Next Article in Journal
A Review on Electrospun Nanofiber Composites for an Efficient Electrochemical Sensor Applications
Previous Article in Journal
Strategies for Mitigating Commercial Sensor Chip Variability with Experimental Design Controls
Previous Article in Special Issue
Power Converter Resonant Control for an Unbalanced and Non-Constant Frequency Supply
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Solving the Power Flow Problem in Bipolar DC Asymmetric Distribution Networks Using Broyden’s Method

by
Oscar Danilo Montoya
1,*,
Ángeles Medina-Quesada
2,* and
Walter Gil-González
3
1
Grupo de Compatibilidad e Interferencia Electromagnética (GCEM), Facultad de Ingeniería, Universidad Distrital Francisco José de Caldas, Bogotá 110231, Colombia
2
Department of Electrical Engineering, University of Jaén, Campus Lagunillas s/n, Edificio A3, 23071 Jaén, Spain
3
Department of Electrical Engineering, Universidad Tecnológica de Pereira, Pereira 660003, Colombia
*
Authors to whom correspondence should be addressed.
Sensors 2023, 23(15), 6704; https://doi.org/10.3390/s23156704
Submission received: 26 May 2023 / Revised: 10 July 2023 / Accepted: 24 July 2023 / Published: 26 July 2023

Abstract

:
This research addresses the power flow analysis in bipolar asymmetric direct current (DC) networks by applying Broyden’s numerical method. This general successive approximations method allows for a simple Newton-based recursive formula to reach the roots of multiple nonlinear equations. The main advantage of Broyden’s approach is its simple but efficient structure which can be applied to real complex nonlinear equations.The power flow problem in bipolar DC networks is still challenging, as multiple operating options must be considered, e.g., the possibility of having a solidly grounded or floating neutral wire. The main goal of this research is to contribute with a generalization of Broyden’s method for the power flow solution in bipolar DC networks, with the main advantage that, under well-defined conditions, this is a numerical method equivalent to the matricial backward/forward power flow, which is equivalent to the successive approximations power flow method. Numerical results in the 21-, 33-, and 85-bus grids while considering two connections for the neutral wire (i.e., solidly grounded at any node or floating) show the effectiveness of Broyden’s method in the power flow solution for bipolar asymmetric DC networks. All numerical simulations were carried out in the MATLAB programming environment.

1. Introduction

1.1. General Context

Bipolar DC networks are emerging technologies that aid in providing electricity in medium- and low-voltage networks by using three wires associated with the positive (p), neutral (o), and negative (n) poles [1]. These networks can be considered to be the DC equivalent of the conventional three-phase AC distribution networks given that multiple constant power loads can be connected between their poles. These may be monopolar (connected between the positive or negative pole and the neutral wire) or bipolar (connected between the positive and negative poles) [2,3]. Figure 1 illustrates the typical configuration of a bipolar DC network with multiple constant power terminals [4].
The main characteristics shown in Figure 1 are:
  • The operation of a bipolar DC network can be unbalanced due to the presence of constant monopolar and bipolar power terminals, which implies that no reductions (monopolar equivalents) must be applied [5].
  • Concerning purely monopolar configurations, bipolar DC grids imply an increase of about 34 % in construction investments. However, more than two times the power can be transferred by these grids, including the possible connection of exceptional loads, i.e., bipolar compositions [2].
  • Depending on the operating practices of the distribution company, the neutral wire can be operated in two main ways: floating in all nodes except the substation bus or solidly grounded at any network node [6].

1.2. Motivation

Considering the main characteristics of bipolar DC networks, including their unbalanced operation and the possible connections of the neutral wire, power flow studies for multipolar DC networks with constant power terminals can be modeled as a set of nonlinear equations that must be solved through the application of numerical methods, as their analytical solution is impossible [7]. This research is motivated by applying Broyden’s (also known as the secant) method for finding roots in simultaneous sets of nonlinear equations [8]. The selection of this method is based on its easy formulation and implementation, as well as on its linear convergence, with the main advantage that infinite possible initial matrices A t (with t = 0 ) may be selected for its numerical validation.

1.3. Literature Review

Several authors have focused on studying the steady-state operation of bipolar DC networks with unbalanced conditions while employing power flow analysis.
The authors of [9] proposed a power flow formulation that uses the classical nodal voltage method in order to compute the voltages and power generation of bipolar DC distribution networks while including multiple constant power terminals. Furthermore, this power flow allows considering the neutral wires in grounded or non-grounded modes. These authors only took a small bipolar DC system (three nodes) into account without analyzing the scalability of the proposed method.
The authors of study [10] used a current injection model to solve the power flow in a bipolar DC microgrid. This model was based on the Newton–Raphson power flow, which used the Jacobian matrix as index sensitivity.
The authors of [1] described a generic power flow algorithm for bipolar DC grids that employs the Newton–Raphson method. This method classifies the grid nodes into six types based on their grounding scheme and voltage control mode. This classification identifies the unknown pole voltages which are used as mismatch equations to solve the power flow problem. One of the limitations of this generic power flow algorithm is that it is not possible to establish the non-convergence condition.
The authors of [11] analyzed a power flow method under different operation modes and control strategies in bipolar high-voltage DC (HVDC) grids integrated with voltage source converters (VSCs). The power flow method was based on layers and the admittance matrix of the bipolar grid.
The authors of study [7] proposed a successive approximations method to solve power flow in bipolar DC distribution networks. This method allows considering a grounded or non-grounded neutral wire.
The authors of study [3] demonstrated the exact conditions and necessities for the convergence and uniqueness of the power analysis solution in bipolar DC grids. This study also considered the over-current protection scheme of power electronic converters.
The authors of work [6] tackled the power flow problem in bipolar DC grids with multiple constant power loads by employing a triangular-based power flow formulation. This formulation is suitable for radial setups and considers whether the neutral wire is grounded or not at all system nodes.
The authors of study [7] used a successive approximations technique based on the classical backward/forward method to solve the power flow analysis in bipolar DC grids, including the possibility of grounding or not grounding the neutral wire. Furthermore, the convergence of the proposed approximation was demonstrated using the Banach fixed-point theorem.
The authors of [12] presented a formulation to solve the power flow problem in bipolar DC networks, which used the Taylor expansion in the bus injection equations, generating a hyperbolic formulation that can be implemented in both meshed and radial networks.
Previous studies have shown promising results, but some of them struggle to achieve convergence in their performance. Additionally, some of these studies lack a comprehensive framework to address these limitations. This paper presents a solution to the power flow problem in bipolar DC asymmetric distribution networks using Broyden’s method. This method is a quasi-Newton method that numerically solves systems of nonlinear equations through iterative processes. In addition, it offers several advantages over other approaches [13,14]. For example, this method provides greater versatility, making it applicable to a broader range of problems without requiring additional modifications. Additionally, Broyden’s method has demonstrated good and rapid convergence. Moreover, it is robust, as it can be implemented in cases where other techniques, such as Newton’s method, may encounter difficulties due to ill-conditioned Jacobian matrices.

1.4. Contributions and Scope

Considering the state of the art in numerical methods applied to the solution of the power flow problem in bipolar DC networks with asymmetric loading, the main contributions of this research are the following:
  • The application of Broyden’s method to the power flow problem in bipolar DC grids with the aim to solve the set of Equations f x = 0 by using different A t matrices.
  • The evaluation of the convergence properties of Broyden’s method using random initialization matrices A t with t = 0 , as well as an analysis of its equivalence with the successive approximations method when A 0 is selected as part of the conductance matrix of the system.
  • A demonstration of the equivalence between the successive approximations power flow (SAPF) and Broyden’s method, which proves that the former is a particular case of the latter in the studied problem.
Regarding the scope of our contribution, the following facts are considered during the numerical validations carried out in the 21-, 33-, and 85-bus grids: (i) two possible connections for the neutral wire are tested: the first case corresponds to the floating connection, i.e., the neutral wire is only solidly grounded at the substation terminals, and the second case assumes that all the nodes are solidly grounded; (ii) the load consumption values are assumed to be perfectly known, i.e., no uncertainties are considered in the values of the constant power terminals; and (iii) the voltage output at the substation bus for all the poles is fixed as an input parameter.

1.5. Document Structure

The remainder of this document is structured as follows. Section 2 presents the general formulation of the power flow problem for bipolar DC networks with asymmetric loading. Section 3 describes the general implementation of Broyden’s method for a general set of nonlinear equations. Section 4 presents the application of Broyden’s method to the power flow problem. Section 5 shows the main characteristics of the test feeders, which correspond to the 21-, 33-, and 85-bus grids. Section 6 presents the numerical validations of the proposed power flow problem, including the voltage profile performance and the power losses for each test feeder, as well as some numerical comparisons against the literature reports. Finally, Section 7 lists the main concluding remarks derived from this work and some possible future studies.

2. Power Flow Problem in Bipolar DC Networks

The power flow solution for bipolar DC networks with asymmetric loading is a challenge due to the presence of multiple nonlinear equality constraints associated with each pole as a function of the connection of multiple constant power loads (monopolar or bipolar) [15]. This set of constraints requires implementing numerical methods in order to obtain a solution with an acceptable convergence error [1]. The power flow problem in a bipolar unbalanced network can be represented with seven equations (three linear and four nonlinear) per node and pole. These equations are presented below.
I g , k p I d , k p I d , k p n = r P j N G j k p r V k r , k N ,
I g , k o I d , k o I d , k ground = r P j N G j k o r V k r , k N ,
I g , k n I d , k n + I d , k p n = r P j N G j k n r V k r , k N ,
I d , k p = P d , k p V k p V k o , k N ,
I d , k n = P d , k n V k n V k o , k N ,
I d , k o = P d , k p V k o V k p + P d , k n V k o V k n , k N ,
I d , k p n = P d , k p n V k p V k n , k N ,
where I g , k p , I g , k o , and I g , k n represent the current injection in the slack source per pole (i.e., positive, neutral, and negative - p o n -); I d , k p , I d , k o , and I d , k n are the current demanded by the monopolar constant power loads, i.e., P d , k p and P d , k n (note that the monopolar loads refer to those connected between the positive or negative pole and the neutral pole); I d , k p n corresponds to the current absorbed by the constant power load P d , k p n connected between the positive and negative poles, i.e., a bipolar consumption; I d , k ground means the current drained from the neutral wire to the physical ground at each node; V k r represents the voltage magnitude at node k in pole r; G j k p r , G j k o r , and G j k n r correspond to the conductance values (obtained from the conductance matrix) that relate nodes j and k and poles p o n with pole r, respectively. Note that P and N denote the sets that contain all the poles and nodes of the bipolar DC grid under analysis.
If Equations (4)–(7) are substituted into (1)–(3), the studied problem is reduced to a set of three nonlinear equality constraints.
I g , k p P d , k p V k p V k o P d , k p n V k p V k n = r P j N G j k p r V k r , k N ,
I g , k o P d , k p V k o V k p + P d , k n V k o V k n I d , k ground = r P j N G j k o r V k r , k N ,
I g , k n P d , k n V k n V k o + P d , k p n V k p V k n = r P j N G j k n r V k r , k N .
Remark 1. 
The set of nonlinear Equations (8)–(10) can be compacted using a matricial representation with the help of the conductance matrix and its components G g g , G g d , G d g , and G d d , as defined in (11) [7].
I g I d = G g g G g d G d g G d d V g V d ,
where, considering that the cardinalities of the sets P and N are 3 and n, I g R 3 × 1 and V g R 3 × 1 are the vectors that contain the current injection in the slack source (unknown variables) and the voltage output at the terminals of the slack source, i.e., perfectly known voltages. I d R 3 ( n 1 ) × 1 is the vector containing the current demanded at each node, which is ordered by node and pole (unknown variables); and V d R 3 ( n 1 ) × 1 is the vector of voltage profiles at each demand node, also ordered by node and pole (unknown variables).
From the two equations in (11), it can be noted that:
  • The first row of (11) shows that the solution of the current injections at the substation will be only known when all the demanded voltage profiles are determined. In addition, this is a linear equation that does not require any iterative process for its solution.
  • The second row of (11) is a nonlinear set of equations, as the demanded currents I d are hyperbolic functions of the demanded voltages, which implies that its solution requires efficient numerical methods [1].
To determine the set of demanded currents by comparing the second row of (11) against Equations (8)–(10), note that
I d = I d B + I d M ,
where I d B and I d M are vectors associated with the currents demanded by the bipolar and monopolar loads, respectively, which are calculated per node, as follows:
I d , k B = diag 1 B V d , k P d , k B , k N ,
I d , k M = diag 1 M 1 V d , k P d , k M 1 + diag 1 M 2 V d , k P d , k M 2 , k N ,
where
B = 1 0 1 0 1 0 1 0 1 , M 1 = 1 1 0 1 1 0 0 1 1 , M 2 = 0 0 0 0 1 1 0 0 0 , P d , k B = P d , k p n 0 P d , k p n , P d , k M 1 = P d , k p P d , k p P d , k n , P d , k M 2 = 0 P d , k n 0 , V d , k = V d , k p V d , k o V d , k n .
Remark 2. 
The solution to the power flow problem in bipolar DC grids with asymmetric loading corresponds to the solution of the following recursive formula:
G d g V g + G d d V d = I d B I d M
using a numerical method based on the dependence of the vectors I d B and I d M on the demanded voltages V d .

3. The Secant or Broyden’s Method

The secant or Broyden’s method is a numerical approach developed for solving sets of nonlinear equations with f x = 0 . This is performed without resorting to the implementation of Newton-based approaches [8,16]. The general successive approximations formula for the secant method is defined in (6).
x t + 1 = x t A t 1 f x t ,
where t is the iteration counter and A t corresponds to the Jacobian matrix, which is, however, approximated via secant hyperplanes [17].
Consider the following linear relation:
A t x t x t 1 = f x t f x t 1 ,
which is simplified as (17) by defining s t = x t x t 1 and y t = f x t f x t 1 .
A t s t = y t .
Now, the following two hyperplanes are defined:
l t 1 x = f x t 1 + A t 1 x x t 1 ,
l t x = f x t + A t x x t .
The main idea of the secant method is that, at the solution point, hyperplanes (18) and (19) must be equal, i.e.,
f x t 1 + A t 1 x x t 1 = f x t + A t x x t .
Note that, in (20), if x = x t is defined while considering the definition in (17) and making some algebraic manipulations, the following result is reached:
A t A t 1 s t = y t A t 1 s t .
By simplifying (21), the general updating formula for A t can be determined as presented in (22).
A t = A t 1 y t A t 1 s t s t s t s t .
Note that, for the general iteration t + 1 , the way to update A t + 1 is obtained from (22), as defined in (23).
A t + 1 = A t + y t + 1 A t s t + 1 s t + 1 s t + 1 s t + 1 .
The general algorithm for solving the set of equations f x = 0 is presented in Algorithm 1 [18].
Algorithm 1: General implementation of Broyden’s method for solving sets of nonlinear equations
Sensors 23 06704 i001

4. Application of Broyden’s Method to the Power Flow Problem

This section presents the general application of Broyden’s method to the problem regarding the power flow of bipolar DC networks with asymmetric loading, which is based on Algorithm 1. As presented in Section 2, this work deals with a complex nonlinear problem, where the main idea is to efficiently obtain its roots via numerical methods [1]. For the application of Broyden’s method, as described in Section 3, using the compact representation in Equation (14) is recommended. Note that this Equation is necessary as the equivalent gradient function f V d t is defined from it, as follows [18]:
f V d t = G d g V g + G d d V d t + I d t , B + I d t , M = 0 ,
where the components of the demanded currents in I d t , B and I d t , M are defined from (12) to (13).
Considering the structure of Algorithm 1, Algorithm 2 presents the application of Broyden’s method to solve the power flow problem in asymmetric bipolar DC distribution grids.
Remark 3. 
The main characteristic of Algorithm 2 is the selection of the initial value of matrix A 0 , as it has multiple alternatives. Depending on this selection, the number of iterations required to reach the desired convergence varies.
Algorithm 2: Application of Broyden’s method for solving the power flow problem in bipolar DC networks
Sensors 23 06704 i002

5. Test Feeders

To validate the effectiveness of Broyden’s method in addressing the power flow problem in bipolar asymmetric distribution grids, three test feeders composed of 21, 33, and 85 nodes with unbalanced structures were considered.

