Next Article in Journal
A Supervisory Control Strategy for Improving Energy Efficiency of Artificial Lighting Systems in Greenhouses
Previous Article in Journal
Analytical and Experimental Study of Thermoelectric Generator (TEG) System for Automotive Exhaust Waste Heat Recovery
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Improved Procedure for Earth Fault Loop Impedance Measurement in TN Low-Voltage Network

1
Electrical, Electronic and Computer Engineering Department, Technical University of Cluj-Napoca, 400114 Cluj-Napoca, Romania
2
“Anghel Saligny” Technical College, 430295 Baia Mare, Romania
*
Author to whom correspondence should be addressed.
Energies 2021, 14(1), 205; https://doi.org/10.3390/en14010205
Submission received: 26 November 2020 / Revised: 23 December 2020 / Accepted: 28 December 2020 / Published: 2 January 2021
(This article belongs to the Section F: Electrical Engineering)

Abstract

:
The difficulties and uncertainties related to earth fault loop impedance measurement are addressed in this paper. Based on the presentation of the measurement procedure implemented in the test equipment (diagrams and measured quantities, respectively, interpretation of results), the shortcomings and errors that accompany it are highlighted. The position in the power system, the influence of power transformers, and the use of effective quantities instead of phasors are important sources of errors, but, as will be seen, the switching of loads at the consumer sides and/or the occurrence of fault regimes during measurements can lead to the most serious impairment of the accuracy in the impedance assessment. The clarification of these aspects is achieved, both starting from the equivalent diagrams of the measurement circuits and the analytical interpretation of the phenomena associated with the measurements, as well as based on the modeling and simulation of TN low-voltage electrical distribution networks, in a specialized program, Eaton xSpider, which allows the complete and complex analysis of a large number of scenarios. Thus, essential conclusions were drawn regarding the level of errors and their causes, obviously, with the research coming with solutions to be implemented at the level of the measurement protocols of the devices used.

1. Introduction

The energy dependence of human society is indisputable. In the current context of the energy crisis and the problems related to global warming, electricity is the bridge to the new energy era of the planet. Due to the lack of accessible technology solutions for storing significant amounts of electricity, it is consumed simultaneously with production, which implies the need for the existence of power systems, the most complex and extensive man-made systems. Their exploitation must be safe and as simple as possible from the consumers’ perspective. This desideratum is strongly dependent on the initial and periodic evaluations, through measurements and prophylactic tests to ensure the safety of the electrical installations.
This research deals with the above verifications in low-voltage distribution networks. The most common configuration of these networks is the TN, i.e., the grounded neutral (symbol T) and a network-driven protective earth connection (symbol N), either separately to the neutral conductor (TN-S) or combined with the neutral conductor (TN-C) or mixed (TN-C-S).
Generally, a TN low-voltage distribution network goes as TN-C on the transformer and distribution sides and, from the supplier–consumer delimitation point, it becomes TN-S (Figure 1). The Zt1, Zt2, and Zt3 are the phase transformer impedances, Zd1, Zd2, and Zd3 are the phase impedances of the distribution line between transformer and supplier–consumer delimitation point, and ZPEN is the impedance of the common protective earth (PE) and neutral (N) conductor, with ZN and ZPE being the corresponding impedances of separate conductors N and PE.
According to the standards in force, e.g., [1,2], in low-voltage electrical networks, one of the measurements that highlight the safety of electricity operation is the measurement of the earth fault loop impedance. Based on its values, the required disconnection times are correlated with the nominal voltage levels, of course, based on the tripping characteristics of the protection equipment and also it must prove that the touch voltage that may occur by an insulation failure will be below the allowable value.
The safe disconnection times for the TN low-voltage networks are presented in Table 1 [3], where Vph is the rated phase voltage.
To reach these tripping times, the following condition must be met:
Z l o o p · I a V p h
where Zloop is the earth fault loop impedance and Ia is the tripping current for safe disconnection time.
It becomes easier to treat (1) as:
Z l o o p V p h I a = Z l o o p M A X
ZloopMAX is the result of analyzing the tripping characteristics of the usual protective equipment. According to [4], in TN low-voltage distribution network equipped with protective devices, circuit breaker (CB) or general-purpose fuse (gG), the maximum measured values of earth fault loop impedance should not exceed the values specified in Table 2 when the conductors are at their normal operating temperature (e.g., 70 °C for thermoplastic insulated conductors).
Due to the difficulty of assessing the temperature of the electrical network at the time of measurement, [3] recommends considering the worst-case scenario, i.e., under no-load condition measurement, at a low temperature, and in interpreting the inequality (2) (see the corresponding values in Table 2).
The earth fault loop impedance measurement method, implemented in most testers, is based on the simplified equivalent scheme, shown in Figure 2 [4], in which the voltages are measured between the live and PE (earth) conductors, through a known resistor, Ri, or in no-load (from points a and b perspective) condition.
Consequently, the earth fault loop impedance results as the sum of the impedances of the network components, namely:
Z _ l o o p = Z _ t 1 + Z _ d 1 + Z _ c 1 + Z _ P E + Z _ P E N
where Zc1 is the phase impedance of the line between the supplier–consumer delimitation point and the measurement point a.
The tester measures the rms voltage VopenS with the switch S open and the rms voltage VclosedS with the switch S closed. Because the internal resistance Ri of the device is known, the current I flowing through it can be determined or, alternatively, by measuring the current, the voltage VclosedS can be deduced:
V c l o s e d S = I · R i I = V c l o s e d S R i
V c l o s e d S = V p h 1 I · Z l o o p
V o p e n S = V p h 1 = I · ( R i + Z l o o p ) = V c l o s e d S R i · ( R i + Z l o o p )
Finally, based on the measurement of two variables, VopenS and I or VopenS and VclosedS, the earth fault loop impedance is depicted as:
Z l o o p = V o p e n S I R i = R i · ( V o p e n S V c l o s e d S V c l o s e d S ) .

2. Source of Errors

The result of determining the loop impedance, according to the above algorithm, is an approximate one. The first error that occurs is related to the operation with effective quantities instead of the phasors [4,5,6,7,8,9,10,11,12]. The correct value of the loop impedance would be:
Z _ l o o p = V _ o p e n S I _ R i = R i · ( V _ o p e n S V _ c l o s e d S V _ c l o s e d S ) ,
and
Z l o o p = | V _ o p e n S I _ R i | = | R i · ( V _ o p e n S V _ c l o s e d S V _ c l o s e d S ) | ,
With V _ o p e n S , I _ and V _ c l o s e d S being the phasors of the voltages and current involved in fault loop impedance measurement.
In low-voltage distribution networks, the inductive and capacitive reactance generally have low values, the important exception being the inductive reactance of the transformer. Thus, if the measurement of the loop impedance takes place at a point of the network away (electrically) from the transformer, then the error will be significantly reduced.
Moreover, the presence of other consumers in the distribution network is not quantified, i.e., the simplified equivalent circuit during earth fault loop impedance measurement generates errors. The complete circuit is shown in Figure 3 (the switch S is shown closed to illustrate the current flow in the network), where all consumers are reduced to an equivalent one, placed at the end of an equivalent distribution network. It is obvious that for no other consumer connected to the distribution network, except the one denoted simply consumer, at which the loop impedance test is performed, the complete circuit is equivalent to the simplified one.
The Zt1, Zt2, and Zt3 are the phase transformer impedances. Zed1, Zed2, and Zed3 are the phase impedances of the equivalent distribution line between transformer and supplier–consumer delimitation point. ZePEN is the impedance of the equivalent PEN conductor. Zc1, Zc2, and Zc3 are the phase impedances of the line between the supplier–consumer delimitation point and the measurement point. ZN and ZPE are the corresponding impedances of separate conductors n and PE in consumer installation and, finally, Zec1, Zec2, Zec3, ZeN, and ZePE are the equivalent consumer impedances.
The potential source of error coming from other connected consumer is revealed in the following Equations:
V _ c l o s e d S = I _ · R i I _ = V _ c l o s e d S R i ,
V _ c l o s e d S = V _ p h 1 ( I _ + I _ 1 ) · ( Z _ t 1 + Z _ e d 1 ) I _ · ( Z _ c 1 + Z _ P E ) ( I _ 1 + I _ 2 + I _ 3 + I _ ) · Z _ e P E N
V _ o p e n S = V _ p h 1 I _ 1 · ( Z _ t 1 + Z _ e d 1 ) ( I _ 1 + I _ 2 + I _ 3 ) · Z _ e P E N
Rearranging (11) as:
V _ c l o s e d S = V _ p h 1 I _ 1 · ( Z _ t 1 + Z _ e d 1 ) ( I _ 1 + I _ 2 + I _ 3 ) · Z _ e P E N I _ · ( Z _ t 1 + Z _ e d 1 + Z _ c 1 + Z _ P E + Z _ e P E N )
and (12) as:
V _ o p e n S V _ p h 1 = I _ 1 · ( Z _ t 1 + Z _ e d 1 ) ( I _ 1 + I _ 2 + I _ 3 ) · Z _ e P E N
it can be written:
V _ c l o s e d S = V _ o p e n S I _ · Z _ l o o p
Apparently, other consumers do not influence earth loop impedance measurement, but relation (14) is a consequence of (10) to (12) only if the circuit is not modified during the measurement. That is, if the currents I1, I2, or I3 change by connecting/disconnecting some loads of any consumer powered by the analyzed network or, even worse, if fault regimes occur (overcurrents or under/overvoltages) exactly when switch S changes state, the relationship (14) is no longer correct, i.e., the Equations (11) and (12) are written as:
V _ c l o s e d S = V _ p h 1 ( I _ + I _ 1 ) · ( Z _ t 1 + Z _ e d 1 ) I _ · ( Z _ c 1 + Z _ P E ) ( I _ 1 + I _ 2 + I _ 3 + I _ ) · Z _ e P E N
V _ o p e n S = V _ p h 1 I _ 1 · ( Z _ t 1 + Z _ e d 1 ) ( I _ 1 + I _ 2 + I _ 3 ) · Z _ e P E N
with:
I _ 1 I _ 1   or / and   I _ 2 I _ 2   or / and   I _ 3 I _ 3   or / and   V _ p h 1 = V _ p h 1
meaning that (15) could not be reached anymore.

3. Suggested Procedure

Analyzing the sources of errors, we can suggest an improved procedure to perform the earth fault loop testing.
Due to the technical and financial implication we divided the procedure into two available solutions:
  • To rule out problems associated with loads switching at the consumer’s side, or the influence of defect regimes, the next protocol of measurements must be applied: Repetitive measurement of the voltages: VclosedS, VopenS, VclosedS, … VopenS, VclosedS until the values of the voltage VclosedS of two successive measurements is the same (obviously within the limits of an imposed error).
  • To avoid the error associated with the effects of measurement and calculations with effective quantities instead of phasors, the two required variables, VopenS and I or VopenS and VclosedS, must be measured as rms values but also the phase shift between them must be recorded.

4. Validation

For validation, a low-voltage TN distribution network was analyzed in several configurations and operating modes. For faster computation, a dedicated graphically oriented design system for dimensioning and calculation of low-voltage networks, xSpider [13] developed by Eaton, was used.
First, we considered an ideal network consisting of purely resistive elements to highlight the influence of consumer switching on the distribution network during the measurement of the fault loop impedance (Figure 4). Please note that the commutation and protective equipment are not represented.
The equivalent consumer was considered with different powers and the measurement instrument in the “closed S” regime was simulated by introducing a 2.3-kW resistive load. “Cable 1” is the consumer line between the supplier–consumer delimitation point, “NODE 1”, and the measurement point. In other words, “Cable 1” and “Measurement instrument at the Consumer” from Figure 4 are “Consumer” and “Measurement instrument” from Figure 3.
XSpider uses for calculation two algorithms: one omitting the impact of the voltage drop and the other one taking into account the impact of the voltage drop, i.e., either the load currents are constant or the load outputs are constant [13].
“Cable 2” and “Equivalent consumer” from Figure 4 are “Equivalent consumer” from Figure 3. “NET” and “Cable 3” from Figure 4 cover the “Transformer” and “Equivalent distribution” sections from Figure 3.
Using “the constant load current”, we can obtain the earth fault loop impedance, from (6), as:
Z l o o p = V o p e n S V c l o s e d S I
The equivalent power supply, “NET pure resistive”, has the active positive-sequence network resistance, R1 = 0.02 Ω.
Cables 2 and 3, length 1 m and 500 m, respectively, are 4 × 95 mm2 polyvinyl chloride (PVC) insulated aluminum conductor cables, installed in air with the specific positive-sequence network resistance, r1 = 0.326 mΩ/m, and the specific active zero-sequence network resistance, r0 = 1 mΩ/m. Of course, both specific inductive reactances, positive-sequence network x1 and zero-sequence network x0, are zero.
Cable 1 is also a PVC insulated aluminum conductor cable, but 4 × 16 mm2 having r1 = 1.935 mΩ/m and r0 = 7.74 mΩ/m, x1 = x0 = 0.
In Table 3 are presented the simulation results and interpretations for earth fault loop impedance measurement based on (7).
In a purely resistive network, the earth fault loop impedance presents no error in the measurement procedure compared with the computed one. This statement is true if VopenS and VclosedS refer to the same current circulation. If, for example, the testing instrument measures a value of VclosedS = 224.204 V, which is the value for a 5-kW equivalent consumer connected, and a value of 229.977 for VopenS, corresponding to no equivalent consumer, the error between measured and real values of the Zloop is 32.1%. The above results could have arrived if, during the measurements, the 5-kW load is disconnected.
Taking, for example, the extreme values illustrated in Table 4, the error reaches 646.32%:
Z l o o p m e a s u r e d = 229.977 V 197.363 V 10 A = 3.2614 Ω
ε = Z l o o p m e a s u r e d Z l o o p a c c u r a t e Z l o o p a c c u r a t e · 100 = 646.32 %
If the algorithm for repetitive voltage measurement with switch S of the device closed, open, …, closed is implemented, this error can be avoided.
To quantify the error level associated with the effects of measurement and calculations with effective quantities instead of phasors, a typical low-voltage distribution network is considered (Figure 5).
The network component parameters are depicted in Table 4.
The simulation results of the above networks, along with the earth fault loop impedances determined based on (7), and the accurate values are presented in Table 5, Table 6, Table 7 and Table 8.
It is visible that, not taking into account the switching of some loads during the loop impedance measurement, the errors increased over 30%, maximum allowable error [1,2], only in the case of networks fed by low-power transformers and for measuring points close to it. See the network with 100-kVA transformer and L = 10 m for cable 3.
If the errors determined by the use of the effective quantities instead of the phasors overlap those generated by the switching of the various loads between the moments of the voltage measurement, the cumulated values can exceed 700%. For example, for a distribution network with a 400-kVA transformer and a cable 3 length of 500 m, this error, if the measurement of VopenS and VclosedS are performed with no load, respectively, with 100 kW and cosφ = 0.5 connected, could achieve the next value:
Z l o o p m e a s u r e d = 229.977 V 191.82 V 10 A = 3.8157 Ω
ε = Z l o o p m e a s u r e d Z l o o p a c c u r a t e Z l o o p a c c u r a t e · 100 = 765.24 % .

5. Conclusions

The sources of errors that occur when measuring the loop impedance in a TN distribution network are:
  • The switching of loads at the consumer sides and/or the occurrence of fault regimes during measurements and
  • The use of effective quantities instead of phasors, which becomes significant if the inductive reactance of the network components becomes comparable to their resistance.
To minimize these errors, based on the presented results, two essential aspects can be clearly distinguished in terms of fault loop impedance measurement:
  • The next protocol must be applied: repetitive measurement of the voltages, VclosedS, VopenS, VclosedS, … VopenS, VclosedS, until the values of the voltage VclosedS of two successive measurements is the same (obviously within the limits of an imposed error). This first rule is mandatory because it avoids the huge errors that occur due to the switching of the loads during the measurement and, also, it is simple and cheap to implement in the measuring equipment.
  • To avoid the error associated with the effects of measurement and calculations with effective quantities instead of phasors, the two required variables, VopenS and I or VopenS and VclosedS, must be measured as rms values but also the phase shift between them must be recorded. As seen in those presented in the paper, errors of over 30% occur in measurements near distribution transformers if they have low-rated powers. As the cost of implementing such an algorithm is higher, the solution may be unjustifiable at the usual measurements, i.e., far from the power transformers. Another comment has to be made here: We used a two-wire, high-current testing method [14] for analyzing measurement apparatus, but with a two- or three-wire “no trip” algorithm implemented [14], the errors will be greater than those presented here due to the external influences and the need for increased voltage measurement accuracy. In this case, using phasors can be reconsidered.
In summary, measuring the impedances of the fault loops is a rather complex process and can be accompanied by significant errors. On the other hand, the interpretations that can be obtained, based on the measurements of the mentioned impedance being very important regarding the safety of the power system operation, fully justify the need to improve the methodology implemented in the measuring devices.

Author Contributions

Conceptualization, L.N., A.N., and O.C.; methodology, L.N.; validation, L.N., A.N., and O.C.; writing—original draft preparation, L.N.; writing—review and editing, L.N. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

The data presented in this study are fully available in the body of the paper.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Low-Voltage Electrical Installations—Part 6: Verification; HD 60364-6; IEC: Geneva, Switzerland, 2016.
  2. Electrical Safety in Low Voltage Distribution Systems up to 1000 V a.c. and 1500 V d.c. Equipment for Testing, Measuring or Monitoring of Protective Measures; EN 61557; IEC: Geneva, Switzerland, 2007–2008.
  3. Low-Voltage Electrical Installations—Part 4-41: Protection for Safety—Protection against Electric Shock; IEC 60364-4-41; IEC: Geneva, Switzerland, 2012.
  4. Neamt, L.; Balan, H.; Chiver, O.; Hotea, A. Considerations about Fault Loop Impedance Measurement in TN Low-Voltage Network. In Proceedings of the 8th International Conference on Modern Power Systems (MPS), Cluj Napoca, Romania, 21–23 May 2019; pp. 1–4. [Google Scholar]
  5. Roskosz, R.; Musial, E.; Czapp, S. A method of earth fault loop impedance measurement without unwanted tripping of RCDs. In Proceedings of the Progress in Applied Electrical Engineering (PAEE), Koscielisko, Poland, 18–22 June 2018; pp. 1–4. [Google Scholar]
  6. Mitolo, M.; Bajzek, T.J. Measuring the electrical safety in low-voltage distribution systems. In Proceedings of the IEEE/IAS 54th Industrial and Commercial Power Systems Technical Conference (I&CPS), Niagara Falls, ON, Canada, 7–10 May 2018; pp. 1–4. [Google Scholar]
  7. Liu, H.; Mitolo, M.; Qiu, J. Ground-Fault Loop Impedance Calculations in Low-Voltage Single-Phase Systems. IEEE Trans. Ind. Applic. 2014, 50, 1331–1337. [Google Scholar]
  8. Czapp, S. Fault Loop Impedance Measurement in Low Voltage Network with Residual Current Devices. Electron. Electr. Eng. 2012, 122, 109–112. [Google Scholar]
  9. Hadziefendic, N.; Kostic, N.; Trifunovic, J.; Kostic, M. Detection of Poor Contacts in Low-Voltage Electrical Installations. IEEE Trans. Comp. Pack. Man. Techn. 2019, 9, 129–137. [Google Scholar] [CrossRef]
  10. Mitolo, M.; Liu, H. Touch Voltage Analysis in Low-Voltage Power Systems Studies. IEEE Trans. Ind. Applic. 2016, 52, 556–559. [Google Scholar] [CrossRef]
  11. Mitolo, M.; Bajzek, T.J. New Generation Tester to Assess the Electrical Safety in Low-Voltage Distribution Systems. IEEE Trans. Ind. Applic. 2019, 55, 106–110. [Google Scholar] [CrossRef]
  12. Czapp, S. Method of earth fault loop impedance measurement without nuisance tripping of RCDs in 3-phase low-voltage circuits. Metrol. Meas. Syst. 2019, 26, 217–227. [Google Scholar]
  13. Eaton Industries (Austria) GmbH. xSpider Version 3.3, User’s Manual; Eaton: Wien, Austria, 2019. [Google Scholar]
  14. Megger. Earth Electrode and Earth Loop Impedance Testing. Theory and Applications. Available online: https://uk.megger.com/support/technical-library/application-notes/earth-electrode-and-earth-loop-impedance-testing-t (accessed on 1 November 2020).
Figure 1. A TN-C-S network.
Figure 1. A TN-C-S network.
Energies 14 00205 g001
Figure 2. Simplified equivalent circuit during earth fault loop impedance measurement.
Figure 2. Simplified equivalent circuit during earth fault loop impedance measurement.
Energies 14 00205 g002
Figure 3. Complete equivalent circuit during earth fault loop impedance measurement.
Figure 3. Complete equivalent circuit during earth fault loop impedance measurement.
Energies 14 00205 g003
Figure 4. Purely resistive network.
Figure 4. Purely resistive network.
Energies 14 00205 g004
Figure 5. Typical low-voltage distribution network.
Figure 5. Typical low-voltage distribution network.
Energies 14 00205 g005
Table 1. Safe disconnection time in TN low-voltage network.
Table 1. Safe disconnection time in TN low-voltage network.
Rated Phase Voltage Vph Range (V)Safe Disconnection Time (s)
(50; 120]0.8
(120; 230]0.4
(230; 400]0.2
>4000.1
Table 2. Maximum measured values of the earth fault loop impedance at normal and at the unknown operating temperature.
Table 2. Maximum measured values of the earth fault loop impedance at normal and at the unknown operating temperature.
Rated Current (A)ZloopMAX (Ω)
CB Type BCB Type CgG Fuse
Normal Operating TemperatureUnknown Operating TemperatureNormal Operating TemperatureUnknown Operating TemperatureNormal Operating TemperatureUnknown Operating Temperature
104.373.502.181.744.853.88
162.722.181.351.082.562.05
251.741.390.860.691.351.08
321.351.080.680.540.990.79
630.690.550.340.270.4250.34
1000.430.340.20.160.210.17
Table 3. Purely resistive network.
Table 3. Purely resistive network.
Equivalent ConsumerMeasurement Instrument
Based on (7)
Zloop (Ω)
Accurate Value
p (kW)cosφVopenS (V)VclosedS (V)Zloop (Ω)
01229.977225.6070.4370.437
5228.574224.2040.437
10227.171222.8010.437
100201.733197.3630.437
Table 4. Purely resistive network.
Table 4. Purely resistive network.
ComponentParameter
NETShort-circuit power (3-phase short-circuit), Sk3 p = 300 MVA
TR1Rated power Sr = 100 kVA, 22/0.4 kV, Yzn1,
Short-circuit losses Pk = 2.15 kW, Short-circuit voltage uk = 4%
and
Rated power Sr = 400 kVA, 22/0.4 kV, Dyn1,
Short-circuit losses Pk = 6.265 kW, Short-circuit voltage uk = 6%
Cable 1r1 = 1.935 mΩ/m, r0 = 7.74 mΩ/m, x1 = 0.082 mΩ/m, x0 = 0.2952 mΩ/m,
L = 10 m
Cable 2r1 = 0.326 mΩ/m, r0 = 1.586618 mΩ/m, x1 = 0.082 mΩ/m,
x0 = 0.2952 mΩ/m, L = 1 m
Cable 3r1 = 0.326 mΩ/m, r0 = 1.58618 mΩ/m, x1 = 0.082 mΩ/m,
x0 = 0.2952 mΩ/m, L = 10 ÷ 500 m
Equivalent consumerPn = 0; 5; 10 and 100 kW, cosφ = 0.5; 0.75 and 1
Measurement instrumentPn = 0 and 2.3 kW
Table 5. The 100-kVA transformer and L = 10 m for cable 3.
Table 5. The 100-kVA transformer and L = 10 m for cable 3.
Equivalent ConsumerMeasurement Instrument
Based on (7)
Zloop (Ω)
Accurate Value
p (kW)cosφVopenS (V)VclosedS (V)Zloop (Ω)
01230.000229.4480.05520.0845 = |0.0725 + j·0.0425|
5229.977229.4250.0552
10229.954229.4020.0552
100229.448228.8960.0552
00.75230.000229.4480.0552
5229.977229.4250.0552
10229.931229.3790.0552
100229.333228.7810.0552
00.5230.000229.4480.0552
5229.977229.4250.0552
10229.931229.3790.0552
100229.241228.6890.0552
Table 6. The 100-kVA transformer and L = 500 m for cable 3.
Table 6. The 100-kVA transformer and L = 500 m for cable 3.
Equivalent ConsumerMeasurement Instrument
Based on (7)
Zloop (Ω)
Accurate Value
p (kW)cosφVopenS (V)VclosedS (V)Zloop (Ω)
01229.977225.6070.4370.464 = |0.449 + j·0.1175|
5228.574224.2040.437
10227.171222.8010.437
100201.756197.3860.437
00.75229.977225.6070.437
5228.321223.9510.437
10226.642222.2720.437
100197.386193.0160.437
00.5229.977225.6070.437
5228.068223.6980.437
10226.159221.7890.437
100196.190191.8200.437
Table 7. The 400-kVA transformer and L = 10 m for cable 3.
Table 7. The 400-kVA transformer and L = 10 m for cable 3.
Equivalent ConsumerMeasurement Instrument
Based on (7)
Zloop (Ω)
Accurate Value
p (kW)cosφVopenS (V)VclosedS (V)Zloop (Ω)
01230.000229.4480.05520.0585 = |0.0.053 + j·0.0235|
5229.977229.4250.0552
10229.954229.4020.0552
100229.448228.8960.0552
00.75230.000229.4480.0552
5229.977229.4250.0552
10229.931229.3790.0552
100229.333228.7810.0552
00.5230.000229.4480.0552
5229.977229.4250.0552
10229.931229.3790.0552
100229.241228.6890.0552
Table 8. The 400-kVA transformer and L = 500 m for cable 3.
Table 8. The 400-kVA transformer and L = 500 m for cable 3.
Equivalent ConsumerMeasurement Instrument
Based on (7)
Zloop (Ω)
Accurate Value
p (kW)cosφVopenS (V)VclosedS (V)Zloop (Ω)
01229.977225.6070.4370.441 = |0.4295 + j·0.05|
5228.574224.2040.437
10227.171222.8010.437
100201.756197.3860.437
00.75229.977225.6070.437
5228.321223.9510.437
10226.642222.2720.437
100197.386193.0160.437
00.5229.977225.6070.437
5228.068223.6980.437
10226.159221.7890.437
100196.190191.8200.437
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Neamt, L.; Neamt, A.; Chiver, O. Improved Procedure for Earth Fault Loop Impedance Measurement in TN Low-Voltage Network. Energies 2021, 14, 205. https://doi.org/10.3390/en14010205

AMA Style

Neamt L, Neamt A, Chiver O. Improved Procedure for Earth Fault Loop Impedance Measurement in TN Low-Voltage Network. Energies. 2021; 14(1):205. https://doi.org/10.3390/en14010205

Chicago/Turabian Style

Neamt, Liviu, Alina Neamt, and Olivian Chiver. 2021. "Improved Procedure for Earth Fault Loop Impedance Measurement in TN Low-Voltage Network" Energies 14, no. 1: 205. https://doi.org/10.3390/en14010205

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop