3.3.2. Simulation of Pollution Load Reduction Scenarios
Water quality objectives must be determined based on water environmental management requirements; according to the requirements of Jiangsu Province, the water quality objectives of the Wujin River watershed are Grade IV water quality standards [
25]. In this study, the end of the river was used for water quality control. Grade IV water quality standards are 30.0 mg/L, 1.5 mg/L, 1.5 mg/L, and 0.3 mg/L for COD, NH
3-N, TN and TP, respectively. By simulating different scenarios, the load reduction rate of different scenarios was obtained such that the water quality at the end of Wujin River reached the required standards. The initial concentrations of various programs are Grade IV water quality standards. In the simulation, the input pollution concentrations of COD, NH
3-N, TN and TP were adjusted by trial and error until the water quality simulation results met the water quality objectives.
Point sources and non-point sources simultaneously reduced. Simultaneous point source and non-point source reductions of 13.35%, 27.26% and 37.08% for COD, NH
3-N, and TP were required, respectively, for concentrations to meet the standards at the end of the river. As shown in
Figure 5, simultaneous point source and non-point source reductions of 58.77% were required for TN concentrations to meet the standards, meanwhile, COD, NH
3-N, and TP concentrations were lower than the Grade IV standards; therefore, the water quality of the river would meet the required standards.
Figure 5.
Simulation curves from implementing point source and non-point source simultaneous reductions of 58.77%.
Figure 5.
Simulation curves from implementing point source and non-point source simultaneous reductions of 58.77%.
Point source reduction. The simulation results for the point source reduction scenario are shown in
Figure 6. The results show that the pollution load of point sources needed to be reduced by 83.41% for COD concentrations to meet the standards; however, NH
3-N, TN, and TP did not meet the standards with a 100% point source pollution load reduction. This is because non-point source pollutants (including domestic sewage and agricultural non-point source pollutants) in the watershed accounted for more than 80% of pollutant emissions; therefore, reducing only the point source pollution load did not achieve the water quality standards.
Figure 6.
Simulation curves from implementing point source reduction of 100%.
Figure 6.
Simulation curves from implementing point source reduction of 100%.
Non-point source reduction. The simulation results for the non-point source reduction scenario are shown in
Figure 7. The results show that pollution load of only non-point sources needed to be reduced by 17.14%, 29.73%, 40.06% and 62.59% for COD, NH
3-N, TP and TN concentrations, respectively, to meet the standards.
Figure 7.
Simulation curves from implementing non-point source reduction, as required for the concentrations of various water quality variables to meet the standards.
Figure 7.
Simulation curves from implementing non-point source reduction, as required for the concentrations of various water quality variables to meet the standards.
Control of rivers using ecological purification technologies. The scenario based on implementation of only water pollution control technologies and ecological purification measures in the river to control and govern the pollution of the river network resulted in an increase in the water quality degradation coefficient of Wujin River. This would improve the degradation and absorption properties of pollutants such as nitrogen and phosphorus, so the river water quality can be improved.
As shown in
Figure 8, river pollution control and ecological purification measures resulted in degradation coefficients of 0.38 d
−1, 0.52 d
−1, 0.41 d
−1, 0.59 d
−1, 0.53 d
−1, and 0.65 d
−1 for COD, organic nitrogen, ammonia nitrogen, nitrate nitrogen, organic phosphorus and inorganic phosphorus, respectively, and COD, NH
3-N, TN, and TP concentrations would reach the standards at the river’s end. However, the biomass, aquatic plant density and size of project required to achieve these parameters needs further site-based experimental studies [
3,
39].
Control point sources, non-point sources, and the rivers simultaneously. The pollution loads of COD, NH
3-N, TN, and TP were all reduced by about 30% as a result of river pollution control projects [
40,
41,
42,
43]. Therefore, this scenario assumed that river control can reduce 30% of the pollution load; hence, the pollution load of point sources and non-point sources was reduced on this basis.
The simulation results showed that COD, NH
3-N, and TP concentrations met the standards without reducing the pollution load of point sources and non-point sources; however, point source and non-point source pollution load reductions of 23.20% are needed for TN concentrations to meet the standards (
Figure 9). The results show that the implementation of pollution control engineering and ecological purification measures in the river results in COD, NH
3-N, and TP concentrations that meet the standards. Integrated pollution control measures or environmental management countermeasures need to be implemented to reduce the discharge of pollution load by 23.20% and, combined with the implementation of ecological purification measures in the rivers, would result in the water quality at the end of the river meeting the standards.
Figure 8.
Simulation curves from implementing the river control measures.
Figure 8.
Simulation curves from implementing the river control measures.
Figure 9.
Simulation curves from implementation of river control measures and a pollution load reduction of 23.20%.
Figure 9.
Simulation curves from implementation of river control measures and a pollution load reduction of 23.20%.
Based on the above discussion, the simulation results of various load reduction scenarios are shown in
Table 8.
Table 8.
Simulation results for various load reduction scenarios.
Table 8.
Simulation results for various load reduction scenarios.
Type of Scenario | Objective | Reduction Rate of Point Sources | Reduction Rate of Non-Point Sources |
---|
Control point sources and non-point sources | COD up to standard | 13.35% | 13.35% |
NH3-N up to standard | 27.26% | 27.26% |
TP up to standard | 37.08% | 37.08% |
TN up to standard | 58.77% | 58.77% |
Control point sources | COD up to standard | 83.41% | — |
NH3-N up to standard | 100%, still not up to standard | — |
TP up to standard | 100%, still not up to standard | — |
TN up to standard | 100%, still not up to standard | — |
Control non-point sources | COD up to standard | — | 17.14% |
NH3-N up to standard | — | 29.73% |
TP up to standard | — | 40.06% |
TN up to standard | — | 62.59% |
Control the rivers | water quality up to standards | — | — |
Control point sources, non-point sources, and rivers | water quality up to standards | 23.20% | 23.20% |
3.3.3. Evaluation of Pollution Load Reduction Scenarios
The following four pollution load reduction scenarios were selected for further evaluation because in these scenarios COD, NH3-N, TN, and TP concentrations each met the standards at the river’s end.
Scenario A: The pollution loads of point sources and non-point sources were simultaneously reduced by 58.77%. Scenario B: The pollution loads of non-point sources were reduced by 62.59%. Scenario C: Implementation of river pollution control and ecological purification measures resulted in river degradation coefficients of 0.38 d−1, 0.52 d−1, 0.41 d−1, 0.59 d−1, 0.53 d−1, and 0.65 d−1 for COD, organic nitrogen, ammonia nitrogen, nitrate nitrogen, organic phosphorus, and inorganic phosphorus, respectively. Scenario D: The pollution loads of point sources and non-point sources were reduced by 23.20% based on a 30% pollution load reduction for river control.
An evaluation indicator system for the pollution load reduction scenarios was constructed using the evaluation indicators of environmental, social, economic, ecological and investment (
Table 9).
Table 10 shows a judgment optimization matrix for pairwise comparisons of the five evaluation indicators using the ratio-scale method [
44,
45,
46], these data were obtained based on social and economic development, people's environmental expectations and a field survey of the watershed.
Table 9.
The evaluation indicator system of pollution load reduction scenarios.
Table 9.
The evaluation indicator system of pollution load reduction scenarios.
Indicators | Factor | Correlation |
---|
Environmental | COD; NH3-N; TN; TP | Positive |
Social | Population; Scientific and cultural quality; Environmental awareness | Positive |
Economic | Gross National Product; Per capita income | Positive |
Ecological | Living environment; Per capita water resources; Vegetation cover | Positive |
Investment | The proportion of investment accounting for Gross National Product; Investment | Negative |
Table 10.
Judgment optimization matrix for pairwise comparisons of the evaluation indicators.
Table 10.
Judgment optimization matrix for pairwise comparisons of the evaluation indicators.
Indicators | Environmental | Social | Economic | Ecological | Investment |
---|
Environmental | 1 | 4/5 | 3/2 | 5/4 | 2 |
Social | 5/4 | 1 | 2 | 5/3 | 3 |
Economic | 2/3 | 1/2 | 1 | 3/4 | 4/3 |
Ecological | 4/5 | 3/5 | 4/3 | 1 | 3/2 |
Investment | 1/2 | 1/3 | 3/4 | 2/3 | 1 |
Initial weight coefficients and normalized weight coefficients (
Table 11) for each of the evaluation indicators were calculated. For each of the pollution load reduction scenarios, the increasing rates of the five evaluation indicators were forecast based on the Delphi method [
47,
48,
49] (
Table 12). The comprehensive evaluation values for the effects of each of the four load reduction scenarios were calculated using the weight coefficients of the evaluation indicators in
Table 11 and the increasing rates of the evaluation indicators in
Table 12. The comprehensive evaluation values for the scenarios A, B, C, and D were 0.246, 0.217, 0.180, and 0.194, respectively.
Table 11.
Weight coefficients of the evaluation indicators.
Table 11.
Weight coefficients of the evaluation indicators.
Weight Coefficients | Environmental | Social | Economic | Ecological | Investment |
---|
Initial weight coefficient (Wi') | 1.24 | 1.61 | 0.80 | 0.99 | 0.61 |
Normalized weight coefficient (Wi) | 0.23 | 0.30 | 0.16 | 0.19 | 0.12 |
Table 12.
Evaluation indicator increasing rates of each load reduction scenarios.
Table 12.
Evaluation indicator increasing rates of each load reduction scenarios.
Indicators Increasing Rates | Scenario A | Scenario B | Scenario C | Scenario D |
---|
Environmental | 42% | 35% | 26% | 31% |
Social | 40% | 35% | 25% | 30% |
Economic | −13% | −8% | 5% | −3% |
Ecological | 36% | 30% | 21% | 25% |
Investment | 15% | 11% | 3% | 8% |
The comprehensive evaluation values indicate that the scenarios in order of decreasing effect were A, B, D, and C. The comprehensive evaluation effect of Scenario A was the largest, suggesting that control the discharge of point sources and non-point sources from the sources is the optimal measure for prevention and control of pollution. This scenario had positive environmental, social and ecological effects; however, it would affect economic development and requires large investment. The comprehensive evaluation effect of Scenario C was the smallest, indicating that not controlling from the sources but controlling after pollution is an ineffective means of environmental pollution control; however, economic growth was ensured. The comprehensive evaluation effect of Scenario D, which controlled the sources as well as the environmental pollution, was between that of A and C; this result is reasonable and logical.
Table 7 shows that domestic sewage emissions accounted for 67.60%, 78.89%, 82.20% and 63.48% for COD, NH
3-N, TN, and TP, respectively, of total emissions of pollution load. The pollutants discharged in domestic sewage can be removed using measures such as home sewage processing purification tanks, home-constructed wetland systems, and centralized sewage treatment plants. The average removal of home wetland system treatments is 93.0%, 88.4%, 87.7%, 97.0% and 89.6% for COD, ammonia nitrogen, total phosphorus, total suspended solids and turbidity, respectively [
50]. The removal of home sewage distributed processing purification tanks is 93%, 76% and 91% for COD, TN, and TP, respectively [
51,
52]. Therefore, COD, ammonia nitrogen, TN and TP of domestic sewage can be removed by more than 80% using these measures; thus, pollution load reductions of 54.08%, 63.11%, 65.80% and 50.78% for COD, ammonia nitrogen, TN, and TP, respectively, can be achieved in the Wujin River watershed. According to the pollution load reduction rates shown in
Table 8, the COD, ammonia nitrogen, TN, and TP reductions meet the standards at the river’s end. Based on the above, Scenarios A and B have the greatest feasibility and operability.