Next Article in Journal
Deep Learning-Based 6-DoF Object Pose Estimation Considering Synthetic Dataset
Previous Article in Journal
Monitoring of Lake Ice Phenology Changes in Bosten Lake Based on Bayesian Change Detection Algorithm and Passive Microwave Remote Sensing (PMRS) Data
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

The Design, Fabrication, and Evaluation of a Phase-Resolved Partial Discharge Sensor Embedded in a MV-Class Bushing

1
Department of Electrical and Electronics Engineering, Korea Maritime and Ocean University, Busan 49112, Republic of Korea
2
Department of Electrical and Electronics Engineering, Silla University, Busan 46958, Republic of Korea
*
Author to whom correspondence should be addressed.
Sensors 2023, 23(24), 9844; https://doi.org/10.3390/s23249844
Submission received: 11 November 2023 / Revised: 8 December 2023 / Accepted: 13 December 2023 / Published: 15 December 2023

Abstract

:
This paper proposes a novel phase-resolved partial discharge (PRPD) sensor embedded in a MV-class bushing for high-accuracy insulation analysis. The design, fabrication, and evaluation of a PRPD sensor embedded in a MV-class bushing aimed to achieve the detection of partial discharge (PD) pulses that are phase-synchronized with the applied primary HV signal. A prototype PRPD sensor was composed of a flexible printed circuit board (PCB) with dual-sensing electrodes, utilizing a capacitive voltage divider (CVD) for voltage measurement, the D-dot principle for PD detection, and a signal transducer with passive elements. A PD simulator was prepared to emulate typical PD defects, i.e., a metal protrusion. The voltage measurement precision of the prototype PRPD sensor was satisfied with the accuracy class of 0.2 specified in IEC 61869-11, as the maximum corrected voltage error ratios and corrected phase errors in 80%, 100%, and 120% of the rated voltage (13.2 kilovolts (kV)) were less than 0.2% and 10 min, respectively. In addition, the prototype PRPD sensor had good linearity and high sensitivity for PD detection compared with a conventional electrical detection method. According to performance evaluation tests, the prototype PRPD sensor embedded in the MV-class bushing can measure PRPD patterns phase-synchronized with the primary voltage without any additional synchronization equipment or system. Therefore, the prototype PRPD sensor holds potential as a substitute for conventional commercial PD sensors. Consequently, this advancement could lead to the enhancement of power system monitoring and maintenance, contributing to the digitalization and minimization of power apparatus.

1. Introduction

Insulation degradation in power equipment can be predicted by detecting partial discharge (PD) pulses in the early stages. Various PD sensors have been adapted to detect PD pulses [1,2], including a coupling capacitor, employing the conventional method based on IEC 60270 [3], and a high-frequency current transformer (HFCT), ultra-high-frequency (UHF) sensor, and an acoustic emission (AE) sensor, based the non-conventional method. The conventional detection method produces high-precision PD measurements and shows the output in picocoulomb (pC) by applying external voltage sources. However, it has the disadvantages of requiring the installation of a coupling capacitor for quantitative measurements, being unusable during operation, and limits on-site PD measurements to a maximum measurement frequency of 1 megahertz (MHz) [4,5,6,7]. On the other hand, UHF sensors have several advantages, including high sensitivity, good signal-to-noise ratio (S/N), high frequency range (300 kilohertz (kHz) to 3 gigahertz (GHz)), ability to estimate fault location, and continuous monitoring. Despite these advantages, UHF measurements have the disadvantage of being unable to calibrate the output magnitude in a unit of pC and are expensive [8,9,10]. AE sensors are widely used to detect internal defects in electrical power equipment owing to their cheap price and easy installation. The internal fault location can be estimated by calculating the amplitudes and different arrival times of several AE sensors. It cannot be measured in terms of pC, much like with UHF sensors, and the effects of reflections, attenuations, and the scattering of acoustic waves due to the internal structures of the equipment must be considered [11,12,13,14,15]. The above PD sensors are selected based on installation conditions and purpose. The most suitable method for insulation diagnosis is phase-resolved partial discharge (PRPD) analysis, which includes the phase angle ( ), PD magnitude ( q ), and the number of PD pulses ( n ) over a period within one cycle of the applied voltage source [16,17].
An accurate measurement of system voltage signals is critical to improve the safety and reliability of power equipment. The voltage signals obtained with various instruments, including iron-core-type potential transformers (PTs), capacitive potential transformers (CPTs), and resistive potential transformers (RPTs), have a critical role in the operation of protective relays to counter abnormal voltage surges. Iron-core-type PTs require a significantly large installation space due to their iron core and copper wire components, and can be susceptible to external transients when connected directly between primary and secondary circuits [18]. Capacitive potential transformers must be connected to high-input impedance instruments, typically exceeding several megohms. Alternatively, an impedance transformer must be used to match the input and output impedance between the CPT and the instrument. While these instruments can be used effectively within a narrow frequency band corresponding to commercial frequencies, their accuracy can be compromised if the voltage signal is contaminated with high-frequency noise components [19,20]. Therefore, the development of high-precision voltage measurement instruments with broadband frequency capability is essential. To address the challenges associated with ensuring an adequate insulation distance for direct connections to primary high-voltage conductors, as well as issues such as magnetic saturation, the deformation of internal cores, and the need for significant installation space, a novel voltage measurement method for low-power voltage transformers (LPVTs) has been the subject of recent research. This need prompted the International Electrotechnical Commission (IEC) to publish IEC 61869-11 [21], relevant to low-power voltage transformers (LPVTs) using passive elements, to replace IEC 60044-7 [22], which is currently applied to electronic voltage transformers (EVTs). This is intended for connection to stand-alone merging units (SAMUs) or metering devices according to IEC 61869-13 [23].
Wagoner et al. [24] diagnosed the current and voltage output signals in the vacuum section of a 20-mega-ampere (MA) 3-megavolt (MV) pulsed-power accelerator using differential D-dot and B-dot sensors with a common mode for noise rejection. Wang and colleagues [25] developed voltage transformers using the basis of a differential D-dot sensor. They experimented and simulated the designed D-dot probe sensor for the verification of measurement accuracy. Kim et al. [26] developed an electronic voltage transformer (EVT) with an accuracy class of 0.2 using a D-dot sensor. They showed that the prototype EVT can accurately detect voltage signals up to the third, fifth, and seventh harmonics at a commercial frequency of 60 hertz (Hz) upon employing a non-contact voltage measurement method.
Wang and colleagues [27] investigated an electronic voltage transformer with a self-integral D-dot sensor using the D-dot principle for high-voltage signal measurement. They found that the D-dot sensor operates self-integrated modes with excellent phase frequency characteristics by applying parallel and differential structures of multiple electrodes. Yao and colleagues [28] proposed a compensation method that improves the accuracy of output signals by minimizing the offset due to the integrated circuit of the D-dot electric field sensor. A mathematical method from this study was proposed to reduce the offset value by the integration circuit. However, in the view of condition monitoring, the proposed devices and methods cannot detect abnormal pulses from internal defects because they are mainly designed to measure system voltage signals.
Hussain et al. [29] studied an online monitoring sensor, capturing abnormal electrical fault signals generated from an internal arc for medium-voltage (MV) switchgears based on the differential D-dot principle. Hussain and colleagues [30] compared the detection characteristics of a Rogowski coil, loop antenna, HFCT, and D-dot sensor in air-insulated switchgears, and discovered that a Rogowski coil sensor and D-dot sensor are more suitable for PD measurements due to their high S/N. Rostaghi-Chalaki and colleagues [31] investigated the output characteristics of a D-dot and B-dot measuring DC PD pulses propagating through a transmission line (TL) using the electromagnetic (EM) field principle. They found that the apparent discharge measured by the EM field sensors was almost identical to the reference PD pulse measured with an oscilloscope. Jin and colleagues [32] studied the measurement of a transient-pulsed electromagnetic field using a D-dot sensor and outlined a compensation system for the recovery of the incident E-field to improve the dynamic characteristics.
Information about the phase distribution of PD pulses is essential for the PD diagnosis of high-voltage power equipment since the PRPD analysis method is typically used to identify types of PD defects for on-site PD measurement. However, acquiring the reference voltage signals directly from the power equipment in on-site operation is challenging and inconvenient. In addition, sometimes, the reference voltage signal is measured at a considerable distance from the expected PD defect location. In terms of PD fault identification, the diagnostic accuracy depends on the synchronization of the detected PD pulse with the phase of the reference voltage signal. Therefore, many studies have been conducted regarding how to obtain PD pulses phase-synchronized with the applied high voltage or the zero-crossing point of the applied high voltage. Kim et al. [33] suggested a possible diagnosis technique of unknown phase-shifted PD signals for GISs. The new diagnosis method utilized the shapes, distribution ranges, density, and peak values of the PD pulses and could classify internal defect types and noises without the phase distribution information of the applied voltage. Lee and colleagues [34] developed a neural network algorithm to discriminate phase-shifted PRPD patterns. They proposed a new method which was able to convert the fundamental phase-shifted parameters, such as phase angle, magnitude, and the number of PD pulses, to standardized parameters by applying the neural network algorithm method. However, there are limitations to setting criteria for determining internal defects, as their identification relies on the knowledge and experience of the engineer. Therefore, the development of techniques for the acquisition of accurate phase angles of applied voltage signals for insulation diagnosis remains necessary.
To address these limitations, this paper proposes a PRPD sensor embedded in a MV-class bushing, capable of detecting phase-synchronized PD pulses through precise measurements of the primary HV signal. The prototype PRPD sensor demonstrated a voltage measurement accuracy that was satisfied with an accuracy class of 0.2 by analyzing the error ratio and phase error according to the test guidelines in IEC 61869-11. Furthermore, the PRPD sensor was found to have good linearity and sensitivity in PD detection by comparing the output magnitude and PRPD pattern detected using the conventional electrical detection method specified in IEC 60270. It is expected that the prototype PRPD sensor can minimize the installation area of epoxy insulation and help to improve the precision of insulation diagnosis for acquiring PD pulses phase-synchronized with the applied signal.

2. Design and Fabrication

Detecting PD pulses phase-synchronized with the applied voltage signal is very important to identify and distinguish insulation defects. The prototype PRPD sensor embedded in a MV-class bushing consists of dual-sensing electrodes and signal transducers for voltage signal measurement and PD detection.

2.1. PRPD Sensor Embedded in a Bushing

Figure 1 shows a configuration and photograph of the prototype PRPD sensor embedded in a MV-class bushing. The PRPD sensor was designed using a non-contact detection method. The dual-sensing electrodes consisted of a voltage transformer (VT) for voltage signals with a commercial frequency band (around 60 Hz) and a D-dot sensor for PD pulses with high-frequency ranges, respectively. The electrodes were installed on a flexible PCB to encircle the HV conductor and minimize external environmental impacts such as shock or vibration. The main manufacturing process of PRPD sensors consists of the following steps: Initially, the PRPD sensor is designed and fabricated on a flexible PCB by calculating the geometric parameters and insulation distance. The PRPD sensor is then embedded within an epoxy-insulated metal enclosure to minimize the influence of unexpected external electric fields. Finally, the PRPD sensor, housed in a metal enclosure, is installed in a MV-class bushing.
The capacitive divider principle was applied for the design and fabrication of the VT sensor as this does not allow for derivative output signals according to IEC 61869-11. The output voltage of the VT, V V ( t ) , is proportional to the primary HV signal, U P ( t ) , and it can be calculated using Equation (1):
V V ( t ) = C H C H + C L + C V × U P ( t )
where C H is a HV stray capacitor between the HV conductor and the sensing electrode of the VT, C L is an LV capacitor between the sensing electrode and a grounded metal sheath, and C V is a capacitor for controlling the transformation ratio in parallel with the LV capacitor. For the study outlined in this paper, the rated transformation ratio of the prototype PRPD sensor was set to 10,000:1.
Contrastingly, in accordance with the Gaussian law [20,21,34], the output voltage of the D-dot sensor V PD ( t ) is proportional to the primary derivation value of the incident electrical field, E ( t ) , and can be calculated using Equation (2):
V PD t = R m × S eq × ε × d E t dt
where R m is an output impedance of V PD , S eq is an equivalent area of the closed surface of the D-dot electrode, ε is the permittivity of an epoxy insulation, and E ( t ) is the magnitude of the incident electrical field generated by the HV conductor. Since the duration time of PD pulses is less than the range of a few to several hundreds of nanoseconds, they do not require the application of a restoration process.
Table 1 shows the geometric parameters of the prototype PRPD sensor outlined in this paper. A high-glass-transition-temperature (Tg-type) PCB was used to prevent deformation by heat generated during the epoxy-molding process. The PRPD sensor was housed within an aluminum alloy metal sheath for protection from external electrical fields such as shocks, vibration, or surges. The new application of the PRPD sensor was designed and fabricated with advantages such as good linearity, high sensitivity, low manufacturing cost, and being installation location-agnostic.
The geometric parameters of diameter, height, width, and thickness of the sensing electrodes were calculated to ensure not only the output accuracy of the PRPD sensor but also a sufficient insulation distance from the HV conductor.

2.2. Signal Transducer

The output signals from the VT and D-dot sensor of the PRPD sensor were connected with each signal transducer, as shown in Figure 2. In a signal transducer for the VT, C V as the transformation ratio control capacitor and R m 1 for impedance matching were installed in parallel with C L , the LV capacitor of the VT. The magnitude of C L was fixed by the insulation material and geometric parameters including thickness, length, and width. Therefore, based on Equation (1), the magnitude of C V should be chosen carefully to satisfy the high-accuracy measurement specified in IEC 61869-11. The output resistance, R m 1 , was set to 2 megaohm (MΩ) for impedance matching with the measuring instrument. A gas discharge tube (GDT) was installed at the front of the transducer circuit to protect from unexpected surges during the experiment.
On the other hand, in the signal transducer for the D-dot sensor, C PD and L PD were installed for operating as high-pass filters (HPFs) to obtain PD pulses with a high frequency range. The output resistor, R m 2 , was set to 50 ohm (Ω) and was connected in parallel with L PD for impedance matching with the measurement instrument.
Figure 3 shows the frequency response of the signal transducer for the PD pulses. Due to the propagation characteristics of the distributed elements of a conductor, the UHF component of PD pulses is attenuated by dielectric loss (tan δ) [35,36]. Therefore, the low cut-off frequency of the transducer was set about 63 kHz (−3 decibel (dB)). The gain was set to 1 for frequencies above 200 kHz, considering the attenuation of UHF band signals caused by the distributed element.

3. Experiment and Method

3.1. PD Simulator

PD pulses are important indicators of insulation deterioration analysis because they occur at an early stage inside electrical equipment. Therefore, internal defects can be predicted by detecting PD pulses before their breakdown. Despite the scientific efforts of manufacturers, installers, and operators to prevent the introduction of foreign objects and contaminants during the manufacturing, installation, and operation phases, small defects are still detected in electrical equipment. These defects can lead to insulation degradation.
Throughout the manufacturing process or during operation, the existence of imperfections or irregularities in materials, welding, or assembly can lead to the formation of sharp metal protrusions. When the electrical field is concentrated at the apex of these metal protrusions, it triggers a corona-type PD. Typically, PD pulses originate from a specific location on the metal protrusion, where it may be on an enclosure of electrical equipment.
Figure 4 shows the PD simulator of a metal protrusion defect. The metal protrusion was fabricated by using an Ogura needle with a curvature radius diameter of 5 micrometers (μm) on a flat electrode with a diameter of 80 mm as the ground plate and a spherical conductor with a diameter of 20 mm as the HV side. The Ogura needle represented a micro-size metal protrusion on the enclosure of the power apparatus. The distance between the spherical HV side electrode and the Ogura needle on the plate ground side electrode was 3 mm. The PD simulator was filled with SF6 gas of the gas pressure at 0.5 megapascals (MPa). The upper and bottom covers were made of aluminum alloy (AL-6061), and a gas valve and gas pressure indicator were installed at the bottom cover. A spherical conductor with a diameter of 25 mm was installed to prevent the electric field from concentrating on the high-voltage connection.

3.2. Experimental Setup

Figure 5 shows an experimental setup for evaluating the accuracy of voltage measurement according to IEC 61869-11’s requirements and the PD detection of the prototype PRPD sensor. A dry-type transformer with a maximum output of 100 kV was used to apply a high voltage and was controlled by an induction-type automatic voltage regulator (IVR). An HV divider with an accuracy class of 0.2 and a ratio of 1000:1 was connected to compare the output of the PRPD sensor. A 50 Ω non-inductive resistor (NIR) was installed between the PD simulator and the ground as a conventional electrical detection method according to IEC 60270. All signals from the PRPD sensor, HV divider, and the 50 Ω NIR were recorded using a digital storage oscilloscope (DL9140, YOKOGAWA, Tokyo, Japan), with a sampling rate of 10 megasamples per second (MS/s).
The HV Tr., IVR, HV divider, PD simulator, and measuring devices were grounded to avoid an unexpected electrical potential difference. The level of background noise was less than 3 millivolts (mV) (measured using the prototype PRPD sensor) and 2 mV (measured using a 50 Ω NIR), respectively, in the experiment. To enhance reproducibility, measurements of output accuracy and PD pulses were conducted through experiments repeated more than five times. All parameters were systematically analyzed under consistent conditions to derive reliable results.

4. Performance Evaluation

Performance evaluation tests were conducted in two steps: the first was a voltage measurement accuracy test according to the test guidelines in IEC 61869-11; the second was a PD detection test comparing the conventional electrical detection method, according to IEC 60270. Each test step was conducted separately. All performance tests were carried out in a high-voltage laboratory at a room temperature (RT, 23 °C).

4.1. Voltage Measurement

To assess the sensitivity and accuracy of the voltage measurement, 80%, 100%, and 120% of the rated voltage (13.2 kV) U P were applied according to the test guideline in IEC 61869-11. Figure 6 shows example waveforms and phase errors of the applied voltage and the PRPD sensor at each voltage level. The voltage waveforms were captured for six cycles to compare the average voltage levels. In addition, the phase errors were confirmed by analyzing each zero-crossing (ZC) point of the waveforms of the applied voltage and the PRPD sensor.
The deviations of the output voltages and phase errors between the applied voltage and the PRPD sensor can be adjusted by the correction factor CF U within a range of 0.900 to 1.100 and phase offset correction φ o   cor within a range of 300 min (5 degrees (°) or 231 μs). The correction factor CF U and phase offset correction φ o   cor of the prototype PRPD sensor were set to 1.000 and 76 min, respectively. The corrected voltage ratio error ε cor   U and corrected phase error φ e   cor were calculated using Equations (3) and (4), respectively:
ε cor   U ( % ) = CF U × K r × V L V H V H × 100
φ e   cor = φ S φ P φ cor   φ o
where K r is the rated transformation ratio of 10,000, V H is the applied voltage, V L is the output voltage of the PRPD sensor, φ S is the phase angle of the PRPD sensor, φ P is the phase angle of the applied voltage, and φ cor   φ o is the corrected phase offset.
Table 2 shows the corrected error ratio ε cor   U and corrected phase error φ e   cor at each applied voltage, i.e., 80%, 100%, and 120% of the rated voltage, calculated using Equations (3) and (4). The maximum values of the voltage ratio error and the phase errors were 0.166% and + 3.06 min, respectively. From the voltage measurement test, the PRPD sensor could meet the accuracy class of 0.2, as specified in IEC 61869-11, because the voltage ratio error and phase error at each applied voltage did not exceed 0.2% and 10 min.

4.2. PD Detection

Before the PD detection experiment, a calibration test was conducted to evaluate the linearity of the prototype PRPD sensor using the PD simulator. Artificial calibration pulses of 10 pC, 20 pC, 50 pC, and 100 pC with a rising time of tens of nanoseconds were injected into the PD simulator using a calibrator (CAL 1A, Power Diagnostix Systems GmbH, Aachen, Germany). Figure 7 shows the average output voltage detected by the PRPD sensor and the conventional electrical detection method in accordance with the calibration pulses. Each output voltage of the 50 Ω NIR and PRPD sensor was recorded five times to calculate their average values. The calibration test confirmed that the output of the prototype PRPD sensor had linearity with respect to the calibration inputs and was more sensitive than the conventional method.
Figure 8 shows examples of the single PD pulses from a metal protrusion defect at 4 kV, measured simultaneously with the prototype PRPD sensor and the 50 Ω NIR, and the fast Fourier transform (FFT) results. The rising time, falling time, and pulse width were analyzed by calculating the average values of 10 single PD pulses. They were 47.2 ns, 52.9 ns, and 51.6 ns in the PRPD sensor and 15.8 ns, 13.3 ns, 16.3 ns in the 50 Ω NIR, respectively. The rising and falling time and pulse width of the PRPD sensor were approximately three times longer than those of 50 Ω NIR. The main frequency ranges and maximum frequency with the highest magnitude were distributed from 2 MHz to 10 MHz and 3 MHz in the PRPD sensor, and 13 MHz to 24 MHz and 14 MHz in the 50 Ω NIR, respectively. The frequency spectrums of the PRPD sensor are relatively lower than those of 50 Ω NIR. This is because as the PD pulse flows through the conductor, the UHF component is attenuated by the distributed element. In this case, the frequency ranges over 40 MHz were attenuated.
Figure 9 shows example PRPD patterns measured by the prototype PRPD sensor and 50 Ω NIR at the same applied voltage of 4 kV. The PD pulses generated from the PD simulator accumulated for 1 min. The applied voltage signal of the prototype PRPD sensor and the 50 Ω NIR was measured by using the VT of the PRPD sensor and HV divider, respectively. The PD pulses of the PRPD sensor were distributed at phase angles of 26° to 105° and 221° to 276°. On the other hand, the PD pulses of the 50 Ω NIR were distributed at phase angles of 25° to 106° and 220° to 269°.
From the comparison of the phase distributions detected by each sensor, the PRPD sensor and 50 Ω NIR, there were no differences between them. In addition, the shape of the PRPD pattern detected by using the prototype PRPD sensor was similar to that of the 50 Ω NIR. According to the PRPD measurement, the prototype PRPD sensor could detect the PRPD patterns phase-synchronized with the applied voltage signals without any additional devices.

5. Conclusions

Many PD detection techniques have been extensively studied to diagnose insulation degradation in power equipment, but conventional PD sensors are hampered by the drawback of necessitating an independent device or system for the synchronous detection of PD patterns alongside the applied high-voltage signal. Detecting the PD pulses phase-synchronized with the applied voltage signals is a critical issue due to the PD pulses depending on the magnitude and phase of the applied voltage. This study proposed a novel PRPD sensor embedded in a MV-class bushing which could detect PD pulses phase-synchronized with applied voltage signals for the insulation deterioration diagnosis of electrical power equipment. The prototype PRPD sensor consisted of dual-sensing plates fabricated on the insulated flexible PCB and the signal transducer for calibrating the outputs of the voltage signals and PD pulses. The CVD and D-dot principles were applied to the voltage measurement and PD detection, respectively. In order to assess the efficacy of the suggested PRPD sensor, an experimental system was established. The voltage measurement accuracy of the PRPD sensor was evaluated in accordance with the testing standards specified in IEC 61869-11. Furthermore, the linearity and sensitivity of PD detection were compared with conventional electrical sensing techniques. The experimental results are summarized below:
A.
Voltage measurement
The evaluation of voltage measurement accuracy was focused on the deviation of the output magnitude and phase among the applied voltage and PRPD sensor. The designed rated transformation ratio was 10,000:1. The correction factor and corrected phase offset were set to be 1.000 and 76 min. The maximum corrected error ratio and corrected phase error were 0.126% and +3.06 min, respectively, and they were commonly detected at 100% of the rated voltage.
B.
PD detection
The prototype PRPD sensor was linear to the artificial PD calibration pulses. Alongside that, the outputs of the PRPD sensor were approximately 1.5 times larger than those of the conventional electrical detection method via a 50 Ω NIR. Regarding the time and frequency domains, the rising time of the PD pulse was relatively longer than the falling time, and the maximum magnitude was analyzed in the frequency range of about 24 MHz. The prototype PRPD sensor was able to detect the PRPD patterns phase-synchronized with the applied voltage signal successfully. The phase ranges of the PD pulses detected by the PRPD sensor were almost the same as those detected using the conventional method.
From the experimental results, it is expected that the proposed PRPD sensor holds potential as a viable alternative to conventional PD sensors due to its usefulness in diagnosing internal degradation. However, the PRPD sensor proposed in this paper has the limitation that the PRPD sensor embedded in the MV-class bushing needs to be replaced in terms of installation. Despite these difficulties, once applied, the PRPD sensor is expected to contribute to the continuous PD diagnosis of high-voltage facilities. Furthermore, the PRPD sensor has the potential to be connected to digital interfaces with intelligent electrical devices (IEDs) in line with the transition to digital substations.
Figure 10 shows a flowchart of the proposed PRPD measurement method phase-synchronized with the applied voltage signal, as proposed in this study. Further research is required as more PD characteristics need to be analyzed for the precise analysis of PD defects. Based on these considerations, additional PD characteristics of various types of PD defects, such as epoxy voids, delamination, cracks, metal suspension, and metal particles in the enclosure, should be investigated, and further research should be conducted on identifying PD defect types and identifying PD sources in the future.

Author Contributions

G.-Y.L. and N.-H.K. conceived and designed the experiments; G.-Y.L., N.-H.K. and D.-E.K. performed the experiments; N.-H.K. and D.-E.K. generated the raw data and G.-Y.L. and S.-W.K. analyzed the data; G.-Y.L., D.-E.K. and S.-W.K. wrote the paper; G.-S.K. was the supervisor of this work and provided insight and technical expertise to improve the quality of this study. All authors have read and agreed to the published version of the manuscript.

Funding

This work was supported by the Technology Innovation Program (No. 20010965, Development of Electronic Current Voltage Transformer and Spacer based on Eco-friendly Solid Insulation) funded by the Ministry of Trade, Industry & Energy(MOTIE) and Korea Evaluation Institute of Industrial Technology(KEIT) of the Republic of Korea.

Informed Consent Statement

Not applicable.

Data Availability Statement

Data are contained within the article.

Conflicts of Interest

The authors declare no conflict of interest.

Abbreviations and Physical Quantities

The following abbreviations and symbols and expressions of physical quantities are used in this manuscript.
AbbreviationsFull Name
PRPDPhase-resolved partial discharge
PDPartial discharge
PCBPrinted circuit board
CVDCapacitive voltage divider
HFCTHigh-frequency current transformer
UHFUltra-high frequency
AEAcoustic emission
S/NSignal-to-noise ratio
PTPotential transformer
CPTCapacitive potential transformer
RPTResistive potential transformer
LPVTLow-power voltage transformer
IECInternational Electrotechnical Commission
SAMUStand-alone merging unit
EVTElectronic voltage transformer
TLTransmission line
EMElectromagnetic
VTVoltage transformer
Tg-typeHigh glass transition temperature
GDTGas discharge tube
HPFHigh-pass filter
IVRInduction-type automatic voltage regulator
NIRNon-inductive resistor
DSODigital storage oscilloscope
HV Tr.High-voltage transformer
HV dividerHigh-voltage divider
ZCZero-crossing
FFTFast Fourier transform
Physical quantitiesSymbolsDefinitionsUnits
Corrected ratio error ε cor   U Ratio error of an individual passive LPVT corrected by the factor±%
Correction factor CF U Factor by which the rated transformation ratio evaluated at rated burden and rated frequency of an individual passive LPVT is to be multiplied to achieve the specified accuracy class-
Rated transformation ratio K r Ratio of output voltage to the input voltage of the passive LPVT-
Phase offset correction φ o   cor Value to be added to the rated phase offset evaluated at rated burden and rated frequency of an individual passive LPVT to achieve the specified accuracy class±Minutes
±Centiradians
Corrected phase error φ e   cor Phase error of an individual passive LPVT corrected by the value±Minutes
±Centiradians
Corrected phase offset φ cor   φ o individual phase offset of a passive LPVT±Minutes
±Centiradians

References

  1. Pietsch, R.; Hauschild, W. High-voltage On-site Testing with Partial Discharge Measurement. CIGRE Tech. Broch. 2012, 502, 83–93. [Google Scholar]
  2. Chai, H.; Phung, B.T.; Mitchell, S. Application of UHF Sensors in Power System Equipment for Partial Discharge Detection: A Review. Sensors 2019, 19, 1029. [Google Scholar] [CrossRef]
  3. IEC 60270; High-Voltage Test Techniques–Partial Discharge Measurements. International Electrotechnical Commission: Genova, Switzerland, 2000.
  4. Kreuger, F.H. Partial Discharge Detection in High Voltage Equipment. Butterworth 1989, 129, 152. [Google Scholar]
  5. Liu, J.; Zhang, G.; Dong, J.; Wang, J. Study on Miniaturized UHF Antennas for Partial Discharge Detection in High-Voltage Electrical Equipment. Sensors 2015, 15, 29434–29451. [Google Scholar] [CrossRef]
  6. Gulski, E.; Koltunowicz, W.; Ariaans, T.; Behrmann, G.; Jongen, R.; Garnacho, F.; Kornhuber, S.; Ohtsuka, S.; Petzold, F.; Sánchez-Urán, M.A.; et al. Guidelines for Partial Discharge Detection using Conventional (IEC60270) and Unconventional Methods; CIGRE WG D1.37; CIGRE: Paris, France, 2016. [Google Scholar]
  7. Wu, M.; Cao, H.; Cao, J.; Nguyen, H.L.; Gomes, J.B.; Krishnaswamy, S.P. An overview of state-of-the-art partial discharge analysis techniques for condition monitoring. IEEE Electr. Insul. Mag. 2015, 31, 22–35. [Google Scholar] [CrossRef]
  8. Wang, X.; Li, X.; Rong, M.; Xie, D.; Ding, D.; Wang, Z. UHF Signal Processing and Pattern Recognition of Partial Discharge in Gas-Insulated Switchgear Using Chromatic Methodology. Sensors 2017, 17, 177. [Google Scholar] [CrossRef]
  9. Schichler, U.; Koltunowicz, W.; Gautschi, D.; Girodet, A.; Hama, H.; Juhre, K.; Lopez-Roldan, J.; Okabe, S.; Neuhold, S.; Neumann, C.; et al. UHF Partial Discharge Detection System for GIS: Application Guide for Sensitivity Verification. IEEE Trans. Dielectr. Electr. Insul. 2016, 23, 1313–1321. [Google Scholar] [CrossRef]
  10. Reuters, M.; Templeton, D.; Beck, M.; Bélec, M.; Dullni, E.; Hoek, S.; Jung, J.-R.; Kyrkjeeide, S.; Lefter, Z.; Linn, T.; et al. Benefits of PD Diagnosis on GIS Condition Assessment; CIGRE WG B3.24; CIGRE: Paris, France, 2017. [Google Scholar]
  11. Kim, S.W.; Kim, N.H.; Kim, D.E.; Kim, T.H.; Jeong, D.H.; Chung, Y.H.; Kil, G.S. Experimental Validation for Moving Particle Detection Using Acoustic Emission Method. Energies 2021, 14, 8516. [Google Scholar] [CrossRef]
  12. Lundgaard, L.; Skyberg, B.; Schei, A.; Diessner, A. Method and instrumentation for acoustic diagnoses of GIS. CIGRE Session. 2000, 15, 309. [Google Scholar]
  13. Mondal, M.; Kumbhar, G.B. Partial Discharge Localization in a Power Transformer: Methods, Trends, and Future Research. IETE Tech. Rev. 2017, 34, 504–513. [Google Scholar] [CrossRef]
  14. de Castro, B.A.; dos Santos, V.V.; Lucas, G.B.; Ardila-Rey, J.A.; Riehl, R.R.; Andreoli, A.L. A Comparative Analysis Applied to the Partial Discharges Identification in Dry-Type Transformers by Hall and Acoustic Emission Sensors. Sensors 2022, 22, 1716. [Google Scholar] [CrossRef]
  15. Sikorski, W.; Wielewski, A. Low-Cost Online Partial Discharge Monitoring System for Power Transformers. Sensors 2023, 23, 3405. [Google Scholar] [CrossRef]
  16. Shin, G.C.; Kim, S.W.; Kil, G.S. Comparison between the PD Characteristics of g3 and Dry Air for Gas-Insulated Switchgears. Energies 2022, 15, 7043. [Google Scholar] [CrossRef]
  17. Bozzo, R.; Centurioni, L.; Guastavino, F. Measuring the Endurance of Films in Partial Discharges. IEEE Trans. Dielectr. Electr. Insul. 1993, 28, 1050–1056. [Google Scholar] [CrossRef]
  18. Lu, Z.; Li, Z.; Lu, S.; Xu, M.; Liu, W. Fault Mechanism Analysis of Voltage Transformer Caused by Iron Core Saturation. In Proceedings of the 2022 IEEE 6th Advanced Information Technology, Electronic and Automation Control Conference (IAEAC), Beijing, China, 3–5 October 2022; pp. 856–859. [Google Scholar] [CrossRef]
  19. Xiao, Y.; Fu, J.; Hu, B.; Li, X.; Deng, C. Problems of voltage transducer in harmonic measurement. IEEE Trans. Pow. Deliv. 2004, 19, 1483–1487. [Google Scholar] [CrossRef]
  20. Mingotti, A.; Costa, F.; Pasini, G.; Peretto, L.; Tinarelli, R. Modeling Capacitive Low-Power Voltage Transformer Behavior over Temperature and Frequency. Sensors 2021, 21, 1719. [Google Scholar] [CrossRef]
  21. IEC 61869-11; Instrument Transformers—Part 11: Additional Requirements for Low-Power Passive Voltage Transformers. International Electrotechnical Commission: Genova, Switzerland, 2017.
  22. IEC 60044-7; Instrument Transformers—Part 7: Electronic Voltage Transformers. International Electrotechnical Commission: Genova, Switzerland, 1999.
  23. IEC 61869-13; Instrument Transformers—Part 13: Stand-Alone Merging Unit (SAMU). International Electrotechnical Commission: Genova, Switzerland, 2021.
  24. Wagoner, T.C.; Stygar, W.A.; Ives, H.C.; Gilliland, T.L.; Spielman, R.B.; Johnson, M.F.; Reynolds, P.G.; Moore, J.K.; Mourning, R.L.; Fehl, D.L.; et al. Differential-output B-dot and D-dot monitors for current and voltage measurements on a 20-MA, 3-MV pulsed-power accelerator. Phys. Rev. Spec. Top. Accel. Beams 2008, 11, 100401. [Google Scholar] [CrossRef]
  25. Wang, J.; Ban, S.; Yang, Y. A Differential Self-Integration D-Dot Voltage Sensor and Experimental Research. IEEE Sens. J. 2015, 7, 3846–3852. [Google Scholar] [CrossRef]
  26. Kim, N.H.; Kim, D.E.; Kim, S.W.; Kim, J.H.; Kil, G.S. Development of Electronic Voltage Transformer for Electric Rolling Stocks. J. Korean Soc. Railw. 2023, 26, 445–453. [Google Scholar] [CrossRef]
  27. Wang, J.; Gao, C.; Yang, J. Design, Experiments and Simulation of Voltage Transformers on the Basis of a Differential Input D-dot Sensor. Sensors 2014, 14, 12771–12783. [Google Scholar] [CrossRef]
  28. Yao, L.; Huang, J.; Kang, N.; Shen, T.; Liu, D.; Zhang, F.; Sun, H. Compensation of the offset in numerical integration of a D-dot sensor measurement. In Proceedings of the 2014 3rd Asia-Pacific Conference on Antennas and Propagation, Harbin, China, 26–29 July 2014; pp. 898–901. [Google Scholar] [CrossRef]
  29. Hussain, G.A.; Shafiq, M.; Lehtonen, M.; Hashmi, M. Online Condition Monitoring of MV Switchgear Using D-Dot Sensor to Predict Arc-Faults. IEEE Sens. J. 2015, 15, 7262–7272. [Google Scholar] [CrossRef]
  30. Hussain, G.A.; Amjad, G.; Zaher, A.A.; Hummes, D.; Safdar, M.; Lehtonen, M. Hybrid Sensing of Internal and Surface Partial Discharges in Air-Insulated Medium Voltage Switchgear. Energies 2020, 13, 1738. [Google Scholar] [CrossRef]
  31. Rostaghi-Chalaki, M.; Yousefpour, K.; Donohoe, J.P.; Kurum, M.; Park, C.; Klss, J. Design of Transmission Line and Electromagnetic Field Sensors for DC Partial Discharge Analysis. IEEE Trans Dielectr. Electr. Insul. 2020, 27, 2138–2146. [Google Scholar] [CrossRef]
  32. Jin, M.; Li, H.; Liu, S. Identification and Compensation for D-Dot Measurement System in Transient Electromagnetic Pulse Measurement. Sensors 2022, 22, 8538. [Google Scholar] [CrossRef]
  33. Kim, S.W.; Jung, J.R.; Kim, Y.M.; Kil, G.S.; Wang, G. New Diagnosis Method of Unknown Phase-shifted PD Signals for Gas Insulated Switchgears. IEEE Trans Dielectr. Electr. Insul. 2018, 25, 102–109. [Google Scholar] [CrossRef]
  34. Lee, J.H.; Hozumi, N.; Okamoto, T. Discrimination of phase-shifted partial discharge patterns by neural network using standardization method. In Proceedings of the 1994 IEEE International Symposium on Electrical Insulation, Pittsburgh, PA, USA, 5–8 June 1994; pp. 314–317. [Google Scholar] [CrossRef]
  35. Boggs, S.; Pathak, A.; Walker, P. Partial discharge. XXII. High frequency attenuation in shielded solid dielectric power cable and implications thereof for PD location. IEEE Electr. Insul. Mag. 1996, 12, 9–16. [Google Scholar] [CrossRef]
  36. Yifan, Z.; Wang, Y.; Wang, W. A study on the propagation characteristics of partial discharge in cable joints based on the FDTD method. IEEE Access 2020, 8, 130094–130103. [Google Scholar]
Figure 1. The prototype PRPD sensor: (a) configuration and (b) photograph.
Figure 1. The prototype PRPD sensor: (a) configuration and (b) photograph.
Sensors 23 09844 g001
Figure 2. Configuration of the signal transducers: (a) voltage signals and (b) PD pulses.
Figure 2. Configuration of the signal transducers: (a) voltage signals and (b) PD pulses.
Sensors 23 09844 g002
Figure 3. Frequency response of the signal transducer for the PD pulses.
Figure 3. Frequency response of the signal transducer for the PD pulses.
Sensors 23 09844 g003
Figure 4. An artificial PD simulator: (a) photograph and (b) cross-sectional diagram.
Figure 4. An artificial PD simulator: (a) photograph and (b) cross-sectional diagram.
Sensors 23 09844 g004
Figure 5. Experimental setup: (a) schematic diagram; (b) photograph.
Figure 5. Experimental setup: (a) schematic diagram; (b) photograph.
Sensors 23 09844 g005
Figure 6. Example waveforms and phase errors: (a) 80%; (b) 100%; and (c) 120%.
Figure 6. Example waveforms and phase errors: (a) 80%; (b) 100%; and (c) 120%.
Sensors 23 09844 g006
Figure 7. Output voltage for the calibration pulse.
Figure 7. Output voltage for the calibration pulse.
Sensors 23 09844 g007
Figure 8. Example waveform: (a) single pulse; (b) fast Fourier transform (FFT).
Figure 8. Example waveform: (a) single pulse; (b) fast Fourier transform (FFT).
Sensors 23 09844 g008
Figure 9. Comparison of PRPD patterns detected by (a) PRPD sensor; (b) 50 Ω NIR.
Figure 9. Comparison of PRPD patterns detected by (a) PRPD sensor; (b) 50 Ω NIR.
Sensors 23 09844 g009
Figure 10. Flowchart of the PRPD measurement method phase-synchronized with applied voltage.
Figure 10. Flowchart of the PRPD measurement method phase-synchronized with applied voltage.
Sensors 23 09844 g010
Table 1. Geometric parameters of the PRPD sensor.
Table 1. Geometric parameters of the PRPD sensor.
ParameterValue
DiameterΦ 160 mm
Height12 mm
Sensing electrodes
(Voltage and PD)
Width3 mm
Thickness1 ounce (oz)
Insulation layer0.2 mm
Dielectric constant ( ε s )4.7
Table 2. Accuracy test results of the PRPD sensor.
Table 2. Accuracy test results of the PRPD sensor.
Voltage LevelApplied Voltage
V H [kV]
PRPD Sensor
V L [V]
Corrected Error Ratio
ε c o r U [%]
Corrected Phase Error
φ e c o r [min]
Measured
Value
Accuracy Class of 0.2Measured
Value
Accuracy Class of 0.2
0.8 U P 10.5611.0560.0010.2−0.8310
1.0 U P 13.2041.3220.126+3.06
1.2 U P 15.8031.5830.166−2.13
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Lee, G.-Y.; Kim, N.-H.; Kim, D.-E.; Kil, G.-S.; Kim, S.-W. The Design, Fabrication, and Evaluation of a Phase-Resolved Partial Discharge Sensor Embedded in a MV-Class Bushing. Sensors 2023, 23, 9844. https://doi.org/10.3390/s23249844

AMA Style

Lee G-Y, Kim N-H, Kim D-E, Kil G-S, Kim S-W. The Design, Fabrication, and Evaluation of a Phase-Resolved Partial Discharge Sensor Embedded in a MV-Class Bushing. Sensors. 2023; 23(24):9844. https://doi.org/10.3390/s23249844

Chicago/Turabian Style

Lee, Gyeong-Yeol, Nam-Hoon Kim, Dong-Eon Kim, Gyung-Suk Kil, and Sung-Wook Kim. 2023. "The Design, Fabrication, and Evaluation of a Phase-Resolved Partial Discharge Sensor Embedded in a MV-Class Bushing" Sensors 23, no. 24: 9844. https://doi.org/10.3390/s23249844

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop