1. Introduction
Oil-immersed electrical equipment plays a critical role in electrical energy transmission and distribution. The safe and stable operation of such equipment has long been the center of electrical industry. When insulation faults occur, a series of decomposition product will be generated. The category and concentration of those decomposition products strongly correlate with the insulation status of transformer. Based on current studies, acetylene (C
2H
2) is generally considered as the most significant decomposition of insulation oil which can stand for the severity of discharge fault in oil-insulated equipment [
1,
2]. To monitor the concentration of dissolved C
2H
2, dissolved gas analysis (DGA) is often considered as the most efficient and convenient way [
3].
In order to diagnose potential insulation fault at early stage, high sensitivity C
2H
2 detection method is required. Compared with conventional gas chromatographic (GC)-based method, photoacoustic spectroscopy (PAS)-based method is with higher accuracy and shorter response time [
4,
5]. Hence, PAS is often employed for highly sensitive DGA and has become more and more approved in the electrical industry [
6]. Nowadays, several kinds of PAS-based commercial DGA equipment have launched the market and they are now gradually replacing conventional GC-based equipment [
7].
On the other hand, dissolved gases need to be extracted first from oil for subsequent analysis in DGA. Under this circumstance, gas–oil separation method affects the results of DGA drastically. Based on the document published by American Society for Testing and Material (ASTM), extraction methods for dissolved gas include vacuum extraction, stripping and headspace [
8]. Aforementioned methods usually require complex mechanical devices and considerate maintenance cost. However, for the electrical equipment with limited space and special location, such as bushing, regular floor type DGA equipment with large size is not applicative. Consequently, DGA equipment with low maintenance frequency and small volume is required. As a novel and promising method, membrane-based gas–oil separation method possesses some merits such as energy saving, cost competitiveness and small volume, therefore, membrane technique stands for a kind of promising perspective for DGA [
9]. The application of membrane in DGA is beneficial to miniaturizing the size of DGA equipment. Such membrane has been used in small-size commercial DGA equipment [
10].
Compared with conventional gas extraction method such as vacuum extraction, the separation efficiency of membrane is limited [
11]. Plentiful studies have been conducted to obtain better performance of membrane [
12,
13]. According to existed researches, the performance of membrane is primarily decided by the status of membrane itself [
14]. However, in practical scenarios, the separation processes are also affected by the surrounding conditions such as pressure and feed velocity [
15,
16]. Under different conditions, the performance of membrane varies. Thus, it is necessary to study the influences of the conditions of oil on the performance of membrane unit since the results of gas–oil separation is fundamental to the accuracy of DGA.
To develop a DGA equipment with both high accuracy and small size, a PAS-based trace C2H2 detection system with membrane unit was established in this work. By setting different conditions, the gas–oil separation process could be observed by collecting photoacoustic signal, therefore, the performance of membrane could be evaluated this way. This work evaluated the performances of membrane under different feed velocity and pressure from both simulation and experiment perspectives. Based on the results of this work, the influences of conditions of oil have on the performance in practical scenarios can be learnt, which may serve as a reference for membrane application in DGA.
2. Theoretical Fundamentals
2.1. Photoacoustic Spectroscopy
PAS detection method is based on gas photoacoustic effect, which is a process from light to sound. In photoacoustic cell, acoustic waves are generated because of periodic transit from gas molecules excited by periodic light. Then, the acoustic waves are collected by microphone and converted to electrical signals. Based on current research, the relationship between converted electrical signals and concentration of investigated gas can be expressed as Equation (1) [
17].
where,
SPAS represents the electrical signal (V),
sm represents the sensitivity of the microphone (V/Pa),
Pinput represents the power of the light source (W),
Fcell represents the cell-specific constant (Pa·cm/W),
α represents the absorption coefficient of investigated gas at the nominal wavelength of the light source (cm
−1),
c represents the concentration of investigated gas (ppm).
2.2. Non-Porous Membrane
Non-porous membrane is the most recognized category of membrane for gas–oil separation. According to existed studies, a prevailing model to describe non-porous membrane was solution-diffusion model [
18,
19]. In this model, with the assumption of total pressure being 1 atm, the concentration in the downstream side, which was the gas room in this work, could be calculated as Equation (2).
where
cg represents the concentration of gas (ppm), which is C
2H
2 in this work, in the gas room after time
t,
k represents the equilibrium constant,
c0 represents the gas concentration in the oil (ppm),
cg0 represents the initial gas concentration in the gas room (ppm),
H represents the permeability of gas in the membrane (cm
2/(s·Pa)),
A represents effective contacting area between membrane and oil (cm
2),
t represents time (s),
d represents the thickness of membrane (cm),
V represents the volume of gas room (mL).
Usually, the gas room was filled with ambient gas in the first place. Therefore, Equation (2) could be rewritten as Equation (3).
Plus, equilibrium constant is related to the category of gas instead of membrane only. In practical scenario, equilibrium can be seen as achieved when the concentration of investigated gas reaches 90% of theoretical maximum. Therefore, the equilibrium time can be calculated as Equation (4) [
20,
21].
In this work, the equilibrium times were collected in this way.
2.3. Concentration Polarization
For a dissolved gas brought to a membrane surface, there is an accumulation of solute gas in the boundary layer adjacent to the membrane. Such phenomenon, which is referred to as concentration polarization, severely impairs membrane separation processes [
22,
23]. Thus, this reduces the performance of membrane and raises the costs of capital and operation. The concentration polarization of the investigated gas can be described as Equations (5)–(7) [
24].
where,
J represents the permeation rate of the gas,
x represents the molar fraction of the gas in the bulk feed,
k represents the mass transfer coefficient which is proportional to the velocity of the feed gas,
P0 represents standard pressure,
T represents the temperature on the feed side,
T0 represents standard temperature,
Pp represents the pressure on the permeate side,
Pf represents the pressure on the feed side,
α0 represents the separation factor of the gas without concentration polarization.
3. Simulation Modeling and Experiment Setups
Based on the theory aforementioned, this paper employed both simulation and experiment and testified the influence of the conditions of fluid to the performance of membrane. Fundamental preparations of simulation and experiment were introduced successively as follows.
3.1. Simulation Modeling
In this work, COMSOL Multiphysics was employed in this work to simulate the dissolution process. Therefore, the qualitative impact of different feed velocity has on the permeability of membrane could be directly demonstrated.
Considering the symmetry of the structure, a symmetrical model that demonstrated upper half of integration photoacoustic cell was established in COMSOL Multiphysics, which is shown in
Figure 1.
From
Figure 1, inlet and outlet were the entrance and exit of oil, with a domain point probe placed in the top center of gas room to detect the concentration of gas.
3.2. Experimental Setups
In this work, the concentration of investigated gas was reflected by the value of photoacoustic signal. To monitor the change of the concentration of investigated gas, a detection system based on PAS was established in this work, whose topological structure is shown in
Figure 2.
In detail, an integration photoacoustic cell was designed for gas–oil separation and detection. The structure is shown in
Figure 3.
From
Figure 3, flat membrane unit was employed in this paper. With the thickness of 12.5 μm, the membrane in this work was made of fluorinated ethylene propylene (FEP). The oil contacted constantly with the membrane in the form of cross fluent. After dissolved gas was separated from oil by membrane, it diffused into the gas room for detection. The integration design of the photoacoustic cell was to reduce the volume of gas room and shorten balance time accordingly. Plus, the speed of gear pump was proportional to its voltage. Therefore, the feed velocity of oil could be adjusted by controlling the output of DC power.
4. Results and Discussions
In this section, the influences of the conditions of oil feed velocity on the performance of membrane were discussed by analyzing the simulation and experiment results. The influences of feed velocity and pressure were studied successively.
4.1. Simulation Results and Analysis
In this work, the influence of feed velocity on membrane performance was studied from both simulation and experiment side, which would be introduced successively.
Firstly, in COMSOL Multiphysics, we set the pressure of oil fluid as 1.0 atm. Then, we set the feed velocity at the inlet in the simulation model as 8 mL/s, 16 mL/s, 24 mL/s, 32 mL/s, 40 mL/s, successively. Next, we conducted time-dependent study at each condition. Finally, we repeated aforementioned procedure with the pressure of 1.5 atm and 2.0 atm. Simulation results of the concentration at domain point probe are shown in
Figure 4.
According to Equation (1), the concentration of investigated gas on the permeate side was proportional to the value of photoacoustic signal. Therefore, the separation process of membrane could be indicated by the variation of the gas concentration in the gas room. On the other hand, the relationship between time and photoacoustic signal was consistent with Equation (3) in the form and R2 > 0.999 testified the correctness of applying solution-diffusion model.
From
Figure 4, it could be seen that the equilibrium time decreased with the increasement of the feed velocity. The increase of feed velocity reduced the level of concentration polarization and contributed to the permeation of gas in the membrane. Therefore, the equilibrium time was shortened as well. For better demonstration, the equilibrium times are listed as
Table 1.
From
Table 1, it could be seen that the equilibrium time drastically decreased when the feed velocity increased, which indicated that the flux increased accordingly. Based on Equation (5), the concentration polarization decreased with the increase of the feed velocity. Consequently, the performance of membrane was improved. So, it could be concluded that the feed velocity of oil should be as large as possible to obtain shorter equilibrium time.
Moreover, with the same feed velocity, the variation of pressure affected the equilibrium time little. Considering the actual fluctuation of pressure in the equipment was usually smaller than the pressure difference in our simulation, it could be concluded that the equilibrium time was barely impacted by the pressure of oil. This indicated that the performance of membrane was rather stable if the pressure varies [
15].
4.2. Experimental Results and Analysis
Based on the topological structure aforementioned in
Figure 2, a detection system for trace C
2H
2 was established in this work to monitor the performance of membrane. Then, we set the pressure of oil as 1.0 atm, 1.5 atm, 2.0 atm, respectively. Under same pressure condition, we set the speed of gear pump at 800 rpm, 1600 rpm, 2400 rpm, 3200 rpm, 4000 rpm. Corresponding feed velocity of oil was 8 mL/s, 16 mL/s, 24 mL/s, 32 mL/s, 40 mL/s, respectively. We successively detected the concentration of separated C
2H
2 every half hour. After the scatter data were collected, corresponding fitting functions were calculated successively. In this work, BoxLucas model was for fitting. The model can be expressed as Equation (8).
where,
y represents photoacoustic signal,
x represents time,
a and
b are fitting parameters. It could be seen that the equilibrium time to reach 90% of maximum was only related to the value of
b. In order to obtain direct comparison of equilibrium time under different conditions, experiment data were normalized and
a was set as 1 in this work.
The data and corresponding fitting functions were as
Figure 5.
The fitting parameters of each curve were listed as
Table 2.
From
Figure 5 and
Table 2, it could be concluded that fitting functions were consistent with Equation (3) in the form.
R2 > 0.95 verified the rationality of the fitting functions. The equilibrium times under different conditions were calculated on the basis of corresponding fitting functions. The equilibrium times in the experiment are listed in
Table 3.
From
Figure 5 and
Table 3, with the increase of the feed velocity, photoacoustic signal increased faster accordingly. Therefore, the time to reach equilibrium decreased. This indicated that the performance of membrane increased with the feed velocity, which agreed with Equation (5). Additionally, the equilibrium time was hardly affected by the pressure of oil on the feed side. The results of experiment demonstrated that it could match simulation results well. Moreover, the experience of the research could also be beneficial to the application in actual scenario. The feed velocity contributed to shortening equilibrium time, but excessive feed velocity would also cause overheating problem because of the friction between oil and boundary. Furthermore, overheating oil was one of the main reasons to generate bubbles [
25]. Bubbles could impair the insulation capability of oil and cause partial discharge [
26]. Therefore, the feed velocity of oil should be as large as possible within a reasonable range. Although no bubble was generated, the feed velocity in this work was large enough to cause obvious temperature rise. Extra cooling measure was used to keep the temperature of integration photoacoustic cell steady. In a practical scenario, this could be a reference for the equipment to maintain stable performance.
5. Conclusions
In this work, the influences of the conditions of oil on the performance of membrane were studied. To be more specific, the performance of membrane under different feed velocity and pressure of oil was analyzed. First of all, relevant theories were introduced to analyze potential influences the conditions of oil had on the performance of membrane.
Next, simulation model and experiment were established to investigate the influences in both ways. Then, simulation and experiment were conducted to study the relationship between equilibrium time and feed velocity and pressure. The results indicated the performance of membrane could be improved by adjusting the conditions of oil to obtain better results of DGA. Finally, the analysis results were further applied to investigate how different conditions were going to influence the membrane performance in practical scenarios. It should be noted that the simulation model represents an ideal situation without any interference from outside. Therefore, compared with simulation, the experiment can simulate the actual scenario better since the experiment equipment was the prototype of the device applied in actual scenario. Still, the simulation results could serve as a guide for an experiment to analyze the performance of membrane under different conditions.
With the prevailing application of novel membrane materials, membrane-based DGA equipment with PAS sensor has become more and more approved in the market. The factors that may affect the outcome of DGA should be attached with much importance. Under this circumstance, the results of this work may serve as a guideline for the application of membrane in DGA, especially the scenarios with limited space where the membrane unit is more suitable than conventional gas extraction methods.
Author Contributions
Conceptualization, T.C., X.X. and G.Z.; Methodology, T.C. and Z.L.; Software, T.C.; Validation, T.C. and Z.L.; Formal analysis, T.C.; Investigation, T.C. and Z.L.; Resources, G.Z.; Data curation, T.C.; Writing—original draft preparation, T.C.; Writing—review and editing, T.C., K.L., Z.L., X.X. and G.Z.; Supervision, K.L., X.X. and G.Z.; Project administration, K.L., X.X. and G.Z.; Funding acquisition, K.L., X.X. and G.Z. All authors have read and agreed to the published version of the manuscript.
Funding
This research was funded by State Key Laboratory of Power Grid Environmental Protection (China Electric Power Research Institute), grant number GYW51202101367. The APC was funded by State Key Laboratory of Power Grid Environmental Protection (China Electric Power Research Institute), grant number GYW51202101367.
Institutional Review Board Statement
Not applicable.
Informed Consent Statement
Not applicable.
Data Availability Statement
Data sharing not applicable.
Acknowledgments
The authors specially thank State Key Laboratory of Power Grid Environmental Protection (China Electric Power Research Institute) for their support.
Conflicts of Interest
The authors declare no conflict of interest.
References
- Ma, F.; Liao, Z.; Zhao, Y.; Qiu, Z.; Wan, L.; Li, K.; Zhang, G. Detection of trace C2H2 in N2 buffer gas with cantilever-enhanced photoacoustic spectrometer. Optik 2021, 232, 166525. [Google Scholar] [CrossRef]
- Chen, T.; Ma, F.; Zhao, Y.; Zhao, Y.; Wan, L.; Li, K.; Zhang, G. Portable ppb-level acetylene photoacoustic sensor for transformer on-field measurement. Optik 2021, 243, 167440. [Google Scholar] [CrossRef]
- Liu, S.; Ma, L.C.; Chen, C.H.; Chen, C.; Lin, Y.S. Highly gas permeable, ultrathin Teflon AF2400/γ-alumina composite hollow fiber membranes for dissolved gas analysis. J. Memb. Sci. 2017, 540, 243–250. [Google Scholar] [CrossRef]
- Zhang, Q.; Chang, J.; Cong, Z.; Sun, J.; Wang, Z. QEPAS sensor for simultaneous measurements of H2O, CH4, and C2H2 using different QTFs. IEEE Photonics J. 2018, 10, 1–8. [Google Scholar] [CrossRef]
- Zhang, Q.; Chang, J.; Cong, Z.; Wang, Z.; Wang, F.; Sun, J.; Zhu, C. Intra-cavity multi-point sensor for C2H2 detection in photoacoustic spectroscopy based on acousto-optic Q-switched fiber laser. Optik 2020, 206, 164277. [Google Scholar] [CrossRef]
- Mao, X.; Zhou, X.; Zhai, L.; Yu, Q. Dissolved Gas-in-Oil Analysis in Transformers Based on Near-Infrared Photoacoustic Spectroscopy. Int. J. Thermophys. 2015, 36, 940–946. [Google Scholar] [CrossRef]
- Bustamante, S.; Manana, M.; Arroyo, A.; Castro, P.; Laso, A.; Martinez, R. Dissolved gas analysis equipment for online monitoring of transformer oil: A review. Sensors 2019, 19, 4057. [Google Scholar] [CrossRef] [Green Version]
- ASTM-D3612-02(2017); Standard Test Method for Analysis of Gases Dissolved in Electrical Insulating Oil by Gas Chromatography. ASTM International: West Conshohocken, PA, USA, 2009. [CrossRef]
- Cheng, J.; Huang, Q.; Huang, Y.; Luo, W.; Hu, Q.; Xiao, C. Study on a novel PTFE membrane with regular geometric pore structures fabricated by near-field electrospinning, and its applications. J. Memb. Sci. 2020, 603, 118014. [Google Scholar] [CrossRef]
- General Electric Company, Hydran M2-X, (n.d.). Available online: https://www.gegridsolutions.com/md/catalog/hydranm2x.htm (accessed on 26 April 2022).
- Ma, L.-C.; Chen, C.; Lin, J.Y.S. Teflon AF2400 Hollow Fiber Membrane Contactor for Dissolved Gas-in-Oil Extraction: Mass Transfer Characteristics. Ind. Eng. Chem. Res. 2020, 59, 16795–16804. [Google Scholar] [CrossRef]
- Park, J.; Yoon, H.W.; Paul, D.R.; Freeman, B.D. Gas transport properties of PDMS-coated reverse osmosis membranes. J. Memb. Sci. 2020, 604, 118009. [Google Scholar] [CrossRef]
- Carrera-Figueiras, C.; Aguilar-Vega, M. Gas permeability and selectivity of hexafluoroisopropylidene aromatic isophthalic copolyamides. J. Polym. Sci. Part B Polym. Phys. 2005, 43, 2625–2638. [Google Scholar] [CrossRef]
- Ma, L.C.; Chen, C.; Chen, C.H.; Tung, K.L.; Lin, J.Y.S. Gas Transport properties of Teflon AF2400/Ceramic Composite Hollow Fiber Membranes in Dissolved-Gas-in-Oil Extraction. Ind. Eng. Chem. Res. 2020, 59, 5392–5401. [Google Scholar] [CrossRef]
- Ahmad, F.; Lau, K.K.; Shariff, A.M.; Yeong, Y.F. Temperature and pressure dependence of membrane permeance and its effect on process economics of hollow fiber gas separation system. J. Memb. Sci. 2013, 430, 44–55. [Google Scholar] [CrossRef]
- Gilbert, R.; Nguyen, H.P.; Jalbert, J.; Charbonneau, S. Transport properties of a mixture of permanent gases and light hydrocarbons through the polytetrafluoroethylene capillary tubes of a GP-100 gas extractor. J. Memb. Sci. 2004, 236, 153–161. [Google Scholar] [CrossRef]
- Wang, J.; Wang, H. Ammonia carbon dioxide and water vapor detection based on tunable fiber laser photoacoustic spectroscopy. Optik (Stuttg.) 2016, 127, 942–945. [Google Scholar] [CrossRef]
- Saleh, T.A.; Gupta, V.K. Applications of Nanomaterial-Polymer Membranes for Oil and Gas Separation. Nanomater. Polym. Membr. 2016, 10, 251–265. [Google Scholar] [CrossRef]
- Wang, L.; Corriou, J.P.; Castel, C.; Favre, E. Transport of gases in glassy polymers under transient conditions: Limit-behavior investigations of dual-mode sorption theory. Ind. Eng. Chem. Res. 2013, 52, 1089–1101. [Google Scholar] [CrossRef]
- Fengxiang, M.; Yu, T.; Ke, C.; Feng, J.; Wang, Z.; Jiong, Q.; Qingxu, Y. Technique for detection of dissolved gas in oil based on miniature photoacoustic sensor. Acta Opt. Sin. 2020, 40, 0730003. [Google Scholar] [CrossRef]
- Han, Y.; Ding, F.; Hao, C.; Lv, S.; Wang, X. The oil-gas separation characteristics of ceramic/Teflon AF2400 composite membrane. Sep. Purif. Technol. 2012, 88, 19–23. [Google Scholar] [CrossRef]
- Denisov, G.A. Theory of concentration polarization in cross-flow ultrafiltration: Gel-layer model and osmotic-pressure model. J. Memb. Sci. 1994, 91, 173–187. [Google Scholar] [CrossRef]
- Sablani, S.; Goosen, M.; Al-Belushi, R.; Wilf, M. Concentration polarization in ultrafiltration and reverse osmosis: A critical review. Desalination 2001, 141, 269–289. [Google Scholar] [CrossRef]
- He, G.; Mi, Y.; Yue, P.L.; Chen, G. Theoretical study on concentration polarization in gas separation membrane processes. J. Memb. Sci. 1999, 153, 243–258. [Google Scholar] [CrossRef]
- Lu, L.; Ichimura, S.; Rokunohe, T. Interaction between Partial Discharge and Generated Bubbles under Repeated Lightning Impulses in Transformers Using a Complex Structure Model. IEEE Trans. Dielectr. Electr. Insul. 2021, 28, 727–735. [Google Scholar] [CrossRef]
- Zhang, R.; Zhang, Q.; Guo, C.; He, X.; Wu, Z.; Wen, T. Bubbles in Transformer Oil: Dynamic Behavior, Internal Discharge, and Triggered Liquid Breakdown. IEEE Trans. Dielectr. Electr. Insul. 2022, 29, 86–94. [Google Scholar] [CrossRef]
| Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations. |
© 2022 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).