5.1. Bipolar DC 21-Bus Network

The 21-bus grid corresponds to a radial distribution network composed of 21 buses and 20 lines, as depicted in Figure 2 [6]. The main characteristics of this feeder are the following: (i) the substation bus is located at bus 1, and the voltage outputs in the positive and negative poles are ± 1 kV with respect to the neutral point, which is solidly grounded; and (ii) the total monopolar consumption is 554 kW in the positive pole and 445 kW in the negative pole, while the bipolar power consumption is 405 kW.
The information regarding branches and monopolar and bipolar power consumptions is presented in Table 1.

5.2. Bipolar DC 33-Bus System

This bipolar DC network is a modification of the original single-phase distribution network originally proposed by the authors of [19]. The schematic single-line representation of this system is presented in Figure 3. The main characteristics of this distribution network are the following: (i) the substation bus is located at bus 1, and the voltage outputs in the positive and negative poles are ± 12.66 kV with respect to the neutral point, which is solidly grounded; and (ii) the total monopolar consumption is 2615 kW in the positive pole and 2185 kW in the negative pole, while the bipolar power consumption is 2350 kW.
The information regarding branches and monopolar and bipolar power consumptions is presented in Table 2 [20].

5.3. Bipolar DC 85-Bus Network

The bipolar DC 85-network is a radial distribution network composed of 85 nodes and 84 branches, as depicted in Figure 4. The main characteristics of this distribution network are the following: (i) the substation bus is located at bus 1, and the voltage outputs in the positive and negative poles are ± 11 kV with respect to the neutral point, which is solidly grounded; and (ii) the total monopolar consumption is 1745.48 kW in the positive pole and 2682.19 kW in the negative pole, while the bipolar power consumption is 2258.58 kW.
The information regarding branches and monopolar and bipolar power consumptions is presented in Table 3 [21].

6. Numerical Validations

To validate Broyden’s method, all the bipolar DC networks were simulated in the MATLAB programming environment via the researchers’ own scripts. For this implementation, version 2021b was used on a PC with an AMD Ryzen 7 3700 2.3 -GHz processor and 16.0 GB RAM, running on a 64-bit version of Microsoft Windows 10 Single language.

6.1. Number of Iterations and Convergence Behavior

In this section, the A 0 matrix is generated using the conductance matrix G d d with the following rule: A 0 = γ G d d , where γ = α + rand ( 1 ) β α . rand(1) is a random number generated using a uniform distribution, and the parameters α and β are set as 0.5 and 2.0 , respectively. In addition, to test the variations in the number of iterations required to reach the power flow solution while considering a convergence error of about ε = 1 × 10 10 , for these simulations, it is assumed that the neutral wire is floating in all nodes except in the substation bus. The number of iterations required for solving the power flow problem with Broyden’s method in each one of the test feeders is depicted in Figure 5.
The main characteristics of the behavior shown in Figure 5 allow stating that:
  • The number of iterations after 100,000 repetitions exhibits a Gaussian distribution, with a mean value of about 11 iterations for all the test feeders. This is due to the fact that the Gaussian distribution carried most of the γ -factor around its center, i.e., α + β 2 = 1.25 , which is the region where 11 iterations are the most probable result.
  • Depending on the γ -factor, for all the test feeders, a minimum number of iterations of about seven was observed. The average values of the γ -factor were 0.9750 , 0.9659 , and 0.9783 , for the bipolar DC 21-, 33-, and 85-bus networks, respectively. These values imply that in order to reach a better numerical performance with Broyden’s method, the γ -factor must be tuned for each test feeder.
  • The maximum number of iterations for the 21-bus grid was about 14, whereas for the 33- and 85-bus grids it was 13. For these results, the γ -factor is when this parameter is located near the α of β values, i.e., near the extreme values used in simulations.
To determine the convergence properties of Broyden’s method in all the test feeders under analysis, a logarithmic error graph is presented in Figure 6. Equation (25) presents the function that defines the error’s evolution.
e t = log V d t + 1 V d t .
The convergence behavior exhibited by Broyden’s method in Figure 6 for all the tested feeders when the γ -factor was selected to ensure the minimum or the maximum number of iterations within the range assigned for α and β shows that, in general, this algorithm has a linear tendency to solve the power flow problem, with some oscillations. However, these oscillations are caused by the updating of the A t matrix, which is carried out by using the information of the previous iteration. Still, this does not compromise the stability of this method.
Remark 4. 
The γ-factor is a key parameter in the implementation of Broyden’s method. However, as observed for all the test feeders, the recommended value to ensure the minimum number of iterations must be contained in the 0.90–1.10 interval.

6.2. Comparative Analysis

To demonstrate the effectiveness of the proposed secant method to deal with the power flow problem in bipolar DC asymmetric distribution networks, the power flow was solved while considering the two connection modes of the neutral wire (i.e., solidly grounded or floating) in the tested feeders. A comparison was made with the hyperbolic approximations power flow (HAPF) approach reported in [6], the successive approximations power flow (SAPF) method proposed by [7], and the triangular-based power flow (TBPF) approach reported in [12]. Table 4 lists the results for all the test feeders, including the two connections applicable to the neutral wire. For the sake of simplicity, the gamma factor was selected to ensure minimal iterations in Broyden’s power flow method.
The numerical results in Table 4 show that:
  • In all simulation cases, Broyden’s method reaches the same numerical solution regarding power losses in the tested feeders for both neutral wire operating conditions. Nevertheless, when the neutral wire is floating, this approach takes 7 iterations; otherwise, 11 iterations are needed. These values were independent of the number of nodes of the test feeder under analysis.
  • Contrary to the behavior of the comparison methods, the number of iterations increases when the neutral wire is considered to be solidly grounded. However, this behavior can be attributed to the fact that Broyden’s recursive formula is general and does not depend on the nonlinear set of equations under analysis, which implies that, under some particular conditions (i.e., the connection of the neutral wire), its evolution differs from that of specialized methods for power flow studies. On the other hand, the increase in the number of iterations is not directly related to that of the required processing times.
  • The main characteristic of the simulations in the three test feeders is that (as expected) when the neutral wire is solidly grounded, the power losses are lower than in the floating operation scenario. These differences are 4.1536 , 10.0629 , and 37.2778 kW, for the 21-, 33-, and 85-bus networks, respectively.
On the other hand, the behavior of the voltage profiles in the tested feeders shows voltage regulations of 11.1740 % , 9.4264 % , and 7.9629 % for the neutral floating case in the 21-, 33-, and 85-bus networks, as well as 10.9898 % , 9.3176 % , and 8.1086 % when the neutral wire is solidly grounded. As expected, voltage regulation improves when the neutral wire is solidly grounded, which is a direct consequence of the reduction in the number of power losses evidenced in Table 4.

6.3. Demonstration of the Equivalence between the SAPF and Broyden’s Method

The main characteristic of Broyden’s method is that it can reduce the number of calculations (iterations) required to solve the power flow problem in bipolar DC networks under floating operating conditions. However, the time taken by Broyden’s method is superior to that of the SAPF method, as the former needs to update the A t matrix. Although it is feasible under some particular conditions, Broyden’s method is equivalent to the SAPF approach. This equivalence is demonstrated below.
Lemma 1. 
The SAPF method is an iterative procedure to solve the power flow problem in electrical networks which can be obtained from Equation (14), as demonstrated in [7], which takes the following form:
V d t + 1 = G d d 1 G d g V g + I d t , B + I d t , M ,
which converges if the G d d is a diagonally dominant matrix and the bipolar DC network operates far from the voltage collapse point [22].
To demonstrate that Broyden’s method is equivalent to the SAPF approach, let us consider the following assumptions:
Assumption A1. 
The γ -factor is selected as the unity, which implies that A 0 = G d d .
Assumption A2. 
No updating is implemented for the A t + 1 matrix, i.e., A t + 1 = A t = A 0 .
Proof. 
Considering Assumptions 1 and 2, the general evolution rule of Broyden’s method in Equation (15) takes the following form:
x t + 1 = x t A 0 1 f x t .
Now, considering that, for the bipolar DC power flow problem f x t = f V d t , and given the definition in (24), Equation (27) takes the following form:
V d t + 1 = V d t A 0 1 f V d t , = V d t A 0 1 G d g V g + G d d V d t + I d t , B + I d t , M .
If the definition of A 0 is taken into account, Equation (28) can be simplified as follows:
V d t + 1 = V d t G d d 1 G d g V g + G d d V d t + I d t , B + I d t , M , = V d t G d d 1 G d g V g + I d t , B + I d t , M V d t , = G d d 1 G d g V g + I d t , B + I d t , M ,
which allows noting that Equation (29) is identical to the SAPF formula in Equation (26), thus completing the proof. □
Remark 5. 
It is important to highlight that this proof considers that the SAPF method is a particular case of Broyden’s method for analyzing bipolar DC asymmetric networks.

7. Conclusions

This research applied Broyden’s method to solve the power flow problem in bipolar DC asymmetric distribution networks while considering two possible connections for the neutral pole, i.e., solidly grounded or floating case. Numerical results demonstrated that:
  • The number of iterations required by the proposed numerical method to solve the studied problem highly depends on the γ factor selection. This parameter must be tuned for each test feeder and neutral wire connection, with its recommended values being between 0.90 and 1.10 . Note that the γ -coefficient can be considered to be the equivalent value of the α -coefficient in the classical Gauss–Seidel method implemented for AC power systems.
  • The convergence behavior, i.e., the evolution of e t , exhibits a linear behavior as a function of the selected γ -factor, with slight oscillations attributed to the updating rule applicable to Broyden’s method, which adds the effect of the difference between two consecutive nonlinear function evaluations to the calculation of A t . In addition, after 100 thousand consecutive evaluations of Broyden’s method for different values of the γ -factor, it was observed that the highest probability in the expected number of iterations was 11, regardless of the test feeder, with a minimum value 7 for all test systems, as well as a maximum of 14 for the 21-bus grid and 13 for the remaining grids.
  • Numerical comparisons with the literature reports showed that the processing times in the solution of the power flow increase with the number of nodes of the network, as expected. However, regarding the number of iterations, the opposite behavior was evidenced in the methods used for comparison (SAPF, TBPF, and HAPF): in the case of the floating neutral wire, the number of iterations was lower for our method, and, when the neutral wire was solidly grounded, the number of iterations increased. This, however, was inversely related to the average processing times.
  • A demonstration of the equivalence between the SAPF approach and Broyden’s method under Assumptions 1 and 2 confirmed the generality of the proposed technique in dealing with power flow problems in bipolar DC networks with asymmetric loads, with the main advantage that the number of iterations or processing times can be prioritized as a function of the γ -factor and the selection and adapting of the A t + 1 matrix.
The main advantage of Broyden’s method for addressing the power flow problem in bipolar DC networks with asymmetric loading is that it can apply to radial and meshed networks as an equivalent to the SAPF and the HAPF approaches given that its formulation is based on a conductance matrix that is constructed without considering the tree configuration of the network under analysis. However, numerical tests were only conducted in three radial distribution networks since these configurations correspond to the worst possible case regarding power losses and voltage regulation indicators.
In regard to future works, the following studies can be conducted: (i) extending the proposed power flow method to three-phase asymmetric distribution networks; (ii) including, in Broyden’s formulation, the possibility of having multiple voltage-controlled nodes and distributed energy resources; and (iii) demonstrating the equivalence between the SAPF method and the proposed approach.

Author Contributions

Conceptualization, methodology, software, and writing (review and editing): O.D.M., Á.M.-Q. and W.G.-G. All authors have read and agreed to the published version of the manuscript.

Funding

This research received support from the Ibero-American Science and Technology Development Program (CYTED) through thematic network 723RT0150, Red para la integración a gran escala de energías renovables en sistemas eléctricos (RIBIERSE-CYTED).

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

No new data were created or analyzed in this study. Data sharing does not apply to this article.

Acknowledgments

To God, who opens the doors of scientific knowledge and enlightens us to achieve our goals.

Conflicts of Interest

The authors declare no conflict of interest.

Nomenclature

Indices
p , o , n Superscripts associated with poles
0Superscripts associated with the initial value
tSuperscripts associated with the iteration counter
j , k Subscripts associated with nodes
gSubscripts associated with the generators
dSubscripts associated with the demands
Parameters
G j k p r Value of the conductance matrix that associates nodes j and k between poles p and r (S)
G g g Value of the conductance matrix associated only with generators (S)
G g d , G d g Value of the conductance matrix associated with generators and demands (S)
G d d Value of the conductance matrix associated only with demands (S)
P d , k p n Bipolar constant power consumption connected between the positive and negative poles and node k (W)
P d , k p Monopolar constant power consumption at node k for the positive pole p (W)
P d , k n Monopolar constant power consumption at node k for the negative pole n (W)
V nom Nominal voltage at the substation terminal (V)
f x Gradient of the function f ( x )
Sets
P Set that contains all the poles in the network, i.e.,  p , o , n
N Set that contains all nodes in the network
Variables
V k r Voltage value at node k for the r t h pole (V)
I g , k p Current injection in the slack source at node k for the positive pole p (A)
I g , k o Current injection in the slack source at node k for the neutral pole o (A)
I g , k n Current injection in the slack source at node k for the negative pole n (A)
I d , k p Current consumption at node k for the positive pole p (A)
I d , k o Current consumption at node k for the neutral pole p (A)
I d , k n Current consumption at node k for the negative pole p (A)
I d , k ground Current consumption at node k for the ground (A)
v g Vector that contains the voltage in the slack source (V)
I g Vector that contains the current injection in the slack source (A)
V d Vector that contains the voltage in the demands (V)
I d Vector that contains the current consumptions (A)
I d B Vector that contains the current in bipolar loads (A)
I d M Vector that contains the current in monopolar loads (A)
A t Jacobian matrix in iteration t

References

  1. Lee, J.O.; Kim, Y.S.; Jeon, J.H. Generic power flow algorithm for bipolar DC microgrids based on Newton–Raphson method. Int. J. Electr. Power Energy Syst. 2022, 142, 108357. [Google Scholar] [CrossRef]
  2. Chew, B.S.H.; Xu, Y.; Wu, Q. Voltage Balancing for Bipolar DC Distribution Grids: A Power Flow Based Binary Integer Multi-Objective Optimization Approach. IEEE Trans. Power Syst. 2019, 34, 28–39. [Google Scholar] [CrossRef] [Green Version]
  3. Garcés, A.; Montoya, O.D.; Gil-González, W. Power flow in bipolar DC distribution networks considering current limits. IEEE Trans. Power Syst. 2022, 37, 4098–4101. [Google Scholar] [CrossRef]
  4. Gil-González, W.; Montoya, O.D.; Hernández, J.C. Optimal Neutral Grounding in Bipolar DC Networks with Asymmetric Loading: A Recursive Mixed-Integer Quadratic Formulation. Energies 2023, 16, 3755. [Google Scholar] [CrossRef]
  5. Tavakoli, S.D.; Khajesalehi, J.; Hamzeh, M.; Sheshyekani, K. Decentralised voltage balancing in bipolar dc microgrids equipped with trans-z-source interlinking converter. IET Renew. Power Gener. 2016, 10, 703–712. [Google Scholar] [CrossRef]
  6. Medina-Quesada, Á.; Montoya, O.D.; Hernández, J.C. Derivative-Free Power Flow Solution for Bipolar DC Networks with Multiple Constant Power Terminals. Sensors 2022, 22, 2914. [Google Scholar] [CrossRef] [PubMed]
  7. Montoya, O.D.; Gil-González, W.; Garcés, A. A successive approximations method for power flow analysis in bipolar DC networks with asymmetric constant power terminals. Electr. Power Syst. Res. 2022, 211, 108264. [Google Scholar] [CrossRef]
  8. Ramli, A.; Abdullah, M.L.; Mamat, M. Broyden’s Method for Solving Fuzzy Nonlinear Equations. Adv. Fuzzy Syst. 2010, 2010, 1–6. [Google Scholar] [CrossRef]
  9. Kim, J.; Cho, J.; Kim, H.; Cho, Y.; Lee, H. Power flow calculation method of DC distribution network for actual power system. KEPCO J. Electr. Power Energy 2020, 6, 419–425. [Google Scholar]
  10. Lee, J.O.; Kim, Y.S.; Moon, S.I. Current injection power flow analysis and optimal generation dispatch for bipolar DC microgrids. IEEE Trans. Smart Grid 2020, 12, 1918–1928. [Google Scholar] [CrossRef]
  11. Li, B.; Wang, W.; Liu, Y.; Li, B.; Wen, W. Research on power flow calculation method of true bipolar VSC-HVDC grids with different operation modes and control strategies. Int. J. Electr. Power Energy Syst. 2021, 126, 106558. [Google Scholar] [CrossRef]
  12. Sepúlveda-García, S.; Montoya, O.D.; Garcés, A. Power Flow Solution in Bipolar DC Networks Considering a Neutral Wire and Unbalanced Loads: A Hyperbolic Approximation. Algorithms 2022, 15, 341. [Google Scholar] [CrossRef]
  13. Al-Baali, M.; Spedicato, E.; Maggioni, F. Broyden’s quasi-Newton methods for a nonlinear system of equations and unconstrained optimization: A review and open problems. Optim. Methods Softw. 2014, 29, 937–954. [Google Scholar] [CrossRef]
  14. Jarlebring, E. Broyden’s method for nonlinear eigenproblems. SIAM J. Sci. Comput. 2019, 41, A989–A1012. [Google Scholar] [CrossRef] [Green Version]
  15. Mackay, L.; Guarnotta, R.; Dimou, A.; Morales-Espana, G.; Ramirez-Elizondo, L.; Bauer, P. Optimal Power Flow for Unbalanced Bipolar DC Distribution Grids. IEEE Access 2018, 6, 5199–5207. [Google Scholar] [CrossRef]
  16. Yang, H.; Wen, F.; Wang, L. Newton-Raphson on power flow algorithm and Broyden Method in the distribution system. In Proceedings of the 2008 IEEE 2nd International Power and Energy Conference, Johor Bahara, Malaysia, 1–3 December 2008; IEEE: Piscataway, NJ, USA, 2008. [Google Scholar] [CrossRef]
  17. Sangadiev, A.; Poddubny, A.; Pozo, D.; Gonzalez-Castellanos, A. Quasi-Newton Methods for Power Flow Calculation. In Proceedings of the 2020 International Youth Conference on Radio Electronics, Electrical and Power Engineering (REEPE), Moscow, Russia, 12–14 March 2020; IEEE: Piscataway, NJ, USA, 2020. [Google Scholar] [CrossRef]
  18. Mirzaee, M.; Zolfaghari, A.; Minuchehr, A. The Broyden method applied for the analysis of two-phase flow in a BWR fuel bundle based on the drift-flux model. Prog. Nucl. Energy 2019, 112, 80–95. [Google Scholar] [CrossRef]
  19. Baran, M.; Wu, F. Optimal sizing of capacitors placed on a radial distribution system. IEEE Trans. Power Deliv. 1989, 4, 735–743. [Google Scholar] [CrossRef]
  20. Grisales-Noreña, L.F.; Montoya, O.D.; Hernández, J.C. Efficient Reallocation of BESS in Monopolar DC Networks for Annual Operating Costs Minimization: A Combinatorial-Convex Approach. Batteries 2023, 9, 190. [Google Scholar] [CrossRef]
  21. Montoya, O.D.; Gil-González, W.; Hernández, J.C. Efficient Integration of Fixed-Step Capacitor Banks and D-STATCOMs in Radial and Meshed Distribution Networks Considering Daily Operation Curves. Energies 2023, 16, 3532. [Google Scholar] [CrossRef]
  22. Garces, A. Uniqueness of the power flow solutions in low voltage direct current grids. Electr. Power Syst. Res. 2017, 151, 149–153. [Google Scholar] [CrossRef]
Figure 1. Schematic representation of a bipolar DC network.
Figure 1. Schematic representation of a bipolar DC network.
Sensors 23 06704 g001
Figure 2. Schematic of nodal connections in the bipolar DC 21-bus network.
Figure 2. Schematic of nodal connections in the bipolar DC 21-bus network.
Sensors 23 06704 g002
Figure 3. Schematic of the nodal connections in the bipolar DC 33-bus network.
Figure 3. Schematic of the nodal connections in the bipolar DC 33-bus network.
Sensors 23 06704 g003
Figure 4. Schematic of the nodal connections in the bipolar DC 85-bus network.
Figure 4. Schematic of the nodal connections in the bipolar DC 85-bus network.
Sensors 23 06704 g004
Figure 5. Behavior of the iterations as a function of the initial matrix A 0 : (a) bipolar DC 21-bus network, (b) bipolar DC 33-bus network, and (c) bipolar DC 85-bus network.
Figure 5. Behavior of the iterations as a function of the initial matrix A 0 : (a) bipolar DC 21-bus network, (b) bipolar DC 33-bus network, and (c) bipolar DC 85-bus network.
Sensors 23 06704 g005
Figure 6. Convergence behavior of Broyden’s method for all the tested feeders: (a) when the γ -factor is selected to ensure the minimum number of iterations, and (b) when the γ -factor is selected to ensure the maximum number of iterations.
Figure 6. Convergence behavior of Broyden’s method for all the tested feeders: (a) when the γ -factor is selected to ensure the minimum number of iterations, and (b) when the γ -factor is selected to ensure the maximum number of iterations.
Sensors 23 06704 g006
Table 1. Parametric information regarding branches and constant power loads in the bipolar DC 21-bus network (all powers in kW).
Table 1. Parametric information regarding branches and constant power loads in the bipolar DC 21-bus network (all powers in kW).
Node jNode k R jk (Ω) P d , k p P d , k n P d , k p n
120.053701000
130.054000
340.0543640120
450.063400
460.0513600
370.037000
780.07932500
790.072800100
3100.0530100
10110.03845300
11120.07968700
11130.07810075
10140.083000
14150.06522300
15160.06423100
16170.07443060
16180.08134600
14190.0789150
19200.084211050
19210.08221200
Table 2. Parametric information regarding branches and constant power loads in the bipolar DC 33-bus network (all powers in kW).
Table 2. Parametric information regarding branches and constant power loads in the bipolar DC 33-bus network (all powers in kW).
Node jNode k R jk (Ω) P d , k p P d , k n P d , k p n
120.09221001500
230.493090750
340.36601201000
450.381160900
560.8190600200
670.187210050150
781.711410000
891.03006070100
9101.0400608025
10110.19664500
11120.374460900
12131.46806060100
13140.5416120100200
14150.5910603050
15160.74631100350
16171.289060900
17180.732090450
2190.1640901500
19201.504215050115
20210.40950900
21220.7089090145
3230.45129011035
23240.8980120040
24250.8960150100100
6260.203060800
26270.2842600225
27281.059000130
28290.80421207565
29300.50751001000
30310.974450150125
31320.310517510075
32330.34109560120
Table 3. Parametric information regarding branches and constant power loads in the bipolar DC 85-bus network (all powers in kW).
Table 3. Parametric information regarding branches and constant power loads in the bipolar DC 85-bus network (all powers in kW).
Node jNode k R jk (Ω) P dk p P dk p P dk p n Node jNode k R jk (Ω) P dk p P dk p P dk p n
120.1080010.07534441.00217.6417.9950
230.16350040.3544450.9115017.6417.995
340.2172828.565045460.9112517.6417.995
450.10810050046470.54677.1410
560.43517.6417.99525.1835480.6370100
670.27208.625048490.1820025
781.19717.6417.99530.2949500.36418.14018.505
890.10817.835040.4650510.4552828.5650
9100.5980100048521.36630015
10110.5442828.565052530.45517.643517.995
11120.5440404553540.546283028.565
12130.598454022.552550.54638048.565
13140.27217.6417.99535.1349560.54674032.14
14150.32617.6417.99520.1759570.2734835.06510
2160.72817.6467.533.4957580.8190500
3170.45556.157.1550.2558590.1821828.56525
5180.8202828.56520058600.5462843.5650
18190.6372828.5651060610.7281828.56530
19200.45517.6417.99515061621.00212.529.0650
20210.81917.6470152.560630.18277.145
21221.54817.6417.9953063640.7280050
19230.182287528.56564650.18212.52537.5
7240.910017.6417.99565660.1824048.56533
8250.45517.6417.9955064670.455000
25260.36402828.56567680.910000
26270.5461107517568691.0921318.56525
27280.2732812528.56569700.4550200
28290.5460507570710.54617.6438.27517.995
29300.54617.64017.99567720.1822813.5650
30310.27317.6417.995068731.1843000
31320.1820175073740.273285028.565
32330.18277.1412.573751.00217.646.2317.995
33340.81900070760.5463848.5650
34350.637005065770.091717.1425
35360.18217.64017.99510780.63728628.565
26370.364283028.56567790.54617.6442.9950
27381.0022828.5652512800.7282828.56530
29390.54602828.56580810.36445075
32400.45517.64017.99581820.0912853.750
40411.002100081831.09212.6432.99562.5
41420.27317.642517.99583841.0026272.20
41430.45517.6417.995013850.819101010
Table 4. Comparative analysis between Broyden’s method and literature reports.
Table 4. Comparative analysis between Broyden’s method and literature reports.
Neutral Wire FloatingNeutral Wire Solidly Grounded
Bipolar DC 21-Bus Network
MethodLosses (kW)IterationsTime (ms)Losses (kW)IterationsTime (ms)
SAPF95.4237130.527591.2701100.4911
TBPF95.4237130.834091.2701100.7672
HAPF95.4237131.554291.270141.0212
Proposed95.423771.159391.2701110.8776
Bipolar DC 33-bus network
SAPF344.4797111.2537334.416891.0594
TBPF344.4797112.1875334.416892.0171
HAPF344.4797115.5386334.416843.4675
Proposed344.479772.5657334.4168111.9950
Bipolar DC 85-bus network
SAPF489.5759136.4419452.2981106.3261
SAPF489.5759138.4913452.2981108.3822
HAPF489.57591315.1654452.2981410.5698
Proposed489.5759712.4023452.2981118.7853
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Montoya, O.D.; Medina-Quesada, Á.; Gil-González, W. Solving the Power Flow Problem in Bipolar DC Asymmetric Distribution Networks Using Broyden’s Method. Sensors 2023, 23, 6704. https://doi.org/10.3390/s23156704

AMA Style

Montoya OD, Medina-Quesada Á, Gil-González W. Solving the Power Flow Problem in Bipolar DC Asymmetric Distribution Networks Using Broyden’s Method. Sensors. 2023; 23(15):6704. https://doi.org/10.3390/s23156704

Chicago/Turabian Style

Montoya, Oscar Danilo, Ángeles Medina-Quesada, and Walter Gil-González. 2023. "Solving the Power Flow Problem in Bipolar DC Asymmetric Distribution Networks Using Broyden’s Method" Sensors 23, no. 15: 6704. https://doi.org/10.3390/s23156704

APA Style

Montoya, O. D., Medina-Quesada, Á., & Gil-González, W. (2023). Solving the Power Flow Problem in Bipolar DC Asymmetric Distribution Networks Using Broyden’s Method. Sensors, 23(15), 6704. https://doi.org/10.3390/s23156704

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop