Method for Determining Sensor Location for Automated Shading Control in Office Building
Abstract
:1. Introduction
2. Automated Shading Control Related Works
2.1. Literature Review
2.2. Key Parameters for Shading Control
2.2.1. The Glare Metrics
2.2.2. Daylighting Design
3. Method of Sensor Location for Automated Shading Control
3.1. The Principles for Sensor Location
- (1)
- For the selection of the sensor position in the shading control logic, the glare index, effective daylighting, and the lighting effect on the whole room for the different control objects should be considered.
- (2)
- The [50%] and [50%] index should be used to compare and analyze a whole year, working hours should be selected for calculation and processing, and consideration should be given to the changes of the four seasons as well as the shading effect during the work day so that the results are representative.
- (3)
- Only one sensor position should be used to control the shading for a small room, and the glare index calculated from this sensor should trigger the shading adjustment. The shading control logic should be simple, the project investment should be low, and the practical application should be simple.
3.2. The Steps for Sensor Location
- (1)
- Divide the work surface into grids, to ensure all sensor positions in the room are considered.
- (2)
- Substitute all the sensor positions into the shading control logic. Obtain the [50%] and [50%] index values corresponding to each shading control position by indoor light environment numerical simulation methods.
- (3)
- Obtain the optimal sensor position for shading control using a suitable multi-attributes decision-making method to prioritize the schemes. The index is called attributes.
3.3. The Multi-Attributes Decision-Making Method
- (1)
- Construct a normalized matrix
- (2)
- Determine the positive ideal point and the negative ideal point
- (3)
- Calculate the distance between each solution and the positive ideal point or the negative ideal point.
- (4)
- Calculate the relative proximity between each solution and the ideal solutionThe relative proximity:
3.4. Determining the Attributes’ Weight
- (1)
- Attribute index normalization
- (2)
- Calculate attribute information entropy
- (3)
- Calculate the weight of the attribute
4. Analysis and Discussion
4.1. Model Parameters
4.2. Shading Control Sensor Position in Different Rooms
4.2.1. The Characteristics of the Sensor Location in a Small Office Room
4.2.2. The Characteristics of Sensor Locations in the Open-Plan Office Room
4.3. Shading Control Sensor Position on Different Window-to-Wall Ratios
4.4. Shading Control Sensor Position on Different Building Orientations
5. Conclusions
Author Contributions
Funding
Institutional Review Board Statement
Informed Consent Statement
Conflicts of Interest
References
- Albert, A.T.; Djamel, O. Shading and day-lighting controls energy savings in offices with fully-Glazed façades in hot climates. Energy Build. 2017, 151, 263–274. [Google Scholar] [CrossRef]
- Pedro, C.S.; Vítor, L.; Marilyne, A. Influence of shading control patterns on the energy assessment of office spaces. Energy Build. 2012, 50, 35–48. [Google Scholar] [CrossRef] [Green Version]
- Chaiwiwatworakul, P.; Chirarattananon, S.; Rakkwamsuk, P. Application of automated blind for daylighting in tropical region. Energy Convers. Manag. 2009, 50, 2927–2943. [Google Scholar] [CrossRef]
- Zhang, S.; Birru, D. An open-loop venetian blind control to avoid direct sunlight and enhance daylight utilization. Sol. Energy 2012, 86, 860–866. [Google Scholar] [CrossRef]
- Borowczyński, A.; Heim, D.; Szczepańska, R.E. Application of Sky Digital Images for Controlling of Louver System. Energy Procedia 2015, 78, 1769–1774. [Google Scholar] [CrossRef] [Green Version]
- Chan, Y.-C.; Tzempelikos, A. Efficient venetian blind control strategies considering daylight utilization and glare protection. Sol. Energy 2013, 98, 241–254. [Google Scholar] [CrossRef]
- Meek, C.; Brennan, M. Automated and Manual Solar Shading and Glare Control: A Design Framework for Meeting Occupant Comfort and Realized Energy Performance. In Proceedings of the 40th ASES National Solar Conference 2011 (SOLAR 2011), Raleigh, NC, USA, 17–20 May 2011. [Google Scholar]
- Iwata, T.; Taniguchi, T.; Sakuma, R. Automated blind control based on glare prevention with dimmable light in open-plan offices. Build. Environ. 2017, 113, 232–246. [Google Scholar] [CrossRef]
- Goovaerts, C.; Descamps, F.; Jacobs, V. Shading control strategy to avoid visual discomfort by using a low-cost camera: A field study of two cases. Build. Environ. 2017, 125, 26–38. [Google Scholar] [CrossRef]
- Gunay, H.B.; O’Brien, W.; Beausoleil-Morrison, I.; Gilani, S. Development and implementation of an adaptive lighting and blinds control algorithm. Build. Environ. 2017, 113, 185–199. [Google Scholar] [CrossRef]
- Thalfeldt, M.; Kurnitski, J. External shading optimal control macros for 1- and 2-piece automated blinds in European climates. Build. Simul. 2014, 8, 13–25. [Google Scholar] [CrossRef]
- Oh, M.H.; Lee, K.H.; Yoon, J.H. Automated control strategies of inside slat-type blind considering visual comfort and building energy performance. Energy Build. 2012, 55, 728–737. [Google Scholar] [CrossRef]
- Koo, S.Y.; Yeo, M.S.; Kim, K.W. Automated blind control to maximize the benefits of daylight in buildings. Build. Environ. 2010, 45, 1508–1520. [Google Scholar] [CrossRef]
- Hu, J.; Olbina, S. Illuminance-based slat angle selection model for automated control of split blinds. Build. Environ. 2011, 46, 786–796. [Google Scholar] [CrossRef]
- Yun, G.; Yoon, K.C.; Kim, K.S. The influence of shading control strategies on the visual comfort and energy demand of office buildings. Energy Build. 2014, 84, 70–85. [Google Scholar] [CrossRef]
- Tyukhova, Y.I. Discomfort Glare from Small, High Luminance Light Sources in Outdoor Nighttime Environments. Ph.D Thesis, University of Nebraska—Lincoln, Lincoln, NE, USA, 2015. [Google Scholar]
- Atzeri, A.M.; Cappelletti, F.; Gasparella, A. Comparison of different glare indices through metrics for long term and zonal visual comfort assessment, Ratio. WWR 2017, 45, 75. [Google Scholar]
- Carlucci, S.; Causone, F.; De Rosa, F.; Pagliano, L. A review of indices for assessing visual comfort with a view to their use in optimization processes to support building integrated design. Renew. Sustain. Energy Rev. 2015, 47, 1016–1033. [Google Scholar] [CrossRef] [Green Version]
- Hopkinson, R. Glare from daylighting in buildings. Appl. Ergon. 1972, 3, 206–215. [Google Scholar] [CrossRef]
- Wienold, J.; Christoffersen, J. Evaluation methods and development of a new glare prediction model for daylight environments with the use of CCD cameras. Energy Build. 2006, 38, 743–757. [Google Scholar] [CrossRef]
- Mcneil, A.; Burrell, G. Applicability of DGP and DGI for evaluating glare in a Brightly Daylit Space. In Proceedings of the ASHRAE and IBPSA-USA SimBuild 2016, Building Performance Modeling Conference, Salt Lake City, UT, USA, 8–12 August 2016. [Google Scholar]
- Nabil, A.; Mardaljevic, J. Useful daylight illuminance: A new paradigm for assessing daylight in buildings. Light. Res. Technol. 2005, 37, 41–57. [Google Scholar] [CrossRef]
- Nabil, A.; Mardaljevic, J. Useful daylight illuminances: A replacement for daylight factors. Energy Build. 2006, 38, 905–913. [Google Scholar] [CrossRef]
- GB/T 50033-2013; Standard for Daylighting Design of Buildings. China Architecture and Architecture Press: Beijing, China, 2012.
- GB/T 5699-2017; Method of Daylighting Measurements. China Architecture and Architecture Press: Beijing, China, 2016.
- Hwang, C.L.; Yoon, K. Multiple Attribute Decision Making: Methods and Applications; Springer: Berlin/Heidelberg, Germany, 1981. [Google Scholar]
Researchers | Time | Parameters | Sensor Location |
---|---|---|---|
C. Goovaerts [9] | 2017 | Daylight Glare Probability (DGP) | 2 m from window, 1.4 m high |
H. Burak Gunay [10] | 2016 | Illuminance of ceiling | 3 m from window, above working plane |
Toshie Iwata [8] | 2016 | Predicted Glare Sensation Vote (PGSV) | 2.5 m from window, 1.2 m high |
Martin Thalfeldt [11] | 2014 | Indoor temperature Illuminance of working plane | Ceiling above seat |
Ying-Chieh Chan [4] | 2013 | Under direct solar radiation or not DGP | 2 m from window, 1.15 m high |
Myung Hwan Oh [12] | 2012 | Daylight Glare Index (DGI) Indoor temperature | 2 m from window, 1.65 m high |
So Young Koo [13] | 2010 | Under direct solar radiation or not | Assigned seat level |
Jia Hu [14] | 2010 | Illuminance of working plane | 0.75 m and 2.75 m from window, 0.75 m high |
UDI | Light Environment |
---|---|
UDI < 100 lux | Insufficient lighting, dim vision |
100 lux ≤ UDI < 2000 lux | Effective lighting |
UDI ≥ 2000 lux | Excessive lighting, visual discomfort |
Space Type | Area | Shape Feature | Orientation | Window-to-Wall Ratio |
---|---|---|---|---|
Open-plan office space | 80~120 m2 | East–west strip | South | 0.5~0.7 |
Small office space | Around 30 m2 | North–south strip | South | 0.3~0.7 |
East | 0.4~0.5 | |||
North | 0.2~0.3 |
City | Space Type | Space Size (Width × Depth × Height)/m | Orientation | Window-to-Wall Ratio |
---|---|---|---|---|
Shanghai | Open-plan office space | 16 × 8 × 3 | South | 0.5 |
South | 0.3/0.5/0.7 | |||
Small office space | 4.5 × 7.5 × 3 | East | 0.4 | |
North | 0.2 |
Location | ||
---|---|---|
R1-EAST | 0.178 | 0.063 |
R1-MIDDLE | 0.178 | 0.063 |
R1-WEST | 0.178 | 0.063 |
R2-EAST | 0.240 | 0.100 |
R2-MIDDLE | 0.223 | 0.088 |
R2-WEST | 0.223 | 0.088 |
R3-EAST | 0.315 | 0.125 |
R3-MIDDLE | 0.305 | 0.125 |
R3-WEST | 0.285 | 0.125 |
R4-EAST | 0.334 | 0.156 |
R4-MIDDLE | 0.349 | 0.131 |
R4-WEST | 0.343 | 0.138 |
R5-EAST | 0.355 | 0.175 |
R5-MIDDLE | 0.351 | 0.169 |
R5-WEST | 0.341 | 0.169 |
R6-EAST | 0.365 | 0.175 |
R6-MIDDLE | 0.365 | 0.175 |
R6-WEST | 0.365 | 0.175 |
Index | Weight |
---|---|
𝑈𝐷𝐼450−2000lux [50%] | 0.360 |
[50%] | 0.640 |
Index | Weight |
---|---|
0.726 | |
[50%] | 0.274 |
Window-to-Wall Ratio | ||
---|---|---|
0.3 | 0.188 | 0.812 |
0.5 | 0.360 | 0.640 |
0.7 | 0.549 | 0.451 |
Orientation | 𝑈𝐷𝐼450−2000lux [50%] | 𝑈𝐷𝐼2000lux [50%] |
---|---|---|
East | 0.790 | 0.210 |
North | 0.100 | 0.900 |
Orientation | Window-to-Wall Ratio | 𝑈𝐷𝐼450−2000lux [50%] | 𝑈𝐷𝐼2000lux [50%] |
---|---|---|---|
East | 0.4 | 0.790 | 0.210 |
North | 0.2 | 0.100 | 0.900 |
South | 0.3 | 0.188 | 0.812 |
South | 0.5 | 0.360 | 0.640 |
South | 0.7 | 0.549 | 0.451 |
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations. |
© 2022 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).
Share and Cite
Li, C.; Yu, X.; Li, Z.; Zhao, Y.; Liu, Y.; Lian, X.; Feng, Y.; Zhu, H. Method for Determining Sensor Location for Automated Shading Control in Office Building. Energies 2022, 15, 4931. https://doi.org/10.3390/en15134931
Li C, Yu X, Li Z, Zhao Y, Liu Y, Lian X, Feng Y, Zhu H. Method for Determining Sensor Location for Automated Shading Control in Office Building. Energies. 2022; 15(13):4931. https://doi.org/10.3390/en15134931
Chicago/Turabian StyleLi, Cui, Xuyun Yu, Zhengrong Li, Yi Zhao, Yuxin Liu, Xiangchao Lian, Yanbo Feng, and Han Zhu. 2022. "Method for Determining Sensor Location for Automated Shading Control in Office Building" Energies 15, no. 13: 4931. https://doi.org/10.3390/en15134931
APA StyleLi, C., Yu, X., Li, Z., Zhao, Y., Liu, Y., Lian, X., Feng, Y., & Zhu, H. (2022). Method for Determining Sensor Location for Automated Shading Control in Office Building. Energies, 15(13), 4931. https://doi.org/10.3390/en15134931