Article

Eco-Efficient Vehicle Cooling Modules with Integrated Diffusers—Thermal, Energy, and Environmental Analyses

1
Energy and Thermofluid Group, The International University of Beirut BIU, Beirut 146404, Lebanon
2
College of Engineering and Technology, American University of the Middle East, Kuwait
3
Energy and Thermo-Fluid Group, Lebanese International University LIU, Bekaa 1803, Lebanon
4
LARIS EA 7315, Polytech Angers, University of Angers, 49000 Angers, France
5
ISTHY, l’Institut International sur le Stockage de l’Hydrogène, 90400 Meroux-Moval, France
6
Electrical Power and Machines Department, Faculty of Engineering, Zagazig University, Zagazig 44519, Egypt
7
Interdisciplinary Energy Research Institute (PIERI), University Paris Diderot, Sorbonne Paris Cite, 75013 Paris, France
*
Author to whom correspondence should be addressed.
Energies 2022, 15(21), 7917; https://doi.org/10.3390/en15217917
Submission received: 19 September 2022 / Revised: 7 October 2022 / Accepted: 20 October 2022 / Published: 25 October 2022

Abstract

:
The automotive domain is a very good candidate for energy management, particularly due to the huge amounts of energy lost by heat through exhaust and water-cooling systems. This makes the optimization of vehicle cooling modules directly related to energy consumption and carbon dioxide emission. In this context, contemporary designs that employ diffusers between the forward-facing of an automobile and its heat exchanger subjected to airflow are presented in this work. The ultimate aim is to reduce the fuel consumption and carbon dioxide emissions of vehicles. Based on the aforementioned design, the intensity of the air velocity would be decreased but distributed over a larger exchanger surface. Consequently, the velocity non-uniformity of the airflow upstream would decrease and therefore, the thermal performance would increase. The above-mentioned conclusion is a result of parametric numerical analysis and its associated numerical results that disclosed the enhancement of water-air heat exchanger thermal performance. To perform a parametric numerical analysis of the heat exchanger thermal performance for the new suggested configurations, a computational code was developed and validated to estimate the thermal performance for a known set of parameters. It was shown that for an automobile, with engine power ranging from 100–200 kW that is utilized for three hours a day and equipped with a diffuser, reduction of up to 2.91 kg (3.89 L) of gasoline consumption and 9.51 kg of CO2 emission can be achieved per day. The originality of the present work resides in the use of diffusers in cooling modules of vehicles, the thermal modeling of heat exchanger’s thermal performance along with its associated code, and the parametric analysis performed to prove the potential enhancement related to the use of diffusers in the cooling modules.

1. Introduction

Current trends in energy research lean toward fuel consumption and carbon dioxide emission reduction [1,2]. These aims fall under broad titles in research such as renewable energy and energy management systems. Engineering systems and applications often include processes and components that require and consume significant energy; this makes energy management one of the primordial solutions to achieve a suitable setup in terms of performance, consumption, and emission [3,4]. The automotive domain is a prime example of a system that requires energy management, particularly due to the huge amounts of energy lost by heat through the exhaust and water-cooling systems [5,6]. Therefore, the optimization of vehicle cooling modules is directly related to energy consumption and carbon dioxide emission reduction goals. Moreover, with the optimization of the cooling system operation, acceptable magnitude orders of fuel consumption and carbon dioxide emission reductions can be obtained.
Cooling modules of vehicles are composed of minimum two heat exchangers: the radiator and the condenser [7]. Heat exchangers (HX) are devices that allow for heat exchange between two fluid streams. Fields involved in energy production (power plants, solar systems, nuclear reactors, etc.), heating/cooling (residential applications, automotive industry, etc.), industrial processing (chemicals, pharmaceuticals, food, etc.), and others such as robotics and aerospace applications utilize heat exchangers [8,9,10]. It is well known that the mode of interaction between cold and hot streams dictates the characteristics of heat exchangers.
Some popular heat exchanger types are shell-tube, tube-fin, micro-channels, and counter-flow channels heat exchangers [11,12,13]. From these types, the fin and tube heat exchangers are commonly used in different industries, especially in automotive applications, primarily since fin and tube heat exchangers are characterized by their lightweight and compact design, in addition to being thermally efficient [14,15,16]. Furthermore, the tube-and-fin is one of the best layouts that could be used for air-water heat exchangers. The water circulates in the tubes of elliptical cross-sections and the air flows between the fins. Generally, in the automotive industry, there exist two types of front-engine air intakes: the high lattice air intake and the low lattice air intake [7]. Air intake designs can be classified as described in Figure 1.
These designs are highly dependent on compromises that must take place between aerodynamic and thermal requirements so that components in the underhood function soundly. These front-end openings induce non-uniform upstream airflow velocity distribution over the first exchanger at their downstream (most commonly the condenser of the vehicle) where a part of its area will be cooled by a given velocity and the rest of the overall area will be cooled by small or negligible velocities.
Researchers have performed extensive studies and analyses on the non-uniformity of air velocity to predict how various types of air-liquid exchangers will thermally perform under these maldistributions, including ranges of industrial applications and functioning parameters. Beiler and Kroger [17] reported that non-uniformity in the distribution of airflow leads to a decrease in the performance of heat exchangers. Nonetheless, these reductions could be neglected when using elegant air-cooled exchangers. In addition, simulation programs to calculate the influence of uniform liquid flow with non-uniform airflow have been developed by researchers. T’Joen et al. [18] presented a computational tool that facilitates obtaining well-organized heat exchanger design configurations and showed that exchanger performance deteriorates due to airflow maldistribution.
Mueller [19] showed that the performance of the heat exchanger depends on the type of airflow. For turbulent flow, the impact on the performance of the heat exchanger is minimal, whereas the impact is more significant for laminar flow. Mao et al. [20] investigated the thermal aspects of the performance of a louvered fin-and-tube heat exchanger and its pressure drop when subjected to airflow maldistribution, obtaining 6% and 34% as the maximum reduction capacity and pressure drop increment, respectively. Chin and Raghayan [21] adopted a statistical approach and found that the thermal performance of the fin-tube heat exchanger is influenced by the mean, skew, and standard deviation of a non-uniform airflow profile, but not its kurtosis.
Kaern et al. [22] numerically investigated the performance of an evaporator under maldistributions in the feeder tube bend, inlet liquid/vapor phase, and airflow. It was demonstrated that the cooling capacity in addition to the coefficient of performance are reduced in case of misdistribution in airflow.
Fin-and-tube heat exchanger, which is the dominant HX type in automotive applications, was investigated by Khaled et al. [23] to understand the impact of airflow velocity maldistribution on its performance. Results revealed a clear effect of non-uniformity on the HX’s performance, as a thermal performance reduction of up to 35% occured for maximum degrees of velocity maldistribution (represented by a ratio of 1 of the velocity distribution standard deviation to its mean).
Huang and Wang [24] provided 3D U-type compact parallel flow HX designed to obtain a uniform tube flow. Chu et al. [25] numerically simulated four novel designs through computational fluid dynamics to obtain a uniform inlet flow for a HX in high-temperature applications. A 52% non-uniformity reduction was obtained for a manifold with helical baffles which induced a 24% increase in the Nusselt number.
Yaici et al. [26] investigated, through CFD-3D simulations, the effect of inlet airflow non-uniformity on thermo-hydraulic performance. An enhancement or deterioration of up to 50% in the Colburn j-factor was observed in comparison to a HX with a maldistributed inlet air velocity profile.
The existence of airflow non-uniformities in compact heat exchangers was reviewed by Singh et al. [27]. The review was performed in terms of temperature and flow and their effects on the performance of different energy transfer equipment. A decline of the thermal performance of many types of equipment due to the flow non-uniformity effect was reported.
Therefore, based on the aforementioned studies of heat exchanger thermal performance in relation to upstream airflow velocity maldistribution, the following two points can be made:
  • Performance deterioration due to airflow maldistribution is evident and well-proven in liquid-air heat exchangers;
  • Scarce are the studies that take advantage of controlling or acting on the airflow non-uniformity to improve HX performance (by reducing airflow non-uniformity).
In this context and as depicted in Figure 2, the present manuscript suggests a new concept of integrating a diffuser downstream of the vehicle’s front air intake and upstream of the first exchanger such that the non-uniformity in the airflow velocity distribution is reduced and the thermal performance of water-air heat exchangers is improved. Diffusers, in terms of physical parameters, are devices that decrease the velocity but increase the pressure. Diffusers are known for providing a more uniformly distributed flow which is evident in their use in heating, ventilating, and air conditioning systems [28] to supply rooms with an evenly distributed conditioned airflow. Diffusers also serve the purpose of slowing the compressor airflow and increasing its uniformity before entering the combustion chamber in a jet engine [29], hence the motivation to utilize diffusers in a vehicle’s cooling module, as shown in the complete setup illustrated in Figure 3.
It is obvious that the diffuser causes a reduction in the velocity magnitude of the flow supplied to the HX. Moreover, while the flow rate is the same at the air inlet opening and over the area of the exchanger such that the velocity distribution has the same mean velocity, the standard deviation is now lower, i.e., more uniform airflow velocity distribution. This decrease in air non-uniformity will increase thermal performance. Based on the above, parametric analyses that included the effect of various parameters was considered in Section 4. The parameters considered are detailed below:
  • Area ratio of the inlet opening to that of the HX.
  • Diffuser length, i.e., the distance from the air inlet to the first HX.
  • Diffuser angle and the mass flowrates of water and air.
Calculations were done using an in-house computational code that is detailed in Section 2. Section 3 is then devoted to the experimental validation of the code. Section 4 presents then the results and observations. Then, Section 5 exposes details on energy consumption and carbon dioxide emission reductions. Finally, Section 6 draws the main conclusions of the work.

