4.1. Estimation of the Required SW Mass Flow Rate
In the present study a parametric investigation was conducted to determine the SW mass flow rate required to cover the cooling load of the central cooling system examined, as the SW HX inlet temperature decreases from its highest value (equal to 32 °C, corresponding to the heat exchanger design/tropical conditions), to a lower temperature equal to 13 °C, with a step of 1 °C, for all the range of main engine loads (25% ÷ 100%). The variation of seawater temperature in the range of 13 ÷ 32 °C is within the typical values found in Mediterranean Sea [
29] and covers the majority of the seawater temperatures found in the major sea shipping routes worldwide.
Therefore the SW HX inlet temperature and the main engine load are the independent variables, while the mass flow rate of the FW is maintained constant and equal to the one determined at the heat exchanger design conditions (
Table 1), and the control variable is the SW mass flow rate through which the heat capacity of the central cooler is adjusted to ensure that the set-point temperature requirements for the SW outlet (T
t2 ≤ 50 °C) and FW outlet (T
s1 ≤ 36 °C) are satisfied. Since all the parameters of the heat exchanger performance are intrinsically coupled, an iterative procedure is followed and at each step the SW outlet temperature (T
t2), the FW inlet temperature (T
s1) and the FW outlet temperature (T
s2) are determined at steady state conditions, via the energy conservation equation (assuming that there are no heat losses at the central cooler), as shown in Equations (38) and (39).
At first, the effect of SW inlet temperature is examined assuming that the central cooler heat load is equal to the heat exchanger design load QHX = 4251 kW. The parametric study starts with a SW inlet temperature equal to Tt1 = 32 °C (tropical/HX-design conditions), while all the other parameters have values equal to the ones corresponding to the design conditions of the heat exchanger. As SW inlet temperature lowers, a new SW mass flow rate is determined to keep the cooling capacity of the heat exchanger constant (equal to the one corresponding to the heat load examined), while ensuring that the set-point requirements for the SW and FW outlet temperatures are satisfied (i.e., Tt2 ≤ 50 °C and Ts1 ≤ 36 °C).
In
Figure 6, the SW mass flow rate (
) is shown as a function of the SW inlet temperature (T
t1), when the variable speed drive (VSD) scheme is selected, compared to the conventional case where the pump speed remains constant. It is noticed that in the case of the VSD pump being used, two mass flow rates have been determined, i.e., one using a thermodynamic model (namely VSD-Thermodynamic Model) and another using the HX-model (namely VSD-HX Model). The first corresponds to the SW mass flow rate that would be determined using only the energy balance Equation (20), which is the most widely used approach for the techno-economic evaluation of the VSD control on the central cooling pumps, while the second is the SW mass flow rate determined by the proposed methodology in the current study, taking into account how the effectiveness of heat exchanger is affected by the variation of its boundary conditions (temperatures and mass flow rates). It is obvious that as the SW inlet temperature decreases, the required SW mass flow rate decreases too and is almost identical when calculated with either the conventional method (thermodynamic model) or the proposed one (HX-model). This is mainly attributed to the fact that the heat load examined is equal to the design heat load of the heat exchanger, and as will be presented later, this will not be the case at part-load conditions.
For SW temperature equal to 13 °C, the required SW mass flow rate is approximately 51% lower (27.46 kg/s) than the one corresponding to the constant SW pump speed (56.48 kg/s). The reduction of the SW mass flow rate is followed by a reduction of the SW pump power demand, which can be determined according to affinity laws (Equation (1)) and is equal to 88.5% compared to the constant speed case. This is a considerable reduction, although it should be stated that as the operating point of the pump changes, its efficiency is also affected, and most importantly the VSD and the motor induce additional terms of power losses (variable speed drive efficiency and electric motor efficiency at part loads) which should also be taken into account for precise determination of the actual power reduction of the SW pump [
11].
In case the heat load of the central cooler is reduced, i.e., at 25%, 50%, 75% and 100% of full engine load, the variation of the SW mass flow rate as a function of the SW inlet temperature is presented in
Figure 7. The heat load of the heat exchanger for each case is estimated based on
Figure 5. It can be observed that as the cooling load decreases, there is a higher potential for reducing the SW mass flow rate compared to the HX-design heat load case (4251 kW), leading to approx. an 81% reduction of the SW mass flow rate (10.82 kg/s) at 13 °C compared to the constant pump speed case at 25% of engine load. It is interesting to note that in all part-load cases examined (lower than the HX-design cooling load of 4251 kW), the estimated SW mass flow rate using the proposed method (HX-model) is higher than that obtained using the conventional model (thermodynamic model), with the difference being higher at high SW temperatures. This is attributed to the fact that as the heat load reduces, while the initial FW inlet temperature is high (equal to the HX-design conditions), the estimation of the required SW mass flow rate based only on the heat balance would lead to FW outlet temperatures higher than the ones accepted (T
s2 ≤ 36 °C). An analogous situation may occur with the SW outlet temperature. When the heat load is low and depending on the SW inlet temperature, it is possible that the estimated SW mass flow rate using the conventional heat balance method would be very low, and based on the heat exchanger design configuration, this would lead to SW outlet temperatures higher than the maximum accepted ones (in the present study T
t2 ≤ 50 °C). Therefore, the advantageous feature of the proposed method is that the energy balance equations (used in conventional techno-economic studies for the evaluation of VSD pump drives) are dynamically linked with the actual heat exchanger performance (depending on the boundary conditions, i.e., mass flow rates and temperatures), leading to a more accurate estimation of the required SW mass flow rate as a function of the SW inlet temperature, taking into account all the restrictions of the problem (set-point temperatures).
4.3. Estimation of Fuel Saving Using VSD Cooling Pump
In the standard configuration of the cooling system examined, a constant speed cooling pump is used for the SW cooling circuit, with the characteristic curves presented in
Figure 8 and with a pump power demand corresponding to reference operational conditions (Flow rate = 197.62 m
3/h, Pump Efficiency = 71.8%, Pump Head = 31.90 mH
2O), equal to 24.62 kW. Hence the rated power of the electric motor used to drive the pump is assumed equal to 30 kW. This cooling pump power demand will be used as a reference for the estimation of the relative reduction of the required pumping power when a VSD is used.
According to the power conversion path considered in this study (
Figure 9), electric energy is generated by a Diesel Generator unit with a typical brake specific fuel consumption equal to 200 g/kWh, and then this electric power goes through a Variable Frequency Drive (VFD) or variable speed controller which can control electric motor speed by varying the frequency of the electric power supply, and this motor drives the SW pump, covering its power demand. Through this process, three efficiency coefficients are introduced, each one for each component, i.e.,
for the Variable Speed Drive controller,
for the electric motor and
for the SW pump accordingly.
At part-load conditions and depending on the actual operating point (required SW mass flow rate) the values of these efficiencies vary. Specifically, the motor efficiency at part load is estimated based on the average values suggested by Reference [
30] for TEFC (Totally Enclosed Fan Cooled) motors, as shown in
Table 6. As far as the effect of part-load operation on VSD efficiency is concerned, this is estimated based on Reference [
31], assuming a typical PWM (Pulse Width Modulated) type VFD, as show in
Table 7.
As the speed of the SW pump varies (according to the required mass flow rate), its hydraulic efficiency
is also affected and is estimated based on the expression proposed by Reference [
32] shown in Equation (40), where,
is the reference pump efficiency at reference pump speed (
) and
, is the pump speed at each operating condition examined. In the present study,
, and
RPM.
Based on the above, the wire-to-water efficiency
is calculated according to Equation (41):
Assuming a continuous operational profile of the SW cooling pump (just as a reference for the comparative study conducted), i.e., the annual operating hours equal to 8720 h, a total fuel consumption equal to 49.24 tn is estimated for the one SW cooling pump considered.
In the previous section, the required SW mass flow rate has been estimated at each engine load and for all the range of SW inlet temperatures examined, using the proposed HX-model. Based on these mass flow rates, the pump affinity law (Equation (1)), and the wire-to-water efficiency according to Equation (41), the VSD pump power is estimated and the corresponding annual fuel savings are calculated compared to the reference case, and presented in
Figure 10, for each engine load and the whole SW inlet temperatures range examined. As expected, the estimated fuel savings are higher at lower engine loads and at lower SW inlet temperatures since in these cases the cooling demand is lower and the required SW mass flow rate is also lower, leading to lower pumping power demand.
It must be stated that the fuel savings estimated in
Figure 10, only take into account the operation of the SW cooling pump and disregard the actual effect of reduced SW mass flow rate on the FW outlet temperature and on the engine’s inlet air temperature via the corresponding effect on the performance of the charge air cooler (CAC). However, the scope of this study is to capture the overall effect of substituting the constant speed SW cooling pump with a VSD cooling pump. As shown in
Figure 7, when using the VSD cooling pump, the FW outlet temperature is approximately constant and equal to the set-point temperature of 36 °C at all operating conditions examined (irrespective of the SW temperature). In the conventional case of constant speed SW cooling pump, the FW outlet temperature (which is also the scavenge air cooler water inlet temperature) is assumed to be 4 °C higher than the corresponding SW inlet temperature, as suggested by Reference [
19] and shown in
Figure 2. Moreover, to estimate the effect of ambient conditions on engine’s bsfc, it is assumed that the inlet air temperature (
) is three degrees higher than the corresponding SW inlet temperature, thus,
°C (according to Reference [
19] the inlet air temperature is expected to be 1 to 3 °C higher than the corresponding SW temperature).
Based on the aforementioned assumptions and using the MAN publicly available software platform “CEAS Engine Calculations” [
21], the effect of seawater temperature on engine’s bsfc is estimated with and without the usage of a VSD SW cooling pump, and presented in
Figure 11. It is observed that using a VSD cooling pump, the bsfc is higher at all engine loads examined compared to the conventional case with constant speed SW cooling pump, with the difference being higher as the SW temperature decreases, reaching values up to 1.88 g/kWh.
As shown in
Figure 11, the effect of seawater temperature on bsfc is higher in the conventional case (constant speed SW cooling pump) compared to the case with VSD. This is better shown in
Figure 12, where the variation of engine’s bsfc is presented as a function of engine load for various SW inlet temperatures with and without VSD SW cooling pump, as estimated using the MAN CEAS software [
21]. When using a VSD SW cooling pump, one of the targets set in the iterative procedure followed for the estimation of the required SW mass flow rate is the FW outlet temperature to be as close as possible to the set-point temperature T
s2 = 36 °C. Therefore, the variation of FW outlet temperature when using a VSD SW pump is very limited (as already presented in
Figure 7), contrary to what applies in the case of constant speed cooling pump, where the FW outlet temperature is assumed to be 4 °C greater than the corresponding SW temperature. This explains the more intense effect of SW temperature on the engine’s bsfc at constant speed SW pump.
From the analysis above it is obvious that using a VSD SW cooling pump has two contradictory effects on fuel consumption: On the one hand, it has a very strong positive effect on SW cooling pump power demand, which leads to a drastic reduction of the required fuel consumption for the operation of the SW cooling pump, but on the other hand, it leads to increased FW inlet temperature in the charge air cooler which in turn has a small (on a percentage basis) negative effect on the engine’s bsfc. Although as already presented, the relative positive effect on fuel consumption using a VSD pump is significantly higher regarding the power of SW pump compared to the negative effect on engine’s bsfc, one must consider the rated power of these two energy systems. In the case examined in this study, i.e., a handy-size bulk carrier, there are two SW cooling pumps rated at 30 kW each, serving an engine rated at 7410 kW. Combining the effect of VSD cooling pump on engine bsfc and pump power, assuming a continuous annual operation (8720 h) at each engine load and at each seawater temperature examined (only as a basis for our comparative study and not as a realistic operational scenarios), the estimated annual fuel saving (in tn/year) obtained by the substitution of the constant speed cooling pump with a VSD one is presented in
Figure 13.
As observed, the higher benefit is achieved in lower engine loads, while at full engine load, there is a SW temperature threshold below which the usage of VSD SW cooling pump has a detrimental effect on the total fuel consumption of the main engine and the two cooling pumps. Specifically, at full engine load, when the seawater temperature is lower than 18 °C, it seems that the benefit of using a VSD diminishes, and below that value, using a VSD pump leads to increased fuel consumption compared to the conventional case (constant speed SW cooling pump). Moreover, from the parametric study conducted, it is obvious that at each engine load, the highest prospected benefit from using a VSD cooling pump is observed when the seawater temperature is around 29 °C, while as the seawater temperature decreases this positive effect is reduced.
It should be noted that in the parametric analysis conducted in this study, the required seawater mass flow rate (and consequently the cooling pump power demand) has been estimated having set a target to maintain the FW outlet temperature as close as possible to its reference value of 36 °C, and the SW outlet temperature to be below the maximum accepted value by the class society which is equal to 50 °C. In real life applications, depending on the actual operating conditions (engine load and ambient sea and air temperatures) and using the proposed HX-model to capture the real effect of boundary conditions on the performance of the SW/FW cooler, it is possible to identify the optimum settings for the VSD pump in order to maximize the benefit of lowering the pumping power with the minimum compromise for the bsfc of the engine. One of the main outcomes of the present study is that it has been demonstrated that an integrated approach should be followed to determine the optimum control scheme used for the operation of a VSD cooling pump, to ensure actual fuel savings in real life operating conditions.