DFIG current controller.
Energies 17 02214 g007
Figure 8. The figure shows a global schematic of the SDSVM.
Figure 8. The figure shows a global schematic of the SDSVM.
Energies 17 02214 g008
Figure 9. The figure shows a line-to-line space vector diagram of a three-level converter.
Figure 9. The figure shows a line-to-line space vector diagram of a three-level converter.
Energies 17 02214 g009
Figure 10. The figure shows the corrected reference voltage vector in hexagon H1.
Figure 10. The figure shows the corrected reference voltage vector in hexagon H1.
Energies 17 02214 g010
Figure 11. The figure shows an expanded view of the studied sector S1.
Figure 11. The figure shows an expanded view of the studied sector S1.
Energies 17 02214 g011
Figure 12. The figure shows the simulation results of three-level NPC-converter-based standalone WECS control: (a) DFIG stator line-to-neutral rms voltage (reference and simulated); (b) wind turbine rotating speed; (c) voltage across the capacitors C1 and C2; (d) reference-modulated voltages and voltage vectors used for the three-level converter in the plan (um1, um2); (e) modulated line-to-line output voltage of the three-level NPC converter; and (f) single-sided amplitude spectrum of the line-to-line output voltage.
Figure 12. The figure shows the simulation results of three-level NPC-converter-based standalone WECS control: (a) DFIG stator line-to-neutral rms voltage (reference and simulated); (b) wind turbine rotating speed; (c) voltage across the capacitors C1 and C2; (d) reference-modulated voltages and voltage vectors used for the three-level converter in the plan (um1, um2); (e) modulated line-to-line output voltage of the three-level NPC converter; and (f) single-sided amplitude spectrum of the line-to-line output voltage.
Energies 17 02214 g012
Figure 13. The figure shows the simulation results of the standalone WECS control with load variation: (a) DFIG stator line-to-neutral rms voltage (reference and simulated); (b) active and reactive powers produced by the DFIG to the load; (c) three-phase load currents; and (d) zoom of the three-phase load currents around time 1.5 s.
Figure 13. The figure shows the simulation results of the standalone WECS control with load variation: (a) DFIG stator line-to-neutral rms voltage (reference and simulated); (b) active and reactive powers produced by the DFIG to the load; (c) three-phase load currents; and (d) zoom of the three-phase load currents around time 1.5 s.
Energies 17 02214 g013
Figure 14. The figure shows the laboratory experimental test bench: (a) experimental test bench of the three-level NPC converter supplying a three-phase load; (b) experimental test bench of the whole standalone three-level NPC-converter-based WECS.
Figure 14. The figure shows the laboratory experimental test bench: (a) experimental test bench of the three-level NPC converter supplying a three-phase load; (b) experimental test bench of the whole standalone three-level NPC-converter-based WECS.
Energies 17 02214 g014
Figure 15. The figure shows the experimental results of the three-level NPC controlled by the SDSVM supplying a three-phase load: (a) experimental waveforms of the line-to-line output voltage (200 V/div), line-to-neutral output voltage (200 V/div), and load current (3 A/div); (b) experimental waveforms of the DC link voltage (200 V/div), voltage across capacitor C1 (200 V/div), and voltage across capacitor C2 (200 V/div) during the balancing time; (c) angle evolution θ defining the hexagons, and angle evolution θc defining the sectors; (d) hexagons and sectors; (e) experimental waveforms of line-to-line output voltage (200 V/div) and single-sided amplitude spectrum; (f) experimental waveforms of line-to-line output voltages (200 V/div), load current (3 A/div), and DC link voltage (200 V/div) with a step change in frequency.
Figure 15. The figure shows the experimental results of the three-level NPC controlled by the SDSVM supplying a three-phase load: (a) experimental waveforms of the line-to-line output voltage (200 V/div), line-to-neutral output voltage (200 V/div), and load current (3 A/div); (b) experimental waveforms of the DC link voltage (200 V/div), voltage across capacitor C1 (200 V/div), and voltage across capacitor C2 (200 V/div) during the balancing time; (c) angle evolution θ defining the hexagons, and angle evolution θc defining the sectors; (d) hexagons and sectors; (e) experimental waveforms of line-to-line output voltage (200 V/div) and single-sided amplitude spectrum; (f) experimental waveforms of line-to-line output voltages (200 V/div), load current (3 A/div), and DC link voltage (200 V/div) with a step change in frequency.
Energies 17 02214 g015aEnergies 17 02214 g015b
Figure 16. The figure shows the experimental results of three-level NPC-converter-based standalone WECS control: (a) experimental waveforms of the three-level NPC converter line-to-line output voltage (200 V/div), DFIG rotor current (10 A/div), DFIG stator current (3 A/div), and DFIG stator voltage (200V/div); (b) used voltage vectors of the three-level NPC converter in the plane (um1, um2); (c) experimental waveforms of the reference rms voltage, regulated rms voltage (200V/div), and frequency (25 Hz/div); (d) experimental waveforms of the three-level NPC converter line-to-line output voltage (200 V/div), DFIG rotor current (10 A/div), DFIG stator current (3 A/div), and DFIG stator voltage (200 V/div) with load change; (e) experimental waveforms of the reference and measured output voltage (200 V/div), DFIG rotor current (10 A/div), and DFIG stator voltage (200 V/div) during step-up change of the voltage reference; (f) experimental waveforms of the reference and measured output voltages (200 V/div), DFIG rotor current (10 A/div), and DFIG stator voltage (200 V/div) during step-down changes in the voltage reference.
Figure 16. The figure shows the experimental results of three-level NPC-converter-based standalone WECS control: (a) experimental waveforms of the three-level NPC converter line-to-line output voltage (200 V/div), DFIG rotor current (10 A/div), DFIG stator current (3 A/div), and DFIG stator voltage (200V/div); (b) used voltage vectors of the three-level NPC converter in the plane (um1, um2); (c) experimental waveforms of the reference rms voltage, regulated rms voltage (200V/div), and frequency (25 Hz/div); (d) experimental waveforms of the three-level NPC converter line-to-line output voltage (200 V/div), DFIG rotor current (10 A/div), DFIG stator current (3 A/div), and DFIG stator voltage (200 V/div) with load change; (e) experimental waveforms of the reference and measured output voltage (200 V/div), DFIG rotor current (10 A/div), and DFIG stator voltage (200 V/div) during step-up change of the voltage reference; (f) experimental waveforms of the reference and measured output voltages (200 V/div), DFIG rotor current (10 A/div), and DFIG stator voltage (200 V/div) during step-down changes in the voltage reference.
Energies 17 02214 g016
Table 1. The table shows hexagon detection.
Table 1. The table shows hexagon detection.
Angle θHexagon (H)
7π/4 < θ < π/8H1
π/8 < θ < 3π/8H2
3π/8< θ < 3π/4H3
3π/4< θ < 9π/8H4
9π/8< θ < 11π/8H5
11π/8< θ < 7π/4H6
Table 2. The table shows sector detection.
Table 2. The table shows sector detection.
Angle θcSector (S)
0 < θc < π/4S1
π/4 < θc < π/2S2
π/2 < θc < πS3
π < θc < 3π/4S4
5π/4 < θc < 3π/2S5
3π/2 < θc < 2πS6
Table 3. The table shows the duration calculation for hexagon H1.
Table 3. The table shows the duration calculation for hexagon H1.
t/SS1S2S3S4S5S6
t1X-Y 2 X YY-X 2 X Y
t2 2 Y Y-XX 2 Y X-YX
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Ghennam, T.; Belhadji, L.; Rizoug, N.; Francois, B.; Bacha, S. A Three-Level Neutral-Point-Clamped Converter Based Standalone Wind Energy Conversion System Controlled with a New Simplified Line-to-Line Space Vector Modulation. Energies 2024, 17, 2214. https://doi.org/10.3390/en17092214

AMA Style

Ghennam T, Belhadji L, Rizoug N, Francois B, Bacha S. A Three-Level Neutral-Point-Clamped Converter Based Standalone Wind Energy Conversion System Controlled with a New Simplified Line-to-Line Space Vector Modulation. Energies. 2024; 17(9):2214. https://doi.org/10.3390/en17092214

Chicago/Turabian Style

Ghennam, Tarak, Lakhdar Belhadji, Nassim Rizoug, Bruno Francois, and Seddik Bacha. 2024. "A Three-Level Neutral-Point-Clamped Converter Based Standalone Wind Energy Conversion System Controlled with a New Simplified Line-to-Line Space Vector Modulation" Energies 17, no. 9: 2214. https://doi.org/10.3390/en17092214

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop