Article

Finite Element Modeling of Geothermal Source of Heat Pump in Long-Term Operation †

AGH University of Science and Technology, Faculty of Geology, Geophysics and Environmental Protection, 30-059 Krakow, Poland
*
Author to whom correspondence should be addressed.
This paper is an extended version of article presented at the 6th Scientific Conference Renewable Energy Systems, Engineering, Technology, Innovation ICoRES 2019, to be published in E3S Web of Conferences.
Energies 2020, 13(6), 1341; https://doi.org/10.3390/en13061341
Submission received: 31 January 2020 / Revised: 10 March 2020 / Accepted: 11 March 2020 / Published: 13 March 2020

Abstract

:
Model simulation allows to present the time-varying temperature distribution of the ground source for heat pumps. A system of 25 double U-shape borehole heat exchangers (BHEs) in long-term operation and three scenarios were created. In these scenarios, the difference between balanced and non-balanced energy load was considered as well as the influence of the hydrogeological factors on the temperature of the ground source. The aim of the study was to compare different thermal regimes of BHEs operation and examine the influence of small-scale and short-time thermal energy storage on ground source thermal balance. To present the performance of the system according to geological and hydrogeological factors, a Feflow® software (MIKE Powered by DHI Software) was used. The temperature for the scenarios was visualized after 10 and 30 years of the system’s operation. In this paper, a case is presented in which waste thermal energy from space cooling applications during summer months was used to upgrade thermal performance of the ground (geothermal) source of a heat pump. The study shows differences in the temperature in the ground around different Borehole Heat Exchangers. The cold plume from the not-balanced energy scenario is the most developed and might influence the future installations in the vicinity. Moreover, seasonal storage can partially overcome the negative influence of the travel of a cold plume. The most exposed to freezing were BHEs located in the core of the cold plumes. Moreover, the influence of the groundwater flow on the thermal recovery of the several BHEs is visible. The proper energy load of the geothermal source heat pump installation is crucial and it can benefit from small-scale storage. After 30 years of operation, the minimum average temperature at 50 m depth in the system with waste heat from space cooling was 2.1 °C higher than in the system without storage and 1.6 °C higher than in the layered model in which storage was not applied.

1. Introduction

Increasing climate change awareness and the popularity of renewable energy sources are connected with the increasing attention to geothermal energy and devices such as heat pumps. According to [1], in 2050, electric heat pumps will become more common in most parts of the world. In 2017, there were 10,572,395 heat pumps units in operation in Europe [2]. This number is growing constantly. The main advantage of a heat pump solution is the possibility of providing not only heating during cold periods, but also space cooling during summer hot days. Ground source heat pumps (GSHP) are a popular solution, especially for bigger installations. Several regional studies of the shallow geothermal potential of heat pumps in different geological conditions have been conducted, for example, in Japan [3], Germany [4], and Finland [5]. The efficiency of the system and the economic advantage should be estimated for each specific case [6].
The increase in popularity of geothermal source heat pumps may create future problems regarding the space available for new ground sources and the negative influence of neighbouring heat exchangers and their arrays on each other [7]. Therefore, evaluating of the thermal impact is crucial for high-density Ground Source Heat Pumps (GSHP) [8].
Knowing hydrogeological conditions and the performance of the ground source system is very important for its exploitation [9]. Thermal parameters and ground water flow can have a significant effect on the development of borehole heat exchangers systems [10] and the temperature recovery rate [11]. In cases in which the layout is sufficiently constructed, the ground water flow can improve the long-term operation conditions [12]. The influence of groundwater flow on storage systems has also been investigated [13].
Several studies considered the performance of the ground sources at different times of operation, —for example [14]—during 15 years and the optimization of borehole heat exchangers (BHE) for both deep [15] and shallow units [16]. Typically, the ground source heat pump itself is considered to work for about 20 years [17]. However, the heat source may operate longer, for 30 or even 50 years. Therefore, it is crucial to conduct long-term modelling [18] and measurements of such systems [19]. Ground temperature changes depend on the annual heat imbalance between injected and extracted heat rate [20]. According to [21], the soil’s thermal imbalance provides problems like soil temperature decrease, heating performance deterioration and a decline of the heating reliability. Moreover, there is a risk of the influence of the remaining thermal imbalance on new installations. There is also a need to provide more efficient heating/cooling applications. In this context, a seasonal thermal energy storage is gaining attention. Several applications of thermal energy storage implement Borehole Thermal Energy Storage (BTES) [22], often associated with solar [23] or waste heat [24] or developed for industrial projects [25]. These research projects regard mostly larger installations.
This paper presents a case in which waste thermal energy from space cooling applications during the summer months was used to upgrade the thermal performance of the ground source. Thirty years of operation of the system was used for the simulation.
The aim of the study was to compare the different thermal regimes of BHEs’ operation and examine the influence of small-scale and short-time thermal energy storage on ground source thermal balance. In the study, three-dimensional modelling of 25 borehole heat exchangers (ground source) was carried out in order to determine the performance of the system in long-term operation. It is assumed that ground temperature partially regenerates during the summer months due to space cooling in central Poland conditions.
The simulation allows to show the temperature distribution in the ground source for the heat pump. The temperature distribution and the cold plume are affected by the ground water flow and its nature as well as the balancing of the energy load. The central Poland study area was chosen because of recent intensive deep geothermal research in this area [26]. An added value of this research is that it provides another option to compare different geothermal applications in the area.

