1. Introduction
As an effective means of application of distributed generation technology, microgrid has attracted more and more attention in recent years [
1,
2,
3]. A microgrid generally consists of several renewable energy resources, storage systems, loads, and electronics devices. Due to the diversity and decentralization of distributed energy, power converters are usually used to connect them in order to realize energy conversion and management. How to achieve parallel operation, accurate load current sharing between power converters, and maintain stability has become a research hotspot in microgrids [
4,
5,
6,
7,
8,
9,
10,
11,
12,
13,
14,
15,
16,
17,
18,
19,
20,
21,
22]. With the increasing demand of DC power at load side and the rapid development of distributed DC power sources such as photovoltaic cells, wind power, storage batteries, fuel cells, and supercapacitors, the research on DC microgrids has been gradually increasing in recent years [
7,
8,
9]. Nowadays, DC microgrids have been preliminarily applied in independent power supply systems such as marine power systems, aerospace systems, and data centers [
10,
11,
12].
In islanded DC microgrids, DC–DC converters are widely used for the distributed generations to connect the common bus. To study the parallel operation problem of distributed generations is essentially to study the current sharing control of multiple paralleled DC–DC converters. Accurate current sharing between paralleled converters and no deviation regulation for bus voltage are two important control objectives in islanded DC microgrid [
13,
14,
15,
16,
17,
18,
19,
20,
21,
22,
23]. At present, the current-sharing strategies that are most commonly used are master–slave control and peer-to-peer control.
In reference [
13], a master–slave control method based on current-mode controlled dc-dc converters was proposed to maintain power balance of the parallel system. A power generation module is selected as the master module to stabilize bus voltage, and the other modules divide current equally according to the bus voltage and inject energy into the load in the form of current sources. The work in [
14] proposed a master–slave control strategy based on adaptive multi-master power supply. When the load power changes, the distributed generations switch to the master control module in turn and adaptively adjust their own operation mode and output power. Reference [
15] set up a central controller based on a multiagent system to adjust the output of each unit. By controlling the frequency oscillation of each agent, the controller minimizes the production cost of the whole interconnected system. The master–slave control methods are simple and easy to implement, but the whole system has a strong dependence on the master unit. Meanwhile, due to the existence of high-speed communication, the distance between generation units is limited. If the master unit or the communication failure occurs, the system may collapse.
When the peer-to-peer control is adopted, every unit in the system has the same status and can control itself through local information. High-speed communication is not required, so it is easy to implement the function of “plug and play”. Now, the peer-to-peer control methods have become the research mainstream, among which, droop control is the most widely applied. The V-I droop method based on virtual impedance is usually adopted in DC microgrid. The introduction of virtual resistance can change the equivalent impedance of the power converter, and reduce the impedance difference caused by line impedance, so as to improve the load current sharing accuracy. This method does not need any communication, but its droop characteristics would cause serious voltage drop, and the uncertain line impedance would also affect the current sharing accuracy. Then, some optimization methods with variable droop coefficients were proposed [
16,
17,
18]. According to the output current range, voltage deviation information, and the defined droop index of the converter, the optimal value of virtual impedance is calculated and then different droop coefficients are set to optimize the current sharing among the micro-sources. However, the above methods can not directly determine the droop coefficients, which are difficult to coordinate with each other if the number of micro-sources is large. So, these methods have no generality. The work in reference [
19] changed the research idea. The droop curves are shifted by changing the reference voltages, not by changing the droop coefficients. This method can realize the current sharing among multi-converters and control the DC bus voltage within the allowable range. However, similar to the methods of variable droop coefficients, it is difficult to coordinate the variations of reference voltages when the number of converters in parallel is large. Based on this, hierarchical control methods based on low-bandwidth communication were proposed in references [
20,
21,
22,
23,
24]. The primary control layer of converters follow the traditional virtual impedance droop control, and larger droop coefficients are selected to ensure the accuracy of power sharing. The secondary control layer is used to compensate the bus voltage drop by adjusting the droop curve. In the early stage of microgrid research, the related literatures usually adopted the centralized hierarchical control method. The information of each converter is transmitted to the central controller through low-speed communication, and then the compensation signal is sent to the primary layer of each converter through secondary control [
20]. However, the centralized hierarchical control depends on the central controller. Once the central controller has problems, the whole system would fail or even collapse. In order to overcome the problem above, the concept of distributed hierarchical control was proposed. The secondary control layer is embedded in the bottom controller of each converter, so that every converter in the microgrid can be regarded as a relatively independent agent [
21,
22,
23,
24]. References [
21,
22] achieved the sharing of all local information through a global low-speed communication network, then the secondary control calculates the required control values based on the above information. References [
23,
24] combined the idea of autonomous decentralization. Each generation unit only needs to communicate with its neighboring units, after a certain number of iterations, the target parameters converge to the average value. These methods greatly improved the contradiction between power sharing accuracy and bus voltage drop. However, the existence of a communication network would bring stability, redundancy, and cost problems to the microgrid, especially in the case of operating many sources along long feeders.
After that, some distributed control strategies, in which the units inject sinusoidal signals of specific frequency into the common bus, were proposed instead of the communication [
25,
26,
27,
28,
29,
30]. In references [
25,
26], the power line signaling (PLS) was used to transmit the frequency signals and realize the cooperation of multiple converters. The merit is prominent since the power network is the only communication medium. However, PLS is more complex to be implemented and it is not conducive to the expandability of the system. In references [
27,
28], a small ac signal, whose frequency is controlled by the harmonic power, was injected into the output voltage of each inverter as a control signal. Then, the active power produced by the injected signal was detected and utilized to adjust the virtual impedance at terminal of each distributed generation (DG) unit. Similar to AC microgrid, in references [
29,
30], the method with ac signal injection was used in a DC microgrid. The small frequency signal was superimposed onto the output voltage of each converter, and then the dc output voltage can be adjusted through the reactive power generated by the superimposed ac voltages. This method can improve the load current sharing accuracy, but it does not consider the bus voltage drop caused by line impedances. When the line impedance or the line impedance deviation is large, the bus voltage drop is still very serious. Besides, the principle of accurate power sharing under the injection method was not analyzed.
In order to overcome the bus voltage drop caused by line impedances, as well as to obtain the current sharing objectives, a novel current-sharing control strategy for multiple paralleled DC–DC converters is proposed. A small ac voltage, whose frequency is related to output current, is superimposed onto the output DC voltage of each converter. Then, the reactive circulating power would be generated in the parallel system and be used to regulate the output DC voltage of each converter. Under the feedback mechanism, the accurate current sharing can be realized. On this basis, an improved autonomous bus voltage regulation method is used to compensate bus voltage drop by adding limiter link and virtual negative impedance. In the proposed approach, every converter can locally carry out the load current sharing and the voltage regulation without utilizing communication network, which leads to reliable and flexible operation.
The rest of this paper is organized as follows: In
Section 2, the proposed current sharing control strategy based on injected small ac voltage is discussed in detail. In
Section 3, the autonomous bus voltage regulation strategy based on limiter link and virtual negative impedance is performed. The small signal modeling, as well as the stability analysis, is given in
Section 4. Then, the simulation and experiment results under various working conditions are presented to verify the effectiveness of the proposed control strategy in
Section 5 and
Section 6, respectively. Finally, the achievements are summarized in
Section 7.
3. Autonomous Bus Voltage Regulation Strategy
When the line impedance and load current are large, the bus voltage drop caused by line impedance can’t be ignored. In this section, an improved bus voltage regulation method based on reactive power-voltage regulation limiter link and virtual negative impedance is proposed, which further reduces the voltage drop caused by line impedances. The control structure is shown in
Figure 5.
3.1. Analysis of Limiter Link
For simplicity, the parallel system with two equal converters is also illustrated, and the control process of the parallel system with limiter link is shown in
Figure 6.
Compared with the control method without limiter link, the difference is that if the reactive power is greater than zero, the compensation value will be forced to be zero due to the existence of the limiter link, and then Uo1 will increase and Uo2 will not change. Then, Io1 will increase with the increase of Uo1. The negative feedback can also be formed, and the feedback effect will not be affected by increasing the value of feedback coefficient dq.
The feedback mechanism can also be extended to the parallel system with multiple converters. Next, the parallel system with three converters will be illustrated briefly. Assuming Rline1 > Rline2 > Rline3, and the sum of Q1, Q2, Q3 is approximately zero. Then there will be two cases at the initial time:
1) Q1 < Q2 < 0, Q3 > 0
In this case, according to the feedback mechanism with limiter link, Uo1 and Uo2 would increase, and Uo1 > Uo2, Uo3 would remain unchanged. Under the feedback mechanism, the system would gradually stabilize.
2) Q1 < 0, Q3 > Q2 > 0:
In this case, according to the feedback mechanism with limiter link, Uo1 would increase, and Uo2 and Uo3 would remain unchanged. The system is obviously unstable. At this moment, there would inevitably be a new reactive circulating power between converter #2 and #3 because of Rline2 ≠ Rline3. Under the further action of feedback mechanism, Uo2 would increase and Uo3 would remain unchanged. At this time, the reactive circulating between the three converters would form a new balance, and make Q1 < Q2 < 0, Q3 > 0. Finally, the system would gradually stabilize.
From the above analysis, the line impedance of converter #3 is the smallest and its output voltage remains unchanged, so its equivalent impedance
is the line impedance
Rline3. Under the feedback mechanism, the output currents of the three converters tend to be equal. Therefore, according to the requirement of current sharing, the conclusion can be obtained that
. In other words, the function of the reactive power-voltage regulation limiter link is essentially to make the equivalent output impedance of each converter tend to become the minimum line impedance. This principle can obviously be extended to multiple converters with equal power rating. When the parallel system is finally stable,
would satisfy the following relationship:
where
Rline-min represents the minimum value of the line impedances among the parallel converters. The proposed control method with limiter link makes the final equivalent output impedance of the converter change from the average line impedance (Equation (15)) to the minimum value (Equation (16)). This method further restrains the bus voltage droop, especially when the line impedance deviation is large.
3.2. The Selection of Q-U Regulation Coefficient dq
From the above analysis, it can be seen that the core of the injection method is to compensate the line impedance by reactive power. So the total equivalent output impedance in Equation (12) must be able to meet the requirements of compensation. In order to ensure the validity of the injection method, the selection of dq has some limitations. For simplicity, the parallel system with only two equal converters is illustrated.
According to Equations (8), (9), (12), and (16) and
Figure 5, when the system is in steady, the relationship can be obtained as follows:
where
and
. Then, it can be derived as
Therefore, in order to ensure that Equation (18) is always valid and maintains a certain margin,
dq should meet the following condition:
where
is the rated output voltage of the converter,
Rmin is the minimum load resistance,
represents the maximum load current.
3.3. Virtual Negative Impedance
From the analysis of
Section 3.1, it can be seen that how much the control method with limiter link makes the bus voltage drop is entirely dependent on the minimum line impedance of each converter. If the minimum line impedance is large, the bus voltage drop is still serious. In order to further eliminate voltage drop caused by line impedance, the virtual negative impedance is added to the voltage control link. In order to simplify the analysis, next the parallel system with equal power rating is taken as an example in the following.
Combined with
Figure 6 and Equation (16), the dc bus voltage can be deduced:
in which
i represents the converter with the smallest line impedance and
Rv is the virtual negative impedance. At this time, as long as the value of
Rv +
Rline-min is zero, the bus voltage can be adjusted without error. It should be noted that the value of
Rv +
Rline-min should not be too small, and only needs to satisfy the requirement of maximum allowable bus voltage drop. This is because if the equivalent output impedance is too small, very small voltage change between parallel converters would also lead to serious current fluctuations. Therefore, the value of
Rv should be determined according to the size of
Rline-min, and the basic rules are as follows:
where
Rlimit represents the maximum allowable equivalent output impedance of the converters, and
The key of this method is how to get the minimum line impedance of the converters. According to
Figure 6 and the corresponding analysis, when the system is stable, the output voltage of the converter with the smallest line impedance is the reference given the voltage
. So the minimum line impedance can be obtained by measuring the bus voltage, that is, the virtual negative impedance can be calculated. Assuming that the measured bus voltage is
, then
When the parallel system first runs or the state of power supplies changes, first the value of Rv needs to be set as zero and a certain load in the system needs to be connected, then, after the system is stable, the bus voltage can be measured. Then, the value of Rv can be obtained from the Equations (21)–(23). Due to the fact that the line impedance is usually a fixed value, even if there is parameter drift or estimation error, the influence on bus voltage deviation would not be great. Therefore, only when the parallel system first runs or the state of power supplies changes, does the virtual negative impedance need to be measured and calculated. So in normal operation, the virtual negative impedance is a fixed value.
4. Small Signal Modeling and Stability Analysis
In order to ensure the system stability as well as to design the control system parameters, a small signal model of the parallel system is established in this section. Taking the dc microgrid with two converters as an example, the relationship between the output voltages, output currents, and bus voltage of the converters can be obtained:
in which
R is the load resistor. The linear form of (24) can be obtained as
where
I10 and
I20 are the DC output currents of the two converters at
R =
R0, Δ(.) depicts the small variation of each variable.
For convenience of calculation, assume that
Rline1 <
Rline2 and ignore the voltage gain caused by the voltage–current double-loop. According to the analysis of
Section 3 and the Equations (10)–(12) and (20), the output voltage of each converter can be obtained as:
The linear form of Equation (26) can be written as
From the Equation (9), the small variation of
Q2 can be described as:
where
φ0 is the steady state value of phase angle difference. According to the Equation (7), the small variation of phase difference can be expressed as:
Combining the Equations (4), (25), and (27)–(29), and taking into considering
as a state variable and
as a disturbance, the state space representation can be obtained as (30).
where
.
The characteristic equation for a closed loop system in Laplace domain can be obtained as:
Then, the root locus of the system can be obtained by introducing the converter parameters into the characteristic equation. Since
α is always greater than zero, the Equation (31) would have a pair of conjugate complex roots. Hence, the closed loop system is dynamically stable, and its dynamic performance is mainly affected by
ωc,
A2,
dq,
df1,
λ, and
R. In order to facilitate analysis, the influence of
A2
dq
df1 on the closed loop system is considered together, because
A2,
dq, and
df1 have the same control effects.
Figure 7 shows the root locus diagrams with the variation of
ωc,
A2dqdf1,
λ, and
R, respectively.
It can be seen from
Figure 7a, the system is a typical second-order system. If
ωc is too small, the poles tend towards an imaginary axis, and the system would become oscillatory and even unstable. If
ωc is too large, the system damping would increase and the adjustment time would be too slow. Here
ωc = 35 rad/s is selected, where the poles of the system would have a pair of conjugate complex roots and the performance would be good. The effort of
A2dqdf1 is demonstrated in
Figure 7b. For small
A2dqdf1, one of the poles is near the origin and it affects the system damping performance. So, the selection of
A2dqdf1 in this system should be greater than 5. Of course, the selection of
A2dqdf1 should not to be too large, which would lead to system oscillation. Besides the root locus, the selection of
A2,
dq, and
df1 is also influenced by bus voltage ripple, sensor accuracy, converter rated capacity, and so on. The effort with the variation of the rated power ratio
λ is shown in
Figure 7c. Obviously, when the rated powers are unequal, the system dynamic performance would become worse. Finally, as it can be seen in
Figure 7d, the system is not significantly affected by the load variation. Therefore, the performance of the control system at different load conditions is guaranteed.
6. Experimental Tests
In order to further validate the proposed control strategy, some experimental tests were performed, taking into account load variations, as well as equal and unequal converter ratings and different load types. The experiment setup, which consists of storage batteries, two boost converters, dc electronic load, dc/dc power converter load, and dSPCAE 1103 controller, is shown in
Figure 12. The parameters are listed in
Table 3 and the results are reported in the following.
First, the proposed control strategy was verified with two equal converters in parallel. The frequency-current droop coefficients
dfk were both set as 0.2 Hz/A, and the results are shown in
Figure 13.
In the figure,
ubus is the bus voltage,
uo1 and
io1 were the output voltage and current of DC#1,
io2 was the output current of DC#2.
Figure 13a,b show the bus voltage and output current waveforms under load variations from 80 Ω to 40 Ω, and from 40 Ω to 80 Ω, respectively.
Figure 13c shows the detailed waveforms under the 40 Ω load. It can be seen that the small signal of 3.5 V ac voltage could be better injected into the output voltage of each converter. In the process of load variations, both voltage and current had good dynamic performance, and the dynamic recovery times were both less than 100 ms. Moreover, the influence of load variations on bus voltage could be neglected, and the dc bus voltage was always maintained at the rated value. As shown in
Figure 13a, when the load was 80 Ω, the output currents of the two converters were about 0.9 ± 0.15 A, and when the load was 40 Ω, the output currents were about 1.8 ± 0.3 A. Combining with
Figure 13c, it is not difficult to find that the load current could be equally shared between the two converters, and the output dc currents had the same value. Furthermore, the phase between the two ac current components was approximately inversed, which is consistent with the theoretical analysis and simulation results.
Figure 14 shows the experiment results of two unequal converters in parallel. The power rating of DC#1 and DC#2 is 1:2, and the frequency-current droop coefficients
dfk were set as 0.3 and 0.15 Hz/A. As shown in the figure, when the load was 80 Ω, the output currents of the two converters were 0.6 ± 0.15 A and 1.2 ± 0.15 A, when the load was 40 Ω, the output currents were 1.2 ± 0.2 A and 2.4 ± 0.2 A. So in steady state, the current ratio is approximately 1:2 and the current sharing accuracy can be guaranteed. At the same time, it can found that the influence of load variations on voltage can be neglected, just the same as the case of two equal converters in parallel. When the load resistance decreased, as shown in
Figure 14a, the dynamic recovery time of output currents was about 400 ms. When the load resistance increased, as shown in
Figure 14b, the dynamic recovery time was about 600 ms. Compared with
Figure 13, the dynamic performance of output currents was relatively poor, but it also met the dynamic requirements. Further, the experimental results are basically consistent with the simulation case one.
Finally, the case of two equal converters with the dc/dc power converter-based load, which is shown in
Figure 15, is considered.
Figure 16 shows the bus voltage and output current waveforms under load variations between 200 W and 400 W. It can be seen from the figure that the load current could be equally shared between the two converters and the output dc components had the same value. The system dynamic performance was good and similar to that under resistive load. Unlike the resistive load condition, the phases of the output ac current components were not opposite. This is because the load shown in
Figure 15 had a capacitive component, and the injected ac voltage generated reactive power, thus making the sum of the output reactive power a fixed value that was not equal to zero. The experimental results indicate that this did not affect the effectiveness of the proposed control method.
The experiments above show that the parallel system with the proposed control strategy has better current sharing and dynamic performance, and the bus voltage has better static and dynamic performance without any communication, regardless of whether the converters in parallel have equal or unequal power rating.
7. Conclusions
This paper has presented a novel current-sharing control strategy based on injected small ac voltage for multiple paralleled DC converters. The DC converters are coordinated together with an injected frequency, and hence, accurate current sharing is realized utilizing the feedback mechanism of reactive circuiting power-voltage regulation. On this basis, an autonomous dc bus voltage regulation method has been proposed. Through adding the limiter link and virtual negative impedance, the bus voltage drop caused by line impedance is almost compensated. The basic principle of the proposed control strategy was analyzed in detail, and the stability and dynamic performance were discussed by using small signal modeling. The effectiveness of the proposed control system was evaluated by simulations, including equal and unequal converter ratings, as well as resistive and motor-based constant power load. Finally, the load sharing and bus voltage regulating performance of the proposed method were experimentally verified.
The proposed method is easy to implement without any communication or changing of the hardware structure. However, it is not difficult to find that it also introduces some power quality problems. The output voltage and current ripples of the converter would increase with the injected small ac voltage. Of course, the voltage and current ripples can be controlled within the allowable ranges by reasonably designing the parameters of the proposed controller. Meanwhile, due to the sensor accuracy, parasitic parameters, external interference, and other reasons, the output current ripple of the experimental results is obviously higher than that of the simulation results. How to further reduce the output ripple and design the injected frequency stopping mechanism after steady state would be the focus research on the proposed control method in the future.