2.1. Virtual Air Flow Sensor of VAV Terminal Unit
The influencing factors for the HVAC system affecting the air flow rate of the VAV terminal unit are the damper opening ratio, damper differential pressure, and supply fan speed. The in-situ damper performance curve of the VAV terminal unit can be expressed by the quadratic equation of the air flow rate and damper differential pressure at the maximum speed of the supply fan, as shown in Equation (2). In order to derive the coefficients () of the in-situ damper performance curve, it is necessary to measure the air flow rate and damper differential pressure, while varying the damper opening ratio with the supply fan running at full speed.
As shown in
Figure 3, the air flow rate and damper differential pressure of the VAV terminal unit vary according to the damper opening ratio and the supply fan speed. As the speed of the supply fan changes, the relationship between the air flow rate and differential pressure can be corrected using Equation (3), based on the Fan Laws, and Equation (4) can be derived [
6,
23].
Using Equation (5), the air flow rate of the VAV terminal unit can be calculated, using the fan speed and damper differential pressure as input values. However, the damper differential pressure sensor must be additionally installed to measure the virtual air flow of the VAV terminal unit. In a building with multiple terminal units, the installation of a damper differential pressure sensor at every point gives rise to the problem of high costs. Therefore, we intend to analyze the relationship between the damper opening ratio and the damper differential pressure, which is one of the existing control factors of terminal units in order to substitute it for damper differential pressure and use it as an input value.
The damper differential pressure can be measured by changing the fan speed at the minimum damper opening ratio, and the relationship between the damper opening ratio and the damper differential pressure ratio can be derived as a cubic equation, as shown in Equation (6). The damper differential pressure ratio can be expressed as the ratio of the partial damper differential pressure to the maximum damper differential pressure for the same fan speed, as shown in Equation (7).
The maximum damper differential pressure according to the change in the fan speed can be derived, as shown in Equation (8).
By combining Equations (6)–(8), Equation (9), which contains the damper opening ratio and fan speed as its components, can be derived from the measured differential pressure. Additionally, Equations (5) and (9) can be combined to derive Equation (10), the final equation for virtual sensing of the air flow rate of the VAV terminal unit.
2.2. In-Situ Measurement Procedure
When the hot-wire anemometer, differential pressure sensor, and the BAS system which enables control and measurement of the damper opening ratio and fan speed are prepared, measurements are performed according to the following procedure.
Step 1: The in-situ measurement of the VAV terminal unit is conducted. The measurement is performed twice. First, the damper differential pressure and the air flow rate (or air velocity) are measured by varying the damper opening ratio of the terminal unit at the maximum fan speed. Second, the damper opening ratio of the terminal unit is fixed at the minimum value, and the damper differential pressure and air flow rate (or air velocity) are measured by varying the fan speed.
Step 2: The in-situ damper performance curve is derived from the damper differential pressure and air flow rate of the VAV terminal unit measured by varying the damper opening ratio at the maximum fan speed.
Step 3: The equation for the relationship between the damper opening ratio and differential pressure ratio is derived using the damper differential pressure and the air flow rate of the VAV terminal unit measured by varying the damper opening ratio at the maximum fan speed.
Step 4: The equation for the relationship between the fan speed and the damper differential pressure is derived using the damper differential pressure of the VAV terminal unit measured by varying the supply fan speed at the minimum damper opening ratio.
Step 5: Equation (10) was derived using Equations (3)–(9) for calculating the virtual air flow rate of the VAV terminal unit.
Figure 4 shows the in-situ measurement procedure algorithm for the development of the virtual air flow sensor of the VAV terminal unit.
2.3. Error Analysis
The virtual air flow rate of the VAV terminal unit is calculated using various input variables. The measurement sensors can generate errors in all the input variables, and all the errors in the input variables can affect the calculated air flow rates. Common sensor errors include accuracy and bias errors, and errors can be detected as combined errors [
26].
The errors of input variables affecting the calculated virtual air flow rates can be estimated using the Taylor series method, and uncertainty can be calculated using Equation (11) [
21,
25]. The types and sources of errors in input variables are shown in
Table 1.
Statistical methods for error analysis, such as the absolute error (
AE), relative error (
RE), root-mean square error (
RMSE), and coefficient of determination (
R2), were used to validate the developed virtual air flow sensor. Smaller
RMSE and error values indicate a better virtual sensor, in which the R
2 value is close to 1 [
27]. The statistical values are expressed as Equations (12)–(15).