2. Materials and Methods

This study presents a hypothetical system of a ground source for heat pumps implemented for central Poland conditions. To present the performance of the system according to its geological and hydrogeological factors, a Feflow® software (MIKE Powered by DHI Software, Hørsholm, Denmark) was used. The software provides Finite Element Modeling of Flow, Mass and Heat Transport in Porous and Fractured Media. The nodes belong to the boreholes were coupled to the rest of the modelled area [11]. Borehole heat exchangers (BHEs) were modeled according to [27]. A BHE is considered as a specific fourth type of boundary condition (BC) [28] which applies a predefined extraction or injection of thermal energy to a model [29].

2.1. The Model

A non-uniform grid of the area was used. In the vicinity of wells, grid points were refined to obtain a better accuracy (Figure 1). Optimal mesh refinement for nodes around BHEs were calculated according to the Nillert method [27]. The total model dimensions were set to 240 × 240 × 105 m. The mesh consists of 169,477 elements and 92,940 nodes.
To minimalize the influence on the result and calculation time, the size of the model domain was chosen after pre-calculations. Moreover, the second type of boundary conditions were applied to the model’s northern and southern edges. A larger domain size does not affect the results. All boundary conditions applied to the models’ domain are given in Figure 2. There were 3 types of boundary conditions applied in this model: the 1st boundary condition (Dirichlet) is temperature applied at the top surface; the 2nd boundary condition (Neumann) is heat-flux at the bottom surface and fluid-flux applied at the edges or in the aquifer elements (in the 3rd scenario); the 4th boundary conditions are borehole heat exchangers.
The multiple system considered consists of 25 borehole heat exchangers (BHEs). They are in 5 × 5 layout with 10-m spacing. The spacing was chosen to fulfill the heat pump’s branch recommendations [30]. The BHEs are not connected in arrays, all (equal) parameters are set for single BHE. Each BHE is 100 m in length, which equates to 2500 m of heat exchangers’ total length. The exchangers were of the double U-shaped type, which consist of two inlet pipes and two outlet pipes surrounded by grout (Figure 3). A single BHE setting is provided in Table 1.
In the simulation, an Eskilson and Claesson [31] (quasi-stationary) method, which assumes the local thermal equilibrium between all the elements of BHE during the whole time of the simulation, was applied.
The difference in thermal energy per time between inlet and outlet of BHE is variable. It was set according to energy demand on a given day. The BHEs did not work longer than 6 hours a day. Their power was variable, from 0 to 3 kW. Each simulation was run for 30 years (262,800 h).

2.2. Thermal and Hydrogeological Settings

The model is considered as fully saturated. The initial temperature condition across the model was set to 9 °C (referenced ground temperature in the central Poland area). To show the thermal regime, heat flux from the ground during the year was set to the top surface according to the change of the earth’s surface monthly average temperature (Table 2). Earth’s temperature for the central Poland area is provided. These values were set as the first type of boundary conditions. Moreover, a geothermal heat flux of 0.06 W/m2 assessed for this area was applied to the base surface of the model.
The BHE system was operating according to the assessed monthly load, as shown in Table 2.
In order to compare different operating regimes, three scenarios were taken into consideration:
  • 1st scenario: homogeneous parameters of the ground source, not balanced energy load (only heating in winter)
  • 2nd scenario: homogeneous parameters of the ground source, partially balanced energy load (heating in winter and cooling in summer)
  • 3rd scenario: parameters according to different layers of the model, not balanced energy (only heating in winter).
The hydrogeological and thermal parameters are shown in Table 3. The initial conditions of the models were obtain by applying the simulation in steady-state conditions first.
The area was poorly recognized in the field of shallow geothermal energy and this study reflects some assumptions according to thermal and hydrogeological parameters in the area. The model is considered as the confined one. Aquifers have good flow conditions. The fluid flow direction is from the south to the north, as the fluid flux speed is constant, being limited by groundwater conductivity. Other borders of the model are defined as impermeable. The geological settings of the model are based on variability observed in boreholes located in the vicinity of Poddebice town, central Poland [33].
In the 1st and 2nd scenarios, the whole model had good porosity and permeability conditions and the groundwater flowed throughout the model. In the 3rd scenario, the permeability conditions worsened and the water flow was mostly limited to an aquifer of 10 m. The aquifer layer has better conditions of thermal and fluid conductivity (Figure 4).

3. Results and Discussion

In this project, three sets of simulations were run to verify different scenarios for the performance of heat pump geothermal heat exchangers. For each simulations, two check-points were selected: after 10 and 30 years of the system operation, at 87,600 and 262,800 h, respectively.

3.1. First Scenario: Homogeneous Parameters of the Ground Source, Not Balanced Energy Load

According to the simulation, the temperature of the ground decreased with time. At the beginning stage, the drop of temperature was most visible in the centre between BHEs. The difference in temperature between the points of the minimum temperature and the surrounding domain after the first year of operation is ca. 4.5 °C. Later, the influence of the water flow was more visible in the model and since the second year of the system operation, the points with minimum temperature shifted towards the north. At the same time, different BHEs started to work on different ground parameters. In Figure 5, the temperature model is presented for a depth of 50 m (the mid-section of the BHE). After 10 years of system operation (A), an increase in the cold plume can be observed. The range of the model zone where the temperature dropped to 5 °C was ca. 45 m from the centre of the BHE system and ca. 24 m from the BHE on the edge. During this time, the minimum ground temperature dropped to 0.1 °C.
After 30 years of system operation (B), the decrease of temperature was even more visible and the cold plume travelled further north due to the fluid flow conditions. The minimum average temperature at the same surface of 50 m depth was −0.7 °C, which implies the risk of ground freezing. Particularly, the refrigeration fluid temperature in several BHEs can even drop to −3.5 °C. After 30 years of system operation (B), the range of the model zone in which the temperature dropped to 5 °C was ca. 100 m from the centre of the BHE system and ca. 75 m from the BHE on the north edge. The distribution of temperature in 3D view is shown in Figure 6.
In the most affected BHEs, the average working fluid’s temperature decreased significantly during the first 15 years of operation. Then, the drop of the temperature was rather small as time passed (Figure 7). The difference between the warmest and the coldest BHE’s average temperature in this layout is 4.5 °C after 30 years of operation.
The ground water flow provides the differences in temperature. The temperature in some BHEs (in the centre and north) dropped due the cold plume travelling. However, water of a higher temperature moved from the south to the BHE system. The southern edges of BHE system, which recover faster, have a higher temperature. In fact, the average temperature in the southern BHEs was almost constant after the initial first few years. For example, the minimal average temperature of the BHE on the southern edge stayed at level of ca. 4 °C after the fifth year.
The vertical distribution of temperature is given in Figure 8. In cross-sections A-A’ and B-B’, it is clearly visible that the northern side of the BHE system has a significantly lower temperature than the southern one. The BHEs’ had an influence on each other and there was a decrease in temperature in the central BHEs.

3.2. Second Scenario: Homogeneous Parameters of the Ground Source, Balanced Energy Load (Heating in Winter and Cooling in Summer)

A balanced energy load affects the drop in the system’s temperature less. The average temperature of the system did not drop below 1 °C during the 30 years of operation.
At the beginning stage, the drop in temperature is the most visible in the centre, between BHEs. The difference in temperature between the points of the minimum temperature and the surrounding domain after the first year of operation is ca. 4.4 °C.
Starting from the second year, different BHEs started to work on different ground parameters due to the interaction between the BHEs and water flow. In Figure 9, the temperature model is presented for a depth of 50 m (the mid-section of the BHE). After 10 years of system operation (A), the zone with a temperature of 5 °C was concentrated near BHEs and was not present outside of the BHEs layout.
The distribution and layout of the temperature in the 3D model is provided in Figure 9. After 10 years of operation, the minimum ground temperature dropped to 1.9 °C at a 50-m depth.
After 30 years of system operation (Figure 10), despite the partly balanced energy load, there is a cold plume observed to be travelling north, according to the fluid flow direction. However, its shape is more slender than those observed in the first scenario. The range of the model zone in which the temperature dropped to 5 °C is ca. 50 m from the centre of the BHE system and ca. 30 m from the BHE on the north edge. The minimum average temperature at the surface of a 50 m depth was 1.4 °C, which dismiss the risk of ground freezing.
In the most affected BHEs, the temperature decreased significantly during the first 15 years of operation. Then, the drop in temperature was rather small over time (Figure 11). The difference between the warmest and the coldest BHE’s average temperature was ca. 3.1 °C after 30 years of operation.
The vertical distribution of the temperature is given in Figure 12. In cross-sections A-A’ and B-B’, smaller difference between the northern and southern site can be observed compared to the first scenario. The influence of the system into the neighboring ground is lower than in the first scenario (C-C’, D-D’). As the groundwater flow was set as homogenous, the BHEs in the centre were the most affected by the heat withdrawal.

3.3. Third Scenario (Layered Model): Parameters According to Different Layers of the Model, Not Balanced Energy (Only Heating in Winter)

In Figure 13, the temperature of the ground source is shown after 10 and 30 years of the simulation at a 50-m depth. After 10 years of system operation, the temperature at a depth of 50 m was 2.7 °C. The cold plume is rather round-shaped and did not shift significantly towards the north (it was not affected by the ground water flow).
After 30 years of operation, the cold plume travelled slightly north and was slightly more visible in the permeable layers. At a depth of 50 m, the range of the model zone in which the temperature dropped to 5 °C was ca. 45 m from the centre of the BHE system and ca. 25 m from the BHE on the northern edge. The most visible decrease of the temperature is observed inside the BHEs’ system layout (Figure 14).
In the northern BHEs, there is a risk of ground freezing, while the ground temperature can drop to −0.2 °C (layers with the worst thermal conditions). At the same time, the average temperature of the refrigerant can be as low as −2 °C at the coldest time of the season (Figure 15). The figure shows the average temperature of BHE’s working fluid temperature within the 3rd scenario (system without cooling) within a single year. This was for the last and 30th year considered in the simulation.
Figure 16 depicts differences in the vertical distribution of temperature around BHEs. Some sections or layers interfered more strongly than the others due to the different hydrogeological and thermal parameters of the layers. The influence of the groundwater flow in the aquifer is less significant to the system.
Figure 17 shows the comparison between the cold plumes that appeared after 30 years of operation for the different scenarios. A temperature value of 5 °C was arbitrary chosen as the cold plume boundary. Normally, heat pumps can work on temperatures below 5 °C; however, lower temperatures are no clearly visible in these 3D models.
The cold plume from the 1st scenario is the most developed in length and width. It travelled further to the north according to the ground flow direction. This BHE system might threats future installations in the vicinity.
In the 2nd scenario, due to the balanced energy load and energy storage, the range of the cold plume is definitely smaller, even also directed to the north (groundwater flow). Moreover, thermal energy storage (understood here as cooling of space in summer) can partially overcome the negative influence of traveling of a cold plume.
The most exposed to freezing are BHEs from the north edge of the system located at the core of the plumes. In the 1st and 2nd scenario, the influence of the groundwater flow on the thermal recovery of the southern BHEs is clearly visible. They worked with a higher temperature regime the whole time.
In the 3rd scenario, where the best groundwater conditions are limited to the aquifer, the heat conductions have a greater influence on the system (more rounded shape of the plume). There was no significant thermal recovery in the south. The cold plume travelled much more slowly to the north (similarly to the 2nd scenario with a balanced energy load) and the cold plume shift was slight.
The model allows to simulate the time-varying temperature of the ground source for heat pumps. The temperature regime is important for proper heat pump operation. Even the ground source heat pumps can work with a temperature below 0 °C; this temperature is associated with the freezing of the ground and water in the BHE vicinity, which can have a negative impact on the BHE itself (cracks, air presence, etc.) [30]. It was observed that after 15 years, the system’s temperature stabilized and the system’s elements worked with similar parameters. However, after that long period of exploitation, there is a risk of ground freezing in several locations. It is important to determine how the cold plume location changes, how it propagates and how BHEs interfere with each other and with the cold plume.
In the layered model, the influence of the groundwater flow was limited to the aquifer and provided lower temperatures in the centre BHEs. The thermal parameters’ diversity in each section of the BHE have a lower influence on the thermal layout of the whole system than the balanced energy load. This balance can be obtained by small-scale and short-time thermal energy storage, which requires the use of waste heat from space cooling during the summer months. In the system with small-scale energy storage, the zone of a temperature of 5 °C is two times smaller and the cold plume does not travel as far as in the system without storage.
The proper energy load of the geothermal source heat pump installation is crucial, and it can benefit from small-scale storage. After 30 years of operation, the minimum average temperature at a 50-m of depth in the system with waste heat from space cooling was 2.1 °C higher than in the system without storage and 1.6 °C higher than in the layered model where storage was not applied.
The groundwater flow influences the improvement of parameters of BHEs located in the south (in the model). At the same time, it shifts the cold plume to the north, which negatively influences the northern BHEs. BHEs that are the most affected by the cold plume or by interference with other BHEs can be found thanks to the simulation.
Balanced energy load (including e.g., summer cooling) can increase system efficiency by providing higher temperatures. The study shows differences in the temperature in the ground around BHEs. Therefore a proper layout of the BHE system can be adopted prior to the system construction.

4. Conclusions

Geological and hydrogeological conditions have a great impact on BHEs’ system performance. Thus, good recognition of the parameters and suitable long-term simulation are necessary prior to installing a sustainable ground source for heat pumps. Installations with seasonal storage (if possible) are preferred for long-time operation due to their better ground thermal recovery which causes a higher effectiveness of heat pumps’ installation and prevents ground freezing. FEM modelling of such installations would answer the question of whether a given heat pump and BHE’s installation can work efficiently in specific conditions and locations of installation.

Author Contributions

Methodology E.H.; validation, E.H. and L.P.; writing—original draft preparation, E.H.; writing—review and editing, B.P. and L.P.; supervision, L.P. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by AGH University of Science and Technology statutory work No. 16.16.140.315/05.

Acknowledgments

This research was supported by DHI by making the mentioned MIKE Powered by DHI Software available for the research. I would thank DHI for support. Although, they may not agree with all of the interpretations/conclusions of this paper.

Conflicts of Interest

The authors declare no conflict of interest. The funders had no role in the design of the study; in the collection, analyses, or interpretation of data; in the writing of the manuscript, or in the decision to publish the results.

References

  1. IRENA. Global Energy Transformation. A Roadmap to 2050; International Renewable Energy Agency (IRENA): Abu Dhabi, UAE, 2018; ISBN 978-92-9260-059-4. [Google Scholar]
  2. EHPA. The European Heat Pump Market and Statistics Report 2018; European Heat Pump Association: Brussels, Belgium, 2018. [Google Scholar]
  3. Ishihara, T.; Shrestha, G.; Kaneko, S.; Uchida, Y. Analysis of Shallow Subsurface Geological Structures and Ground Effective Thermal Conductivity for the Evaluation of Ground-Source Heat Pump System Installation in the Aizu Basin, Northeast Japan. Energies 2018, 11, 2098. [Google Scholar] [CrossRef] [Green Version]
  4. Agemar, T.; Schellschmidt, R.; Schulz, R. Subsurface temperature distribution in Germany. Geothermics 2012, 44, 65–77. [Google Scholar] [CrossRef]
  5. Janiszewski, M.; Caballero Hernández, E.; Siren, T.; Uotinen, L.; Kukkonen, I.; Rinne, M. In Situ Experiment and Numerical Model Validation of a Borehole Heat Exchanger in Shallow Hard Crystalline Rock. Energies 2018, 11, 963. [Google Scholar] [CrossRef] [Green Version]
  6. Christodoulides, P.; Aresti, L.; Florides, G. Air-conditioning of a typical house in moderate climates with Ground Source Heat Pumps and cost comparison with Air Source Heat Pumps. Appl. Therm. Eng. 2019, 158, 113722. [Google Scholar] [CrossRef]
  7. Tolooiyan, A.; Hemmingway, P. A preliminary study of the effect of groundwater flow on the thermal front created by borehole heat exchangers. Int. J. Low-Carbon Technol. 2014, 9, 284–295. [Google Scholar] [CrossRef]
  8. Meng, B.; Vienken, T.; Kolditz, O.; Shao, H. Evaluating the thermal impacts and sustainability of intensive shallow geothermal utilization on a neighborhood scale: Lessons learned from a case study. Energy Convers. Manag. 2019, 199, 111913. [Google Scholar] [CrossRef]
  9. Li, Y.; Geng, S.; Han, X.; Zhang, H.; Peng, F. Performance Evaluation of Borehole Heat Exchanger in Multilayered Subsurface. Sustainability 2017, 9, 356. [Google Scholar] [CrossRef] [Green Version]
  10. Li, M.; Mao, J.; Xing, Z.; Zhou, J.; Li, Y. Analysis of geo-temperature restoration performance under intermittent operation of borehole heat exchanger fields. Sustainability 2016, 8, 35. [Google Scholar] [CrossRef] [Green Version]
  11. Emad Dehkordi, S.; Schincariol, R.A.; Olofsson, B. Impact of groundwater flow and energy load on multiple borehole heat exchangers. Groundwater 2015, 53, 4. [Google Scholar] [CrossRef]
  12. Capozza, A.; De Carli, M.; Zarrella, A. Investigations on the influence of aquifers on the ground temperature in ground-source heat pump operation. Appl. Energy 2013, 107, 350–363. [Google Scholar] [CrossRef]
  13. Mielke, P.; Bauer, D.; Homuth, S.; Götz, A.E.; Sass, I. Thermal effect of a borehole thermal energy store on the subsurface. Geotherm. Energy 2014, 2, 5. [Google Scholar] [CrossRef] [Green Version]
  14. Chan Choi, J.; Park, J.; Rae Lee, S. Numerical evaluation of the effects of groundwater flow on borehole heat exchanger arrays. Renew. Energy 2013, 52, 230–240. [Google Scholar] [CrossRef]
  15. Pan, S.; Kong, Y.; Chen, C.; Pang, Z.; Wang, J. Optimization of the utilization of deep borehole heat exchangers. Geotherm. Energy 2020, 8, 6. [Google Scholar] [CrossRef]
  16. Kumar, S.; Murugesan, K. Optimization of geothermal interaction of a double U-tube borehole heat exchanger for space heating and cooling applications using Taguchi method and utility concept. Geothermics 2020, 83, 101723. [Google Scholar] [CrossRef]
  17. Ma, W.; Kim, M.K.; Hao, J. Numerical Simulation Modeling of a GSHP and WSHP System for an Office Building in the Hot Summer and Cold Winter Region of China: A Case Study in Suzhou. Sustainability 2019, 11, 3282. [Google Scholar] [CrossRef] [Green Version]
  18. Bae, S.M.; Nam, Y.; Shim, B.O. Feasibility Study of Ground Source Heat Pump System Considering Underground Thermal Properties. Energies 2018, 11, 1786. [Google Scholar] [CrossRef] [Green Version]
  19. Bockelmann, F.; Fisch, M.N. It Works—Long-Term Performance Measurement and Optimization of Six Ground Source Heat Pump Systems in Germany. Energies 2019, 12, 4691. [Google Scholar] [CrossRef]
  20. Capozza, A.; Zarrella, A.; De Carli, M. Long-term analysis of two GSHP systems using validated numerical models and proposals to optimize the operating parameters. Energy Build. 2015, 93, 50–64. [Google Scholar] [CrossRef]
  21. You, T.; Wu, W.; Shi, W.; Wang, B.; Li, X. An overview of the problems and solutions of soil thermal imbalance of ground-coupled heat pumps in cold regions. Appl. Energy 2016, 177, 515–536. [Google Scholar] [CrossRef]
  22. Janiszewski, M.; Siren, T.; Uotinen, L.; Oosterbaan, H.; Rinne, M. Effective Modelling of Borehole Solar Thermal Energy Storage Systems in High Latitudes. Geomech. Eng. 2018, 16, 503–512. [Google Scholar]
  23. Naranjo-Mendoza, C.; Oyinlola, M.A.; Wright, A.J.; Greenough, R.M. Experimental study of a domestic solar-assisted ground source heat pump with seasonal underground thermal energy storage through shallow boreholes. Appl. Therm. Eng. 2019, 162, 114218. [Google Scholar] [CrossRef]
  24. Skarphagen, H.; Banks, D.; Frengstad, B.S.; Gether, H. Design Considerations for Borehole Thermal Energy Storage (BTES): A Review with Emphasis on Convective Heat Transfer. Geofluids 2019, 4961781. [Google Scholar] [CrossRef]
  25. Nilsson, E.; Rohdin, P. Performance evaluation of an industrial borehole thermal energy storage (BTES) project e Experiences from the first seven years of operation. Renew. Energy 2019, 143, 1022–1034. [Google Scholar] [CrossRef]
  26. Sowiżdżał, A.; Hajto, M.; Hałaj, E. Thermal waters of central Poland: A case study from Mogilno–Łódź Trough, Poland. Environ. Earth Sci. 2020, 79, 112. [Google Scholar] [CrossRef] [Green Version]
  27. Diersch, H.J.G. FEFLOW; Springer: Berlin/Heidelberg, Germany, 2014. [Google Scholar]
  28. Diersch, H.J.G.; Bauer, D.; Heidemann, W.; Ruhaak, W.; Schatzl, P. Finite Element Formulation for Borehole Heat Exchangers in Modeling Geothermal Heating Systems by FEFLOW; White Papers; DHI-WASY GmbH: Berlin, Germany, 2010; Volume V. [Google Scholar]
  29. Diersch, H.J.G.; Bauer, D. Analysis, modeling and simulation of underground thermal energy storage (UTES) systems. In Advances in Thermal Energy Storage System; Elsevier Ltd.: Amsterdam, The Netherlands, 2015. [Google Scholar]
  30. Lachman, P. Guidelines for Projecting and Constructing Heat Pumps Installations; PORT PC: Krakow, Poland, 2013. (In Polish) [Google Scholar]
  31. Eskilson, P.; Claesson, J. Simulation model for thermally interacting heat extraction boreholes. Numer. Heat Transf. 1988, 13, 149–165. [Google Scholar] [CrossRef]
  32. NASA. NASA’s Satellite Provided for Use with the RETScreen Software via the NASA Prediction of Worldwide Energy Resource (POWER) Project; NASA: Washington, DC, USA, 2012.
  33. Central Geological Database–Portal. Available online: http://geoportal.pgi.gov.pl/ (accessed on 28 February 2020).
Figure 1. Non-uniform grid model of the study area and 25 borehole heat exchangers (2D), cross-section lines (green). Spatial discretization of BHE nodes (in frame) according to [27].
Figure 1. Non-uniform grid model of the study area and 25 borehole heat exchangers (2D), cross-section lines (green). Spatial discretization of BHE nodes (in frame) according to [27].
Energies 13 01341 g001
Figure 2. The scheme of boundary conditions applied to the model.
Figure 2. The scheme of boundary conditions applied to the model.
Energies 13 01341 g002
Figure 3. Double U-shaped pipe scheme.
Figure 3. Double U-shaped pipe scheme.
Energies 13 01341 g003
Figure 4. Thermal conductivity in the 3rd scenario model. The numbers refer to lithological layers (1: medium sands, 2: brown-gray marl, 3: brown-gray marly mudstone, 4: light gray marly mudstone, 5: sandstone, 6: beige mudstone, 7: marly claystone).
Figure 4. Thermal conductivity in the 3rd scenario model. The numbers refer to lithological layers (1: medium sands, 2: brown-gray marl, 3: brown-gray marly mudstone, 4: light gray marly mudstone, 5: sandstone, 6: beige mudstone, 7: marly claystone).
Energies 13 01341 g004
Figure 5. Results of the simulation of ground temperature after 10 years (a) and 30 years (b) of heat pump operation within the 1st scenario (homogeneous model). Two-dimensional view of the surface at a depth of 50 m.
Figure 5. Results of the simulation of ground temperature after 10 years (a) and 30 years (b) of heat pump operation within the 1st scenario (homogeneous model). Two-dimensional view of the surface at a depth of 50 m.
Energies 13 01341 g005
Figure 6. Results of 3D simulation of ground temperature after 10 years (a) and 30 years (b) of heat pump operation within the 1st scenario (homogeneous model); the view from the north-west.
Figure 6. Results of 3D simulation of ground temperature after 10 years (a) and 30 years (b) of heat pump operation within the 1st scenario (homogeneous model); the view from the north-west.
Energies 13 01341 g006
Figure 7. Average temperature of BHEs within the 1st scenario (system without space cooling) during 30 years of operation.
Figure 7. Average temperature of BHEs within the 1st scenario (system without space cooling) during 30 years of operation.
Energies 13 01341 g007
Figure 8. The temperature distribution as cross-section views for the 1st scenario. The cross-section lines are the same as those in Figure 1.
Figure 8. The temperature distribution as cross-section views for the 1st scenario. The cross-section lines are the same as those in Figure 1.
Energies 13 01341 g008
Figure 9. Results of the simulation of ground temperature after 10 years (a) and 30 years (b) of heat pump operation within the 2nd scenario (homogeneous model). Two-dimensional view of the surface at a depth of 50 m.
Figure 9. Results of the simulation of ground temperature after 10 years (a) and 30 years (b) of heat pump operation within the 2nd scenario (homogeneous model). Two-dimensional view of the surface at a depth of 50 m.
Energies 13 01341 g009
Figure 10. Results of the 3D simulation of ground temperature after 10 years (a) and 30 years (b) of heat pump operation within the 2nd scenario (homogeneous model); the view from the north-west.
Figure 10. Results of the 3D simulation of ground temperature after 10 years (a) and 30 years (b) of heat pump operation within the 2nd scenario (homogeneous model); the view from the north-west.
Energies 13 01341 g010
Figure 11. Average temperature of BHEs within the 2nd scenario (system with space cooling) during 30 years of operation.
Figure 11. Average temperature of BHEs within the 2nd scenario (system with space cooling) during 30 years of operation.
Energies 13 01341 g011
Figure 12. The temperature distribution as cross-section views for the 2nd scenario. The cross-section lines are the same as those used in Figure 1.
Figure 12. The temperature distribution as cross-section views for the 2nd scenario. The cross-section lines are the same as those used in Figure 1.
Energies 13 01341 g012
Figure 13. Results of the simulation of ground temperature after 10 years (a) and 30 years (b) of heat pump operation within the 3rd scenario (layered model). Two-dimensional view of the surface at a depth of 50 m.
Figure 13. Results of the simulation of ground temperature after 10 years (a) and 30 years (b) of heat pump operation within the 3rd scenario (layered model). Two-dimensional view of the surface at a depth of 50 m.
Energies 13 01341 g013
Figure 14. Results of 3D simulation of ground temperature after 10 years (a) and 30 years (b) of heat pump operation within the 3rd scenario (layered model); view from the north-west.
Figure 14. Results of 3D simulation of ground temperature after 10 years (a) and 30 years (b) of heat pump operation within the 3rd scenario (layered model); view from the north-west.
Energies 13 01341 g014aEnergies 13 01341 g014b
Figure 15. Average temperature of BHEs within the 3rd scenario (system without cooling) during the 30th year of operation.
Figure 15. Average temperature of BHEs within the 3rd scenario (system without cooling) during the 30th year of operation.
Energies 13 01341 g015
Figure 16. The temperature distribution as a cross-section view for the 3rd scenario. The cross-section lines are the same as those used in Figure 1.
Figure 16. The temperature distribution as a cross-section view for the 3rd scenario. The cross-section lines are the same as those used in Figure 1.
Energies 13 01341 g016
Figure 17. Cold plumes in 3D models for 3 different scenarios (1st scenario, 2nd scenario and layered model (3rd scenario)) after 30 years of system operation.
Figure 17. Cold plumes in 3D models for 3 different scenarios (1st scenario, 2nd scenario and layered model (3rd scenario)) after 30 years of system operation.
Energies 13 01341 g017
Table 1. Borehole heat exchanger (BHE) settings.
Table 1. Borehole heat exchanger (BHE) settings.
BHE GeometryDouble U-Shape
Borehole diameter0.15 m
Inlet Pipe diameter0.032 m
Refrigerant volumetric heat capacity4 MJ/m/s/K
Refrigerant thermal conductivity0.48 J/m/s/K
Computational methodEskilson & Claesson method
PowerVariable, acc. to monthly energy load (Table 2)
Flow rate53 m3/d
Table 2. Earth’s average temperature in the study area [32] and energy load during a year.
Table 2. Earth’s average temperature in the study area [32] and energy load during a year.
MonthEarth’s Surface
Temperature [°C]
Average Energy per BHE [kWh]
1st scenario2nd scenario3rd scenario
I−3.5558558558
II−2.2504504504
III2.3558558558
IV9.2360360360
V15.3186186186
VI18.30−180 (cooling)0
VII20.90−372 (cooling)0
VIII20.60−186 (cooling)0
IX14.7000
X8.6186186186
XI1.8540540540
XII−2.5558558558
Table 3. Ground and water initial parameters.
Table 3. Ground and water initial parameters.
Parameter1st Scenario2nd Scenario3rd Scenario
Porosity0.30.30.18–0.2;
0.3 in aquifer
Volumetric heat capacity of groundwater4.2 106 J/m3/K4.2 106 J/m3/K4.2 106 J/m3/K
Volumetric heat capacity of solid phase2.52 106 J/m3/K2.52 106 J/m3/K2.52 106 J/m3/K
Thermal conductivity of groundwater0.65 W/m/K0.65 W/m/K0.65 W/m/K
Thermal conductivity of solid phase2 W/m/K2 W/m/Kaccording to layer (Figure 4)
Fluid flux4000 mm/a4000 mm/a4000 mm/a in aquifer
Groundwater conductivity2.5 10−4 m/s2.5 10−4 m/s1.0 10−4 m/s; 2.5 10−4 m/s in aquifer

Share and Cite

MDPI and ACS Style

Hałaj, E.; Pająk, L.; Papiernik, B. Finite Element Modeling of Geothermal Source of Heat Pump in Long-Term Operation. Energies 2020, 13, 1341. https://doi.org/10.3390/en13061341

AMA Style

Hałaj E, Pająk L, Papiernik B. Finite Element Modeling of Geothermal Source of Heat Pump in Long-Term Operation. Energies. 2020; 13(6):1341. https://doi.org/10.3390/en13061341

Chicago/Turabian Style

Hałaj, Elżbieta, Leszek Pająk, and Bartosz Papiernik. 2020. "Finite Element Modeling of Geothermal Source of Heat Pump in Long-Term Operation" Energies 13, no. 6: 1341. https://doi.org/10.3390/en13061341

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop