2. PSSE-Based Network Visibility Using PMU
PMUs are very powerful and fast devices that enable power network users to fully monitor the network in real time. One of the most important applications of online security analysis in system control centers is power system status estimation, which has improved a lot with the advent of PMUs. The power system consists of generation, transmission, and distribution parts. As shown in
Figure 1, the PMU can be used in different parts of the power network and the values measured by them can be transferred to the system control center for network monitoring, analysis, and estimation.
Power system status estimation is a process to provide the best estimate of what is happening in the network. This is done in control centers based on real-time measurements and a predetermined system model, in which a set of measured data is collected from the entire power grid and transmitted to the system control centers to the status of the estimation system during static analysis, usually performed by the weighted least square (WLS) method. The governing equations between the measured parameters and the system status variables are determined from the model intended for the system, and then, despite the additional measurements and support available, an optimization problem is formulated, and by solving it properly, they get as close as possible to the actual values of the system status variables. The variables of network status are the amplitude and phase of current and voltage of network buses. Sometimes parameters such as tap changer and transformer phase shift can also be considered as status variables. However, it is not possible to measure the voltage and current phase of all system buses using the current measuring devices, which is the main reason for some processing and optimization issues in status estimation. The new PMU technology makes it possible to measure the amplitude and phase of voltage and current of the buses with very high accuracy, at present for economic reasons, it is not possible to install PMUs in all buses of the system. Nevertheless, the measuring equipment in the power system has a certain accuracy, which is not very desirable. Therefore, the problem could be turned into an optimization problem with additional measurements that are done from the system, and in this way, the exact amount of system status variables can be obtained with appropriate accuracy. The PMU is used in this article to estimate the network parameters as well as to identify and pinpoint the network fault location, which will be discussed below.
2.1. WLS Method to Solve PSSE Problem
The status of a power system refers to the operating conditions of that system, such as loading, voltage, power passing lines, transformers, substations, and so on. Mathematically, all of these variables can be obtained from the magnitude and angle of the voltage and current of the buses. Therefore, in principle, the status of a power system should be defined as a set of magnitudes and angles of voltages and currents. Finally, the purpose of estimating the status in the power system is to find the best estimate of the status variables in such a way that in the power flow model of the power system, the best fit for the measurement data is obtained.
The PSSE mathematical model can be written as Equation (1) based on the mathematical relationships between the measured values and the system status values. Where
Z is the vector of the measured variables,
x is the vector of the status variables (magnitude and phase of the voltage and current of the buses),
h is the vector of the nonlinear functions connecting the status variables to the measured variables, and
e is the vector of the measurement error.
Assume that the errors {
e1,
e2,…,
eN} are independent random errors with a Gaussian distribution with a mean of zero. The variance (
σi2) of the measurement error
ei is an indicator of the degree of certainty of a particular measurement. Large values for variance indicate that the corresponding measurement is not very accurate. Finally, the covariance matrix (
R) of the measurement error can be expressed as Equation (2):
In Equation (1),
x is an unknown vector that contains definite values (not random). Since the errors of
e are random variables, the measured values of
Z will also be random. Here
Z has a normal distribution with mean
h(
x) and covariance
R. The probability density function
Z can be written as Equation (3):
For the static estimation problem, a set of network variables called Z is observed or measured to estimate the x status vector. It makes sense for x values to be estimated in such a way that the probability density function maximizes. The estimated value of x is called the “maximum likelihood estimate”.
Given the exponential characteristic of Equation (3), it is clear that maximizing
f(
Z) is equivalent to minimizing the quadratic expression in its power according to Equation (4).
An accurate estimate should minimize the squares of the weighted error with accurate measurements. Therefore, the answer to the WLS problem gives the estimated status vector that must be true in the optimization condition of Equation (5):
where
H(
x) is the Jacobin matrix of the measurement function expressed as Equation (6).
By extending the nonlinear function g(
x) to its Taylor series around the status vector, we have Equation (7):
Regardless of the higher degree expressions, a process for extracting the answer to the problem can be obtained by the iterative method called the Gauss-Newton method. So, we will have:
where
k is the iteration index and the answer vector of the problem in
k iteration.
G(x) is called the gain matrix, which is a sparse, positive, and symmetric matrix from which the visibility of the network can be determined. Network visibility indicates whether the meters installed in the system, in terms of number and location, allow estimating all network status variables.
2.2. Using the PMU in the PSSE Problem before the Fault
This section describes how to use the PMU in the PSSE problem. The phasor representation for a sine quantity such as
X can be expressed as Equation (11).
In this case,
X(
t) shows the signals sampled at time
t =
τ with
X(
t) =
Xk, where
τ is the sampling interval. Using discrete Fourier transform (DFT), phase
X(
t) is defined as Equation (12).
where
N is the number of samples in a base frequency period and
θ is the sampling angle corresponding to
τ and is expressed as Equation (15).
For most of the measuring and relaying device applications, the typical sampling rate is 12 times the power system frequency. The above-mentioned discrete Fourier transform equation was non-recursive. In practical uses, time-varying phases are calculated using Equation (16) as an iterative equation. Suppose
is the phasor obtained from the set of samples
x {
k =
r,
r + 1,…,
N +
r − 1}. In this case, when a new sample is obtained, the new sample set is displayed as
x {
k=
r + 1,…,
N +
r}. In this case, the updated phasor will be obtained using Equation (16):
whereas requesting two samples at each stage, the recursive calculation method with a moving sampling window is quicker than the non-recursive method. If
X(
t) has transient changes, the moving window will track amplitude and phase changes with a delay that depends on the sampling time rate.
PMUs, as shown in
Figure 2, can measure the amplitude and angle of the bus voltage as well as the current of the lines and transformers connected to the bus. To use PMUs in estimating the status, the PMU bus voltage phasors and the current of the connected lines must be considered in measurement vector
Z. Also consider the nonlinear functions of these phasors with the system status variables in the vector h. For this purpose, the relationship between these phasors and system status variables must be extracted. Therefore, according to
Figure 3, the relationships between the measured data of PMUs in lines and transformers with status variables through branch current equations of the line π model can be obtained.
According to
Figure 3, the relationship current
Iij can be calculated as Equation (17):
For the participation of the data measured by PMUs in the Jacobin matrix of H-status estimation, the linearized relations of the branch current equations in terms of amplitude and angle of voltage in the corresponding bus and the end of the connected lines can be considered. Therefore, the Jacobin matrix elements can be defined as Equation (20) to Equation (27).
Thus, the PMU’s contribution to the answer vector and the Jacobin status estimation matrix can be expressed as Equations (28) and (29). Also, for a better understanding of the PSSE problem-solving method, the references are set out below [
48,
49,
50].
2.3. Utilization of Pre-Fault PSSE Information for Fault Location
In this paper, we use pre-fault PSSE information to estimate the voltage and current of network buses after a fault occurs. As can be seen in
Figure 4a, using the PSSE, the voltage status of the nodes, the current passing through each branch, and the voltage drop across each line can be determined.
Following that, all the currents of various network lines change direction to the point of fault according to
Figure 4b, assuming a fault occurs in lines 2–3 of
Figure 4a. It will be crucial to locate the problematic area in this case given the size and complexity of the network. When a fault occurs, only the voltage and current at the network’s beginning can be measured, making it challenging to identify the faulty section. In the normal state of the network, it is possible to estimate the voltage and current of network nodes using a variety of techniques. One solution is to use a PMU to measure the current and voltage of various network nodes, allowing for the detection of the faulty section through sporadic measurements throughout the network. The right local to install these devices will be crucial because the cost of these measuring devices prevents their widespread use in the network.
Due to the size of the distribution network, faults could occur in either the main branch or the lateral branches. In this study, the faulty line is located using a combination of data estimated by PSSE and data measured by PMUs. The voltage drop of each network line prior to the fault can also be calculated by PSSE, which allows for the installation of PMUs in each node of the main branch of the network. By doing this, the current flowing through the entire network, including the main and lateral branches, can be estimated, allowing for the identification of the faulty section. As an illustration,
Figure 5 depicts the changes in the direction of current flowing through each network line for faults 1, 2, and 3. The faulty line can now be identified if PMUs can be installed in the network’s main branch nodes. Each PMU that is closer to the fault will have a larger value, and each PMU that is farther from the fault will measure less. For example, for fault 3, the fault current measured by PMU3 will have the highest value compared to PMU1 and PMU2. It is possible to identify the problematic area of the network by comparing the PMUs’ data. The voltage drop calculation performed by PSSE prior to the fault can then be used to estimate the end current of each faulty line. As an illustration,
Figure 6 depicts a line that is connected to the PMU both before and after the fault. The voltage values
V1−PSSE,
V2−PSSE, and current
I1−PSSE can be estimated in the pre-fault condition by putting the values measured by the PMU in the PSSE problem and using Equation (30) to calculate them after taking into account the line voltage drop (Δ
V1−2).
According to
Figure 6b, after the fault, only the values of
V1−fault and
I1−fault can be measured by the PMU, so at this stage, knowing the amount of voltage drop Δ
V1−2, the fault voltage of
V2−fault can be calculated from the Equation (31).
Then, through the line transfer matrix, the fault current of
I2−fault can be obtained from Equation (32).
As a result, with knowledge of the voltage drop of the lines, the voltage and current changes at the beginning and end of the faulty line can be easily calculated at the time of the fault. In addition, the fault point voltage (
Vf) can be calculated depending on the
I 1−faultand
I2−fault currents through Equations (33) and (34).
Now, by equating Equations (33) and (34), we can estimate the location of fault
x by knowing the voltage and current at both ends of the line through Equation (35).
So far, authors have found how to locate faults using PSSE data (prior to the fault) and use the PMU to measure the voltage and current after the fault. The method for finding the faulty section and fault location in the distribution network will be explained in the section that follows.
3. Faulty Section Estimation and Fault Location in the Distribution Network Based on Optimization Problem Solving
Using information from PSSE and PMUs, we try to define the distribution network fault location as an optimization problem in this paper. We then estimate the fault location by resolving the problem. The voltage and current at the start and end of the line are first connected using a feature of the travelling wave model.
Figure 7 shows the status of a grid line with the π model.
Equation (36) can be used to describe the relationship between voltage and current at the beginning and end of the line under normal circumstances (without a fault).
where
γ = √
zy constant or diffusion coefficient, (
Zc = √
z/
y) is the characteristic impedances in ohms and
Z and
Y are the series impedance and shunt admittance, respectively. With a little algebraic operation, the above steady-state equations can be written in the form of Equation (37):
Now suppose that a fault occurs at point
F according to
Figure 7a at distance
x. In this case, similar to Equations (33) and (34), the fault voltage at the vision of the beginning and end of the line can be calculated through the KVL law according to Equation (38).
According to Equation (38), two indicators
M and
N are defined, which represent the voltage vision from both sides of the network line. The value of these two indicators is zero in the without fault state and increases suddenly when a fault occurs, which can be used to detect the faulty line. For example,
Figure 8 shows a three-line network with four nodes. Suppose a fault occurs here on the
LS line (between nodes
S,
P). According to what has been said, the voltage and current on both sides of each network line must be calculated, and any line whose value at both ends is not the same will be a faulty line. That is, in this case, the symmetric components of voltage and current point
P (
VP,
IP) should be calculated using the voltage and current phasors estimated in nodes
R,
T, and
S, in this case in node
R,
T approximately with it will be equal to but not equal to what is calculated based on the phasors of node
S. By this logic, the voltage of the node and the injection currents from the nodes can be calculated according to Equations (39) and (40).
By considering Equation (41), we can convert Equations (39) and (40) into Equations (42) and (43):
Finally, for the fault in the
LS line in
Figure 8, Equation (44) will be established:
As shown in Equation (44), the difference between the magnitude of the voltage and current without fault state lines is almost zero, and the faulty line will be greater than the specified threshold value. With such a criterion, it is possible to define the identity of the defective distribution network section as an optimization problem that seeks to identify the network line with the greatest voltage or current difference. Therefore, the objective function of the fault location problem can be defined as Equation (45). Where in,
L = Number of network lines = 1, …,
N,
i = Number of network buses = 1,…,
M,
j = Number of network buses = 1,…,
M,
I ≠
j.
In the objective function of Equation (45), instead of voltage changes on both sides of the line, it is possible to use changes in the current at both ends of the line, since the absolute value of voltage or current at both ends of the line is used, so in both cases, the changes will be incremental. As is well known, in short-circuit faults the voltage decreases, and in series faults the voltage increases. However, since the absolute value of voltage is used, these changes will be incremental, so the proposed objective function can be used for all types of faults, including short-circuit and series. In this paper, to solve the problem according to the problem space shown in
Figure 9, the genetic algorithm is used to find the maximum points.
3.1. Fault Location in the Distribution Network for Different Types of Faults
In the previous step, the method of detecting the faulty section was presented. In this section, the method of calculating the fault distance from the beginning of the faulty line for different types of faults will be introduced. In Equation (35), the fault distance
x is shown for the information at the beginning and end of the line. Now, Equation (35) can be defined as Equation (46) according to the π model of the network line.
The authors can use the same technique described to identify the faulty section and define a new objective function for fault location since our attempt in this article is to define the fault location as an optimization problem. An objective function for fault location is presented in Equation (47), where the difference between the calculated fault voltage is considered from the perspective of the two sides of the line for the variable
x. Here,
x = Fault location,
F = Fault point,
i,
j = Nodes at the beginning and end of the faulty line. Equation (47) has two major differences from Equation (45). In Equation (45) the problem variable is the faulty line and in Equation (47) the problem variable is the fault point
x. The next difference in Equation (45) is because the current seen from the two ends of the line is inverted (−
I) and in the problem, there is a sign (−) so the two values are added together and the value of the objective function will be incremental, but in Equation (47), since the voltage at the fault location must be equal from the point of view of the two sides of the line, the solution to the problem is close to zero.
Equation (47) defines the problem’s objective function as precisely locating the fault between the two faulty buses,
Ij. The basis of the work will be that, similar to
Figure 10, we will move the length of the fault location between the two buses
i, and
j, respectively, and at the same time calculate the fault voltage from the point of view of the two buses
i,
j (i.e.,
VF→i,
VF→j) and repeat this process until the objective function of the problem for
x is minimized.
There are two types of distribution network faults: short-circuit faults and series faults. The calculation of the voltage and current of the fault point depends on the type of fault in the network and will vary depending on the characteristics of each fault. In short-circuit faults, the fault current increases and then the voltage decreases, whereas in series faults, the opposite occurs, i.e., the voltage increases and the current decreases. This section introduces how to calculate the voltage and current of the fault for each type of fault based on the positive, negative, and zero sequence components.
Figure 11 shows the different types of faults that will be examined in this article.
3.1.1. Short-Circuit Faults
Figure 11a shows the single-phase short-circuit fault at point F. One of the fault analysis techniques is to use the positive, negative, and zero sequence components of the fault current and voltage.
Figure 12 shows the equivalent circuit of symmetrical components for a single-phase fault to ground. In a single-phase fault to ground, there will be all three positive, negative, and zero sequences. In this case, the fault voltage (
VF) based on the sequences can be calculated from Equation (48) to Equation (50).
For two-phase and three-phase faults, the zero-sequence can be omitted, and the fault voltage (
VF) can be calculated based on the positive and negative sequences. Therefore, according to Equation (55), we will have:
3.1.2. Series Faults
Series faults are asymmetric faults that can be analyzed through symmetric components. In this type of fault, the faulty phase current is reduced at the beginning of the line and becomes zero at the end of the line. Also, in this type of fault, the voltage of the without fault phases is zero and the voltage of the faulty phase is increased.
Figure 13 shows the equivalent circuit of symmetric components for series faults. According to
Figure 13, Equation (56) will be established for one open conductor fault and Equation (57) for two open conductors fault.
Also note that for series faults, there is no need to solve Equation (47), since the node j side of the information is zero and it is easy to estimate the fault location for this type of fault with Equations (56) and (57). Finally, a flowchart of the steps of the proposed method to solve the fault location problem is shown in
Figure 14.
The suggested method has three steps, as shown in
Figure 14. Estimating the voltage and current of the network nodes and then the voltage drop across the network lines are the goals of the initial stage, which takes place before the fault occurs. In the second stage, after the fault occurs, the goal is to identify the faulty section using the values of PMUs and using the information from the first stage. In the third stage, the goal is to fault location after identifying the faulty line in the second stage. These three actions are classified as optimization problems, it should be noted. The genetics algorithm (GA) is employed in this paper to resolve the issue and the same conventional techniques are used in the GA algorithm, the accurate details of which are provided in reference [
51].
4. Simulation Results
In this paper, a proposed fault location algorithm is implemented on the IEEE 123-node distribution feeder. In this section, the effect of various factors on the accuracy of the proposed algorithm, including the effect of values measured by PMUs, type of fault, angle of occurrence of a fault, and fault resistance will be evaluated.
Figure 15 shows the network under study along with the status of DG resources and PMUs installed in the network. At the beginning of the distribution feeder and the connection point of DG sources to the network, it is possible to measure the voltage and current of the nodes. According to the proposed method, PMUs have been installed in a limited number of nodes in the main branches of the network in such a way that the information of the whole network can be estimated with appropriate accuracy. As mentioned in
Section 3, our goal is to obtain the line voltage drop before the fault, so that after the fault occurs, by combining the values measured by the PMUs and the voltage drop obtained from the first step, we can estimate the voltage and current of each node after the fault. This depends on how the PMUs are installed on the network, which both improves the accuracy of the estimation and covers the entire network. It should be noted that in reference [
8] we have presented a new technique for installing PMUs in the network for fault location. The conventional technique for installing PMUs in the distribution network is to place these devices at the end of the lateral branch of the network, which causes the installation of a large number of these devices in the distribution network. The reference technique [
8] is by installing PMUs in the main nodes of the network and using the PSSE problem, in addition to reducing the number of PMUs installed in the network, efforts have been made to obtain the information of the entire network. Therefore, in this article, the technique presented in reference [
8] is used to install PMUs in the network. As shown in
Figure 15, by measuring the voltage and current at eight nodes, the entire network is covered and the network is divided into eight zones by PMUs. Of course, it should be noted that the more PMUs, the better the accuracy of the method, but their installation will be expensive.
The first step in the design is to estimate the voltage and current of the network nodes before the fault occurs.
Figure 16a,b show the estimated voltage and current of the network nodes, respectively. Next, according to the voltage information of the network nodes, the voltage drop of each network line can be calculated, which is shown in
Figure 16c. One of the main challenges in the distribution network is the detection of the faulty section due to its many branches, and it is more difficult for several faults to occur simultaneously in the network, which makes it difficult to identify the fault points because it is no longer possible to use conventional single-location fault location equations to identify multiple fault locations, as the direction of branch current to the fault location will vary. In this article, we have tried to solve these problems by presenting a new objective function for the fault location problem.
Let us suppose that two faults F1 and F2 occur simultaneously in the network. Fault F1 is a single-phase fault ground in Zone 2 between nodes 23 and 24, and fault F2 is a two-phase fault in Zone 8 between nodes 78 and 79. At this stage, the goal is to identify these two points of fault by solving Equation (45) using a genetic algorithm, since in solving optimization problems the goal is to minimize the objective function so Equation (45) can be defined as (1/objective function). Finally,
Figure 17 shows the results of the performance of the GA algorithm in solving the fault location problem. As shown in
Figure 17, respectively, (a) and (b) the convergence curve of the GA algorithm regarding the best and average solutions, (c) the curve of selection changes and the children created in each generation, (d) and (e) respectively the fitness value and the final convergence of the solutions to the optimal value and the stopping condition and calculation time for all generations, (f) the average distance between the solutions, and (g) the output of the algorithm for all the variables of the algorithm are shown.
According to Equation (42) to Equation (44) defined for each line, the voltage seen from both ends of the line without fault is equal, and for the two faulty lines, this voltage difference is not equal because of the current passing through each line. In lines without fault, a certain current passes, and in the faulty line, two currents enter the line from both sides. Therefore, for lines without fault dif (
L), Equation (45) will be decreased and for faulty lines dif (
L), Equation (45) will be incremental, but from there the goal is to optimize the objective function, so these changes are inverted and the faulty line is it will be a decrease.
Figure 17 shows, for faults F1 and F2, the value of dif (
L) for the line between nodes 23 and 24 and the line between nodes 78 and 79 has the lowest value, so a fault has occurred in these two lines. After this step, by identifying the faulty line, the exact location of the fault can be identified by solving Equation (47) for the faulty line.
In the following, the performance of the proposed algorithm is evaluated for different types of faults. One method to evaluate the accuracy of the algorithm in estimating the fault location is to use Equation (58) to calculate the percentage error estimation (
EE) of the proposed method. Here,
xl is the actual location,
xe is the estimated location, and
L is the length of the line.
Table 1 compares the performance results of the proposed algorithm for types of faults with other methods.
According to reference [
52], it is suggested to locate faults in the distribution network using network monitoring with PMUs and the presence of DG in the network. In this method, voltage data are collected from the PMU and the fault location is obtained based on the calculation of the equivalent current vector and network impedance matrix. This method depends on the PMUs’ measurements of the network’s nodes and the DG’s connection point; the more of these devices there are in the network, the more accurate the algorithm is. In this scheme, five DGs in nodes 30, 35, 64, 151, 450, and 31 PMUs in nodes 6, 11, 16, 22, 27, 29, 32, 37, 39, 42, 46, 56, 57, 59, 63, 65, 66, 71, 75, 83, 95, 98, 100, 104, 111, 114, 150, 151, 250, 300, and 450 have been used. The maximum estimation error of this method is 3.71%, as shown in
Table 1.
Reference [
53] suggests an automatic fault location technique based on PMU data. The basis of the work depends on the information before and after the fault and by estimating the load current at the end of the line, using the impedance method, each line is checked in order and if the fault distance (
x) is greater than the length of the line, the adjacent line is checked. Therefore, to estimate the load current, PMUs are used at the end of the line, which is installed in nodes 149, 250, 96, 85, 151, 300, and 450, respectively. In this method, the maximum estimation error is 3.85%.
Mixed-integer linear programming is used in reference [
54] to pinpoint distribution network faults. By calculating the network impedance matrix, the work in this method is based on calculating the voltage changes of the nodes before and after the fault. Where PMUs are used to collect measured data at the end of the line and form an impedance matrix. Here PMUs are installed in nodes 1, 2, 4, 6, 10, 11, 12, 16, 17, 20, 22, 24, 32, 33, 250, 37, 39, 41, 43, 46, 48, 151, 56, 59, 66, 610, 96, 94, 92, 90, 88, 83, 85, 79, 75, 71, 450, 104, 107, 111, 114, and 300. The maximum estimation error in this method is 1.75%.
By comparing the proposed method with other methods such as references [
52,
53,
54], there are obvious difference in the proposed method. However, in the proposed method, PMUs are installed in the nodes of the main branches of the network, and values measured by PMUs applying to the PSSE problem, the total information of the network nodes can be estimated before and after the fault, so in addition to reducing the number of PMUs in the network, this also allows for the estimation of the total information of the network nodes. As shown in
Table 1, the maximum estimation error of the proposed method is 1.21%. In addition, the proposed method can be used for all types of faults (including short-circuit and series faults) because the fault location problem is defined as an optimization problem with a new objective function that will be able to identify the faulty section for different types of faults. The optimization problem is finally solved by a genetic algorithm in the proposed method, allowing it to simultaneously identify multiple fault locations in a maximum of 23.87 s.
Sensitivity Analysis of the Proposed Method
Various factors affect the accuracy of fault location algorithms. As shown in
Figure 18a, a fault consists of three important factors: fault resistance, fault angle, and fault location. Here, the purpose of the fault location algorithm is similar to
Figure 18b, which estimates the fault distance with the lowest error percentage. In this section, a sensitivity analysis is performed on the performance of the proposed algorithm for various factors including the status of PMUs, fault type, fault resistance, fault occurrence angle, and type of problem-solving algorithm. Let us suppose that in
Figure 15, an F2 fault occurs for 60 different types of faults by changing the fault parameters.
Table 2 shows the performance accuracy of the proposed algorithm for changes in fault resistance, fault angle, and type of fault. In this table, the EE value is the average value of these errors, as it can be seen that the EE value of the proposed algorithm has increased for high fault resistance, zero-angle fault occurrence, and three-phase faults.
Another factor influencing the fault location problem is the uncertainty in the network loading states before the fault occurs.
Table 3 shows the performance of the proposed algorithm for 10% to 50% network loading states uncertainty. As shown in
Table 3, network uncertainty loading states do not have much effect on the accuracy of the algorithm, since the proposed algorithm uses the measured PMU data in the PSSE problem, in practice, the results obtained from the PSSE problem are close to reality and after considering the voltage and current measurement of the nodes connected to the PMU, the changes in the network load can be estimated correctly.
Another factor that has a direct impact on the performance of the proposed fault location algorithm is the accuracy of measuring the PMUs installed in the network. Here, assuming a measurement error between 1% and 3%, the average EE value of the proposed algorithm is calculated.
Table 4 shows the performance results of the proposed algorithm for PMU measurement error. As shown, the PMU measurement error increases the average EE value. Since the proposed algorithm before and after the fault depends on the measured PMU values, the measurement error will certainly have a direct effect on the accuracy of the fault location algorithm. The next case in
Table 5 shows the effect of the number of PMUs installed on the network on the performance of the proposed algorithm. The accuracy of the algorithm decreases with decreasing the number of PMUs, and the accuracy of the algorithm increases with increasing the number of PMUs, which indicates the dependence of the algorithm on PMUs. However, it should be noted that the number of PMUs used in the IEEE 123-node distribution feeder network with the proposed algorithm is much less than other fault location algorithms due to the use of the PSSE problem.
Finally, the problem of fault location is defined by solving with different algorithms and its performance is compared with genetic algorithms.
Table 6 shows the results of different algorithms. As shown, the accuracy of the genetic algorithm is better than other algorithms, and the only drawback is its computational speed, which, of course, was able to identify the fault location for a 123-bus network in a maximum of 23.87 s, which is a good time.
Finally,
Figure 19 shows the mean EE value for the various factors presented in
Table 2 to
Table 6 for comparison. As shown, the greatest impact on the EE value is due to the PMU status in the network and the type of problem-solving algorithm.
In reference [
51], a fault location method based on solving the optimization problem is presented, which is clearly different from the proposed method:
In reference [
51], there are weaknesses in the defined objective function, which makes the proposed method not applicable to all types of faults in the distribution network.
Since in reference [
51], the objective function was based on the calculation of voltage changes of all nodes with the impedance matrix method, it is not possible to use it for series faults. In the new article, a new objective function based on current and voltage at the beginning and end of the line is defined so that in addition to reducing the calculations and improving the accuracy of the method, it can be implemented for all types of series and short circuit faults.
The equations defined for the objective function of reference [
51] are more complicated and their implementation will be difficult for large networks. In the new article the equations are based on the feature of the traveling wave model and the relationship between the voltage and current at the beginning and end of the line is defined to simplify calculations. So there is an obvious difference between the equations in the two papers. In addition, the line model considered in the new article has been modified to improve the accuracy of the method.
In the new article, it is possible to identify several faults simultaneously, but in reference [
51], due to the type of the objective function, this is not possible, and the algorithm suffers in this case.
In the new article, a sensitivity analysis was performed on the proposed method for the types of faults, fault resistance, fault angle, loading states, PMU measurement error, change in the number of PMUs, and algorithms, which did not exist in reference [
51].
Finally, in the new article, there was a maximum time of 23.87 s and an average error of 0.74%, and a maximum error of 1.21%, which was far better than the previous article.