Next Article in Journal / Special Issue
Analysis of the Induction and Wake Evolution of an Offshore Floating Wind Turbine
Previous Article in Journal
Characteristics of CO2 Hydrate Formation and Dissociation in Glass Beads and Silica Gel
Previous Article in Special Issue
Deviation of Cup and Propeller Anemometer Calibration Results with Air Density
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

H Based Control for Load Mitigation in Wind Turbines

by
Asier Diaz De Corcuera
*,
Aron Pujana-Arrese
,
Jose M. Ezquerra
,
Edurne Segurola
and
Joseba Landaluze
IKERLAN-IK4, Arizmendiarreta, 2, E-20500 Arrasate-Mondragon, The Basque Country, Spain
*
Author to whom correspondence should be addressed.
Energies 2012, 5(4), 938-967; https://doi.org/10.3390/en5040938
Submission received: 25 January 2012 / Revised: 20 March 2012 / Accepted: 31 March 2012 / Published: 17 April 2012
(This article belongs to the Special Issue Wind Turbines)

Abstract

:
This article demonstrates a strategy to design multivariable and multi-objective controllers based on the H norm reduction applied to a wind turbine. The wind turbine model has been developed in the GH Bladed software and it is based on a 5 MW wind turbine defined in the Upwind European project. The designed control strategy works in the above rated power production zone and performs generator speed control and load reduction on the drive train and tower. In order to do this, two robust H MISO (Multi-Input Single-Output) controllers have been developed. These controllers generate collective pitch angle and generator torque set-point values to achieve the imposed control objectives. Linear models obtained in GH Bladed 4.0 are used, but the control design methodology can be used with linear models obtained from any other modelling package. Controllers are designed by setting out a mixed sensitivity problem, where some notch filters are also included in the controller dynamics. The obtained H controllers have been validated in GH Bladed and an exhaustive analysis has been carried out to calculate fatigue load reduction on wind turbine components, as well as to analyze load mitigation in some extreme cases. The analysis compares the proposed control strategy based on H controllers to a baseline control strategy designed using the classical control methods implemented on the present wind turbines.

1. Introduction

The continuous increase of the size of wind turbines, due to the demand of higher power production installations, has led to new challenges in the design of the turbines. Moreover, new control strategies are being developed. Today’s strategies trend towards being multivariable and multi-objective in order to fulfill the numerous control design specifications. To be more precise, one important specification is to mitigate loads in the turbine components to increase their life time. This can be done through the components mechanical design, the introduction of new materials or by improving the control itself. In addition to this, the behaviour of a wind turbine is non-linear, which implies that the designed control performance has to be robust.
Over the last few years, several modern control techniques used to replace the classical PI controllers (see Section 3) have been developed. These techniques are fuzzy controllers [1], adaptive control strategies [2], linear quadratic controllers [3] like the Disturbance Accommodating Control (DAC) [4] developed by NREL and tested in the CART real wind turbine [5], QFT controllers [6], Linear Parameter Varying (LPV) controllers [7] and controllers based on the H norm reduction. H controllers have the capacity for robustness and these controllers are multivariable and multi-objective, so their applications in wind turbine control offer a lot of advantages and they achieve interesting results. One article dealing with this topic [8] shows the design of two controllers based on the H norm reduction applied to a simple and analytical model of a wind turbine. The first one reduces the loads on the tower with the tower fore-aft acceleration displacement measurement and controls the generator speed reference with a pitch collective control in the above rated zone. The second controller also reduces the loads on the blades with a cyclic pitch controller based on the H norm reduction. Control strategies using SISO and MISO state-space controllers based on the H norm are tested and compared in the CART3 experimental wind turbine [9]. In this article, torque controllers are used to damp the drive train mode and the tower side-to-side bending mode.
This article presents the design of two H MISO (Multi-Input Single-Output) controllers in the above rated zone (see Section 5). These controllers not only control the generator speed and reduce the fore-aft displacements on the tower using a collective pitch controller, but they also reduce the side-to-side displacements on the tower and the loads on the drive train if a generator torque H controller is used. Furthermore, in terms of the controller design, instead of using a simple analytical model of a wind turbine, complex linear plants extracted from GH Bladed 4.0 are used, although the design methodology could be applied by using linear models obtained from any modeling package. Regarding the H controller design, some notch filters are included in the controller dynamics by means of the correct definition of the weight functions in the augmented plant of the mixed sensitivity problem. In the design process of this control strategy based on H controllers, two software packages are used: GH Bladed 4.0 and MATLAB. GH Bladed is a software package commercialized by Garrad Hassan Company, commonly used by major wind turbine manufacturers to model and simulate wind turbines. The controller synthesis and discretization is carried out in MATLAB and, finally, simulations of the closed loop system are carried out using GH Bladed with different perturbed production winds. Results using H controllers are compared to the baseline controller results, based on classical control strategies, in order to do a load mitigation analysis to test the load mitigation capacity of the new designed control strategy. In the load analysis, both fatigue damage cases (DLC1.2 in IEC61400-1 Second Edition) and some extreme load cases (DLC1.6 in IEC61400-1 Second Edition) are taken into account.

2. Wind Turbine Model

2.1. Non-Linear Model

The Upwind wind turbine defined in the Upwind European project was developed in GH Bladed 4.0 and it is the non-linear model used in this research project. The Upwind model consists of a 5 MW offshore wind turbine [10,11] with a monopile structure in the foundation. It has three blades and each blade has an individual pitch actuator. The rotor diameter is 126 m, the hub height is 90 m, it has a gear box ratio of 97, the rated wind speed is 11.3 m/s, the cut-out wind speed is 25 m/s and the rated rotor rotational speed is 12.1 rpm.

2.2. Linear Models

The wind turbine linear models are obtained in different operational points from the GH Bladed (version 4.0) non-linear model using the linearization tool of this software. Twelve operational points are defined from 3 m/s to 25 m/s. The Campbell diagram shows the frequencies of the structural modes of linear model family with respect to the operational points (see Figure 1).
Figure 1. Campbell diagram for the Upwind model.
Figure 1. Campbell diagram for the Upwind model.
Energies 05 00938 g001
In Table 1, the frequencies of these modes are more accurately shown for the operational point of 11 m/s wind speed and some abbreviations are defined as well as referring to the modes used throughout this article. Linear models (1) are expressed by the state-space matrices and have different inputs and outputs. Inputs are the collective pitch angle and generator torque control signals u(t) and the disturbance output w(t) caused by the wind speed. The outputs y(t) are the sensorized measurements used to design the controller. In this case, these outputs are the generator speed wg, the tower top fore-aft acceleration aTfa and the tower top side-to-side acceleration aTss. Due to the non-linear model complexity, and the number of modes taken into account, the order of the linear models is 55. The linear models are not reduced because, after carrying out an analysis, the best quality of the controller syntheses are obtained using high order linear plants and reducing the higher order obtained controllers:
Energies 05 00938 i001
Table 1. Modal analysis of the Upwind model (BW: backward whirl; FW: forward whirl).
Table 1. Modal analysis of the Upwind model (BW: backward whirl; FW: forward whirl).
Elem.ModeFreq. (Hz)Abbrev.
RotorIn plane 1st3.68MR1ip
In plane 1st FW1.31MR1ipfw
In plane 1st BW0.89MR1ipbw
In plane 2st7.85MR2ip
In plane 2nd FW4.30MR2ipfw
In plane 2nd BW3.88MR2ipbw
Out of Plane 1st FW0.93MR1opfw
Out of Plane 1st0.73MR1op
Out of Plane 1st BW0.52MR1opbw
Out of Plane 2nd FW2.20MR2opfw
Out of Plane 2nd2.00MR2op
Out of Plane 2st BW1.80MR2opbw
Drive TrainDrive Train1.66MDT
Tower1st tower side-to-side0.28MT1ss
1st tower fore-aft0.28MT1fa
2nd tower side-to-side2.85MT2ss
2nd tower fore-aft3.05MT2fa
Non-str.1P0.21P
3P0.63P

3. Baseline Classical Control Strategy (C1)

The wind turbine control strategy is defined by a curve (see Figure 2) which relates the generator torque and the generator speed [12]. Three control zones are distinguished in this curve: below rated zone, transition zone and above rated zone. In the below rated zone the control objective is to maintain the power coefficient (Cp) in the optimum value. In the Upwind baseline controller, this is done by means of a generator torque control depending on the generator speed measurement (2). The generator torque Tbr is proportional to the square of the generator speed by a constant Kopt.
Energies 05 00938 i002
The aim in the transition zone is the control of generator speed by varying the generator torque. In the Upwind model, this can be done with a torque proportional-integral PI (3) controller [13] or with an open loop torque control which produces a ramp [14] to relate the generator torque and the generator speed. In the C1 control strategy, the PI values in the transition zone (wind speed of 11 m/s) used in the Upwind baseline controller are Kpt and Kit (3), where u(s) is the generator torque control signal and e(s) is the generator speed error:
Energies 05 00938 i003
Figure 2. Curve of power production control zones for the Upwind wind turbine.
Figure 2. Curve of power production control zones for the Upwind wind turbine.
Energies 05 00938 g002
In the above rated zone, the goal is the generator speed control at the nominal value of 1173 rpm varying the collective pitch angle in the blades to maintain the electric power at the value of 5 MW. To do this, a gain-scheduled (GS) PI controller [15] is used. In this case, the controller input u(s) is the generator speed error, and the controller output βcol(s) is the collective pitch angle control signal. The linear plants used to tune the gain-scheduled PI controller are the plants which relate pitch angle and generator speed. These plants have different gains, so gain-scheduling is used to guarantee the stability of the closed loop system in spite of the gain differences. To develop the gain-scheduling, two PI controllers (4) in two operational points, winds of 13 m/s and 21 m/s, are tuned:
Energies 05 00938 i004
In the other operational points, the PI parameters are extrapolated by a first order approximation. A similar gain-scheduling strategy is proposed in [14]. Instead of using the wind speed signal from the anemometer, this PI is scheduled by the collective pitch angle in the blades. The corresponding steady-state collective pitch angle is 6.42° for the operational point with a wind speed of 13 m/s, and the corresponding steady-state collective pitch angle value is 18.53° for the operational point with a wind speed of 21 m/s. Finally, some series notch filters are useful to improve the PI controller response [16]. Some design criteria are established to tune these controllers in these operational points:
  • Output sensitivity peak: 6 dB approximately.
  • Open loop phase margin between 30 and 60 degrees.
  • Open loop gain margin between 6 and 12 dB.
  • To maintain constant the PI zero frequency.
The drive train damping filter (DTD) is included. The aim of the DTD is to reduce the wind effect on the drive train mode [15,17]. The DTD for the Upwind model (5) consists of one gain, with one differentiator, one real zero and a pair of complex poles:
Energies 05 00938 i005
The input of the filter is the generator speed wg and the output is a contribution TDTD to the generator torque set-point signal. Finally, the tower fore-aft damping filter (TD) is designed to reduce the wind effect on the tower first fore-aft mode in the above rated power production zone [15,17]. For the Upwind baseline controller, the filter (6) consists of a gain with one integrator, a pair of complex poles and a pair of complex zeros:
Energies 05 00938 i006
The input of the filter is the fore-aft acceleration measured in the tower top aTfa and the output is a pitch contribution βfa to the collective pitch angle. In conclusion, the baseline control strategy is defined in Figure 3. Other strategies to reduce the loads on the wind turbine can be developed, but they are not included in the considered baseline controller.
Figure 3. Baseline C1 control strategy.
Figure 3. Baseline C1 control strategy.
Energies 05 00938 g003

4. Objectives for Designing the New Proposed Control Strategy

The control objectives for the developed wind turbine control strategy working in the above rated power production zone are as follows:
  • Generator speed control (increase of the output sensitivity bandwidth and reduction of the peak in comparison with the baseline controller).
  • To mitigate the load on the drive train reducing the wind effect on the drive train mode.
  • To mitigate the load on the tower reducing the wind effect on the tower first modes (side-to-side and fore-aft).
  • To improve the load mitigation in comparison to a baseline controller based on the classical baseline control strategy.
To achieve these control objectives, a generator speed sensor and an accelerometer on the tower top are used [18].

5. New Proposed Control Strategy Based on H Norm Reduction (C2)

5.1. Design of Control Strategy Based on H Norm Reduction

This strategy consists of two robust, multivariable and multi-objective controllers based on the H norm reduction (see Figure 4). The generator torque controller and the pitch controller are designed separately [19]. The torque controller has two inputs (generator speed wg and tower top side-to-side acceleration aTss) and one output (generator torque control signal TH∞). On the other hand, the pitch controller has two inputs (generator speed wg and tower top fore-aft acceleration aTfa) and one output (collective pith control signal βH∞). The collective pitch angle set-point value is the pitch control signal βH. However, the generator torque set-point value is the addition of the generator torque control signal TH∞ and the generator torque nominal value in the above rated zone.
Figure 4. C2 control strategy based on the H norm reduction.
Figure 4. C2 control strategy based on the H norm reduction.
Energies 05 00938 g004
The control design method can be divided into the following steps:
  • To extract the wind turbine linear models from the GH Bladed non-linear model. The wind turbine used for this design is the 5 MW Upwind model.
  • To analyze the linear models in Simulink extracting the Campbell Diagram.
  • To design the torque H controller in MATLAB.
  • To design the pitch H controller in MATLAB taking into account the previous designed H torque controller.
  • To analyze the controller robustness in MATLAB.
  • To test the controllers in Simulink.
  • To include the controllers in the GH Bladed External Controller.
  • To simulate the GH Bladed non-linear model using the designed two MISO H controllers.
  • To compare the time domain and frequency domain results to the baseline classical controller.
  • To analyze the fatigue loads and extreme loads reduction of the proposed control strategy compared to the baseline control strategy.

5.2. Generator Torque Controller (H Torque Controller)

The designed generator torque controller based on the H norm reduction solves two of the control objectives proposed in Section 4:
  • To reduce the wind effect on the drive train mode MDT.
  • To reduce the wind effect on the tower side-to-side mode MT1ss.
To design the controller, a mixed sensitivity problem (7) will be solved. The nominal plant G(s) is selected at the operational point of 19 m/s wind speed and has one input T (generator torque), two outputs wg and aTss and 55 states (see Figure 5). G11(s) is the plant with a generator torque input and a generator speed output, while G12(s) is the plant with a generator torque input and a tower top side-to-side acceleration output. p1 and p2 are the disturbance outputs of the plant, u is the control signal, y1 and y2 are the controller inputs, and Zp11, Zp12, Zp2, Zp31 and Zp32 are the performance outputs. The augmented plant (see Figure 6) of this mixed sensitivity problem is scaled using the constants Du, De1, De2, Dp1 and Dp2 (8).
Figure 5. Family of plants for the H torque controller design.
Figure 5. Family of plants for the H torque controller design.
Energies 05 00938 g005
Figure 6. Augmented plant for the MISO Mixed-Sensitivity Problem.
Figure 6. Augmented plant for the MISO Mixed-Sensitivity Problem.
Energies 05 00938 g006
Energies 05 00938 i007
The uncertainties of the family of plants are not considered in this mixed sensitivity problem due to the fact that the drive train and tower modes frequencies do not considerably vary in the above rated zone. The weight functions (9) W31 and W32 are not used, so their values are 1 in order not to consider them in the MATLAB Robust Toolbox [20]. W11 is an inverted notch filter centred on the MDT frequency and W12 is another inverted notch filter centred on the MT1ss frequency. W2 is an inverted low-pass filter used to reduce the controller activity in high frequencies (see Figure 7):
Energies 05 00938 i008
Energies 05 00938 i009
Figure 7. Weight functions for H torque controller design.
Figure 7. Weight functions for H torque controller design.
Energies 05 00938 g007
After doing the controller synthesis, the obtained controller (see Figure 8) has to be re-scaled to adapt the inputs and the outputs to the real non-scaled plant. The obtained controller order is 39 but, finally, the controller order is reduced to order 25 and discretized using a sample time of 0.01 s. The discretized controller is represented by the state space matrices ATD, BTD, CTD and DTD (10):
Energies 05 00938 i010
Figure 8. H Torque Controller.
Figure 8. H Torque Controller.
Energies 05 00938 g008

5.3. Collective Pitch Angle Controller (H Pitch Controller)

The collective pitch H MISO controller solves the other control objectives:
  • Generator speed control increasing the closed loop disturbance attenuation bandwidth.
  • Reduction of the wind effect on the tower fore-aft mode.
  • Inclusion of notch filters at particular frequencies in the controller dynamics to mitigate other excited frequencies (see Table 2) in the nominal plant.
Table 2. Frequency of notch filters in the H Pitch Controller.
Table 2. Frequency of notch filters in the H Pitch Controller.
ModeFreq. (Hz)
1P0.20
3P0.60
MT2ss2.86
MR1ip3.69
MR2ip7.36
Another mixed sensitivity problem is proposed to develop this controller. In this case, the nominal plant GI(s) is selected for the operational point of 19 m/s wind speed (see Figure 9), it has one input β (collective pitch angle), two outputs wg and aTfa and considers the coupling caused by the inclusion of the H MISO torque controller designed in the previous section. G11(s) is the plant with a collective pitch input and a generator speed output and G12(s) is the plant with a collective pitch input and the tower top fore-aft acceleration output. This control scenario has new scaled constants (11) and the family of plants is considered as an additive uncertainty model due to the variations of the linear plants according to the operational point in the above rated zone:
Energies 05 00938 i011
Figure 9. Family of plants for the H pitch controller design.
Figure 9. Family of plants for the H pitch controller design.
Energies 05 00938 g009
Regarding the weight functions (12) in this mixed sensitivity problem, the W11 is an inverted high-pass filter which determines the desired profile of the output sensitivity function. W12 is an inverted notch filter centred on the MT1fa and W2 is an inverted low-pass filter used to reduce the controller activity in high frequencies, including some inverted notch filters centred on excited frequencies (see Table 2) to include notch filters in the pitch controller dynamics (see Figure 10).
Energies 05 00938 i012
Figure 10. Weight functions for the H pitch controller design.
Figure 10. Weight functions for the H pitch controller design.
Energies 05 00938 g010
The gains of the upper uncertainty model IncUpp are bounded by W2 weight functions (see Figure 8) to guarantee the robust controller design. After re-scaling the obtained controller (see Figure 11), whose order is 45, it is reduced to order of 24 and discretized using a sample time of 0.01 s. The discretized controller is represented by the state space matrices ABD, BBD, CBD and DBD (13):
Energies 05 00938 i013
Figure 11. H Pitch Controller.
Figure 11. H Pitch Controller.
Energies 05 00938 g011
Figure 12. Effect of the pitch controller notch filter in open loop.
Figure 12. Effect of the pitch controller notch filter in open loop.
Energies 05 00938 g012

5.4. Analysis of the H Control Strategy

Gain variations in the generator speed control are only considered in the controller robust analysis due to the fact that the tower and drive train modes for the Upwind model have constant frequencies in the above rated zone. The controller robustness is guaranteed because the gains of the upper uncertainty model IncUpp are bounded by the inverse of the control sensitivity function Su [21] (see Figure 10). To compare the response of the designed controllers to the baseline controller, the two control strategies in the above rated zone are considered:
  • C1: Baseline control strategy with drive train damping filter and tower fore-aft damping filter activated (see Figure 3).
  • C2: Proposed control strategy with two H MISO controllers.
Using the C2 control strategy, the generator speed output disturbance attenuation bandwidth DABW in the different operational points is higher than using the baseline control strategy (see Table 3) and the generator speed output disturbance attenuation peak DAP is lower near the designed wind speed nominal operational point of 19 m/s. For the nominal plant, for which the controller is designed, the generator speed output sensitivity function (see Figure 13) shows the peak and the bandwidth to control the generator speed output for a generator speed output disturbance. This sensitivity function clearly shows the increase in the bandwidth achieved with the H C2 control strategy. These improvements are of interest in order to reduce extreme loads, as will be shown in section 6.The reduction of the wind effect on the MDT drive train mode is critical for the control strategy design, so it has been designed first. This mode reduction appears in the wind effect on different parts of the wind turbine due to the hard coupling of this mode in the system. For example, Figure 12 shows the MDT mitigation in the plant which relates the generator speed frequency response for a pitch angle input. Figure 14 shows the frequency response of the tower side-side acceleration for a wind input where the drive train mode is mitigated clearly with the C1 and C2 control strategies compared to the plant without the control system.
Table 3. Comparison of generator speed disturbance attenuation.
Table 3. Comparison of generator speed disturbance attenuation.
OP (m/s)C1C2
DABW (Hz)DAP (dB)DABW (Hz)DAP (dB)
130.0376.060.0353.35
150.0456.060.0443.59
170.0526.090.0574.31
190.0586.310.0705.29
210.0616.000.0785.78
230.0656.050.0896.70
250.0696.040.107.84
Figure 13. Generator speed output sensitivity function.
Figure 13. Generator speed output sensitivity function.
Energies 05 00938 g013
To analyze the reduction of the fore-aft and side-to-side tower accelerations due to the mitigation of the wind effect on these modes using the H control strategy, the closed loop response has to be analyzed in time and frequency domains for the two control strategies. The frequency response of the tower top side-to-side acceleration for a wind input (see Figure 14) is mitigated at the MT1ss frequency using the C2 control strategy, but this mode is not reduced when the C1 strategy is used because it was not designed for that. This gain reduction at this frequency involves an amplitude reduction of the tower side-to-side acceleration in time domain (see Figure 14). The frequency response of the tower top fore-aft acceleration for a wind input (see Figure 15) is mitigated at the MT1fa frequency using the C1 and C2 control strategies. This mode is not very excited in the Upwind model, but this mitigation could be more useful in other wind turbine models. This gain reduction at the peak of the MT1fa mode involves an amplitude reduction of the tower fore-aft acceleration in time domain. The gain mitigation on the MT1fa and MT1ss frequencies is important to reduce the momentums in the tower y and x axis respectively, and the momentum reductions mean load mitigations on the tower.
Figure 14. Tower top side-to-side acceleration response for a wind input (a) Frequency response; (b) Time domain wind step response.
Figure 14. Tower top side-to-side acceleration response for a wind input (a) Frequency response; (b) Time domain wind step response.
Energies 05 00938 g014
Figure 15. Tower top fore-aft acceleration response for a wind input (a) Frequency response; (b) Time domain wind step response.
Figure 15. Tower top fore-aft acceleration response for a wind input (a) Frequency response; (b) Time domain wind step response.
Energies 05 00938 g015
Finally, the notch filters included in the pitch controller dynamics are used to mitigate other excited frequencies which appear in the plant which relates the pitch angle with the generator speed. In this plant (see Figure 12), for the operational point of wind 19 m/s, the structural modes MT2ss, MR1ip, MR2ip are excited and they are mitigated using the H C2 control strategy. The effect of the notch filters at the frequencies 1P and 3P (blade passing frequencies) are only observed in the frequency analysis of the time domain simulations, because the excitations in these frequencies are not expressed in the linear plants extracted from GH Bladed.

6. Results in GH Bladed

6.1. External Controller in GH Bladed

The two H MISO controllers are included in the External Controller in GH Bladed to do time domain simulations using the Upwind wind turbine non-linear model. The External Controller [22] is the name of the programmed code to control the wind turbine non-linear model in GH Bladed. GH Bladed calls to the External dynamic library .dll with the frequency determined by the sample time of the control strategy. The C1 and C2 control strategies are included in the External Controller to carry out the control strategies in the above rated power production zone. However, the control strategy in the below rated and transition zones is the same as the baseline control strategy and it is described in section 3. For a more realistic comparison between the results using the C1 control strategy and the results using the C2 control strategy in the above rated zone, the C2 strategy is divided into two cases:
  • C2.1: The accelerometer to measure the tower top side-to-side acceleration is disabled. This is done to compare C1 and C2 control strategies without tower side-to-side damping.
  • C2.2: The tower top side-to-side accelerometer is activated and C2 control strategy works without sensor signals restrictions (see Figure 4).
In the control strategy based on the H MISO discretized controllers, the control signals are calculated for each sample time (0.01 s) using the present vector of states expressed in the state-representation of the controller dynamics. The sample time has been selected after consulting wind turbine manufacturer references. The strategy to calculate the controller output is divided into four steps:
  • To initialize the controller state-space matrices A, B, C, and D from a static library and initialize the actual state vector X(k).
  • To update the present vector of controller inputs e(k) reading the wind turbine measurements from the sensors.
  • To calculate the vector of present controller outputs u(k) using matrices C, D and the current vectors of controller inputs e(k) and states X(k).
  • To calculate the vector of the next sample time controller states X(k) using matrices A and B and the actual vectors of controller inputs e(k)and states X(k). In the next sample time this vector of controller states will be the current vector of controller states.
Figure 16. Hub wind speed for a turbulent production wind of 19 m/s.
Figure 16. Hub wind speed for a turbulent production wind of 19 m/s.
Energies 05 00938 g016

6.2. Fatigue Analysis (DLC1.2 in IEC61400-1 Second Edition)

The rain flow counting algorithm [23,24] is used to analyze the load reduction capacity of the designed controllers. A fatigue analysis is carried out using this algorithm to determine the fatigue damage on the wind turbine components. The fatigue damage analysis, called load equivalent analysis, follows these steps:
  • To carry out time domain simulations using the non-linear wind turbine model and the designed controller. Twelve simulations of 600 s have been carried out using odd production winds from mean speeds from 3 m/s to 25 m/s.
  • To subject some signals of loads in time simulations (stationary hub Mx, stationary hub My, tower base Mx, tower base My, blade MFlap and blade MEdge) to the rain flow counting algorithm (one for each measured variable) using the toolbox in MATLAB [25] to carry out this analysis.
  • To obtain the load equivalent Leq (14) for each kind of material and for each simulated wind. The material is defined by the m value. m is the slope of the SN curve of the material, where S is the fatigue strength and N the number of cycles to failure. Ni, the number of cycles, and Li, the cycles amplitudes, are extracted from the rainflow counting and Nrd is the number of points of the time domain simulation. For glass fibre m = 10, for cast modular iron m = 7 and for welded steel m = 3:
    Energies 05 00938 i014
    Figure 17. Generator speed and electrical power with a turbulent production wind of 19 m/s.
    Figure 17. Generator speed and electrical power with a turbulent production wind of 19 m/s.
    Energies 05 00938 g017
  • The twelve simulations must be taken into account to calculate the total load equivalent for each material. The load equivalent referring to the Weibull distribution weqm (15) is calculated for each wind and each material. The total load equivalent for one material Leqw (16) referring to the Weibull distribution is calculated with the summation of the weqm. wc is a parameter of the Weibull distribution, slife is the standard life of wind turbines (20 years) and tsim is the simulated time of the considered variable in this load equivalent analysis:
    Energies 05 00938 i015
    Energies 05 00938 i016
  • To compare the wind turbine life variations complife (17) between two compared load equivalent analysis. Leqw1 is the total load equivalent value for twelve simulations and Leqw2 is the other total load equivalent value for the other twelve simulations:
    Energies 05 00938 i017
In Figure 17 the controlled signals (generator speed and electric power) are compared for a turbulent production wind of 19 m/s (see Figure 16) using the C1, C2.1 and C2.2 control strategies. The generator speed is controlled for the nominal value 1173 rpm and the electrical power around 5 MW. The power spectral density (PSD) performs a frequency analysis of time domain simulations. In Figure 18 the control signals (collective pitch angle and generator torque) are compared. The time domain simulation shows the quick response of the pitch angle using the C2.1 and C2.2 strategies and the torque contribution signal of the C2.2 control strategy to mitigate the side-to-side displacement on the tower. Figure 19 shows the reduction of the wind effect on the tower fore-aft mode in the tower base momentum My and the reduction of the wind effect on the tower side-to-side mode and drive train mode in tower base momentum Mx.
Figure 18. Generator torque and pitch angle with a turbulent production wind of 19 m/s.
Figure 18. Generator torque and pitch angle with a turbulent production wind of 19 m/s.
Energies 05 00938 g018
Finally, the fatigue damage analysis of the components of the wind turbine is carried out as a result of the load equivalent analysis. Table 4 shows the load reduction percentage of the control strategies on the different components of the Upwind model. C1 is the reference strategy to compare the load reduction achieved with C2.1 and C2.2 control strategies. Results are calculated for three material constants, m, which are commonly used by the commercial companies of wind turbines. If m = 3 using the two H MISO controllers, the load reduction is 0.4% on the Stationary Hub Mx momentum using the C2.2 control strategy and 4.8% using the C2.1 strategy, 13.4% on the Tower Base Mx momentum with the C2.2 and 2.6% using the C2.1, and 4.7% on the Tower Base My momentum respect to the C1 baseline controller using the C2.2 and 5.2% with the C2.1. If m = 9, the load reduction is 3.1% on the Stationary Hub Mx momentum, 19.6% on the Tower Base Mx momentum and 8.8% on the Tower Base My momentum using the C2.2 control strategy. On the other hand, if m = 9 using the C2.1 control strategy, the load reduction is 4.2% on the Stationary Hub Mx momentum, −0.1% on the Tower Base Mx momentum and 10.9% on the Tower Base My momentum. If m = 12 using the C2.2 strategy, the load reduction is 2.9% on the Stationary Hub Mx momentum, 19.2% on the Tower Base Mx momentum and 10.6% on the Tower Base My momentum. For this m value using the C2.1 control strategy, the load reduction is 4.0% on the Stationary Hub Mx momentum, −0.2% on the Tower Base Mx momentum and 13.6% on the Tower Base My momentum. Load reduction figures less than 0.4% should not be considered because they can be caused by mathematical calculation precision in the load equivalent algorithm (in blue colour in Table 4).
Figure 19. Loads on tower base with a turbulent production wind of 19 m/s.
Figure 19. Loads on tower base with a turbulent production wind of 19 m/s.
Energies 05 00938 g019
In these simulations there is an excitation of the rotor in-plane 1st FW mode MR1ipfw (1.2 Hz). This excitation is not critical from the point of view of the load reduction in a wind turbine system as is proven in this load equivalent analysis. The cause of this excitation is the bandwidth of the torque controller. The torque controller reduces the wind effect on the drive train mode MDT (1.6 Hz) and tower 1st side-to-side mode MT1ss (0.28 Hz). The torque H MISO controller (see Figure 8) dynamics from tower top side-to-side acceleration to torque set point value introduces a high gain in frequencies between 0.2 Hz and 1.6 Hz which produces the In plane 1st FW mode excitation. To reduce this excitation, a notch filter in the rotor in-plane 1st FW frequency must be included in the weight functions W2 used to design the torque controller.
Table 4. Comparison of the load equivalent analysis.
Table 4. Comparison of the load equivalent analysis.
mC1-C2.1 (%)C1-C2.2 (%)
Stationary Hub Mx34.80.4
94.23.1
124.02.9
Stationary Hub My30.20.2
90.91
121.21.5
Gearbox Torque34.80.4
94.23.1
124.02.9
Tower Base Mx32.613.4
9−0.119.6
12−0.219.2
Tower Base My35.24.7
910.98.8
1213.610.6
Blade1 MFlap30.1−0.2
90.1−0.1
120.1−0.2
Blade1 MEdge300.1
900
1200

6.3. Extreme Load Analysis (DLC1.6 in IEC61400-1 Second Edition)

The extreme load DLC1.6 analysis studies the system response for different kinds of extreme gusts. This analysis is divided into three different steps:
  • To carry out time domain simulations using the non-linear wind turbine model and the C1 and C2 different control strategies. Six simulations of different kinds of gusts have been carried out. The gusts are called Vr-0, Vr-p, Vr-n, Vout-0, Vout-p, Vout-n.
  • To analyze the six simulations and extract the maximum value of the generator speed signal and some momentums (tower base Mx, tower base My, tower base Mxy, hub total bending Myz, blade MFlap and blade MEdge).
  • To compare these maximum values using the C2 control strategy with regard to the baseline C1 control strategy.
Figure 20. Vout-p extreme gust simulation.
Figure 20. Vout-p extreme gust simulation.
Energies 05 00938 g020
Other extreme load cases (as for instance DLC1.5 in IEC61400-1 Second Edition cases) are not taken into account because results depend especially on the stop strategy, which has not been implemented. Moreover, a safety control strategy is not developed in the supervisory control to stop the wind turbine in generator over-speed cases. This article only shows the response of the developed C1 and C2 control strategies in the above rated zone without taking into account any safety control strategy.
The results of the extreme load DLC1.6 analysis are summarized in Table 5. The C2.1 and C2.2 control strategies, based on the H norm reduction, give better results than the baseline control strategy C1. Using C2.2, the reduction of the generator speed maximum value, compared to the C1 strategy, is 7.8%, the tower base Mx momentum is reduced by 7.8% and the blade MEdge momentum is reduced by 26.3%. The tower base My momentum, tower base Mxy momentum and hub total bending Myz momentum are reduced by around 1.5% when using the C2.2 control strategy. Using C2.1, the reduction of the generator speed maximum value is 7.8%, the tower base Mx momentum is not reduced and the blade MEdge momentum is reduced by 25.9%. However, the tower base My momentum, tower base Mxy momentum and hub total bending Myz momentum are not considerably reduced using the C2.1 control strategy. The blade MEdge momentum is considerably reduced due to the increase in the generator speed output disturbance bandwidth and the reduction in the peak of this sensitivity function. In Figure 20, the results of the simulation in GH Bladed using an input of wind of a Vout-p gust and using the C1 control strategy are compared to the same wind input using the C2 control strategy without including any safety system to avoid generator over-speeds. The higher bandwidth of the generator speed output sensitivity function obtained with the C2 control strategy means a quick response of the collective pitch angle signal and the consistent reduction of the generator speed maximum value. Furthermore, the mitigation of the variations of the generator speed using the H controllers is the main reason for the mitigation of the extreme load on the blade MEdge momentum. The most useful advantage of this reduction of extreme loads using the H control strategy is to avoid the activation of special safety strategies to stop the wind turbine. Usually, these special safety strategies are activated when the generator speed is higher than a critical value and involves losses of the electric power and critical momentary increases of loads in the wind turbine.
Table 5. Comparison of the extreme load analysis.
Table 5. Comparison of the extreme load analysis.
C1C2.1C1-C2.1 (%)C2.2C1-C2.2 (%)
Generator Speed1589 rpm1464 rpm7.861465 rpm7.8
Tower Base Mx29278 KNm29285 KNm0.0226983 KNm7.8
Tower Base My158258 KNm155500 KNm1.74155473 KNm1.7
Tower Base Mxy158311 KNm155500 KNm1.77155555 KNm1.7
Hub total bending Myz12991 KNm12780 KNm1.6212817 KNm1.3
Blade MFlap18341 KNm18400 KNm−0.3218355 KNm−0.07
Blade MEdge9946 KNm7366 KNm25.947327 KNm26.3

7. Conclusions

The work carried out and presented in this article can be summarized as follows:
  • The offshore Upwind 5 MW wind turbine model is developed using the GH Bladed 4.0 software package.
  • A classical control strategy for wind turbines is defined and it is considered the baseline controller for comparing with the new developed control strategies.
  • New design process of a control strategy based on H controllers is defined and validated in GH Bladed. The new strategies are applied in above rated power production zone in wind turbines. The results obtained in the closed loop simulations using GH Bladed 4.0 software package show the fatigue load reduction on the desired components (tower and drive train) compared to the classical baseline control strategy (see Figure 21). Using the designed H controllers, the extreme load reduction in case DLC1.6 does not appear only in the tower, but also in the three blades. Results obtained using H controllers have these outstanding benefits from the load reduction point of view due to some interesting properties:
Figure 21. Review of load mitigation (a) Equivalent load analysis m = 3; (b) Equivalent load analysis m = 9; (c) Equivalent load analysis m = 12; (d) Extreme load analysis.
Figure 21. Review of load mitigation (a) Equivalent load analysis m = 3; (b) Equivalent load analysis m = 9; (c) Equivalent load analysis m = 12; (d) Extreme load analysis.
Energies 05 00938 g021
  • The attenuation of the generator speed output disturbance bandwidth is higher than that obtained using the classical control strategy.
  • The attenuation of the generator speed output disturbance peak is higher than that obtained using the classical control strategy.
  • The proposed control strategy based on the H norm reduction takes into account the coupling between variables in the wind turbine system. The designed controller is multivariable and multi-objective.
  • The controller robustness is guaranteed due to the small gain theorem properties applied to the H controller synthesis.
  • Some notch filters can be included in the controller dynamics using a correct definition of the mixed sensitivity problem. This is very useful for reducing excited modes on non-desired frequencies.

Acknowledgements

The work described in this paper has been supported in part by the Basque Country Government (Spain) and the Regional Council of Aquitaine (France), in the frame of Cooperation Commons Funds Euskadi-Aquitaine (Project Bladed).

