Fault Diagnosis of Medium Voltage Circuit Breakers Based on Vibration Signal Envelope Analysis

1
School of Electrical Engineering, Southeast University, Nanjing 210096, China
2
Nanjing Power Supply Branch Company, State Grid Jiangsu Electric Power Co., Ltd., Nanjing 211102, China
*
Author to whom correspondence should be addressed.
Sensors 2023, 23(19), 8331; https://doi.org/10.3390/s23198331
Submission received: 15 September 2023 / Revised: 6 October 2023 / Accepted: 7 October 2023 / Published: 9 October 2023
(This article belongs to the Special Issue Advanced Sensing for Mechanical Vibration and Fault Diagnosis)

Abstract

:
In modern power systems or new energy power stations, the medium voltage circuit breakers (MVCBs) are becoming more crucial and the operation reliability of the MVCBs could be greatly improved by online monitoring technology. The purpose of this research is to put forward a fault diagnosis approach based on vibration signal envelope analysis, including offline fault feature training and online fault diagnosis. During offline fault feature training, the envelope of the vibration signal is extracted from the historic operation data of the MVCB, and then the typical fault feature vector M is built by using the wavelet packet-energy spectrum. In the online fault diagnosis process, the fault feature vector T is built based on the extracted envelope of the real-time vibration signal, and the MVCB states are assessed by using the distance between the feature vectors T and M. The proposed method only needs to handle the envelope of the vibration signal, which dramatically reduces the signal bandwidth, and then the cost of the processing hardware and software could be cut down.

1. Introduction

Medium voltage circuit breakers (MVCB) play a vital role in modern power systems or new energy power stations, and its operating state will affect the stability and power supply reliability of the power grid [1,2]. Numerous studies have shown that mechanical faults are one of the main problems influencing the operational reliability of the circuit breaker (CB) [3,4,5]. In order to monitor the status and realize a fault diagnosis of the CB, the commonly used acquisition signals may include transient electric field [6], vibration signal [7,8,9,10], current signal [9,10,11], sound signal [12], and travel-time curve [13,14]. Among them, the use of vibration signals for CB fault diagnosis has the advantages of low cost and high diagnosis performance. However, in order to reliably switch on or switch off the circuit, it is important to timely and correctly discriminate among the operating states of the CB and find hidden dangers by analysing the mechanical vibration signal produced during the HVCB operation.
The vibration of the CB is a time-varying, non-steady and non-linear signal. A complex vibration signal is divided by empirical mode decomposition (EMD) into several intrinsic mode functions that each contain local characteristic timescales. The improved EMD energy entropy was selected in [15] to obtain the fault feature of the CB, and a genetic algorithm-based support vector machine (SVM) was applied to classify the CB states. However, the traditional EMD has the disadvantages of border effects, model overlap, and the deficiency of strict theory deduction. In order to make the signal continuous over various time scales, ensemble EMD adds Gaussian white noise to the vibration signal, which can solve the problem of EMD mode aliasing. In [16,17], the EEMD and Hilbert marginal spectrum energy entropy were proposed to extract feature vectors, and the SVM was utilized to classify the mechanical faults of the CB. Nevertheless, the ensemble EMD of the vibration signal still leaves certain noise components, and they will influence the fault diagnosis result. The complete ensemble EMD with adaptive noise could eliminate the model aliasing of the ensemble EMD. In [18,19], the complete ensemble EMD with adaptive noise decomposed and reconstructed the intrinsic mode function to obtain a time–frequency matrix. The variational model decomposition was applied in [20,21,22,23], to extract fault features and address the multi-scale entropy of the reconstructed signal, where variational model decomposition can split the vibration signal up into a range of bandwidth-constrained modal functions. However, the mode number is too arbitrary and lacks a general theoretical foundation in decomposition and reconstruction. The wavelet packet decomposition (WPD) has the advantage of high resolution in the whole frequency band, and feature decomposition of the vibration signals is realized in different time periods and frequency bands. For the WPD algorithm, Ref. [24] used the wavelet packet sample entropy and energy spectrum to obtain the feature vectors of vibration signals. Ref. [25] selected the energy rate in time–frequency Eigen-space of wavelet packets as the basis for the fault diagnosis of the CB. In papers [15,16,17,18,19,20,21,22,23,24,25], the existing fault diagnosis methods need to construct fault features based on the complete operating vibration signal, where the signal processing algorithm is complex, the diagnosis speed is slow, and the hardware and software costs are high.
This paper put forwards a fault diagnosis approach for the MVCB based on vibration signal envelope analysis. The proposed approach has the advantages of accelerating recognition speed, decreasing the expenditure on the hardware and software. The major contributions of this research can be concluded as below:
(1)
Only the envelope of the vibration signal needs to be processed. The bandwidth of the processed signal for the proposed method is greatly decreased, which reduces the expenditure on software and hardware.
(2)
The performance efficiency of the proposed approach is much more than the existing typical fault diagnosis methods, which is adequate for the online fault diagnosis of the MVCB.
The rest of this paper is formed as below. Section 2 discusses the experiment setup and data acquisition system. The fault diagnosis method is introduced in Section 3. The experiment results and discussions are shown in Section 4. Finally, the conclusions of this article are summarized in Section 5.

2. Experiment Setup and Data Acquisition

Figure 1 shows the experiment setup which is used to collect the vibration signal at various operating states.
In this paper, a solid-insulated indoor 40.5 kV 630A vacuum MVCB with spring actuator made by Chinese company (Yunfeng Science & Technology Co. Ltd., Jiangyin, China) is adopted, as shown in Figure 1a. A vibration sensor is installed on the crossbeam at the upper side of the MVCB, and it is closed to the operating mechanism of the MVCB. Figure 1b shows the data acquisition system, which includes power supply, signal preprocessing circuit, data acquisition card and host computer. The signal preprocessing circuit could collect and convert the current signal of the vibration sensor into the voltage signal.
The configuration of the data acquisition system is given in Table 1, where the signal sampling frequency is selected as 125 kHz and the data acquisition card is connected to the host computer with USB 2.0.
The MVCB performed switch-on and switch-off operations at six typical cases, including normal case, iron core jamming, shaft-bearing screw looseness, closing-spring relaxation, low relay coil voltage, and relay high-resistance cases. The normal case and five faulty cases (iron core jamming, bearing-screw looseness, closing-spring relaxation, low relay coil voltage, and relay high resistance) studied in this paper are defined as Case 1, Case 2, Case 3, Case 4, Case 5, and Case 6, respectively, as shown in Table 2. In this paper, five faulty cases are emulated in the lab by suspending a heavy weight on the iron core of the closing relay, loosening one bearing screw of the main drive shaft, loosening spring-end nuts, reducing control voltage, and adding a resistor in the relay coil, respectively. The fault reason and emulation method for five faulty cases are also given in Table 2.
Figure 2a shows the emulation method for the iron core jamming case, where a 54 g weight is hung on the moving iron core by the lead, turning the drag force around. Figure 2b shows the emulation method for the bearing-screw looseness case, where one screw of the drive shaft is released by one turn. As the fault reason of the closing-spring relaxation case is due to the aging of the closing spring, the closing-spring relaxation state could be emulated by adjusting the end nuts to decrease the pretension force of the closing spring, as shown in Figure 2c. Figure 2d shows the emulation method for the low relay coil voltage case, where the control voltage is decreased to 0.9 times the rated voltage. As the fault reason of the relay high-resistance case is due to the relay coil aging or the poor contact of relay, the relay high-resistance case could be emulated by adding a 5 ohm resistor into the circuit of the closing relay coil, as shown in Figure 2e.
For mechanical circuit breakers, the closing spring stores energy for the opening spring during the closing operation. The vibration signal energy of the closing process is greater than that of the opening process, and the fault features of the vibration signal during the closing process are more significant than those during the opening process. Therefore, the vibration signal of the MVCB during the closing operation is collected and studied in this paper. Fifteen sets of vibration signal per case are measured by a data acquisition system. As shown in Table 3, 10 sets of samples (named Database 1) are randomly selected to offline train fault feature, and the remaining five sets of samples (named Database 2) were used for testing to verify online fault diagnosis algorithm.
Figure 3 gives the vibration signals of the MVCB in the time domain under the closing operation, where the vibration signals present strongly non-linear and non-steady properties. The operation process of the MVCB is transitory, and the duration is generally about several tens of millisecond. As shown in Figure 3, it is obvious that two processes are carried out under different states but it is difficult to discriminate the state only by the time-domain signals.
According to the Fast Fourier Transform (FFT) of the original vibration signal, Figure 4 shows the spectrum diagrams of the original vibration signal under six states, where frequency band width is quite large and the main spectrum is within 0–20 kHz. Compared with the five faulty states, the spectrum of Case 1 is richer and has higher wave crests.
Meanwhile, if researchers can select the appropriate feature vector in the frequency spectrum diagram, it will be relatively easy to distinguish the four states by the frequency domain signals. In [7,8], the researcher usually selected four representative vibration feature as the frequency domain features, and the specific feature variables and expressions are shown in Table 4. Here, L is the length of one set sample at 125 kHz. S(f) is the amplitude of the frequency f in the frequency spectrum. Cavf is the average value of the frequency spectrum. Crmsf is the root mean square value of the frequency spectrum. Csdf is the standard deviation value of the frequency spectrum. Cgcf is the center of gravity value of the frequency spectrum.
In [13,18,19], the extreme learning machine (ELM) is applicable to the small sample classification problem in fault diagnosis of the MVCB. The ELM is used to distinguish the six cases of the MVCB in accordance with the selected frequency domain features. Database 1 is adapted to train the ELM model, and Database 2 is used to test the ELM model. The details of the MVCB state identification are shown in Table 5. The average training accuracy is 91.67%, and the average testing accuracy is 76.67% by using the selected features of frequency domain and ELM.

3. Envelope Analysis of Vibration Signal

From the frequency domain signal, four states of MVCB could be discriminated, but the complete operating vibration signal must be processed. To accelerate diagnosis speed and decrease the expenditure on hardware and software, a fault diagnosis approach based on vibration signal envelope analysis is proposed, as shown in Figure 5. The fault diagnosis process consists of offline training of fault features and online fault diagnosis.
In the offline training part, the vibration signal of MVCB during closing under four states is collected by the data acquisition system. The Hilbert transform (HT) is used to extract the envelope of the vibration signal. The wavelet packet energy spectrum is adopted to acquire the fault feature of the vibration signal envelope. The fault feature library is built by the fault feature and fault label of the MVCB. The typical fault feature vector M is calculated by the fault feature library.
The online fault diagnosis part includes collecting the operating vibration signal, extracting the vibration signal envelope, and acquiring the fault feature vector T of the vibration signal envelope based on the wavelet packet energy spectrum. Then, the selected fault feature T and the typical fault feature vector M are input to the distance discrimination block to calculate the fault condition, which shows the case of the MVCB.

3.1. Vibration Signal Envelope

The continuous time signal is assumed to be x(t) for the sake of describing the HT, and the HT of x(t) can be expressed as
y ( t ) = 1 π + x ( τ ) t τ d τ = x ( t ) π t
where y(t) is the HT of x(t).
Using x(t) and y(t), a new analytical signal h(t) can be constructed as
h ( t ) = x ( t ) + j y ( t )
The magnitude a(t) of h(t) is described as
a ( t ) = h ( t ) = x 2 ( t ) + y 2 ( t )
where a(t) is the envelope of x(t).

3.2. Fault Feature Extraction

The vibration signal of the MVCB is composed of multiple instantaneous non-steady vibration events. WPD is a practical way to process non-linear and non-steady signals [15]. Compared with the wavelet analysis, WPD has a higher time–frequency resolution and stronger localization performance in all frequency bands. Figure 6 shows the structure of a three-layer WPD, in which the n-th level and l-th sub-band of the reconstructed wavelet coefficients Wnl represent 1/2n of the frequency information.
After the vibration signal envelope is decomposed by the WPD, the energy value of each frequency band is calculated as
E j * = k = 1 N W n l ( k ) 2           l = 0 , 1 , , 2 n 1 ;   j = 1 , 2 , , 2 n
where n is the amount of WPD layers, and N is the amount of WPD coefficients in Wnl.
The energy value of each frequency band for the n-layer WPD of the vibration signal envelope is:
E * = ( E 1 * , E 2 * , , E j * , , E 2 n * )
The energy value vectors are normalized to gain the fault feature of the MVCB, which is in the form of
E = ( E 1 * / , E 2 * / , , E j * / , , E 2 n * / ) = ( E 1 , E 2 , , E j , , E 2 n )
where = E 1 * + E 1 * + + E j * + + E 2 n * .
For the offline training part, the fault feature library is composed of the fault feature and the label of four states of the MVCB. The author takes out g groups of feature vectors in the same case, adds them to each frequency band and averages them as typical feature vectors. Then, the fault feature vector of a typical case can be expressed as
M i = ( m 1 , m 2 , , m j , , m 2 n )    = 1 g ( i = 1 g E 1 ( i ) , i = 1 g E 2 ( i ) , , i = 1 g E j ( i ) , , i = 1 g E 2 n ( i ) )
The typical fault feature vector M is defined as
M = [ M 1 ; M 2 ; ; M i ; ; M p ] T
where p is the amount of typical cases.
For the online fault diagnosis process, the fault feature vector T can be described as
T = ( t 1 , t 2 , , t j , , t 2 n ) = ( E 1 , E 2 , , E j , , E 2 n )

3.3. Fault Discrimination

The distance discrimination is to establish the distance d(T, Mi) from the judgment object T to Mi. The distance d(T, Wi) adopts the Euclidean distance, and the expression of the Euclidean distance is
d ( T , M i ) = q = 1 2 n ( t q m q ) 2
The discriminant function is defined as
W ( r , T ) = d ( T , M i )
The fault state is discriminated according to the principle of the closest distance. There is:
W ( z , T ) = min { W ( r , T ) | r = 1 , 2 , , p } , T M z

4. Results and Discussions

To evaluate whether the suggested fault diagnosis approach is effective, Database 1 is selected for offline training of fault features, while Database 2 is used for online fault diagnosis. The vibration signal envelope is extracted by the HT method under six cases, as shown in Figure 7, where the vibration signal envelopes under six cases are different.
Based on the vibration signal envelope, the FFT is adopted to acquire the spectrum of the vibration signal envelope. As shown in Figure 8, the frequency band width of the vibration signal envelope is quite small and the main frequency spectrum is within 0–4 kHz, which is less than the frequency spectrum of the original vibration signal. In other word, the bandwidth of the processed signal is greatly decreased.
The WPD is used to acquire the fault feature on the basis of a vibration signal envelope. The selected wavelet basis function and decomposition layer will affect the decomposition result of the WPD. For the wavelet basis function, the Symlet 5 is selected as the wavelet basis function of the WPD with the large tests. For the decomposition layer, when the number of selected decomposition layers is small, the analysis speed is fast, which is especially obvious for high-frequency signals, but the analysis precision is low. Considering the relationship between the decomposition layer and analysis effect, the paper adopts a three-layer WPD for six typical cases of MVCB. Figure 9 shows the WPD result of the normal case of the MVCB. Eight WPD coefficients correspond to eight frequency bands, and the amplitude of the WPD coefficient in the first four frequency bands is much greater than the latter four frequency bands.
Using the same method, the three-layer WPD results of the vibration signal envelop under five fault cases of the MVCB can be obtained, as shown in Figure 10, Figure 11, Figure 12, Figure 13 and Figure 14. It is easy to find that the WPD results of five cases are different in each wavelet coefficient. Compared with the normal case, each wavelet coefficient of the three fault cases is less than the corresponding wavelet coefficient of the normal state.
From (5), the energy of each frequency band after WPD under the six cases of the MVCB can be calculated, and it can be known that the energy corresponding to each frequency band changes greatly. Equation (6) is used to calculate the percentage of the energy of each frequency band in the total energy of the WPD in the six cases. Database 1 is selected for offline training of the fault feature, and the typical feature vector M is further obtained by (7) and (8). As shown in Table 6, M1, M2, M3, M4, M5, and M6 are the typical feature vector of six cases, respectively.
In order to confirm if the suggested strategy is effective, Database 2 is further used as the online test data, and the Euclidean distance between the feature vector T of each online operational vibration signal and the typical fault feature vector M is calculated. In accordance with the principle of closest distance, the fault diagnosis of 30 groups of online test data can be discriminated.
The multiclass confusion matrix is used to show the difference between the actual case and the predicted case. Figure 15 shows the multiclass confusion matrix for the proposed approach. The multiclass confusion matrix provides detailed documentation of the classification outcomes for each case, including information on both correct and incorrect classification. The vertical axis and horizontal axis of the multiclass confusion matrix each represent the actual and predicted cases, respectively.
It should be noted that some pieces are different from those on the main diagonal. The element values in the last column of the multiclass confusion matrix represent the classification accuracy of each case. In the scenario depicted in Figure 15, we can see that Case 3 has the lowest precision, which is 80%. For Case 1, Case 2, Case4, Case 5 and Case 6, the fault diagnosis is 100%. Additionally, the fault diagnosis precision of the proposed approach is 96.67% for all test samples, demonstrating that high performance is achieved for the fault diagnosis of the MVCB.
Based on the desktop computer (Intel(R) Core (TM) i9-10900K [email protected] GHz 24 GB RAM), the influence of WPD layers on the precision and execution time of the proposed approach is studied. As shown in Table 7, with the WPD layers increasing from 1 to 3, the precision of the proposed approach increases from 80% to 96.67%. As the amount of WPD layers increases to 4 or 5, the accuracy remains unchanged at 96.67%, but the time for fault diagnosis also increases.
The efficiency of the proposed approach is compared with two traditional typical methods. The wavelet packet energy spectrum is directly applied to extract the feature vector of the vibration signal, and two classification methods (ELM and back propagation neural network (BPNN)) are used to treat the online data. As shown in Table 8, the accuracy of the proposed approach is better than that of the other two typical methods, and the execution time of the proposed approach is less than that of the other two methods.

5. Conclusions

The fault diagnosis of the MVCB based on vibration signal envelop analysis is proposed in this paper. Firstly, the vibration signals of the MVCB during closing operation under four cases are collected by the data acquisition system. Secondly, the Hilbert transform is used to extract the envelope of the vibration signal, and the fault feature of the vibration signal envelope is acquired by the wavelet packet energy spectrum. Then, the fault feature library is built by the fault feature and the label of the historical vibration signal, and the typical fault feature vector M is calculated by the fault feature library. After that, the online collecting operational vibration signal is extracted from the envelope by the Hilbert transform, and the fault feature vector is acquired from the wavelet packet energy spectrum to gain the fault feature vector T. Finally, the fault state is classified by distance discrimination. The proposed fault diagnosis approach based on vibration signal envelope analysis reduces the expenditure on software and hardware which is applicable for the online fault diagnosis of the MVCB. Till now, the proposed fault method has only undergone laboratory validation. In the future, the practical deployment and application of the proposed fault diagnosis method will be our main tasks.

Author Contributions

Conceptualization, Y.W. and J.Z.; methodology, Y.W.; software, Y.W.; validation, Y.W., Z.Y. and H.C.; formal analysis, Y.W.; investigation, Y.W.; resources, J.Z.; data curation, Y.W. and J.Z.; writing—original draft preparation, Y.W.; writing—review and editing, J.Z. and H.C.; visualization, Z.Y.; supervision, J.Z.; project administration, J.Z.; funding acquisition, J.Z. and H.C. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by the National Key R&D Program of China “Intergovernmental International Science and Technology Innovation Cooperation” Key Special Project (No. 2022YFE0196300) and the Key Laboratory of Medical Electronics and Digital Health of Zhejiang Province.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

The data supporting the findings of this study are available from the first author or corresponding author upon reasonable request.

Acknowledgments

Many thanks go to the Chinese company (Yunfeng Science & Technology Co. Ltd., Jiangsu) for providing their support and necessary technical.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Asghar Razi-Kazemi, A.; Niayesh, K. Condition Monitoring of High Voltage Circuit Breakers: Past to Future. IEEE Trans. Power Deliv. 2021, 36, 740–750. [Google Scholar] [CrossRef]
  2. Wang, Y.; Yan, J.; Ye, X.; Jing, Q.; Wang, J.; Geng, Y. Few-Shot Transfer Learning with Attention Mechanism for High-Voltage Circuit Breaker Fault Diagnosis. IEEE Trans. Ind. Appl. 2022, 58, 3353–3360. [Google Scholar] [CrossRef]
  3. Janssen, A.; Makareinis, D.; Sölver, C.E. International Surveys on Circuit-Breaker Reliability Data for Substation and System Studies. IEEE Trans. Power Deliv. 2014, 29, 808–814. [Google Scholar] [CrossRef]
  4. Zhang, X.; Gockenbach, E.; Liu, Z.; Chen, H.; Yang, L. Reliability Estimation of High Voltage SF6 Circuit Breakers by Statistical Analysis on the Basis of the Field Data. Electr. Power Syst. Res. 2013, 103, 105–113. [Google Scholar] [CrossRef]
  5. Zhang, J.; Wu, C.; Cheng, M.; Jiang, X. Optimal Design of a Tubular Linear Surface-Mounted Permanent Magnet Actuator for High Voltage Breaker. In Proceedings of the 2013 International Conference on Electrical Machines and Systems (ICEMS), Busan, Republic of Korea, 26–29 January 2013. [Google Scholar]
  6. Zhang, H.; Xie, Y.; Yi, T.; Kong, X.; Cheng, L.; Liu, H. Fault Detection for High-Voltage Circuit Breakers Based on Time–Frequency Analysis of Switching Transient E-Fields. IEEE Trans. Instrum. Meas. 2020, 69, 1620–1631. [Google Scholar] [CrossRef]
  7. Ma, S.; Jia, B.; Wu, J.; Yuan, Y.; Jiang, Y.; Li, W. Multi-Vibration Information Fusion for Detection of HVCB Faults using CART and D–S Evidence Theory. ISA Trans. 2021, 113, 210–221. [Google Scholar] [CrossRef] [PubMed]
  8. Ma, S.; Yuan, Y.; Wu, J.; Jiang, Y.; Jia, B.; Li, W. Multi-Sensor Decision Approach for HVCB Fault Detection Based on the Vibration Information. IEEE Sens. J. 2021, 21, 985–994. [Google Scholar] [CrossRef]
  9. Zhu, K.; Mei, F.; Zheng, J. Adaptive Fault Diagnosis of HVCBs Based on P-SVDD and P-KFCM. Neurocomputing 2017, 240, 127–136. [Google Scholar] [CrossRef]
  10. Zhang, J.; Wu, Y.; Xu, Z.; Din, Z.; Chen, H. Fault Diagnosis of High Voltage Circuit Breaker Based on Multi-Sensor Information Fusion with Training Weights. Measurement 2022, 192, 110894. [Google Scholar] [CrossRef]
  11. Razi-Kazemi, A.; Vakilian, M.; Niayesh, K.; Lehtonen, M. Circuit-Breaker Automated Failure Tracking Based on Coil Current Signature. IEEE Trans. Power Deliv. 2014, 29, 283–290. [Google Scholar] [CrossRef]
  12. Zhao, S.; Wang, E.; Hao, J. Fault Diagnosis Method for Energy Storage Mechanism of High Voltage Circuit Breaker Based on CNN Characteristic Matrix Constructed by Sound-Vibration Signal. J. Vibroengineering 2019, 6, 1665–1678. [Google Scholar] [CrossRef]
  13. Niu, W.; Liang, G.; Yuan, H.; Li, B. A Fault Diagnosis Method of High Voltage Circuit Breaker Based on Moving Contact Motion Trajectory and ELM. Math. Probl. Eng. 2016, 2016, 3271042. [Google Scholar] [CrossRef]
  14. Forootani, A.; Afzalian, A.A.; Nadian Ghomsheh, A. Model-Based Fault Analysis of a High-Voltage Circuit Breaker Operating Mechanism. Turk. J. Electr. Eng. Comput. Sci. 2017, 25, 2349–2362. [Google Scholar] [CrossRef]
  15. Huang, J.; Hu, X.; Yang, F. Support Vector Machine with Genetic Algorithm for Machinery Fault Diagnosis of High Voltage Circuit Breaker. Measurement 2011, 44, 1018–1027. [Google Scholar] [CrossRef]
  16. Yang, Q.; Ruan, J.; Zhuang, Z.; Huang, D. Fault Identification for Circuit Breakers Based on Vibration Measurements. IEEE Trans. Instrum. Meas. 2020, 69, 4154–4164. [Google Scholar] [CrossRef]
  17. Zhang, J.; Liu, M.; Wang, K.; Sun, L. Mechanical Fault Diagnosis for High-Voltage Circuit Breakers Based on Ensemble Empirical Mode Decomposition Energy Entropy and Support Vector Machine. Math. Probl. Eng. 2015, 2015, 101757. [Google Scholar]
  18. Gao, W.; Wai, R.; Qiao, S.; Guo, M. Mechanical Faults Diagnosis of High-Voltage Circuit Breaker Via Hybrid Features and Integrated Extreme Learning Machine. IEEE Access 2019, 7, 60091–60103. [Google Scholar] [CrossRef]
  19. Gao, W.; Qiao, S.; Wai, R.; Guo, M. A Newly Designed Diagnostic Method for Mechanical Faults of High-Voltage Circuit Breakers Via SSAE and IELM. IEEE Trans. Instrum. Meas. 2021, 70, 3500613. [Google Scholar] [CrossRef]
  20. Huang, N.; Chen, H.; Cai, G.; Fang, L.; Wang, Y. Mechanical Fault Diagnosis of High Voltage Circuit Breakers Based on Variational Mode Decomposition and Multi-layer Classifier. Sensors 2016, 16, 1887. [Google Scholar] [CrossRef]
  21. Dou, L.; Wan, S.; Zhan, C. Application of Multiscale Entropy in Mechanical Fault Diagnosis of High Voltage Circuit Breaker. Entropy 2018, 20, 325. [Google Scholar] [CrossRef]
  22. Yang, Q.; Ruan, J.; Zhuang, Z.; Huang, D.; Qiu, Z. A New Vibration Analysis Approach for Detecting Mechanical Anomalies on Power Circuit Breakers. IEEE Access 2019, 7, 14070–14080. [Google Scholar] [CrossRef]
  23. Cao, C.; Liu, M.; Li, B.; Wang, Y. Mechanical Fault Diagnosis of High Voltage Circuit Breakers Utilizing VMD Based on Improved Time Segment Energy Entropy and a New Hybrid Classifier. IEEE Access 2020, 8, 177767–177781. [Google Scholar] [CrossRef]
  24. Ji, T.; Yi, L.; Tang, W.; Shi, M.; Wu, Q. Multi-Mapping Fault Diagnosis of High Voltage Circuit Breaker Based on Mathematical Morphology and Wavelet Entropy. CSEE J. Power Energy Syst. 2019, 5, 130–138. [Google Scholar] [CrossRef]
  25. Ma, S.; Chen, M.; Wu, J.; Wang, Y.; Jia, B.; Jiang, Y. High-Voltage Circuit Breaker Fault Diagnosis Using a Hybrid Feature Transformation Approach Based on Random Forest and Stacked Autoencoder. IEEE Trans. Ind. Electron. 2019, 66, 9777–9788. [Google Scholar] [CrossRef]
Figure 1. Experiment setup of MVCB. (a) MVCB; (b) Data acquisition system.
Figure 1. Experiment setup of MVCB. (a) MVCB; (b) Data acquisition system.
Sensors 23 08331 g001
Figure 2. Fault emulation methods. (a) Iron core jamming; (b) Bearing-screw looseness; (c) Closing-spring relaxation; (d) Low relay coil voltage; (e) Relay high resistance.
Figure 2. Fault emulation methods. (a) Iron core jamming; (b) Bearing-screw looseness; (c) Closing-spring relaxation; (d) Low relay coil voltage; (e) Relay high resistance.
Sensors 23 08331 g002
Figure 3. Time-domain vibration signal of the MVCB. (a) Normal case; (b) Closing-spring relaxation case.
Figure 3. Time-domain vibration signal of the MVCB. (a) Normal case; (b) Closing-spring relaxation case.
Sensors 23 08331 g003
Figure 4. Spectrum diagrams of the vibration signal. (a) Case 1; (b) Case 2; (c) Case 3; (d) Case 4; (e) Case 5; (f) Case 6.
Figure 4. Spectrum diagrams of the vibration signal. (a) Case 1; (b) Case 2; (c) Case 3; (d) Case 4; (e) Case 5; (f) Case 6.
Sensors 23 08331 g004
Figure 5. Fault diagnosis structure based on vibration signal envelope analysis.
Figure 5. Fault diagnosis structure based on vibration signal envelope analysis.
Sensors 23 08331 g005
Figure 6. Schematic diagram of the WPD.
Figure 6. Schematic diagram of the WPD.
Sensors 23 08331 g006
Figure 7. Vibration signal envelope under four cases. (a) Case 1; (b) Case 2; (c) Case 3; (d) Case 4; (e) Case 5; (f) Case 6.
Figure 7. Vibration signal envelope under four cases. (a) Case 1; (b) Case 2; (c) Case 3; (d) Case 4; (e) Case 5; (f) Case 6.
Sensors 23 08331 g007aSensors 23 08331 g007b
Figure 8. Vibration signal envelope spectrum under four cases. (a) Case 1; (b) Case 2; (c) Case 3; (d) Case 4; (e) Case 5; (f) Case 6.
Figure 8. Vibration signal envelope spectrum under four cases. (a) Case 1; (b) Case 2; (c) Case 3; (d) Case 4; (e) Case 5; (f) Case 6.
Sensors 23 08331 g008
Figure 9. The WPD result of the normal case. (a) W30; (b) W31; (c) W32; (d) W33; (e) W34; (f) W35; (g) W36; (h) W37.
Figure 9. The WPD result of the normal case. (a) W30; (b) W31; (c) W32; (d) W33; (e) W34; (f) W35; (g) W36; (h) W37.
Sensors 23 08331 g009
Figure 10. The WPD result of the iron core jamming case. (a) W30; (b) W31; (c) W32; (d) W33; (e) W34; (f) W35; (g) W36; (h) W37.
Figure 10. The WPD result of the iron core jamming case. (a) W30; (b) W31; (c) W32; (d) W33; (e) W34; (f) W35; (g) W36; (h) W37.
Sensors 23 08331 g010aSensors 23 08331 g010b
Figure 11. The WPD result of the bearing-screw looseness case. (a) W30; (b) W31; (c) W32; (d) W33; (e) W34; (f) W35; (g) W36; (h) W37.
Figure 11. The WPD result of the bearing-screw looseness case. (a) W30; (b) W31; (c) W32; (d) W33; (e) W34; (f) W35; (g) W36; (h) W37.
Sensors 23 08331 g011
Figure 12. The WPD result of the closing-spring relaxation case. (a) W30; (b) W31; (c) W32; (d) W33; (e) W34; (f) W35; (g) W36; (h) W37.
Figure 12. The WPD result of the closing-spring relaxation case. (a) W30; (b) W31; (c) W32; (d) W33; (e) W34; (f) W35; (g) W36; (h) W37.
Sensors 23 08331 g012aSensors 23 08331 g012b
Figure 13. The WPD result of the reducing control voltage case. (a) W30; (b) W31; (c) W32; (d) W33; (e) W34; (f) W35; (g) W36; (h) W37.
Figure 13. The WPD result of the reducing control voltage case. (a) W30; (b) W31; (c) W32; (d) W33; (e) W34; (f) W35; (g) W36; (h) W37.
Sensors 23 08331 g013
Figure 14. The WPD result of the relay high resistance. (a) W30; (b) W31; (c) W32; (d) W33; (e) W34; (f) W35; (g) W36; (h) W37.
Figure 14. The WPD result of the relay high resistance. (a) W30; (b) W31; (c) W32; (d) W33; (e) W34; (f) W35; (g) W36; (h) W37.
Sensors 23 08331 g014aSensors 23 08331 g014b
Figure 15. Fault diagnosis results of online test data.
Figure 15. Fault diagnosis results of online test data.
Sensors 23 08331 g015
Table 1. Configuration of data acquisition system.
Table 1. Configuration of data acquisition system.
Device NameManufacturerTypeConfiguration
ParametersValue
Vibration sensorLanceLC0158TRange166 g
Sensitivity30.1 mV/g
Acquisition cardShuangnuoMP4221Resolution12 bit
Sampling frequency125 kHz
Power supplyMornsunLM35Output voltage+24 V
Table 2. Typical cases of MVCB.
Table 2. Typical cases of MVCB.
CaseFault ReasonEmulation
Case 1Normal--
Case 2Iron core jammingIron corrosionSuspending heavy weight
Case 3Bearing-screw loosenessVibrationLoosening bearing screw
Case 4Closing-spring relaxationSpring agingAdjusting spring-end nuts
Case 5Low relay coil voltageLow control voltageReducing control voltage
Case 6Relay high resistanceCoil agingAdding a resistor in relay coil
Table 3. Summarizing database of MVCB.
Table 3. Summarizing database of MVCB.
CaseAmountDatabase 1Database 2Description
Case 115 sets10 sets5 setsNormal
Case 215 sets10 sets5 setsIron core jamming
Case 315 sets10 sets5 setsBearing-screw looseness
Case 415 sets10 sets5 setsClosing-spring relaxation
Case 515 sets10 sets5 setsLow relay coil voltage
Case 615 sets10 sets5 setsRelay high resistance
Table 4. Feature definition for spectrum diagram.
Table 4. Feature definition for spectrum diagram.
OrderFeature NameFeature Express
1Average value of the frequency spectrum C a v f = 1 L f = 1 L S ( f )
2Root mean square value of the frequency spectrum C r m s f = ( 1 L f = 1 L S 2 ( f ) ) 1 / 2
3Standard deviation value of the frequency spectrum C s d f = ( 1 L f = 1 L ( S ( f ) C a v f ) 2 ) 1 / 2
4Center of gravity value of the frequency spectrum C g c f = ( f = 1 L f × S ( f ) ) / f = 1 L S ( f )
Table 5. Fault diagnosis based on frequency domain features.
Table 5. Fault diagnosis based on frequency domain features.
Case 1Case 2Case 3Case 4Case 5Case 6Average
Training accuracy (%)90%90%100%100%100%70%91.67%
Testing accuracy (%)80%60%100%80%60%40%76.67%
Table 6. Typical feature vector of six cases.
Table 6. Typical feature vector of six cases.
m1m2m3m4m5m6m7m8
M10.76350.11800.02020.05440.00530.0010.01630.0124
M20.78800.09150.01660.05090.01300.01430.01370.0121
M30.81930.08970.01760.04270.00400.00520.01480.0066
M40.81320.09790.01400.04250.00430.00860.01120.0084
M50.74630.12630.01980.05630.00780.01380.01580.0139
M60.76060.11980.01950.05170.00680.01270.01640.0125
Table 7. Impact of decomposition layers on accuracy and execution time.
Table 7. Impact of decomposition layers on accuracy and execution time.
Configuration
ComputerWindows 10, CPU [email protected] GHz, 24 GB RAM
ToolMATLAB 2020b
Decomposition layers12345
Accuracy (%)80%86.67%96.67%96.67%96.67%
Time (s)0.00890.00950.01310.01620.0191
Table 8. Comparisons of different methods.
Table 8. Comparisons of different methods.
MethodCase 1Case 2Case 3Case 4Case 5Case 6Accuracy (%)Time (s)
Proposed method100%100%80%100%100%100%96.67%0.0131
WPD + ELM40%100%100%100%80%100%86.67%0.0291
WPD + BPNN60%100%100%100%100%80%90%0.0323
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Wu, Y.; Zhang, J.; Yuan, Z.; Chen, H. Fault Diagnosis of Medium Voltage Circuit Breakers Based on Vibration Signal Envelope Analysis. Sensors 2023, 23, 8331. https://doi.org/10.3390/s23198331

AMA Style

Wu Y, Zhang J, Yuan Z, Chen H. Fault Diagnosis of Medium Voltage Circuit Breakers Based on Vibration Signal Envelope Analysis. Sensors. 2023; 23(19):8331. https://doi.org/10.3390/s23198331

Chicago/Turabian Style

Wu, Yongbin, Jianzhong Zhang, Zhengxi Yuan, and Hao Chen. 2023. "Fault Diagnosis of Medium Voltage Circuit Breakers Based on Vibration Signal Envelope Analysis" Sensors 23, no. 19: 8331. https://doi.org/10.3390/s23198331

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop