Next Article in Journal
Research on a Safety Assessment Method for Leakage in a Heavy Oil Gathering Pipeline
Next Article in Special Issue
Development of Simulation Tool for Ground Source Heat Pump Systems Influenced by Ground Surface
Previous Article in Journal
Determination of NMR T2 Cutoff and CT Scanning for Pore Structure Evaluation in Mixed Siliciclastic–Carbonate Rocks before and after Acidification
Previous Article in Special Issue
A Study on the Effect of Performance Factor on GSHP System through Real-Scale Experiments in Korea
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

A New Simulation Model for Vertical Spiral Ground Heat Exchangers Combining Cylindrical Source Model and Capacity Resistance Model

1
Faculty of Engineering, Hokkaido University, N13-W8, Kita-ku, Sapporo 060-8628, Japan
2
Faculty of Symbiotic Systems Science, Fukushima University, 1 Kanayagawa, Fukushima 960-1296, Japan
3
INOAC Housing & Construction Materials Co., Ltd., 4-9-27 Taihou, Atsuta-ku, Nagoya 456-0062, Japan
*
Author to whom correspondence should be addressed.
Energies 2020, 13(6), 1339; https://doi.org/10.3390/en13061339
Submission received: 1 February 2020 / Revised: 7 March 2020 / Accepted: 7 March 2020 / Published: 13 March 2020

Abstract

:
Considering the heat capacity inside vertical spiral ground heat exchanger (VSGHEX) in the simulation is one of the most noteworthy challenge to design the ground source heat pump (GSHP) system with VSGHEXs. In this paper, a new simulation model for VSGHEXs is developed by combining the ICS model with the CaRM. The developed simulation model can consider the heat capacity inside VSGHEX and provide dynamic calculation with high speed and appropriate precision. In order to apply the CaRM, the equivalent length was introduced. Then, the equivalent length was approximated by comparing the results of the CaRM and the numerical calculation. In addition, the calculation model of the VSGHEX was integrated into the design and simulation tool for the GSHP system. The accuracy of the tool was verified by comparing with the measurements. The error between supply temperatures of the measurements and calculation is approximately 2 °C at the maximum. Finally, assuming GSHP systems with VSGHEXs, whose spiral diameter was 500 mm and depth was 4 m, were installed in residential houses in Japan, the required numbers of VSGHEXs were estimated. The results showed a strong correlation between the total heating or cooling load and the required number. Therefore, the required number can be estimated by using the simplified approximate equation.

Graphical Abstract

1. Introduction

In recent years, global warming due to increase of CO2 emission has become a worldwide environmental issue. This problem has created interest in applying ground source heat pump (GSHP) systems and borehole thermal energy storage (BTES) systems with vertical ground heat exchangers (GHEXs). However, these systems are not widely installed in Japan because of high installation cost. Especially, the boring cost is more expensive than in other countries. GSHP systems using vertical spiral ground heat exchangers (VSGHEXs) can reduce the installation costs, because the borehole for the VSGHEX can be drilled by using the vehicle that is used for installing the electric poles. However, the diameter of VSGHEXs is much larger than the diameter of conventional GHEXs with U-tubes. Therefore, it is important to consider the heat capacity inside the VSGHEX in the performance prediction of the GSHP system with VSGHEXs. In order to evaluate the VSGHEX, several simulation models were developed in the previous research. The simulation models are mainly categorized into three types, which apply the numerical calculation [1,2], the analytical solution [3,4,5,6,7], and the capacity resistance model (CaRM) [8,9,10,11]. By applying the numerical calculation, it is possible to evaluate the convective heat transfer coefficient and pressure drop in detail [1]. It is effective to evaluate the thermal resistance inside the VSGHEX. However, it is difficult to evaluate the seasonal (or annual) performance due to the huge calculation load. In the simulation models applying analytical solution, the spiral GHEX is regarded as the ring source in the infinite medium [3,4,5,6,7]. These models have the advantage from the viewpoint of calculation speed. On the other hand, the thermal properties of the ground surrounding VSGHEXs and the grout inside VSGHEX must be the same (or can be regarded as the same) in these models. This means that it is difficult to evaluate the VSGHEXs if the thermal properties of the ground and the grout differ from each other. The simulation models applying the CaRM evaluate the VSGHEXs even if the thermal properties of the ground and the grout differ from each other. However, there was no research works in which the problem of multiple VSGHEXs were treated. In addition, the research works, in which the simulation models were validated by comparing with the experimental data in long term (seasonal or annual), were hardly observed in all papers.
On the other hand, the authors have developed the design and simulation tool for the GSHP system [12] by applying the infinite cylindrical source (ICS) model [13,14]. If the ICS model is applied to calculate the ground temperature, the inside of VSGHEX can be regarded as the follow cylinder and it is possible to apply the CaRM to the inside temperature calculation. In this paper, a new simulation model for VSGHEXs is developed by combining the ICS model [12,13] and the CaRM [10]. In the developed simulation model, the ground temperature surrounding the GHEX is calculated by applying the ICS model and the inside of GHEX including the heat carrier fluid and the grout is modeled by the CaRM. This model can consider the heat capacity inside VSGHEX and provide dynamic calculation with high speed and appropriate precision. In addition, it is possible to handle GSHP systems with multiple GHEXs by applying the superposition of temperature field in space that the authors suggested in the precedence papers [15,16,17].
In this paper, the outline of new simulation model combining the ICS model with the CaRM is first explained. In our developed model, the equivalent length is introduced to apply the CaRM. In order to evaluate the equivalent length, a detailed numerical calculation model of the inside of the VSGHEX, which differs from the CaRM, is produced. Then, the equivalent length is approximated by comparing the results of the CaRM and the numerical calculation. In addition, the simulation model for VSGHEX is validated by comparing it with the measurement data. The measurement of GSHP system with VSGHEXs, which was installed in a residential house in Miyagi Prefecture in Japan, was carried out annually. Finally, in future, if GSHP systems with VSGHEXs are installed, we need to estimate the number of VSGHEXs as easy as possible. The authors assumed that GSHP systems with VSGHEXs were installed in residential houses and estimated the number of VSGHEXs.

2. Calculation Method for Vertical Spiral Ground Heat Exchangers

Figure 1 shows the concept of applying the CaRM to VSGHEX and Figure 2 is the plane view. The borehole of VSGHEX is regarded as a hollow cylinder in the infinite solid. The ground temperature surrounding VSGHEX can be calculated by applying the ICS model [12,13] and the temperatures inside VSGHEX are calculated by CaRM [10].

2.1. Calculation Method for Inside Spiral Ground Heat Exchangers

As shown in Figure 2, the grout between Pipe1 and Pipe2 is called as the Core and the grout between Pipe2 and the borehole surface is called as the Shell [10]. Then, the nodes are built at the Core and Shell. In this paper, the inside of the VSGHEX is regarded as a multilayer cylinder as shown in Figure 3 when the CaRM is applied. The heat balance of the heat carrier fluid in Pipe1, Pipe2 (The point T f 1 , T f 2 in Figure 2), the surface of Pipe1, Pipe2 (The point T s p 1 , T s p 2 in Figure 2), Core, and Shell are expressed by Equations (1)–(6), respectively.
Heat carrier fluid in Pipe1
c f ρ f V f 1 d T f 1 d t = c f ρ f G f ( T f 1 i n T f 1 o u t ) + ( T s p 1 T f 1 ) 1 2 π r p i n h l b + 1   2 π l b λ p l n ( r p o u t r p i n )
Heat carrier fluid in Pipe2
c f ρ f V f 2 d T f 2 d t = c f ρ f G f ( T f 2 i n T f 2 o u t ) + ( T s p 2 T f 2 ) 1 2 π r p i n h l s p 2   + 1 2 π l s p 2 λ p l n ( r p o u t r p i n )
Surface of Pipe1
0 = ( T f 1   T s p 1 ) 1 2 π r p i n h l b + 1   2 π l b λ p l n ( r p o u t r p i n ) + ( T c o r e T s p 1 ) 1 2 π l b λ g r o u t l n ( r c o r e r p o u t )
Surface of Pipe2
0 = ( T f 2 T s p 2 ) 1 2 π r p i n h l s p 2 + 1   2 π l s p 2 λ p l n ( r p o u t r p i n ) + ( T s h e l l T s p 2 ) 1 2 π l p 2 λ g r o u t l n ( r s h e l l r s p 2 )
Core
c g r o u t ρ g r o u t V c o r e d T c o r e d t = ( T s p 1 T c o r e ) 1 2 π l b λ g r o u t l n ( r c o r e r s p 1 ) + ( T s p 2 T c o r e ) 1 2 π l p 2 λ g r o u t l n ( r s p 2 r c o r e )
Shell
c g r o u t ρ g r o u t V s h e l l d T s h e l l d t = ( T s ( r b , t ) T s h e l l ) 1 2 π l b λ g r o u t l n ( r b r s h e l l ) + ( T s p 2 T s h e l l ) 1 2 π l p 2 λ g r o u t l n ( r s h e l l r s p 2 )
Here, T f 1 i n = T p i n , T f 2 i n = T f 1 o u t , T p o u t = T f 2 o u t . As explained above, the inside of the VSGHEX is regarded as a multilayer cylinder in this paper.
However, the calculation error occurred because the actual configuration of the heat exchanger is spiral as shown at the left in Figure 3. Therefore, the new model is proposed by introducing the equivalent length l p 2 as shown in Equations (4) and (5) to improve the calculation accuracy. In this paper, the equivalent length l p 2 is expressed as the following equation.
l p 2 = d p o u t × ( l p i t c h d p o u t ) c
Here, coefficient c can be expressed as the function of parameters d p o u t , d b , l p i t c h and the parameters are indicated in Figure 3. The coefficient c is determined by comparing the detailed numerical calculation, in which the finite volume method is applied. In order to compare the two calculation methods, the simplified problem shown in Figure 4 was provided. In the simplified problem, the fluid inside the Pipe1 and Pipe2 are not considered. Also, only a part of grout and Pipe2 shown in Figure 4 is considered and the part of Pipe2 is regarded as a ring. The initial and boundary condition are indicated in Figure 4. The parameters d p o u t , d b , l p i t c h (in the numerical calculation), or l p 2 (in the developed method) are changed as shown in Table 1 and the heat transmissions are repeatedly calculated by using the numerical calculation and the developed method. The commercially available numerical software stream Ver. 13 was used for numerical calculation. Then, when the heat transmissions at steady state agree with each other as shown in Figure 5, the value of l p 2 is determined. The values of l p 2 and c are indicated in Table 1. Furthermore, the coefficient c is approximated as the function of parameters d p o u t , d b , l p i t c h by using the multiple linear regression analysis. As the result, the approximate equation of c can be represented in the following equation.
c = 0.826 5.43 d p o u t 0.848 l p i t c h + 0.154 d b   ( R 2 = 0.978 )
Table 2 shows the calculation results of heat transmission at steady state obtained by the numerical calculation and the developed method (Applying the CaRM and l p 2 ). At the maximum, the relative error is 2.1%.

2.2. Calculation Method for Underground Temperature

The ground temperature surrounding the VSGHEX is calculated by applying the ICS model. The GHEX is considered as a hollow cylinder in an infinite medium, and the temperature variation is calculated as a transient heat transfer problem of a two-dimensional cylindrical coordinate system. The temperature change Δ T s ( r b , t ) can be calculated by the following equation, which applies the principle of superposition based on the analytical solution of ICS [13] and Duhamel’s theorem.
Δ T s ( r b , t ) = 1 π 2 r b λ s 0 t q ( τ ) I ( r b , t τ ) t d τ
Now,
I ( r , t ) = 0 ( 1 e a s u 2 t ) J 0 ( u r ) Y 1 ( u r b ) Y 0 ( u r ) J 1 ( u r b ) u 2 [ J 1 2 ( u r b ) + Y 1 2 ( u r b ) ] d u
Also, if the heat injection/extraction from the surface of the underground heat exchanger is considered to occur in a step-wise manner, Equation (9) can be simplified as in Equation (10) [18].
Δ T s ( r b , t ) 1 π 2 r b λ s l = 1 n q l Δ I ( r b , t t l )
Furthermore, Equation (10) is translated to the following equation if the dimensionless quantities t b * = a t / r b 2 , r b * = r b / r b = 1 , and T C * ( 1 , t b * ) = 2 π λ s Δ T C ( r b , t ) / q l ( Δ T C ( r b , t ) = q l π 2 r b , i λ s   I ( r b , i , t ) ) are introduced [17].
Δ T s ( r b , t ) 1 2 π λ s l = 1 n q l Δ T C * ( 1 , t b * t b , l * )
This property has been used to simplify the computation of Δ I ( r b , t t l ) and further speed up the calculation. Having determined q l for each instant from the formula q = ( T s ( r b , t ) T s h e l l ) / ( 1 2 π λ g r o u t l n ( r b r s h e l l ) ) and if the temperature T s ( r b , t ) = T s 0 + Δ T s ( r b , t ) of the external surface of the VSGHEX is calculated, the VSGHEX can be evaluated.
Also, the superposition of the temperature field in space was applied when calculating the underground temperature due to the heat injection/extraction into/from multiple GHEXs. The detail of calculation method for underground temperature due to the heat injection/extraction into/from multiple GHEXs is described in earlier reports [15,16,17]. Furthermore, when the VSGHEXs are applied, there is quite a lot of case where the diameter of borehole is much larger and the borehole depth is much smaller. In this case, in order to consider the influence of heat transfer from the ground surface and the edge of GHEX, the method that calculates the average temperature on the surface of GHEX affected by the ground surface and the edge is applied [15,17].

2.3. Calculation Method for Ground Source Heat Pump System

The operation of the GSHP system was simulated by using the method for calculating the heat carrier fluid and underground temperature described in the previous section. The GSHP system mainly comprises three parts, namely, the indoor unit, the GSHP unit, and the GHEX [12]. The calculation formulas used for each element are shown below. It is assumed that there is no heat loss in the piping connecting the various parts.
(1) Indoor unit
In the indoor unit, it is supposed that hot water with temperature T 2 o u t     is sent to the generated heat load (Heating load) Q 2 to process the load. It is further assumed that only those air conditioners capable of processing the load by the supply of hot water at temperature T 2 o u t are being used.
(2) GSHP unit
Assuming that the coefficient of performance (COP) of the GSHP unit is determined by the primary inlet temperature T 1 i n and the secondary outlet temperature T 2 o u t , it can be expressed as follows.
C O P = f ( T 1 i n , T 2 o u t )
Furthermore, the power consumption E of the heat pump can be obtained from the following equation.
E = Q 2 / C O P
Next, the heat extraction quantity (heat exchange quantity) Q 1 in the primary side evaporator of the GSHP unit can be calculated by the following equation, using Q 2 and E .
Q 1 = Q 2 E
Then, the outlet temperature T 1 o u t in the primary side of the GSHP unit can be calculated using the following equation.
T 1 o u t = T 1 i n Q 1 c 1 f ρ 1 f G 1 f
(3) GHEX
If T 1 o u t is given as the inlet temperature of GHEX T p i n , the outlet temperature of GHEX T p o u t can be calculated by using Equations (1)–(6). If these calculations are carried out repeatedly, the hourly temperature variation can be obtained.

3. Validation of Simulation Model by Comparing with Measurement Data

3.1. Outlines of Measurement

Considering the case of a GSHP system with VSGHEXs installed in a residential house in Miyagi Prefecture, Japan, the temperature change of heat carrier fluid at the outlet of VSGHEXs was calculated, and its reproducibility was verified by comparing with the measured values. The outlines of the residential house are shown in Table 3. The floor area of the residential house is 57 m2, and the Q value (Heat loss coefficient per floor area and temperature difference) is 2.92 W/m2·K. The GSHP system with VSGHEX was installed in the house.
Figure 6 shows the arrangement of VSGHEXs. The number of VSGHEXs was six. Three of the six VSGHEXs had a diameter of 400 mm, and the other three had a diameter of 600 mm. The depth of each VSGHEX was 4 m. The interval of the adjacent VSGHEXs was 3–5 m to prevent a large influence from the neighboring VSGHEX’s injection or extraction. Figure 7 shows the description of GSHP system. A commercially available GSHP unit was installed, and a fan–coil unit was used for heating and cooling. There is an inhabitant in the residential house. In case the resident was absent from home, the temperature setting was fixed, as shown in Table 4. When the inhabitant stayed in the house, the temperature setting depends on the inhabitant.

3.2. Result of Measurement

Figure 8 shows the integrated value of the measured electric energy, heat extraction, and heating output. The system COP (SCOP = heating or cooling output/electric energy of heat pump and circulation pump) is also indicated in Figure 8. The system COPs for the cooling season and heating season were approximately 4.0 and 3.3, respectively. The hourly heating and cooling load is shown in the upper portion of Figure 9, and the temperature variations of heat carrier fluid in the primary side are indicated at the bottom of Figure 9. The temperatures of the heat carrier fluid were changed in response to the heating and cooling load. The supply temperature decreased to approximately 2 °C during the heating period and increased to approximately 30 °C during the cooling period.

3.3. Validation of Calculation

The calculation model of the VSGHEX was integrated into the design and simulation tool for the GSHP system [12,15,16,17]. The accuracy of the tool was verified by comparing with the measurements. The hourly heating and cooling load was given as the condition. Then, the temperature of the heat carrier fluid was simulated by using the tool. Figure 10 shows the supply temperatures of the measurement and calculation, and Figure 11 shows a comparison of the temperatures between measurement and calculation. The error between supply temperatures of the measurements and calculation is approximately 2 °C at the maximum. It can be said that the calculated temperature reproduces the measured one with appropriate accuracy.

4. Estimation of Number of Vertical Spiral Ground Heat Exchangers for a Residential House

Calculation Conditions

By repeating the calculation of heat carrier fluid with changing the conditions of the area, the insulation performance of the residential house, and the thermal conductivity of soil, the required numbers of VSGHEXs were estimated. The floor plan is the same as the standard residential house determined by the Architectural Institute of Japan. The floor area of the house is 125 m2. All the prefectural capital cities in Japan except for Okinawa (46 cities) were selected. It was assumed that the houses have two types of insulation performance, expressed as Q values (heat loss coefficient per floor area and temperature difference) or average U values. Some values were the same as the next-generation energy standard values in Japan, and the others were the lower values, as shown in Table 5. The set temperature is 22 °C for heating and 26 °C for cooling. The hourly heat load was calculated by using a commercially available heat load calculation tool, AE-CAD/AE-Simheat [19]. As example of thermal load calculation, Figure 12 shows the total heating load, the maximum heating load, the total cooling load, and the maximum cooling load when the Q values of next-generation energy standard were given.
The required number of VSGHEXs was defined as the minimum number of VSGHEXs that can satisfy the temperature of heat carrier fluid at the inlet of GSHP’s primary side in the range from −5 °C (Heating) to 35 °C (Cooling). Then, the required number of VSGHEXs was estimated by using the design and simulation tool for the GSHP system integrating the VSGHEX model. The GSHP system description and soil data, which were given as the calculated conditions are shown in Figure 13. It was assumed that the same heat pump as the measurement one was used. The spiral diameter of the VSGHEXs was 500 mm. The depth of the VSGHEXs was 4 m and The VSGHEXs were installed at 1 to 5 m depth. Grout and soil had the same thermal conductivities, which were set at 1.2 and 1.8 W/m·K (these are the thermal conductivities of common unsaturated and saturated sands in Japan). The undisturbed temperatures (=average ambient temperature at each city +1.5 °C) indicated in Figure 14 were used.

5. Result and Discussion

Figure 15 and Figure 16 show the required number of VSGHEXs. Here, in Japan, there is quite a lot of case where the cooling is not operated according to the schedule. In this case, the operation time of cooling is smaller. Therefore, the required numbers of VSGHEXs, that are determined by only the constrains of heating period (T1in > −5 °C), are also shown in Figure 15 and Figure 16. When the thermal conductivity changes from 1.2 W/m·K to 1.8 W/m·K, the required numbers of VSGHEXs can be reduced. In addition, when the Q values were changed from the value of the next-generation energy standard to smaller ones, the numbers of VSGHEXs can be reduced, especially in the case of heating.
Figure 17 shows the relationship between the number of VSGHEXs and the total heating load   Q h and Figure 18 shows the relationship between the number of VSGHEXs and the cooling load   Q c . This figure indicates that the number of VSGHEXs correlates with the total load regardless of the insulation performance of residential house. Also, it seems that the effective thermal conductivity and the undisturbed temperature influence the number of VSGHEXs. Therefore, the required numbers of VSGHEXs are regarded as the function of   Q h or   Q c (The units are MWh), λs and undisturbed (Initial) ground temperature Ts0. The approximate equation of the required number of VSGHEXs is determined by using multiple regression analysis. As a result, Equations (16) and (17) are obtained.
Heating :   n = 14.4 + 0.76   Q h 5.69 λ s 0.11 T s 0   ( R 2 = 0.858 )
Cooling :   n = 20.86 + 3.28   Q c 6.99 λ s 0.27 T s 0   ( R 2 = 0.813 )
By using Equations (12) and (13), the required number of VSGHEXs can be estimated more easily.

6. Conclusions

(1)
A new simulation model for VSGHEXs was developed by combining the ICS model with the CaRM. In this model, the ground temperature surrounding VSGHEX can be calculated by applying the ICS model and the temperatures inside VSGHEX are calculated by CaRM. The developed simulation model can consider the heat capacity inside VSGHEX and provide dynamic calculation with high speed and appropriate precision.
(2)
In order to apply the CaRM, the equivalent length was introduced. Then, the equivalent length was approximated by comparing the results of CaRM and the numerical calculation. As the result, the relative error of heat transmission (thermal resistance) at steady sate between the numerical calculation and the developed method (Applying the CaRM and equivalent length) was 2.1% at the maximum.
(3)
The calculation model of the VSGHEX was integrated into the design and simulation tool for the GSHP system. The accuracy of the tool was verified by comparing with the measurements. The error between supply temperatures of the measurements and calculation is approximately 2 °C at the maximum annually. It can be said that the calculated temperature reproduces the measured one with appropriate accuracy.
(4)
Assuming the GSHP system with VSGHEXs, whose spiral diameter was 500 mm and depth was 4 m, was installed in the residential house in Japan, the required numbers of VSGHEXs were estimated. The results showed a strong correlation between the total heating or cooling load and the required number. Therefore, the required number can be regarded as the function of the total heating or cooling load, the effective thermal conductivity of soil, and the undisturbed ground temperature. Then, the required number can be estimated by using the simplified approximate equation.

Author Contributions

Conceptualization, T.K.; Data curation, T.H. and Y.F.; Investigation, T.K.; Project administration, T.K., H.A. and M.O.; Supervision, Y.S. and K.N.; Validation, T.H. and Y.F.; Writing—original draft, T.K. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by NEDO grant number P14017.

Acknowledgments

This study is based on results obtained from the project “Renewable energy heat utilization technology development,” commissioned by the Japan national agency New Energy and Industrial Technology Development Organization (NEDO). Also, the authors would like to express appreciation to Tohoku-Electric Power Co., Inc. for supporting this research works.

Conflicts of Interest

The authors declare no conflict of interest.

Nomenclature

aThermal diffusivity (m2/s)
cSpecific heat (J/kg·K)
dDiameter (m)
EElectric power consumption of heat pump unit (W)
GFlow rate (m3/s)
hConvective heat transfer rate (W/m2·K)
Jxxth-order Bessel function of first kind (-)
lLength [m]
nNumber of time step (-)
qHeat injection rate per length (W/m)
QHeat extraction, heat load (W)
rRadius (m)
r*Non-dimensional distance (-)
TTemperature (°C)
tTime (h)
t*Non-dimensional time (Fourier number) (-)
T*Non-dimensional temperature (-)
uCharacteristic value (-)
VVolume (m3]
Yxxth-order Bessel function of second kind (-)
λThermal conductivity (W/m·K)
ρDensity (kg/m3)
τParameter relating to time (h)
τ*Non-dimensional parameter relating to time (-)
Subscripts
1Heat pump primary side
1fHeat carrier fluid in the primary side
1inInlet in the primary side
1inOutlet in the primary side
2Heat pump secondary side
bBorehole
CTemperature response of ICS problem
cCooling
coreCore
dDistance
fHeat carrier fluid
f1Heat carrier fluid in Pipe1
f1inHeat carrier fluid at inlet of Pipe1
f1outHeat carrier fluid at outlet of Pipe1
f2Heat carrier fluid in Pipe2
f2inHeat carrier fluid at inlet of Pipe2
f2outHeat carrier fluid at outlet of Pipe2
gGrout
hHeating
lCode number of approximate rectangular step load
nNumber of time step
p2Equivalent (length)
pinInlet of ground heat exchanger
p-inPipe inside
pitchPitch of spiral pipe
poutOutlet of ground heat exchanger
p-outPipe outside
sSoil
s0Soil initial
shellShell
sp1Surface of Pipe1
sp2Spiral pipe (Pipe2), Surface of Pipe2

References

  1. Miyara, A. Thermal performance and pressure drop of spiral-tube ground heat exchangers for ground-source heat pump. Appl. Therm. Eng. 2015, 90, 630–637. [Google Scholar]
  2. Dehghan, B. Experimental and computational investigation of the spiral ground heat exchangers for ground source heat pump applications. Appl. Therm. Eng. 2017, 121, 908–921. [Google Scholar] [CrossRef]
  3. Li, H.; Nagano, K.; Lai, Y. A new model and solutions for a spiral heat exchanger and its experimental validation. Int. J. Heat Mass Transf. 2012, 55, 4404–4414. [Google Scholar] [CrossRef]
  4. Li, H.; Nagano, K.; Lai, Y. Heat transfer of a horizontal spiral heat exchanger under groundwater advection. Int. J. Heat Mass Transf. 2012, 55, 6819–6831. [Google Scholar] [CrossRef]
  5. Go, G.H.; Lee, S.R.; Yoon, S.; Kang, H.B. Design of spiral coil PHC energy pile considering effective borehole thermal resistance and groundwater advection effects. Appl. Energy 2014, 125, 165–178. [Google Scholar] [CrossRef]
  6. Zhang, W.; Yang, H.; Lu, L.; Cui, P.; Fang, Z. The research on ring-coil heat transfer models of pile foundation ground heat exchangers in the case of groundwater seepage. Energy Build. 2014, 71, 115–128. [Google Scholar] [CrossRef]
  7. Li, M.; Lai, A.C. Heat-source solutions to heat conduction in anisotropic media with application to pile and borehole ground heat exchangers. Appl. Energy 2012, 96, 451–458. [Google Scholar] [CrossRef]
  8. Zarrella, A.; De Carli, M. Heat transfer analysis of short helical borehole heat exchangers. Appl. Energy 2013, 102, 1477–1491. [Google Scholar] [CrossRef]
  9. Zarrella, A.; Capozza, A.; De Carli, M. Performance analysis of short helical borehole heat exchangers via integrated modelling of a borefield and a heat pump: A case study. Appl. Therm. Eng. 2013, 61, 36–47. [Google Scholar] [CrossRef]
  10. Zarrella, A.; De Carli, M.; Galgaro, A. Thermal performance of two types of energy foundation pile: Helical pipe and triple U-tube. Appl. Therm. Eng. 2013, 61, 301–310. [Google Scholar] [CrossRef]
  11. Zarrella, A.; Emmi, G.; De Carli, M. Analysis of operating modes of a ground source heat pump with short helical heat exchangers. Energy Convers. Manag. 2015, 97, 351–361. [Google Scholar] [CrossRef]
  12. Nagano, K.; Katsura, T.; Takeda, S. Development of a design and performance prediction tool for the ground source heat pump system. Appl. Therm. Eng. 2006, 26, 1578–1592. [Google Scholar] [CrossRef]
  13. Carslaw, H.S.; Jaeger, J.C. Conduction of Heat in Solid; Oxford University Press: Oxford, UK, 1959. [Google Scholar]
  14. Deerman, J.D.; Kavanaugh, S.P. Simulation of Vertical U-tube Ground-coupled Heat Pump Systems Using the Cylindrical Heat Source Solution. ASHRAE Trans. 1990, 97, 287–295. [Google Scholar]
  15. Katsura, T.; Nagano, K.; Takeda, S. Method of calculation of the ground temperature for multiple ground heat exchangers. Appl. Therm. Eng. 2008, 28, 1995–2004. [Google Scholar] [CrossRef]
  16. Katsura, T.; Nagano, K.; Narita, S.; Takeda, S.; Nakamura, Y.; Okamoto, A. Calculation Algorithm of the Temperatures for Pipe Arrangement of Multiple Ground Heat Exchangers. Appl. Therm. Eng. 2009, 29, 906–919. [Google Scholar] [CrossRef]
  17. Katsura, T.; Nagano, K.; Sakata, Y.; Higashitani, T. A Design and Simulation Tool for Ground Source Heat Pump System and Borehole Thermal Storage System. In Proceedings of the 14th International Conference on Energy Storage EnerSTOCK2018, Adana, Turkey, 25–28 April 2018. [Google Scholar]
  18. Li, S.; Dong, K.; Wang, J.; Zhang, X. Long term coupled simulation for ground source heat pump and underground heat exchangers. Energy Build. 2015, 106, 13–22. [Google Scholar] [CrossRef]
  19. Architecture Environment Solutions: AE-CAD/AE-Simheat. Available online: http://www.ae-sol.co.jp/aesol01.html (accessed on 6 July 2018).
Figure 1. Concept of applying the CaRM to vertical spiral ground heat exchanger (VSGHEX).
Figure 1. Concept of applying the CaRM to vertical spiral ground heat exchanger (VSGHEX).
Energies 13 01339 g001
Figure 2. Concept of applying the CaRM to VSGHEX (Plane view).
Figure 2. Concept of applying the CaRM to VSGHEX (Plane view).
Energies 13 01339 g002
Figure 3. Concept of transformation from spiral pipe to cylinder and equivalent length lp2.
Figure 3. Concept of transformation from spiral pipe to cylinder and equivalent length lp2.
Energies 13 01339 g003
Figure 4. Simplified problem to compare the CaRM and numerical calculation.
Figure 4. Simplified problem to compare the CaRM and numerical calculation.
Energies 13 01339 g004
Figure 5. Example of comparison of heat transmissions between the CaRM and numerical calculation.
Figure 5. Example of comparison of heat transmissions between the CaRM and numerical calculation.
Energies 13 01339 g005
Figure 6. Arrangement of VSGHEXs and ground source heat pump (GSHP) system on plane view.
Figure 6. Arrangement of VSGHEXs and ground source heat pump (GSHP) system on plane view.
Energies 13 01339 g006
Figure 7. Description of GSHP system installed in residential house.
Figure 7. Description of GSHP system installed in residential house.
Energies 13 01339 g007
Figure 8. Integrated value of electric energy, heat extraction (injection) and heating (cooling) output.
Figure 8. Integrated value of electric energy, heat extraction (injection) and heating (cooling) output.
Energies 13 01339 g008
Figure 9. Hourly variation of heating and cooling load (Top) and temperature variations of heat carrier fluid in the primary circuit (Bottom).
Figure 9. Hourly variation of heating and cooling load (Top) and temperature variations of heat carrier fluid in the primary circuit (Bottom).
Energies 13 01339 g009
Figure 10. Supply temperatures obtained by measurement and calculation.
Figure 10. Supply temperatures obtained by measurement and calculation.
Energies 13 01339 g010
Figure 11. Comparison of the temperatures between measurement and calculation.
Figure 11. Comparison of the temperatures between measurement and calculation.
Energies 13 01339 g011
Figure 12. Total heating load, maximum heating load, total cooling load, and maximum cooling load (Q values are the same as the next-generation energy standard values).
Figure 12. Total heating load, maximum heating load, total cooling load, and maximum cooling load (Q values are the same as the next-generation energy standard values).
Energies 13 01339 g012
Figure 13. Calculated conditions.
Figure 13. Calculated conditions.
Energies 13 01339 g013
Figure 14. Undisturbed ground temperature (Initial ground temperature) at each city.
Figure 14. Undisturbed ground temperature (Initial ground temperature) at each city.
Energies 13 01339 g014
Figure 15. Required number of VSGHEXs (λs = 1.8 W/m·K, Q values are the same as the next-generation energy standard values).
Figure 15. Required number of VSGHEXs (λs = 1.8 W/m·K, Q values are the same as the next-generation energy standard values).
Energies 13 01339 g015
Figure 16. Required number of VSGHEXs (λs = 1.2 W/m·K, Q values are the same as the values of ‘high insulated’ in Table 5).
Figure 16. Required number of VSGHEXs (λs = 1.2 W/m·K, Q values are the same as the values of ‘high insulated’ in Table 5).
Energies 13 01339 g016
Figure 17. Relationship between the number of VSGHEXs and total heating load.
Figure 17. Relationship between the number of VSGHEXs and total heating load.
Energies 13 01339 g017
Figure 18. Relationship between the number of VSGHEXs and total cooling load.
Figure 18. Relationship between the number of VSGHEXs and total cooling load.
Energies 13 01339 g018
Table 1. Parameters for calculation.
Table 1. Parameters for calculation.
Tube Diameter dp-out (m)Borehole Diameter db (mm)Spiral Pitch lpitch (mm)Coefficient Clp2 (mm)
CASE116450600.77137.8
CASE216450350.76224.6
CASE3164501400.69357.6
CASE416800600.82442.1
CASE516800350.83227.3
CASE6168001400.73465.4
CASE7204501400.67258.9
CASE8254501400.640 58.7
Table 2. Heat transmission obtained by the numerical calculation and the developed method.
Table 2. Heat transmission obtained by the numerical calculation and the developed method.
NumericalCaRMRelative Error (%)
CASE114.06 13.86 1.4
CASE215.11 15.34 1.5
CASE310.58 10.50 0.8
CASE415.84 15.60 1.5
CASE516.93 16.94 0.1
CASE612.04 12.29 2.1
CASE711.31 11.24 0.6
CASE812.15 12.18 0.2
Table 3. Outlines of residential house.
Table 3. Outlines of residential house.
Year of completion2016/1
Total floor area57 m2
Floor On-storied house
Q value2.92 W/m2·K
Table 4. Set temperature for air-conditioning.
Table 4. Set temperature for air-conditioning.
PeriodSet Temperature (°C)Area of AC (m2)
13 Jan.–16 Mar.2031
Arbitrarily31
15 Jun.–30 Sep.2446
Arbitrarily31
1 Nov.–31 Dec.2231
Arbitrarily 31
Table 5. Insulation performance (Q value and average U value) of residential house.
Table 5. Insulation performance (Q value and average U value) of residential house.
Name of CityQ Value(W/m2 K)
Next-Generation Energy Standard ValueHigh Insulated
Sapporo1.61
Morioka, Nagano1.91.3
Aomori, Akita, Yamagata, Sendai, Fukushima, Toyama2.41.9
Others 2.72

Share and Cite

MDPI and ACS Style

Katsura, T.; Higashitani, T.; Fang, Y.; Sakata, Y.; Nagano, K.; Akai, H.; OE, M. A New Simulation Model for Vertical Spiral Ground Heat Exchangers Combining Cylindrical Source Model and Capacity Resistance Model. Energies 2020, 13, 1339. https://doi.org/10.3390/en13061339

AMA Style

Katsura T, Higashitani T, Fang Y, Sakata Y, Nagano K, Akai H, OE M. A New Simulation Model for Vertical Spiral Ground Heat Exchangers Combining Cylindrical Source Model and Capacity Resistance Model. Energies. 2020; 13(6):1339. https://doi.org/10.3390/en13061339

Chicago/Turabian Style

Katsura, Takao, Takashi Higashitani, Yuzhi Fang, Yoshitaka Sakata, Katsunori Nagano, Hitoshi Akai, and Motoaki OE. 2020. "A New Simulation Model for Vertical Spiral Ground Heat Exchangers Combining Cylindrical Source Model and Capacity Resistance Model" Energies 13, no. 6: 1339. https://doi.org/10.3390/en13061339

APA Style

Katsura, T., Higashitani, T., Fang, Y., Sakata, Y., Nagano, K., Akai, H., & OE, M. (2020). A New Simulation Model for Vertical Spiral Ground Heat Exchangers Combining Cylindrical Source Model and Capacity Resistance Model. Energies, 13(6), 1339. https://doi.org/10.3390/en13061339

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop