Energy Saving in Ship Central Cooling Systems: IMC-Tuned PID with Feedforward Control

1
Division of Marine Engineering System, National Korea Maritime and Ocean University, Busan 49112, Republic of Korea
2
Division of Coast Guard Studies, National Korea Maritime and Ocean University, Busan 49112, Republic of Korea
*
Author to whom correspondence should be addressed.
J. Mar. Sci. Eng. 2025, 13(3), 510; https://doi.org/10.3390/jmse13030510
Submission received: 31 January 2025 / Revised: 28 February 2025 / Accepted: 3 March 2025 / Published: 5 March 2025
(This article belongs to the Special Issue Maritime Logistics and Green Shipping)

Abstract

This study examines the energy savings in a ship’s central cooling system using feedforward control with IMC (Internal Model Control)-based PID tuning. A central cooling system is essential for maintaining the temperature of the engine and other major machinery, thereby improving the overall energy efficiency. The seawater pump in the central cooling system consumes a relatively large amount of power, which makes efficient operation essential. This study compared the power consumption of variable-speed seawater pumps based on actual operational data from a ship. By incorporating a feedforward PI controller into the IMC-based PI-PID controller combinations, this study simulated energy savings. The results indicate that the proposed controller combined with the feedforward PI controller reduces the power consumption of seawater pumps compared with conventional methods. Simulation tests were conducted using approximately 11 days of operational data to verify the effectiveness of the proposed control strategy in achieving energy savings. The proposed controller combination saves approximately 277.4 kWh of power over 11 days compared to conventional control methods.
Keywords: PID control; energy saving; ship; integrated control; variable speed control; feedforward PID control; energy saving; ship; integrated control; variable speed control; feedforward

Share and Cite

MDPI and ACS Style

Jeon, T.-Y.; Lee, Y.-C. Energy Saving in Ship Central Cooling Systems: IMC-Tuned PID with Feedforward Control. J. Mar. Sci. Eng. 2025, 13, 510. https://doi.org/10.3390/jmse13030510

AMA Style

Jeon T-Y, Lee Y-C. Energy Saving in Ship Central Cooling Systems: IMC-Tuned PID with Feedforward Control. Journal of Marine Science and Engineering. 2025; 13(3):510. https://doi.org/10.3390/jmse13030510

Chicago/Turabian Style

Jeon, Tae-Youl, and Young-Chan Lee. 2025. "Energy Saving in Ship Central Cooling Systems: IMC-Tuned PID with Feedforward Control" Journal of Marine Science and Engineering 13, no. 3: 510. https://doi.org/10.3390/jmse13030510

APA Style

Jeon, T.-Y., & Lee, Y.-C. (2025). Energy Saving in Ship Central Cooling Systems: IMC-Tuned PID with Feedforward Control. Journal of Marine Science and Engineering, 13(3), 510. https://doi.org/10.3390/jmse13030510

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop