1. Introduction
Power transformer protection relays in a power system must be able to differentiate internal faults from all other operating conditions, and current differential relays have been widely used for transformer protection. The relays, however, are prone to malfunctioning during magnetic inrush or over-excitation conditions because the magnetizing current becomes significant, but cannot be measured. To prevent malfunctions, the relays adopt restraining or blocking signals that are derived from the current, the voltage, or the flux [
1].
Restraining or blocking signals for a three-winding transformer are determined in a very similar manner to those of a two-winding transformer, except for the number of the signals. A differential relay used the one vector difference as a restraint quantity and the vector sum as the differential operating quantity [
2].
The transformer differential relays with harmonic based restraining or blocking signal [
3,
4,
5,
6] ensure stability during magnetizing inrush and over-excitation, but may reduce the sensitivity for internal faults. In addition, the method causes an operating time delay of a relay because of the restraining or blocking signal.
Transformer protection techniques that rely on the electro-magnetic differential equations of the transformer were suggested [
7,
8,
9]. Since these techniques do not require additional restraining or blocking signals, the operating time of the relays is faster than that of the conventional differential relay with harmonic-based restraining or blocking signals. The delta winding currents, which are practically unavailable, were used in [
7], whilst the line currents of the delta side were used in [
8,
9]. However, these techniques cannot be used directly for fault type classification.
Recently, modern numerical protection technologies for power transformers have been proposed using wavelet transforms [
10,
11], neural networks [
12,
13], Park’s components [
14,
15], and gradient vector of the differential current [
16]. Wavelet-based algorithms were proven to achieve good accuracy [
10,
11]. However, it is crucial to choose the appropriate wavelet for satisfactory analysis and long data windows are required. Moreover, they are susceptible to noises and unpredicted disturbances. Neural networks [
12,
13] were proved as an efficient tool for classification and identification of the events. However, a huge computational burden is inevitable for training or comparing signals.
A restraining signal was obtained using Park’s transform [
14,
15], whilst the slope of the differential current in each phase was used for differential protection [
16]. These techniques successfully differentiate magnetic inrush from internal faults, particularly in the case of simultaneous inrush and internal faults, but difficulties arise in identifying the faulted phase and winding.
Fault classification methods of a power transformer were proposed [
17,
18]. Pseudo-inversion of the linear relationship between faults and protection response, norm in the Banach space, and Bayes probability calculation are used [
17]. The discrete wavelet transform in combination with back propagation neural networks was used to classify internal fault types of a three-phase transformer [
18]. However, difficulties will arise in identifying the faulted phase and winding of a three-winding transformer with delta-connected windings.
This paper proposes an algorithm for fault detection and faulted phase and winding identification of a three-winding power transformer based on the induced voltages in a power system. This paper extends the method in [
9] to a three-winding transformer and suggests a rule for fault detection and fault type identification. The ratio of the induced voltages of the primary-secondary, primary-tertiary and secondary-tertiary windings is the same as the corresponding turns ratio during normal operating conditions, magnetic inrush, and over-excitation. It differs from the turns ratio during an internal winding fault. For a single phase or a three-phase transformer with wye-connected windings, induced voltages of each pair of windings are estimated. On the other hand, for a three-phase transformer with delta-connected windings, the induced voltage differences are estimated to use the line currents, which are practically available. Nine detectors and a rule are suggested for fault detection for faulted phase and winding identification. The performance of the proposed algorithm was investigated with Electromagnetic Transients Program (EMTP)-generated data under various internal fault conditions and normal operating conditions including magnetic inrush and over-excitation. The paper concludes by implementing the algorithm in a prototype relay based on a digital signal processor.
3. Case Studies
Figure 5 shows a single line diagram of the simulated system. The three-winding Y-Y-Δ transformer (345kV/154kV/23kV, 500 MVA) is modeled using EMTP and the sampling rate is 32 samples/cycle. The modeling techniques described in [
19] are used to represent turn-to-ground and turn-to-turn winding faults.
The hysteresis characteristics of the core are modeled using a type-96 element; the saturation point of (100 A, 822 Vs) is selected using HYSDAT, a subroutine of EMTP. Butterworth 2nd order filters with a stop-band cut-off frequency of 960 Hz (sampling frequency/2) are used as anti-aliasing filters.
Figure 5.
Single line diagram of the simulated system.
Figure 5.
Single line diagram of the simulated system.
Equations (8–13) and (19–24) contain derivative terms, which can be approximated numerically. Among the approximation methods using two successive sample points, the trapezoidal rule causes errors smaller than the backward Euler method. However, it causes numerical oscillation. In this paper, the differentiation terms are approximated by the trapezoidal rule, expressed in the form of Equation (37). Numerical oscillations are damped by the use of a parallel damping resistance,
RP, as shown in
Figure 6 [
20]:
RP is calculated using Equation (38), as suggested by Alvarado [
20]:
Figure 6.
Inductance model for the parallel damping.
Figure 6.
Inductance model for the parallel damping.
The performance of the proposed algorithm is verified under various operating conditions such as magnetic inrush, internal winding faults, over-excitation and different core characteristics. For convenience, six Detectors for detecting an internal fault are shown in the case studies.
3.1. Magnetic Inrush
The magnitude of the inrush current depends on the energisation angle, the remanent flux in the core, and the load current. Thus, inrush data is generated by varying the above three parameters in accordance with
Table 3.
Table 3.
Conditions of magnetic inrush data Generation.
Table 3.
Conditions of magnetic inrush data Generation.
Energisation angle (°) | 0, 90 |
Remanent flux (%) | 0, 30, 50, 80 |
Load | No load, full load |
Case 1: Energisation angle of 0°, 80% remanent flux, no load;
Figure 7,
Figure 8,
Figure 9 and
Figure 10 show the results for Case 1. An energisation angle of 0
° and 80% remanent flux results in very large inrush currents in the primary windings. The three-phase voltages are severely distorted as shown in
Figure 8. Using the currents and voltages, induced voltages or induced voltage differences are estimated.
Figure 7.
Three-phase primary currents for Case 1.
Figure 7.
Three-phase primary currents for Case 1.
Figure 8.
Three-phase voltages for Case 1 (a) Primary voltages (v1A, v1B, v1C); (b) Secondary voltages (v2A, v2B, v2C); and (c) Tertiary voltages (v3AB, v3BC, v3CA).
Figure 8.
Three-phase voltages for Case 1 (a) Primary voltages (v1A, v1B, v1C); (b) Secondary voltages (v2A, v2B, v2C); and (c) Tertiary voltages (v3AB, v3BC, v3CA).
Figure 9.
Two induced voltages of Voltage 1‒3 and two induced voltage differences of Voltage 4‒6 for Case 1.
Figure 9.
Two induced voltages of Voltage 1‒3 and two induced voltage differences of Voltage 4‒6 for Case 1.
Figure 10.
Detectors and the trip signals for Case 1.
Figure 10.
Detectors and the trip signals for Case 1.
Two estimated induced voltages of Voltages 1‒3 and two estimated induced voltage differences of Voltages 4‒6, which are terms in the numerator of the six detectors, are shown in six subfigures in
Figure 9. For example, Voltages 4 shows
e1C −
e1A and
N1/
N3(
e3CA −
e3AB) of Detector 4, estimated from Equations (22) and (19), respectively. As expected, they are non-sinusoidal and severely distorted. The results clearly indicate that the two estimated terms are nearly the same even though the inrush currents are very large and the voltages are severely distorted.
The operating threshold for the detectors is determined by considering the noise caused by the hardware, the sensitivity of a relay, stability margin of the relay and so on. For the system studied in this paper, the recommended value is 5%. In addition, a security counter is used to prevent mal-function due to transients. If a sample value in the detector exceeds 5%, the counter is increased by 1; if not, it is decreased by 1. In addition, if the counter is less than 0, it is reset to 0. If the counter exceeds 4, the trip signal is activated.
Figure 10 shows the operating response of the six detectors and the two trip signals. The Trip1 and Trip2 signals are issued based on the results of Detectors 1–3 and Detectors 4–6, respectively. As all six remain below 5%, none of the trip signals are activated.
3.2. Internal Winding Faults
The fault data for various faults on the phase ‘A’ of the primary winding were generated and used to test the algorithm. The test results for the two of the fault scenarios are described in Cases 2 and 3:
Case 2: A turn-to-ground fault, located 60% from the neutral winding end and at 0° inception angle;
Case 3: A turn-to-turn fault, located between 20% and 10% and at 0° inception angle;
Figure 11 and
Figure 12 show the operating responses of the six detectors for Cases 2 and 3, respectively. As expected, the two induced voltage differences are not the same and thus Detectors 1, 4 and 5 exceed the 5% operating threshold. The signals in Detectors 2, 3 and 6 remain small, because they are not affected by a fault on phase A. In Case 2, the Trip1 and Trip2 signals are activated 2.6 and 3.1 ms, respectively, after fault occurrence. In Case 3, these delays are increased to 4.2 and 4.7 ms.
