1. Introduction
The sprinkler system is the most used main system to prevent the spread of fire in buildings. Generally, sprinkler systems are installed on the final finished surface of the ceiling, but if the presence of an obstruction such as an energy recovery ventilator or duct in the ceiling has the potential to impede sprinkler spray, additional sprinklers must be added under the obstruction in the form of a pendant. However, if the upper sprinkler close to the ceiling operates first, the lower sprinkler which is mounted on the pendant of about 30 cm below the ceiling is cooling down by low temperature water droplet from the upper sprinkler. Therefore, the sprinkler skipping problem occurs by this effect of cooling down.
In general, sprinklers used in many buildings operate using a glass bulb that expands and breaks at a specific temperature as a trigger. Therefore, for the sprinkler to work, the glass bulb must receive sufficient heat from the surrounding environment. Ensuring sufficient spray density is particularly important to block convection and radiative heat transfer. Moreover, the sequential operation of sprinklers is an important factor in ensuring spray density. However, if the ‘Sprinkler skipping’ phenomenon occurs, there is a high possibility of problems in preventing and suppressing the spread of fire because sufficient spray density is not secured in the near of fire source. According to previous studies, there are four main mechanisms of sprinkler skipping: cooling by droplet, droplet impingement, water vapor condensation, and air entrainment by spray [
1].
The following studies were conducted to investigate the heat transfer between the droplet and the flow and the cooling effect by the droplet impinging. The cooling effect was presented as an empirical formula by analyzing the temperature variation of sprinkler water temperature according to the droplet flux in a unit space [
2,
3,
4,
5]. As a result of this study, it was shown that the droplet flux is about 80–125 g/m
2s when water is discharging 1.9 L/s [
1]. Additionally, by analyzing the heat transfer mechanism in droplet size distribution, temperature, and fire plume size, the relationship between sprinkler skipping occurrence ratio and heat release rate and temperature was presented.
Air entrainment is the air flow dragged by droplets that are sprayed from the ceiling to the floor. This air flow cools the sprinkler head and causes sprinkler skipping. Specifically, Heskestad et al. [
4] showed that 0.85 m
3/s of air entrainment in the ceiling layer was generated by a sprinkler with a flow rate of 1.9 L/s.
Based on this analysis, sprinkler design was performed to prevent sprinkler skipping. John L. DE RIS presented a theoretical concept for a skip-resistant sprinkler. This study provided a theoretical basis for the cooling of the incoming gas to the sprinkler based on the C-Factor of the sprinkler and the reduction of heat transfer by the shield [
6]. Benjamin ditch et al. [
7] experimented with sprinklers that added a shield to prevent water droplets from impinging. As a result, it was shown that an average maximum of 50% sprinkler skipping prevention effect can be seen when operating at 5.2 bar.
P. Croce et al. [
8] presented a review paper on fast response sprinkler technology. The concepts of quick response residential sprinkler and early suppression fast response sprinkler have been summarized. In particular, early suppression fast response sprinkler was developed to deliver water quickly in the early stage of fire growth in an environment with rapid fire growth such as storage rack fire, but there is a high probability that sprinkler skipping will occur. If sprinkler spray is applied on the 12.2 m obstruction fire from the storage rack, the initial fire source suppression is slightly affected. However, the fire grew and strong plume carried the water droplets into the surrounding space, and the second ring sprinkler did not work, showing that sprinkler skipping occurred [
9]. Therefore, in order to prevent such sprinkler skipping, FM Data sheets have been proposed through various studies and the NFPA 13 Standard has been proposed and continues to be studied [
10]. Subsequently, complicate rules on an early suppression, fast-response sprinkler system installation method with regard to obstructions was proposed [
8].
However, these sprinkler skipping studies are limitedly applicable only to an open space or a space similar to a storage rack, and the shape of obstruction. The reason for this limitation is that the flow caused by a fire should be differences depending on the shape of the space and the boundary of environmental conditions. In particular, in a narrow space, as an air conditioning room, which is recently constructed for aesthetics and safety reasons in high-rise buildings, the effects of space and obstruction should be considered together with the existing sprinkler skipping characteristics. Moreover, various obstructions such as ducts, pipes, and energy recovery ventilators are installed in the air conditioning room, and sprinklers are additionally installed under the obstructions. However, in case of fire, the sprinkler skipping phenomenon under the obstruction causes a lot of casualties.
Therefore, in this study, in order to prevent the sprinkler skipping phenomenon in air-conditioning rooms, the fire characteristics were analyzed by numerical method and the effectiveness of open-type simultaneous opening sprinklers was analyzed.
3. Results
3.1. Effect of Obstruction in Sprinkler Spray Pattern
The change of sprinkler spray pattern according to the presence of obstruction was analyzed as shown in the
Figure 2. Blue and red particles represent water droplets sprayed from sprinklers installed 0.2 and 0.5 m below the ceiling respectively. The time the analysis was performed was 600 s when100 s after the sprinkler was operated.
In Case 1, the blue droplet sprayed from the upper sprinkler was relatively evenly distributed in the air-conditioned room, but there was no red droplet from the lower sprinkler. The upper sprinkler was operated by a fire source, but the lower sprinkler did not work, causing a sprinkler skipping phenomenon. An analysis of the effect of temperature on lower sprinkler operation is detailed in the next chapter. Additionally, the droplets sprayed from the upper sprinkler show the trend of spraying most of the enclosure space in a circular shape as shown in the
Figure 2b side view. Moreover, some of the sprayed droplets show movement toward the louver exit.
Case 2 shows a spray pattern in which droplets sprayed from the upper sprinkler are blocked by obstruction. Since the spray flow is not formed at all toward the fire source due to the spay failure caused by the obstruction, it is considered that there are many problems in suppressing the fire source even if the propagation of the fire to the obstruction can be prevented.
Case 3 is a spray pattern of a system in which the upper sprinkler is activated, and the lower sprinkler is also activated at the same time. The red droplet of the lower sprinkler has insufficient flow to the ceiling side close to the louver, but it shows a trend of sufficiently flowing as a fire source.
3.2. Effect of Obstruction in Temperature
In general, sprinklers operate by breaking glass bulbs by thermal expansion. Therefore, the analysis of the hot combustion gas is important for understanding the sprinkler skipping phenomenon. The temperature contour of XZ plan Y = 0 is represent in
Figure 3 at 600 s. The high-temperature combustion gas rises by the buoyancy flow generated by the fire, and the outside air is entrained under the louver as shown in the
Figure 3a.
In Case 1, since there is no obstruction, the water droplet is sprayed relatively evenly into the space, and the flow temperature discharged to the louver showed about 40–50 °C, which is relatively lower than that of Case 2. In addition, although the flow temperature around the lower sprinkler showed a relatively high trend; since the water droplets were impinged, the lower sprinkler head was sufficiently cooled to cause sprinkler skipping. The detailed temperature change over time of the sprinkler head is analyzed in the next chapter.
In Case 2 and Case 3, the spray flow of the upper sprinkler was blocked by the obstruction. Therefore, spray pattern of water droplets was concentrated under the obstruction. Therefore, the cooling effect of the flow around the lower sprinkler further increased, and the maximum temperature was maintained below 62 °C, which has a more adverse effect on the sprinkler skipping.
Case 3 had the lowest overall temperature distribution because both sprinklers were operating. In Case 3, as described above, when the upper sprinkler works, the lower sprinkler is also set to work. Thus, it works freely with sprinkler skipping. Droplets sprayed from the lower sprinkler were properly sprayed near the fire source; therefore, the overall temperature of the space showed the lowest trend.
The velocity contour of XZ plan Y = 0 is represented in
Figure 4 at 600 s. In all cases, the flow is caused by buoyancy, and after impinging the ceiling, a ceiling jet with a maximum flow velocity of 2 m/s is formed in the direction of the louver. In Case 1, it was formed near the ceiling because there is no obstruction that prevents the flow of the ceiling jet. However, the flows of Case 2 and Case 3 showed downward trends under obstruction. In addition, the flow velocity after exiting the louver was the fastest in Case 2. After exiting the louver, the flow velocity of the flow was most affected by the buoyancy force.
The temperature of the flow exiting through the louver near the ceiling was the highest in Case 2 as shown in the
Figure 5. This variation in temperature is due to the cooling effect of water droplets as described in
Figure 3 above. Moreover, there was relatively high fluctuation in temperature because the velocity of Case 2 was relatively higher than other cases.
The sprinkler head temperatures for each case are shown in
Figure 6. Obstruction delays the upper sprinkler head activation time by about 15 s to block the flow of high-temperature combustion gas about 540 s, 555 s, and 555 s in Case 1, Case 2, and Case 3 respectively. The increasing rate of the lower sprinkler temperature is relatively low because the combustion gases need to come down 50 cm from the ceiling. The maximum temperatures of the lower sprinkler were 65 °C, 57 °C, and 57 °C in Case 1, Case 2, and Case 3 respectively, lower than the sprinkler operating temperature of 68.33 °C.
In particular, after the upper sprinkler operation, the lower sprinkler head temperature of case 1 shows a trend of continuously increasing unlike other cases. This change in the sprinkler head temperature in case 1 is thought to be related to the spray pattern. As explained in the previous chapter, the temperature variation of the sprinkler head is affected by the high-temperature flow from fire source and the cooling effect by sprinkler spray. In Case 2 and Case 3, the spray patterns of the upper sprinkler were concentrated downward due to obstruction, and the water droplet densities were increased, resulting in sufficient cooling, and limiting the temperature rise. However, in case 1, it was analyzed that the temperature rose because the water droplet density was low.
4. Conclusions
The sprinkler skipping phenomenon that occurs in the case of a condenser fire in an air-conditioned room was analyzed by a numerical method. In general, two sprinklers were installed in air conditioner room at ceiling and 30 cm below to avoid spray failure by obstruction as duct and energy recovery ventilator in ceiling. However, the sprinkler skipping phenomenon occurred under all operating conditions, where the high-temperature heat flow from the fire source only operated the upper sprinkler close to the ceiling. In particular, the maximum temperature of the lower sprinkler was 65 °C, which is lower than the sprinkler operating temperature of 68.33 °C. The reason for this is that the water droplets sprayed from the upper sprinkler are sufficiently cooled by the flow temperature in the space, impinging on the sprinkler head. This is because the water droplet sprayed from the sprinkler sufficiently cools the flow in the space, and the low-temperature water droplet is impinged into the sprinkler head. Sprinkler skipping is exacerbated because the spray is blocked by obstruction. Moreover, it is analyzed that spray failure due to obstruction will be a problem because water droplets are not sprayed to the fire source.
Therefore, as an open type, simultaneous operation of two sprinklers could be able to obtain an appropriate fire extinguishing effect by covering the fire source with the spray of the lower sprinkler. This research results are expected to help in fire protection in buildings such as modern apartments with air-conditioned rooms. In addition, the results of this study can be usefully applied not only to air-conditioned rooms, but also to underground parking lots where sprinkler spray is disturbed by ducts and pipes.