1. Introduction
Regenerative braking is widely used since the dawn of electrical railway traction. In the past, all breaking energy produced by the traction motors during the braking stage was dissipated by rheostats placed on-board rolling stock. Nowadays, locomotives have an intelligent system able to direct the braking energy flow towards the overhead contact line if other nearby trains can collect such energy, or towards the braking rheostat to be transformed into heat.
The flat-rate scheme of energy billing, adopted for railway undertakings and used until recently, made the knowledge of the energy dissipated by the braking rheostats marginal. The “new deal” established by the European commission through the Technical Specification on Interoperability [
1] imposes billing to be performed on real rolling stock energy consumption. This choice will foster energy saving and thus will transform the railway system in a more sustainable means of transport. In this context, an accurate estimation of the energy dissipated by the braking rheostat will become important information for the determination of the energy costs for railway undertakings. At the same time, this policy pushes railway system operators towards improving their capabilities of re-using the electrical energy produced by the braking.
From a technical point of view, DC railway systems can be considered as closed systems. More precisely, because of the considerable amount of power required by railway systems, DC systems are fed by AC high-voltage grids through diode-rectifiers that allow only unidirectional flow of the energy from the upstream AC system to the railway DC system. Therefore, an imbalance between the absorbed and generated energy generates an increase of the voltage [
2,
3] and an increase of the energy stored in the stray capacitance of the whole system. This is the only way to store extra energy unless other techniques like batteries, super-capacitors, flywheels, reversible substations [
4,
5,
6], or DC grid connections with domestic loads [
7,
8,
9,
10] will be incorporated. As demonstrated by [
11], even a proper driving style can reduce such extra energy. Several studies have shown that these massive infrastructural modifications ensure the recovery of the energy dissipated on the braking rheostats from 10% up to 30%. [
12,
13,
14]. Accurate knowledge of this energy plays a key role in many applications, for example in economic analyses. The quantification of the real wasted energy enables to evaluate the potential benefit before an infrastructural investment or to measure its impact afterwards.
Nowadays the electrical braking energy dissipated by the rolling stock is estimated by indirect approaches. A commonly used technique exploits the information of speed and braking effort to compute the mechanical energy provided by the motors operating as generators. Together with the generator efficiency and the duty-cycle imposed to the braking chopper the dissipated braking energy is estimated.
An estimation technique, which has been briefly described in [
15], exploits the simultaneous measurement of the instantaneous chopped current flowing through the braking rheostats and the voltage at the input of the breaking chopper. The present paper builds upon the latter method and explores the effect of the distortions introduced by the current sensor, used to measure the chopped current flowing in the braking rheostat, on the estimation of the power dissipated by the braking rheostat. Moreover, this paper discusses and proposes a procedure to improve the simplified measurement model for the power estimation proposed in [
15]. Correction factors allowing a more accurate estimation of the dissipated power are defined based on a model involving the braking rheostat, the transducer, and the sampling mechanism. These correction factors are applied to real measurements performed on-board DC locomotives in the framework of the European Project MyRailS [
16]. The characterization of a current sensor experiencing chopped waveforms with a high slew rate and a high current variation as in the case of the braking rheostat is a challenging topic [
17,
18,
19,
20,
21,
22]. A methodology for laboratory generation of such waveforms and a reference system to accurately calibrate transducers exposed to such waveforms is described in [
23,
24], respectively.
The paper is organized as follows:
Section 2 describes the measurement campaign that provided the electrical quantities related to the braking rheostats which are the basis of this work. A description of the braking chopper and its simplified model are introduced in the
Section 3. A detailed quantification of the systematic error, introduced by the power measurement model, is provided in
Section 4. The systematic error introduced by the current sensor and its laboratory characterization are explained in
Section 5.
Section 6 describes the procedure for the correction of the previously mentioned systematic errors.
Section 7 collects all the results related to the systematic errors, their impact on the dissipated power and the application of the proposed correction procedure to a real braking event. Finally, in
Section 8 a short summary is presented, the results are discussed and conclusions are presented.
2. MyRailS Measurement Campaign
As part of the MyRailS project, a measurement campaign was carried out on-board a train aiming to evaluate the energy consumed by the train, dissipated by the braking resistors and fed back to the overhead line, as well as to estimate the impact of the installation of a reversible station [
14] in a particular section of the metro system in Madrid.
Figure 1 schematically shows the input stage of the train with highlighted measurement points. The pantograph voltage
vF(t) is filtered by the low pass filter formed by the inductance
L and by the bank of capacitors placed in parallel to the traction inverters that control the motors. This filtered voltage
vF(t) is modulated by the chopper and imposed on the braking resistors. During a purely dissipative braking phase, the current through the filter
iF(t) is zero and the output power from the inverters is dissipated in the braking resistors through which the currents
iRa(t) and
iRb(t) are measured. The voltage measurements were obtained using two Ultravolt 40TF transducers with full scale range of 40 kV and nominal ratio of 1000:1. The voltage transducers are verified in the laboratory and used in the field for applications from DC to 1 MHz with an accuracy of 0.25%. To measure the total current
iP(t) drawn by the train and the filter current
iF(t), two LEM HOP 2000 current sensors were used. Except for the nominal current, their characteristics are identical to the LEM HOP 800 discussed later. The latter type of sensor is used for the current measurement of auxiliary services,
iA, and the currents through the braking resistors
iRa(t) and
iRb(t).
All the signals provided by the presented transducers are digitized and collected thanks to a measurement device, positioned in a control cabinet in the wagon underbody, developed within MyRails project. This device is implemented with the National Instruments (NI) CompactRio 9034 equipped with the NI 9467 module for the synchronization with GPS signal and two NI 9223 acquisition modules (16 bits resolution, 50 kSamples/s, 4 channels with synchronized sampling). All data are stored on SD cards, appropriately replaced before the total occupation of the available space. The acquisition system has been tested for a long time in the laboratory. During these tests, no samples have been lost.
Whereas the other current signals have very slow variations over time, the currents iRa(t) and iRb(t) flowing through the braking resistors have a dynamic current range larger than 500 A for a chopping frequency of 300 Hz, with a duty-cycle that can vary between 0.5% and 50%.
Particular attention has been paid to the measurement of dissipated energy because of particular metrological difficulties, as described in the following.
3. The Braking Chopper: Description and Modeling Approach
During braking, the regenerated energy is sent back to the supply system and recovered if other loads can absorb it. If not, this energy is dissipated on-board by means of rheostats. Sending the energy back to the supply system causes an increase of the voltage at the pantograph. If the voltage increases beyond a predefined limit, the braking chopper modulates the DC voltage across the resistor to dissipate the extra energy [
25]. The scheme of the dissipative braking system is shown in the
Figure 2a. The duty-cycle of the chopped voltage is proportional to the voltage increase. This leads to a balance between the generation and consumption so avoiding a fast and abnormal increase of the voltage.
The combination of the chopper and braking rheostat can be described as a variable resistance
Rb connected in parallel with the Thevenin equivalent resistance
RTh representing the supply grid (see
Figure 3). If the duty-cycle of the chopper is low, the equivalent resistance
Rb is high; as a consequence, the equivalent parallel resistance is close to
RTh value; the contribution of the braking rheostat is low. With the increase of the duty-cycle,
Rb reduces and so does the equivalent parallel resistance, such that the voltage of the system reduces when the braking energy is constant.
In our application, the monitoring of the current absorbed by the braking rheostat has been performed on a light train for metro application supplied by a 1.5 kV DC system. The braking rheostat can be easily modeled as a series R-L circuit. The rated value of the resistance
Rb is 3 Ω, whereas the stray inductance
Lb is 36 µH. The model of the dissipative braking system is shown in the
Figure 2b. The braking chopper consists of a gate turn-off thyristor (GTO). The fly-back diode allows the discharge of the energy dissipated by the stray inductance
Lb to avoid overvoltage. A rigorous simulation of the GTO is burdensome for the energy analysis. An easy way to simulate the GTO is to substitute it with a pulse voltage generator that switches between the (time-dependent) filtered pantograph voltage of the DC link,
vF(
t), and zero [
17]. When the GTO is open (off), the pulse voltage generator
vGTO(
t) imposes a voltage equal to
vF(
t); in this way, according to Kirchhoff’s law, the voltage applied to the braking resistor is zero, and so is the current
iR(
t). When the GTO is closed (on), the pulse voltage generator imposes a null voltage, as a consequence the voltage
vF(
t) supplies the braking rheostat. The simulated pulse generator enables to mimic the GTO switch-on and -off time by introducing a rise and fall time.
Figure 4 describes the time characteristics of the pulse voltage when the voltage
vF(
t) is constant and equal to
VDC.
The model of the braking rheostat expressed in the Laplace domain is
It allows to estimate the transfer function that links the chopped voltage to the current flowing through the braking rheostat. An example of the current flowing through the chopper for different chopper duty-cycles δ is provided in
Figure 5. The chopped voltage has a peak value of 1.65 kV (the average value experienced on-site). As can be seen for a duty-cycle of
δ = 0.7%, the current cannot reach the maximum expected value of 550 A because of the delay introduced by the stray inductance of the braking rheostat. For higher duty-cycles the maximum current is reached within approximately 0.1 ms.
It is worthwhile noting that in the specific measurement installation considered (see
Figure 1) it is not possible to measure the actual voltage over the braking rheostat
vR(
t) and instead the value of the filtered pantograph voltage
vF(
t) was measured.
The evaluation of the average power
dissipated by the rheostat is computed over a period
T. The rheostat gets heated in particular for high duty-cycle and the resistance value can vary by about 15%. There model that uses the product of voltage and current has been preferred to a model that involves the varying resistance value and the current squared [
10]. The method used for the estimation of the average dissipated power, is calculated over the chopping period
T, based on the chopped current as measured by the current sensor
and voltage at input of the braking chopper
which is constant and equal to
VDC:
This approach introduces two systematic errors. The first is due to the use of the DC voltage at the input of the braking chopper instead of the chopped voltage applied to the rheostat. This results in an overestimation of the dissipated power that depends on the chopper duty-cycle. The second is due the use of current as measured by the HOP transducer. In fact, the step response of the current transducer to the sudden change of current values can remarkably change the measured current values. In the following section, these two systematic effects are analyzed trying to find a method to compensate them.
4. Systematic Error Due to Simplified Model of the Measurement
A single voltage pulse of duration
t1 and amplitude
VDC inside a burst of pulses, is expressed as
where
T is the repetition time of the pulses. The braking rheostat is modelled as
R-
L (with
) series circuit (see
Figure 2). The current flowing through the rheostat has the following exponential behavior:
It is worthwhile noting that (see
Figure 6), in practical applications,
t1 is always less than
T/2, so the current always reaches zero before the following pulse. The correct mean power,
Pcorr, associated with the pulse and computed over a time-period
T is
Since the voltage is zero for
t >
t1, the second component is zero, and the power can be re-written as
where δ is the duty-cycle (
).
Figure 6 shows the area below the current curve that contributes to the correct power estimation.
Now the question is: what happens if we consider the voltage
vF(
t) that has a constant behavior rather than the chopped voltage
vR(
t)? In this case, Equation (4) applies, and the area below the current that contributes to the mean power is shown in
Figure 7.
The new mean power that is affected by a systematic error is now:
Given that the voltage
is considered constant and equal to
VDC and introducing the definition of
, (4), Equation (8) becomes:
The difference between the wrong power and the correct power is
It is possible to account for this effect by introducing a correction coefficient. Considering that, under real circumstances, the quantity
is not constant, the corrected measured values becomes
Table 1 provides the values of the correction coefficient
KDC for different values of duty-cycle, defined as the ratio between
and
. The values were obtained for a time period of the chopped signal equal to
T = 1/300 Hz, a rheostat resistance
= 3.4 Ω and
= 36 µH.
5. Frequency Characterization of Current Sensors
In the application described in this paper, the current transducer is used under conditions much different from those of common use. For this reason, it is fundamental to know the behavior of the sensor under actual operating conditions; that is, with a pulsed current with amplitude of 500 A and at frequency of 300 Hz [
19]. In order to be able to measure such a pulsed current a LEM HOP 800 sensor was selected, which is an open loop Hall effect sensor designed for measurements of DC, AC and pulsed currents. The current range of the sensor is 800 A root-mean-square (RMS), the maximum attenuation in the 10 kHz band is −1 dB, and the nominal voltage isolation is 2 kV. The primary and secondary circuits are galvanically separated. The sensor loop has an openable core, which simplifies the installation on-board the train.
Figure 8 shows a schematic representation of the HOP 800 sensor.
Table 2 presents the main nominal characteristics of the sensor.
The sensor can be simulated by reconstructing and modeling the frequency response with a transfer function at currents similar to those during a real measurement campaign. The actual frequency response was accurately estimated at the Italian National Metrology Institute (INRiM) using a reference current transducer LEM ITZ Ultrastab, with excellent linearity within 1 to 10 parts in
(parts per million, ppm). It guarantees an overall accuracy at nominal current, 125 A in this case, at +25 °C better than 12 ppm. Moreover, it has a wide frequency bandwidth from DC up to 500 kHz and it is based on closed-loop fluxgate technology. The output of this transducer is a current, that was measured using a broadband 1 A, 100 kHz 7320 Guildline shunt. The frequency dependence of the shunt varies from essentially zero at power frequencies to less than 10 ppm up to 10 kHz. For the current generation a Clarke-Hess Model 8100 trans-conductance amplifier has been used. The six overlapping ranges of the amplifier, 2 mA, 20 mA, 0.2 A, 2 A, 20 A, and 100 A, provide output currents with distortion less than −60 dB up to 10 kHz (typically 20 kHz) and less than −40 dB to 100 kHz at all current ranges. The input signal for the trans-conductance amplifier was generated using a National Instruments 5422 digital-to-analogue converter. The NI 5422 is a waveform generator with the following features: sampling frequency up to 200 MSa/s, 16-bit resolution output channel, full scale range 12 V (peak-to-peak) for a 50 Ω load up to 80 MHz, DC offset up to ± full scale and a bandwidth of 80 MHz [
26].
A National Instruments PXIe-6124 was synchronized to the generator and used to measure the voltage to characterize the HOP sensor. The NI 6124 is a multi-functional simultaneous sampling data-acquisition device, with a 16-bit analog-to-digital converter and a sampling rate up to 4 MSa/s per channel.
Figure 9 shows the block diagram of the setup used to characterize the current sensor. For specific frequencies in the range from 47 Hz to 40 kHz the gain has been evaluated 30 times with an averaging time of 1 s.
The gain for the
-th frequency,
, expressed in dB, can now be defined as follows:
where
and
are the magnitude of the phasors of the primary current
, at frequency
, measured by the HOP sensor and the ITZ sensor respectively. The current
can be written as the product of the voltage measured by the acquisition system,
, multiplied the channel gain,
, and the gain of the HOP transducer in stationary conditions,
. In the same way, the current measured by the reference transducer can be written as the product of the channel gain,
, the reference shunt gain,
, and the gain of the reference transducer,
, multiplied by the voltage read by the acquisition system,
.
Although the transconductance amplifier has the capability to reproduce signals up to 500 kHz, the generation of the current is limited by the circuit connected to it. With an inductive load, increasing the frequency corresponds to an increase in the impedance and therefore an increase in the voltage required by the amplifier for generating the output current. The compliance voltage for this amplifier is 7 V. In order to minimize the impedance, the first tests were carried out with twisted cables as shown in the
Figure 10a.
The result of this characterization shows that, in this configuration, the accuracy of the instrument is highly out of specification. This effect is due to the position of the Hall sensing elements in the current transducer which are influenced by the magnetic field produced by the cables in the vicinity. Subsequently, by reducing the maximum test frequency, tests were carried out with non-twisted cables, as shown in
Figure 10b. The effect of the position of the primary conductor on the transducer scale factor has been investigate and described in [
27]. This activity was limited to the position of the primary conductor rather than the effects of a current flowing close to the hall sensor. Moreover, a limited frequency band was analyzed.
Once the frequency characterization has been obtained, it is possible to proceed with the search for the poles and zeros that define the transfer function of the current sensor. By following the approach already presented in [
28], the transfer function of the current sensor was fitted by the relation between the output current
IHOP and the input current
Ip that best approximates the actual frequency behavior of the scale factor in the Laplace domain:
The function is constituted by two zeros and two poles. The model allows for the estimation of the correction factors as a function of the duty-cycle that were applied to the power and energy estimated by the on-board locomotive measurements, in order to compensate for the systematic errors.
Further, in this case it is possible to account for systematic errors by introducing a correction coefficient. The correction coefficient representing the sensor distortion and the limited sampling frequency can be defined as the ratio between the integral of the measured current squared and the current flowing through the rheostat squared:
The integrals are numerically computed by implementing the trapezoid rule.
6. The Methodology for Accurate Estimation of the Dissipated Power
As shown in the previous section, the systematic deviations due to the voltage-and-current measurement method can be accounted for by correction factors. So, the full measurement model now becomes
As shown in the previous section, the error is dependent on the value of the chopper duty-cycle
δ. However, there is no direct information on duty-cycle because the chopped voltage is not measured. So, the duty-cycle should be estimated using the current measurements, but there is a difference between the duty-cycle measured on current and measured on voltage because of the distortions introduced by the stray inductance of the rheostat and by the current sensor. In particular, the duty-cycle of the chopped current is always higher than the chopped voltage duty-cycle (see
Figure 5). Thanks to the model of the braking rheostat that provides the current behavior by applying a pulsed voltage of known duty-cycle, the relation between the duty-cycle of the chopped current,
δI, and the duty-cycle of the chopped voltage,
δV, applied to the rheostat can be identified. The relation between
δV and
δI is shown in
Figure 11 for the lowest values.
This relation is fitted using the ad hoc function:
where
a,
b, and
c are equal to 4.253, 0.2636 and 26.36, respectively. Formula (16) has been carried out by the black-box approach, exploiting the optimization algorithms provided by Matlab software.
The procedure that provides the corrected power dissipated by the braking rheostat is summarized in
Figure 12. The measured chopped current is processed in order to determine the duty-cycle
δI for a specific period
T and to calculate the power dissipated by the rheostat
P. From this, it follows that the minimum time for the estimation of the duty-cycle and the relative correction of the dissipated power is a single period of the chopped signal, in this case 3.34 ms. In order to reduce the impact of a single outlier on the estimated power, such time-interval can be enlarged of an integer number of times.
7. Results
This section provides the results of the sensor characterization in the frequency domain, i.e., the fit function that approximates the frequency dependence. A comparison between the actual current flowing through the rheostat and the distortion introduced by the current sensor and the subsequent digitization is provided. Furthermore, the behavior of the correction factors as a function of the duty-cycle are described, including a description of the uncertainty introduced by the initial phase of the sampling procedure that is considered as stochastic information. Finally, the impact of the corrections of the estimation on real power and energy dissipated by a braking rheostat on an Italian DC locomotive for commuter service is shown.
7.1. Frequency Behavior of the Current Sensor
The results of the measurement campaign regarding the frequency dependence of the current sensor gain, and the subsequent identification of the function that describes the frequency characteristics with sufficient reliability, are presented in the next subsections.
7.1.1. Measurement Results of the Frequency Dependence of the Correction Coefficients
The two arrangements of the primary conductor described in
Section 5 provide considerably different frequency behavior, in particular around 10 kHz [
29].
As can be seen by
Figure 13 the effect of different primary cable arrangement is very high. The frequency behavior is compliant with the datasheet of such commercial sensor if the forward and return cables of the primary circuit of the sensor are kept far from the yoke. In fact, for case (b) the gain is about −1 dB at 10 kHz, as declared in the datasheet. The frequency band in the twisted cable configuration is considerably lower than rated, i.e., about −1 dB at 2 kHz.
7.1.2. Fitting the Dependency of the Correction Coefficient on the Frequency
The function that approximates the frequency behavior of the current sensor has been tailored considering the behavior obtained with the cables far from the yoke of the magnetic circuit of the sensor (red curve in
Figure 13). It can be deduced that an overshoot occurs around 5 kHz. Such behavior can be reproduced by a couple of two complex and conjugate poles. Moreover, one can note that the slope of the measured frequency dependence is lower than the expected 40 dB per decade produced by the two poles; this is taken into account by introducing a zero at about 3 kHz that reduces the slope and allows a better fit in the frequency range between a few kilohertz to 10 kHz. The description of the fit function
Gfit, in the Laplace domain, is based on Equation (13) described as follows:
A comparison between the fit functions and the measured frequency dependence of the sensor gain is provided in
Figure 14. The fit agrees with the measurement data within 0.5 dB up to 10 kHz.
7.2. The Actual Current Flowing in the Braking Rheostat
Using the transfer function of the braking rheostat and the current sensor, it is possible to compare the time behavior of the simulated-actual current,
, flowing in the braking rheostat, the distorted signal provided by the current sensor,
, its digitization,
, and the samples acquired on-board the locomotive,
.
Figure 15 provides a comparison among such quantities for two different vales of the duty-cycle
δ of the braking chopper:
δ = 0.9% that is the minimum recorded value (
Figure 15a) and
δ = 15 % (
Figure 15b).
For low duty-cycle, the distortion introduced by the current sensor is much more evident, the peak value of the actual current is not detected. For higher duty-cycle, the overshoot on the signal provided by the sensor, shown in
Figure 15b, is the effect of the two complex poles. The good overlap between the measured current and the signal provided by the simulation demonstrates the accuracy of the frequency characterization of the current transducer.
7.3. Sampling Effects in the Dissipated Power/Energy Estimation
The sampling mechanism, in particular for pulses with a low duty-cycle, can dramatically affect the area underneath the sampled curves. Moreover, the position of the first sample following the onset of the pulsed signal can provide different results in terms of the area estimation and thus provide different power estimation. A demonstration of the size of this effect is shown in
Figure 16a for a duty-cycle of
δ = 0.9%. The effect in the time domain of a different position of the first sample is provided in
Figure 16b. In particular, the figure shows the position of the samples that provide the lowest and biggest deviation between the area underneath the actual current wave and the sampled signals.
7.4. Estimation of the Correction Coefficient as a Aunction of the Current Duty-Cycle
The correction coefficient
KHOP, defined in
Section 5, strongly depends on the duty-cycle of the chopped voltage signal. In detail,
KHOP is high with a low duty-cycle, where the distortion effect introduced by the current transducer is higher. Such effect is also evident in
Figure 17. As described in the previous subsection, the value of
KHOP depends on the position of the samples in time with respect to the position of the pulse. This information is not deterministic but random; as a consequence, for each duty-cycle a distribution of possible values of
KHOP is found by varying the temporal position of the samples. This procedure provides a bandwidth of possible values of
KHOP for each duty-cycle value.
Figure 17a describes the behavior of
KHOP as a function of the duty-cycle and the error bars indicate the bandwidth of possible values.
The correction coefficient
KDC that compensates for the error in the definition of the power dissipated by the rheostat is significant for low duty-cycle and tends to unity with increasing duty-cycle, as shown in
Figure 17b. Some values of the two correction coefficients and their product with the associated interval of maximum variability due to the position of the samples in time with respect to the pulse onset position is provided in
Table 3.
7.5. Impact of the Offset Introduced by the Current Sensor
During a real measurement, the acquisition system shows an offset caused by external influence factors or internal offsets of the sampling device. This offset manifests itself even when the chopped voltage is switched off and the power is zero. If neglected, the offset can introduce an error of up to 10% of the whole braking energy during the campaign. Since the offset level is changing in time, it has to be determined for every braking pulse independently. The offset level is estimated using the samples before and after a braking pulse and subtracted from the braking pulse.
7.6. Application of the Correction Methodology to Measured Data
The proposed procedure is applied to a single electrical braking event recorded during a commercial route of a train operating on line 10 B of Metro de Madrid [
30]. The braking event lasts for about 10 s. The DC voltage at the input of the chopper is 1780 V on average (see
Figure 18a). The time behavior of the two input parameters of the methodology proposed for the correction,
δI and the power
P have been calculated by means of the formula shown in
Figure 12, over a time window of 20 ms (six periods of the chopped signal). Such integration time allows to reduce the impact of a single outlier on the estimated quantities without losing the information on their dynamic variations. The variation of these quantities with time is shown in
Figure 18b. The dissipated power is higher at the beginning of the braking, increasing to a maximum of 160 kW; after a couple of seconds the power decreases to about 40 kW. Two power peaks of 60 kW and 80 kW are reached at about 6.5 s and 8.5 s.
As can be seen from
Figure 18b, the power behavior with time follows the behavior of the duty-cycle
δI, computed from the chopped current. The maximum value of
δI of about 15% is reached in the first instant of the braking event, whereas the minimum is about 1.8%.
The time behavior of
δI and the analytical function (16) allow the estimation of the duty-cycle of the chopped voltage and, as a consequence, the time behavior of the correction coefficients
KDC and
KHOP, which is shown in
Figure 19a. As can be seen, the weight of the combined correction coefficients (
KDC∙
KHOP) ranges from about 0.95 to 0.75. The value of
KHOP provided here refers to the mean value. A comparison between the power before the correction,
P, and the values obtained after the application of the correction
Pcorr, is reported in
Figure 19b. The same figure provides the behavior of the percentual deviation Δ between the two powers computed as
The deviation between non-corrected and corrected power ranges from 5% to about 34%; as expected, the deviation is higher for lower power. The considered braking is characterized by an average power dissipation, for a single rheostat, of about 35.8 kW.
As described in
Section 7.4, the correction factor
KHOP is characterized by a range of possible values for each duty-cycle value (
Figure 17a). Such random behavior propagates into the power estimation. The impact of the correction factor on the power is about 11% with an associated range of values of ± 2%.
To give evidence of the impact of the correction on the measured power, a collection of values for the two power magnitudes and their deviation is provided in
Table 4. The table also provides the interval of variability (±var) associated with the corrected power
Pcorr and, as a consequence, to the deviation due to the variability on
KHOP.
8. Discussion and Conclusions
A methodology for the accurate estimation of the power and energy dissipated by a braking rheostat installed on-board rolling stock has been presented. A description of the measurement procedure applied on-board a metro vehicle and a model used for the power estimation is provided. The treatment focuses on the description, modeling and quantification of two systematic errors that affect the power estimation. One is due to the approximate model for the power estimation, a consequence of practical implementation of the measurement setup that has to guarantee an adequate level of safety, reliability and has to reduce, as much as possible the invasiveness towards the electrical apparatuses of the locomotive. The other error is introduced by the limited bandwidth of the current sensor employed in the chopped-current measurement and the limited sample frequency for the digitization of the signal. The variability in the power estimation introduced by the limited sample frequency is studied and quantified. It has been demonstrated that the correction factors dramatically affect the power estimation for low power amplitude, that is, low duty-cycle. For a duty-cycle of about 1%, which is the minimum duty-cycle experienced, the corrected power is reduced by about 36%. The same occurs for the range of variability introduced by the stochastic positions of the sampled data with respect to the current pulse. The variability at 1% duty-cycle ranges from 17% to 41% with an average value of 31%. This means that, as expected, the uncertainty associated with the power estimation is higher for low power amplitude. We conclude that long braking with low duty-cycle, that is, low dissipated power, is estimated with a high uncertainty.
The proposed technique has been applied to a real dissipative braking event recorded on-board a metro vehicle. This braking event, during about 10 s, is characterized by a duty-cycle ranging from 5% to 14%; with the same time behavior, the power ranges from few tens of kilowatts to about 130 kW with an average value of about 60 kW. Under these conditions, the deviation between uncorrected and corrected power is about 20%. Such an error is relevant for proper energy flow analysis as in the design of on-board storage systems. This demonstrates the usefulness of the proposed methodology.