Figure 11.
Detectors and the trip signals for Case 2.
Figure 11.
Detectors and the trip signals for Case 2.
Figure 12.
Detectors and the trip signals for Case 3.
Figure 12.
Detectors and the trip signals for Case 3.
3.3. Over-Excitation
Case 4: Overvoltage of 150% applied, full load;
The algorithm was tested during over-excitation of the transformer.
Figure 13 and
Figure 14 show the results for an extreme over-voltage of 150% of the primary rated voltage and a full load condition. The primary currents and voltages are distorted as shown in
Figure 13. However, the algorithm accurately estimates the induced voltage differences and thus the six Detectors remain below the operating threshold and the trip signals are not issued, as shown in
Figure 14.
Figure 13.
Primary voltages and current for Case 4 (a) Primary voltages (v1A, v1B, v1C); and (b) Primary currents (i1A, i1B, i1C).
Figure 13.
Primary voltages and current for Case 4 (a) Primary voltages (v1A, v1B, v1C); and (b) Primary currents (i1A, i1B, i1C).
Figure 14.
Detectors and the trip signals for Case 4.
Figure 14.
Detectors and the trip signals for Case 4.
3.4. Different Core Characteristics
As the algorithm does not require hysteresis data, it can detect internal faults even if the core characteristics are changed. To validate this statement, tests were performed with different core characteristics; i.e., the excitation currents at the saturation points were changed without modifying the flux linkages. The winding resistances and the leakage inductances remain unchanged.
Case 5: Energisation angle of 0°, 80% remanent flux, no load, saturation point of (200 A, 822 Vs);
Figure 15 shows the results for Case 5; this is identical to Case 1 except for the change in the saturation point. The inrush currents are larger than those observed in Case 1 and the voltages are more severely distorted. However, the signals in the detectors remain below the 5% threshold; and the two trip signals are not activated. The results clearly show that the algorithm accurately estimates the induced voltage differences and is not affected by changing the core characteristics.
4. Hardware Implementation Test
Figure 16 shows the configuration of the test system. The algorithm was implemented on the TMS320C6701 digital signal processor. The sampling rate is 32 samples/cycle. The currents and voltages of 18 channels are passed through the 2nd Butterworth filters (
fc = 960 Hz), which are Sallen & Key active filters, to the 16-bit A/D converter.
Figure 17 and
Figure 18 show the results for Case 1. Noise signals in the hardware result in the larger errors than observed in the simulation results. However, the algorithm performs successfully with a threshold of 5% and a security counter of 4.
Figure 19 shows the results for Case 2. The Trip1 and Trip2 signals are activated 2.6 ms and 3.1 ms after fault occurrence. Consequently, all the test results support the conclusion that a prototype monitoring system, based on the algorithm, can successfully discriminate between internal faults and magnetic inrush.
Figure 15.
Detectors and the trip signals for Case 5.
Figure 15.
Detectors and the trip signals for Case 5.
Figure 16.
Configuration of hardware implementation.
Figure 16.
Configuration of hardware implementation.
Figure 17.
Two induced voltages of Voltage 1‒3 and two induced voltage differences of Voltage 4‒6 for Case 1.
Figure 17.
Two induced voltages of Voltage 1‒3 and two induced voltage differences of Voltage 4‒6 for Case 1.
Figure 18.
Detectors and the trip signals for Case 1.
Figure 18.
Detectors and the trip signals for Case 1.
Figure 19.
Detectors and the trip signals for Case 2.
Figure 19.
Detectors and the trip signals for Case 2.
5. Conclusions
This paper proposes an algorithm for fault detection, faulted phase and winding identification of a three-winding transformer based on the induced voltages. Nine detectors and a rule are suggested for fault detection for faulted phase and winding identification. The algorithm accurately estimates the induced voltage differences and uses them to discriminate between internal winding faults and normal operating conditions. In addition, the algorithm can identify the faulted winding and its phase in a simple manner.
The results clearly demonstrate that the proposed algorithm remains stable during magnetic inrush and over-excitation conditions, and is not affected by changing the core characteristics. The algorithm successfully detected a wide range of internal faults in a fraction of a cycle. A prototype monitoring system, based on the described algorithm, successfully discriminates between internal faults and normal operating conditions.
The proposed algorithm can not only detect an internal fault but also identify the faulted phase and winding of a three-winding transformer. In addition, it does not require hysteresis data and the operating time is faster than that of conventional harmonically restrained differential relays because it operates in the time domain.