References

  1. Caselitz, P.; Geyler, M.; Giebhardt, J.; Panahandeh, B. Hardware-in-the-Loop development and testing of new pitch control algorithms. In Proceeding of European Wind Energy Conference and Exhibition (EWEC), Brussels, Belgium, March 2011; pp. 14–17.
  2. Johnson, K.E.; Pao, L.Y.; Balas, M.J.; Kulkarni, V.; Fingersh, L.J. Stability analysis of an adaptive torque controller for variable speed wind turbines. In Proceeding of IEEE Conference on Decision and Control, Atlantis, Bahamas, December 2004; pp. 14–17.
  3. Nourdine, S.; Díaz de Corcuera, A.; Camblong, H.; Landaluze, J.; Vechiu, I.; Tapia, G. Control of wind turbines for frequency regulation and fatigue loads reduction. In Proceeding of 6th Dubrovnik Conference on Sustainable Development of Energy, Water and Environment Systems, Dubrovnik, Croatia, September 2011; pp. 25–29.
  4. Wright, A.D. Modern Control Design for Flexible Wind Turbines; Technical Report for NREL; NREL/TP-500-35816; Colorado, CO, USA, July 2004. [Google Scholar]
  5. Wright, A.D.; Fingersh, L.J.; Balas, M.J. Testing state-space controls for the controls advanced research turbine. In Proceeding of 44th AIAA Aerospace Sciences Meeting and Exhibit, Reno, NV, USA, January 2006; pp. 9–12.
  6. Sanz, M.G.; Torres, M. Aerogenerador síncrono multipolar de velocidad variable y 1.5 MW de potencia: TWT1500. Rev. Iberoamer. Autom. Informát. 2004, 1, 53–64. [Google Scholar]
  7. Bianchi, F.D.; Battista, H.D.; Mantz, R.J. Wind turbine control systems. In Principles, Modelling and Gain Scheduling Design; Springer-Verlag: London, UK, 2007. [Google Scholar]
  8. Geyler, M.; Caselitz, P. Robust multivariable pitch control design for load reduction on large wind turbines. J. Sol. Energy Eng. 2008, 130, 12. [Google Scholar] [CrossRef]
  9. Fleming, P.A.; van Wingerden, J.W.; Wright, A.D. Comparing state-space multivariable controls to multi-siso controls for load reduction of drivetrain-coupled modes on wind turbines through field-testing; NREL/CP-5000-53500; NREL: Colorado, CO, USA, 2011. [Google Scholar]
  10. Jonkman, J.; Butterfield, S.; Musial, W.; Scott, G. Definition of a 5 MW Reference Wind Turbine for Offshore System Development; NREL/TP-500-38060; Technical Report for NREL: Colorado, CO, USA, February 3806. [Google Scholar]
  11. Upwind Home page. Available online: http://www.upwind.eu (accessed on 12 December 2011).
  12. Bossanyi, E.A. The design of closed loop controllers for wind turbines. Wind Energy 2000, 3, 149–163. [Google Scholar] [CrossRef]
  13. Bossanyi, E.A. Controller for 5 MW reference turbine. European Upwind Project Report; Garrad Hassan & Partners Ltd.: Bristol, UK, 2009. Available online: http://www.upwind.eu (accessed on 12 December 2011).
  14. Wright, A.D.; Fingersh, L.J. Advanced Control Design for Wind Turbines Part I: Control Design, Implementation, and Initial Tests; NREL/TP-500-42437; NREL: Colorado, CO, USA, 2008. [Google Scholar]
  15. Bossanyi, E.A. Wind turbine control for load reduction. Wind Energy 2003, 6, 229–244. [Google Scholar] [CrossRef]
  16. Van der Hooft, E.L.; Schaak, P.; van Engelen, T.G. Wind Turbine Control Algorithms; DOWEC-F1W1-EH-03094/0; Technical Report for ECN: Petten, The Netherlands, 2003. [Google Scholar]
  17. Wright, A.D.; Balas, M.J. Design of controls to attenuate loads in the controls advanced research turbine. J. Sol. Energy Eng. 2004, 126, 1083. [Google Scholar] [CrossRef]
  18. Hau, M. Promising Load Estimation Methodologies for Wind Turbine Components. Technical Report for European Upwind Project. ISET: Kassel, Germany, 2009. Available online: http: //www.upwind.eu (accessed on 12 December 2012).
  19. Bossanyi, E.A.; Ramtharan, G.; Savini, B. The importance of control in wind turbines design and loading. In Proceedings of the 17th Mediterranean Conference on Control & Automation, Thessaloniki, Greece, June 2009; pp. 24–26.
  20. Balas, G.; Chiang, R.; Packard, A.; Safonov, M. MATLAB robust control toolbox. In Getting Started Guide; The MathWorks, Inc.: Natick, MA, USA, 2009. [Google Scholar]
  21. Doyle, J.C.; Francis, B.A.; Tannenbaum, A.R. Feedback Control Theory; MacMillan: Toronto, Canada, 1992. [Google Scholar]
  22. Bossanyi, E.A. Bladed User Manual; Garrad Hassan & Partners Ltd.: Bristol, UK, 2009. [Google Scholar]
  23. Frandsen, S.T. Turbulence and Turbulence Generated Structural Loading in Wind Turbine Clusters. Ph.D. Thesis, Technical University of Denmark, Roskilde, Denmark, 2007. [Google Scholar]
  24. Söker, H.; Kaufeld, N. Introducing low cycle fatigue in IEC standard range pair spectra. In Proceeding of 7th German Wind Energy Conference, Wilhelmshaven, Germany, October 2004; pp. 20–21.
  25. MATLAB Rainflow Counting Algorithm Toolbox. Available online: http://www.mathworks.com/MATLABcentral/fileexchange/3026 (accessed on 12 December 2011).

Share and Cite

MDPI and ACS Style

De Corcuera, A.D.; Pujana-Arrese, A.; Ezquerra, J.M.; Segurola, E.; Landaluze, J. H Based Control for Load Mitigation in Wind Turbines. Energies 2012, 5, 938-967. https://doi.org/10.3390/en5040938

AMA Style

De Corcuera AD, Pujana-Arrese A, Ezquerra JM, Segurola E, Landaluze J. H Based Control for Load Mitigation in Wind Turbines. Energies. 2012; 5(4):938-967. https://doi.org/10.3390/en5040938

Chicago/Turabian Style

De Corcuera, Asier Diaz, Aron Pujana-Arrese, Jose M. Ezquerra, Edurne Segurola, and Joseba Landaluze. 2012. "H Based Control for Load Mitigation in Wind Turbines" Energies 5, no. 4: 938-967. https://doi.org/10.3390/en5040938

Article Metrics

Back to TopTop