2. In-House Computational Code

The in-house computational code is different from the standard finite element, difference, and volume techniques-based software platform. The main difference is that the standard software platforms draw the geometry of the considered element and consider the complex details of this geometry while the suggested in-house computational code considers the geometry of the heat exchanger as a black box and its effect is represented in the experimental determination of the overall heat transfer coefficient. Another important difference is that the in-house computational code relies on correlations obtained from preliminary experimental tests, mainly for the overall heat transfer coefficient. Finally, the main advantages of the in-house developed code are its low computational costs in terms of CPU time and memory space. When compared to a finite element or finite volume, the computational cost of the method is almost negligible. The method is motivated by the fact that the conditions that the heat exchanger may undergo are not necessarily uniform. In other terms, non-uniform conditions may occur in some applications such as non-uniform temperature field distribution or fluid velocity field distribution. The standard heat exchanger modeling approach that considers the heat exchanger domain as one unique patch becomes inaccurate. In other words, it becomes inevitable to adopt an approach that allows taking the non-uniform operational conditions into consideration.
The proposed method facilitates expressing the non-uniform conditions that may be experienced by the heat exchanger, this is achieved by dividing the HX into multiple elements denoted by “Representative Cells” (RC), as shown in Figure 4.
Consequently, obtaining the outlet temperature of each RC, and finally, the overall HX outlet temperature (simultaneously HX thermal performance) is carried out by:
  • Applying the global governing equations of energy balance to each RC.
  • Obtained results from each RC (outlet parameters) serve as the inlet boundary conditions of the neighboring cell.
It should be noted that in the present study, the flow rate of water in each heat exchange tube is uniform.
The global heat exchanger problem is written in terms of overall heat-transfer coefficient U and thermal performance P according to the expression of Equation (1) [30,31]:
P = U A Δ T a m
where A is the heat exchanger area, and Δ T a m is the arithmetic difference of temperature given by:
Δ T a m = T i n , f l u i d + T o u t , f l u i d 2 T i n , a i r
where the inlet and outlet temperatures of the liquid through the HX are respectively T i n , f l u i d and T o u t , f l u i d , T i n , a i r is the air temperature upstream of the exchanger, and U the overall heat transfer coefficient of the HX calculated as a rational function of the heat exchanger liquid flow rate m ˙ f l u i d and the cooling airflow rate m ˙ a i r . By combining the equations of the rate of heat exchange between the two fluids at each cell and the energy balance on the exchanger liquid side between the entrance and the exit of a cell the outlet temperature can be written as follows:
T o u t , c e l l = a m ˙ c e l l , f l u i d ; V c e l l T i n , c e l l + b m ˙ c e l l , f l u i d ; V c e l l T a i r , c e l l
where a and b are written in terms of the parameters of the fluids.
The method used to obtain the overall heat transfer coefficient of the heat exchanger is provided below.

Overall Heat Transfer Coefficient

Experimental data obtained by experiments done on the exchanger alone yield distinct U values of the exchanger such that for every couple of fluid flow rates m ˙ and airflow mean velocity V , a value of U will be obtained, which is assigned at the representative cell level traversed by the aforementioned couple of liquid flowrate and airflow mean velocity. The extrapolation technique of the code permits then to develop a general expression that determines the overall U value of a representative cell of the exchanger traversed by any couple of liquid flowrate and mean airflow velocity. To proceed, the method is based on rational extrapolation functions [30] of the general form:
f x = A + C x D B + x D
with A , B , C , and D being constants to be determined. The idea of the extrapolation method is to obtain these constants by a set of experimental points x i ; f i where i = 1 k ( k is the number of experimental points). The iterative procedure starts by assuming a D value, yielding the algebraic system:
f i = A + C x i D B + x i D for   i = 1 k
The solution of the system of Equation (5) by utilizing three points x i ; f i of the experimental data provides the three constants A , B , C as follows:
C = f 1 f 2 f 3 x 3 D f 1 x 1 D f 1 f 3 f 2 x 2 D f 1 x 1 D f 1 f 2 x 3 D x 1 D f 1 f 3 x 2 D x 1 D
B = f 3 x 3 D f 1 x 1 D x 3 D x 1 D C f 1 f 3
A = f 1 x 1 D + f 1 B x 1 D C
Then, the value of D will be adjusted iteratively so that the error vector’s magnitude is minimized:
E = f exp x i f A , B , C , D x i
where E is the error vector, f exp x i is the vector of experimental data obtained for the overall heat transfer coefficient, and f A , B , C , D x i is the vector of overall heat transfer values obtained using the rational function of Equation (5). The iterative method presented above is then followed to obtain the overall heat transfer coefficient U of an exchanger operating with a prescribed couple of liquid mass flowrate and mean airflow velocity m ˙ f ; V f . Figure 5 shows an illustration of the method used to obtain the overall heat transfer coefficient for a given couple m ˙ f ; V f .
For each mean air velocity V j (for j = 1 l , l is the number of experimental data corresponding to l different configurations of mean air velocity), the functions g j m ˙ are obtained from k experimental values f i i = 1 k (nodal values) using the iterative method presented above:
g j m ˙ = A g j + C g j m ˙ D g j B g j + m ˙ D g j j = 1 l
Thus, with the obtained l expressions g j m ˙ , l nodal values g j m ˙ f for   j = 1 l are obtained from liquid mass flowrates m ˙ f . From these values, f m ˙ f V is also determined using the iteration method presented above:
f m ˙ f V = A m ˙ f + C m ˙ f V D m ˙ f B m ˙ f + V D m ˙ f
Lastly, the exchanger’s overall heat transfer coefficient can be obtained using the following expression:
U m ˙ f ; V f = f m ˙ f V f
An illustration of the U-value estimation with the developed code is shown in Figure 6.

3. Experimental Validation

In this section, numerical data are associated with their experimental equivalents. Comparisons are done for the overall heat transfer coefficient (Section 3.2) and the thermal performance of the exchanger (Section 3.3). The experimental setup used to obtain experimental data is presented in Section 3.1.

3.1. Experimental Setup

The objective of the experimental setup is to measure the heat exchanger’s performance for several configurations of airflow velocities and water flow rates. The schematic of the experimental setup is shown in Figure 7.
The heat exchanger used in the experimental setup is a tubes-and-fins type that has the structure and characteristics shown in Figure 8.
Inlet hot water of any desired inlet temperature can be provided to the HX using the circuit shown.
The thermal circuit of the experimental setup essentially comprises a boiler of variable power, a radiator (fin-and-tube, air to water, airflow of different velocities provided by wind tunnel) of a real vehicle (Peugeot 207), the main water supply, a flowmeter, small taps, and traps.
The boiler has a built-in pump with several speeds and a temperature sensor that allows setting the hot temperature (the temperature at the radiator inlet) according to prescribed values. Three thermocouples are used to provide measurements of the water’s inlet and outlet temperatures as well as the upstream air temperature. Thermocouples used are type T thermocouples having ±1 °C or ±0.75% of accuracy.
Temperature recordings are taken for specified airflow velocity and water flow rate values. The obtained experimental data permit the estimation of the overall U value using Equations (1) and (2). The air velocities tested are 0.5, 1, 2, 3, 4, 5, 6, 7, and 8 m/s and the water flowrates tested are 1500, 3000, 5000, 6000, 8000, and 9000 L/h; which corresponds to 60 configurations of a couple of water and airflow rates where the corresponding overall heat transfer coefficient is measured. Air velocities are measured using a pitot tube having an accuracy ranging from 0.5% to 5%. The flowmeter used has an accuracy of 0.10%.

3.2. Comparisons of Overall Heat Transfer Coefficient

In this part, the experimental validation of the method of estimation of the overall heat transfer coefficient (extrapolation method) of Section 2 is presented.
To proceed, the rational function of the overall heat transfer coefficient is calculated based on the airflow velocity values varying from 0.5 to 7 m/s for each curve. Then, the overall heat transfer coefficient is determined for an airflow velocity of 8 m/s for multiple water flow rates by means of the rational function extrapolation method. The calculated overall U values are then compared to the data obtained by the experimental setup.
Figure 9 shows the overall U value using the extrapolation rational method versus those obtained experimentally (Figure 9a) as well as the relative error of determining the overall heat transfer coefficient with the rational function method (Figure 9b).
As shown in Figure 9a, the overall heat transfer coefficient variation obtained with the rational function method fits very well with the experimental behavior. To exemplify, at a water flow rate of 6000 L/h, the overall heat transfer coefficient conveys an experimental value of 6066 W/m2 K while an estimation of 6024 W/m2 K is found with the rational function.
In terms of relative error, it ranges from 0 to 0.9% as the water flow rate changes between 1500 and 9000 L/h. Therefore, the rational function method calculates the overall heat transfer coefficient with an average relative error of 0.47%. Similarly, the same procedure is followed for all air velocities and water flow rates, yielding results of the same order of magnitude. Therefore, the semi-analytical rational function method is valid for obtaining the overall heat transfer coefficients.

3.3. Comparisons of Thermal Performance

This section concerns the experimental validation of the whole scheme of the in-house computational code. For this purpose, one of the most important outputs of the code which is the exchanger’s thermal performance is selected. To proceed, an exchanger with a water flow rate of 6000 L/h is considered. Water is considered to enter the exchanger at 95 °C while the air upstream of the heat exchanger is considered to be at a temperature of 20 °C. Simulations with the code were performed for an air velocity ranging from 1 to 8 m/s.
Figure 10 presents the evolution of the exchanger’s performance as a function of airflow velocity using the in-house computational code and experimentally obtained data (Figure 10a) as well as the relative error of determining the thermal performance with the in-house computational code (Figure 10b).
From Figure 10a, it is clear that the variation of the performance obtained with the computational code fits very well with the experimental behavior. To illustrate, at an airflow velocity of 6 m/s, with respect to the thermal performance of 74.9 kW obtained experimentally, the thermal performance determined with the computational code is 73.1 kW.
As for the relative error, it varies between 0.43% and 3.76% when the airflow velocity varies between 0.5 and 8 m/s. Therefore, the computational code calculates thermal performances with an average relative error of 1.86%. The above procedure was used for multiple ranges of air velocities and water flow rates, giving the same orders of magnitude.
Therefore, the computational code has sufficient accuracy and precision to calculate thermal performance and overall heat transfer coefficient. The next section will be devoted to the use of the in-house computational code to obtain results for the new design suggested (use of diffusers in cooling modules of vehicles).

4. Results, Observations, and Discussions

In this section, parametric analysis on the enhancement of the heat exchanger’s thermal performance, with the novel setup of introducing a diffuser ahead of the cooling module is presented by employing the above-mentioned code. Figure 11 portrays an illustration of the proposed exchanger-diffuser setup along with the main parameters is presented.
The relation between the diffuser’s geometrical parameters is expressed by:
z = x + 2 y tan θ
Normalization of the parameters x, y, and z is done with respect to the heat exchanger’s length as shown in the following equations:
X = x H
Y = y H
Z = z H
A maximum value of the diffuser’s large cross-sectional height is set to prevent it from exceeding the heat exchanger’s height. Moreover, a suitable spacing between the exchanger and the vehicle’s front opening must be chosen.
The first calculation set is performed for a 6000 L/h water flow rate and 7 m/s airflow velocity. The inlet temperature of water is set at 90 °C and that of air at 20 °C. The angle of the diffuser is fixed at 30°. Under these conditions, for multiple values of ratio X (0.2, 0.3, 0.4, and 0.5), ratio Y is varied from zero to the highest permitted value. Figure 12a shows the variation of the heat exchanger’s thermal performance with a diffuser, and Figure 12b represents the percentage of its enhancement evaluated in reference to the case without a diffuser (Y = 0).
The performance enhancement percentage indicates the additional heat removal from the water stream with the inclusion of the diffuser relative to the basic case where no diffuser is added.
As shown in Figure 12, as the ratios X and Y increase, the thermal performance increases. However, the enhancement of the performance decreases with the increase of X. To elaborate, for a ratio of X = 0.2 (i.e., an air inlet opening height of about 20% of that of the HX), when Y increases from 0 to 0.7, an increase from 16.3 to 23.1 kW is observed in the thermal performance. To further illustrate, when Y is increased from zero to its maximum value which becomes 0.4 at X = 0.5, an increase from 39.6 to 49 kW is observed in the thermal performance. As for the performance enhancement (which increases with Y and decreases with X), it reaches a maximum of 41.9% for the X = 0.2; while for X = 0.5 a maximum enhancement of 23.8% is achieved. Therefore, to have the best improvement it is therefore necessary to provide a fairly long diffuser (large Y) and with a small height of the small cross-sectional area (X).
The second set of calculations is undergone with a 20 °C upstream air temperature and 90 °C water inlet temperature (same conditions as the first set). The ratio X is taken to be equal to 0.3. The ratio Y is fixed at 0.3 and the angle of the diffuser is fixed at 30°. Figure 13 provides the outcomes of the heat exchanger performance enhancement that is obtained in reference to the case without a diffuser (for Y = 0) with respect to air velocity at the air inlet opening for different water flow rates.
It is observed in Figure 13 that the percentage of thermal performance enhancement increases as air velocity increases. As illustrated, at 1500 L/h water flow rate, as the velocity is increased from 2 to 16 m/s, enhancement of the performance leaps from 11.3 to 67%. Moreover, with a 9000 L/h water flow rate and the same range of airflow velocity, the performance enhancement rises from 2.8 to 46.3%. Finally, the enhancement provided by the introduction of the diffuser is larger at high air velocities and low water flow rates.
The third set of calculations is performed with an inlet water flow temperature of 90 °C and upstream air at 20 °C (same conditions as the first and second sets). Air velocity is set to 7 m/s, water flowrate of 9000 L/h is chosen and Y is fixed at 0.3. The diffuser angle is varied for multiple values of ratio X. Consequently, Figure 14 shows the percentage of performance enhancement evaluated in reference to the case without a diffuser (Y = 0).
As mentioned previously, the inlet diffuse area is set to a certain value (X = 0.2, 0.3, 0.4, or 0.5), while the distance between the HX and the inlet opening is constant throughout (Y = 0.3). The trend of the curves clarifies that the thermal performance enhancement increases when the diffuse angle increases. To illustrate, with X = 0.2, a 13% increase in performance enhancement is achieved when increasing the angle of the diffuser from 20 to 55°. It is interesting to note that this improvement is lesser at larger X. For X = 0.5, increasing the angle of the diffuser from 20 to 40° causes an increase in the performance enhancement of 12.5 to 21.8%. It must be observed in Figure 14 that an upper limit exists for the diffuser angle depending on the value of X else the diffuser’s outlet section would be greater than the exchanger’s area.

5. Energy and Environmental Calculations

Now, to quantify the percentages of energy consumption reduction that can be achieved with the suggested novel design, a condenser-radiator cooling module is considered downstream. For each exchanger, namely, the radiator and the condenser, the novel design is considered to result in an enhancement ratio E H X defined as:
E H X = P n P 0 = 1 + η
where P n is the exchanger’s performance with the new design implemented and P o its thermal performance in the original design (i.e., without the new design implementation) and η is the enhancement presented in Figure 12, Figure 13 and Figure 14.
Now, the enhancement of the exchanger’s thermal performance can be seen as a reduction of the flow rates of the radiator’s water and the condenser’s refrigerant by a factor 1 E H X to have the same performance as the exchanger. These flow rate drops induce reductions of approximately 1 E H X of the pump’s power requirement P p u m p ; and 1 E H X 1 + C O P of the HVAC compressor’s power requirement P c o m p r e s s o r , where COP is the HVAC system’s coefficient of performance. Then, the power consumption reduction PCR is:
P C R = P p u m p + P c o m p r e s s o r ( C O P + 1 ) 1 1 E H X
Then, Equations (19) and (20) express the input power consumption reduction IPCR and the fuel consumption reduction FCR, respectively:
I P C R = P C R η = P p u m p + P c o m p r e s s o r ( C O P + 1 ) 1 1 E H X η
F C R = I P C R q c = P p u m p + P c o m p r e s s o r ( C O P + 1 ) 1 1 E H X η q c
where η is the efficiency of the engine and q c the heat of combustion of the fuel. For vehicles with powertrains ranging from 100 kW to 200 kW, the maximum powers P p u m p and P c o m p r e s s o r needed to operate the water pump and the compressor are respectively about 10 kW and 4 kW [7,32]. Moreover, the COP for most of the HVAC systems of vehicles is around 3 [7]. A gasoline vehicle emits, per 1 kg of gasoline, 3.28 kg of carbon dioxide, it has an average efficiency of 0.35 and 47 MJ/kg heat of combustion [32]. Figure 15 shows the variation of the fuel consumption reduction FCR and carbon dioxide emission reduction CDER (3.28 kg for each kg of gasoline burned) in function of the enhancement ratio E H X of the exchanger achieved with the implementation of the new design.
According to Figure 15, it can be shown that around 0.22 kg/h of fuel consumption rate and 0.72 kg/h of carbon dioxide emission rate can be reduced if the diffuser is applied to a given configuration and increases the thermal performance of the exchanger by 10% (enhancement ratio of 1.1). These reductions can reach respectively 0.97 kg/h and 3.17 kg/h if the thermal enhancement is up to 67% (which corresponds to the maximum value obtained with the parametric analysis above). Lastly, for a vehicle that operates about three hours a day, up to 2.91 kg (3.89 L) of gasoline consumption and 9.51 kg of emitted carbon dioxide can be reduced per day.

6. Conclusions

The following conclusions can be drawn:
  • An innovative designing approach of the water-air heat exchanger was presented in this paper.
  • Performance optimization was extensively considered for a water-air heat exchanger which experiences airflow velocity maldistribution caused primarily by the air inlet openings.
  • The contemporary designing approach is based on introducing a diffuser between the vehicle’s front-end openings and the first exchanger subjected to the airflow (usually the condenser). Consequently, the diffuser results in a wider spread of the airflow over the exchanger area, with reduced velocity magnitude. This leads to a decrease in air velocity maldistribution (more uniformity) over the exchanger, and thus enhances its thermal performance. Calculations were carried out with a computational code developed by the authors.
  • It was proven that the thermal performance of the exchanger is increased by up to 67% when the diffuser is present. This enhancement induces up to 0.97 kg/h and 3.17 kg/h of reduction rates of respectively the fuel consumption and carbon dioxide emissions. Finally, with the vehicle considered running three hours per day, up to 2.91 kg (3.89 L) of gasoline consumption and 9.51 kg of carbon dioxide emission can be reduced.

Author Contributions

Conceptualization, M.K.; Data curation, J.F.; Formal analysis, J.F., K.C., M.M., T.L., H.S.R. and M.K.; Investigation, J.F., K.C., M.M., T.L., H.S.R. and M.K.; Methodology, J.F. and M.K.; Project administration, M.K.; Supervision, M.K.; Validation, J.F.; Writing – original draft, J.F.; Writing – review & editing, K.C., M.M., T.L., H.S.R. and M.K. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

Not applicable.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Murshed, M. Pathways to clean cooking fuel transition in low and middle income Sub-Saharan African countries: The relevance of improving energy use efficiency. Sustain. Prod. Consum. 2022, 30, 396–412. [Google Scholar] [CrossRef]
  2. Lipiäinen, S.; Kuparinen, K.; Sermyagina, E.; Vakkilainen, E. Pulp and paper industry in energy transition: Towards energy-efficient and low carbon operation in Finland and Sweden. Sustain. Prod. Consum. 2022, 29, 421–431. [Google Scholar] [CrossRef]
  3. Guo, J.X.; Zhu, K. Operation management of hybrid biomass power plant considering environmental constraints. Sustain. Prod. Consum. 2022, 29, 1–13. [Google Scholar] [CrossRef]
  4. Shooshtarian, S.; Maqsood, T.; Caldera, S.; Ryley, T. Transformation towards a circular economy in the Australian construction and demolition waste management system. Sustain. Prod. Consum. 2022, 30, 89–106. [Google Scholar] [CrossRef]
  5. Pallaro, E.; Subramanian, N.; Abdulrahman, M.D.; Liu, C. Sustainable production and consumption in the automotive sector: Integrated review framework and research directions. Sustain. Prod. Consum. 2022, 4, 47–61. [Google Scholar] [CrossRef]
  6. Fernando, Y.; Tseng, M.L.; Sroufe, R.; Abideen, A.Z.; Shaharudin, M.S.; Jose, R. Eco-innovation impacts on recycled product performance and competitiveness: Malaysian automotive industry. Sustain. Prod. Consum. 2021, 28, 1677–1686. [Google Scholar] [CrossRef]
  7. Khaled, M.; Ramadan, M.; El-Hage, H.; Elmarakbi, A.; Harambat, F.; Peerhossaini, H. Review of underhood aerothermal management: Towards vehicle simplified models. Appl. Therm. Eng. 2014, 73, 842–858. [Google Scholar] [CrossRef]
  8. Chen, J.; Wu, J.; Ji, X.; Lu, X.; Wang, C. Mechanism of waste-heat recovery from slurry by scraped-surface heat exchanger. Appl. Energy 2017, 207, 146–155. [Google Scholar] [CrossRef]
  9. Diaz-Bejarano, E.; Behranvand, E.; Coletti, F.; Mozdianfard, M.R.; Macchietto, S. Organic and inorganic fouling in heat exchangers–Industrial case study: Analysis of fouling state. Appl. Energy 2017, 206, 1250–1266. [Google Scholar] [CrossRef] [Green Version]
  10. Tian, E.; He, Y.L.; Tao, W.Q. Research on a new type waste heat recovery gravity heat pipe exchanger. Appl. Energy 2017, 188, 586–594. [Google Scholar] [CrossRef]
  11. Jagirdar, M.; Lee, P.S. Mathematical modeling and performance evaluation of a desiccant coated fin-tube heat exchanger. Appl. Energy 2018, 212, 401–415. [Google Scholar] [CrossRef]
  12. Zanchini, E.; Jahanbin, A. Correlations to determine the mean fluid temperature of double U-tube borehole heat exchangers with a typical geometry. Appl. Energy 2017, 206, 1406–1415. [Google Scholar] [CrossRef]
  13. Gasia, J.; Tay, N.S.; Belusko, M.; Cabeza, L.F.; Bruno, F. Experimental investigation of the effect of dynamic melting in a cylindrical shell-and-tube heat exchanger using water as PCM. Appl. Energy 2017, 185, 136–145. [Google Scholar] [CrossRef] [Green Version]
  14. Kowsari, M.M.; Niazmand, H.; Tokarev, M.M. Bed configuration effects on the finned flat-tube adsorption heat exchanger performance: Numerical modeling and experimental validation. Appl. Energy 2018, 213, 540–554. [Google Scholar] [CrossRef]
  15. Fumey, B.; Weber, R.; Baldini, L. Liquid sorption heat storage–A proof of concept based on lab measurements with a novel spiral fined heat and mass exchanger design. Appl. Energy 2017, 200, 215–225. [Google Scholar] [CrossRef]
  16. Yang, X.; Lu, Z.; Bai, Q.; Zhang, Q.; Jin, L.; Yan, J. Thermal performance of a shell-and-tube latent heat thermal energy storage unit: Role of annular fins. Appl. Energy 2017, 202, 558–570. [Google Scholar] [CrossRef]
  17. Beiler, M.G.; Kröger, D.G. Thermal performance reduction in air-cooled heat exchangers due to nonuniform flow and temperature distributions. Heat Transf. Eng. 1996, 17, 82–92. [Google Scholar] [CrossRef]
  18. T’joen, C.; Willockx, A.; Steeman, H.J.; De Paepe, M. Performance prediction of compact fin-and-tube heat exchangers in maldistributed airflow. Heat Transf. Eng. 2007, 28, 986–996. [Google Scholar]
  19. Mueller, A.C. Effects of some types of maldistribution on the performance of heat exchangers. Heat Transf. Eng. 1987, 8, 75–86. [Google Scholar] [CrossRef]
  20. Mao, J.N.; Chen, H.X.; Jia, H.; Wang, Y.Z.; Hu, H.M. Effect of air-side flow maldistribution on thermal–hydraulic performance of the multi-louvered fin and tube heat exchanger. Int. J. Therm. Sci. 2013, 73, 46–57. [Google Scholar] [CrossRef]
  21. Chin, W.M.; Raghavan, V.R. The influence of the moments of probability density function for flow maldistribution on the thermal performance of a fin-tube heat exchanger. Int. J. Therm. Sci. 2011, 50, 1942–1953. [Google Scholar] [CrossRef]
  22. Kærn, M.R.; Brix, W.; Elmegaard, B.; Larsen, L.F.S. Performance of residential air-conditioning systems with flow maldistribution in fin-and-tube evaporators. Int. J. Refrig. 2011, 34, 696–706. [Google Scholar] [CrossRef] [Green Version]
  23. Khaled, M.; Harambat, F.; Peerhossaini, H. Analytical and empirical determination of thermal performance of louvered heat exchanger–effects of air flow statistics. Int. J. Heat Mass Transf. 2011, 54, 356–365. [Google Scholar] [CrossRef]
  24. Huang, C.H.; Wang, C.H. The study on the improvement of system uniformity flow rate for U-type compact heat exchangers. Int. J. Heat Mass Transf. 2013, 63, 1–8. [Google Scholar] [CrossRef]
  25. Chu, W.X.; Ma, T.; Zeng, M.; Qu, T.; Wang, L.B.; Wang, Q.W. Improvements on maldistribution of a high temperature multi-channel compact heat exchanger by different inlet baffles. Energy 2014, 75, 104–115. [Google Scholar] [CrossRef]
  26. Yaïci, W.; Ghorab, M.; Entchev, E. 3D CFD analysis of the effect of inlet air flow maldistribution on the fluid flow and heat transfer performances of plate-fin-and-tube laminar heat exchangers. Int. J. Heat Mass Transf. 2014, 74, 490–500. [Google Scholar] [CrossRef]
  27. Singh, S.K.; Mishra, M.; Jha, P.K. Nonuniformities in compact heat exchangers—Scope for better energy utilization: A review. Renew. Sustain. Energy Rev. 2014, 40, 583–596. [Google Scholar] [CrossRef]
  28. Sun, Y.; Smith, T.F. Air flow characteristics of a room with square cone diffusers. Build. Environ. 2005, 40, 589–600. [Google Scholar] [CrossRef]
  29. Lee, G.G.; Allan, W.D.; Boulama, K.G. Flow and performance characteristics of an Allison 250 gas turbine S-shaped diffuser: Effects of geometry variations. Int. J. Heat Fluid Flow 2013, 42, 151–163. [Google Scholar] [CrossRef]
  30. Khaled, M.; Harambat, F.; El Hage, H.; Peerhossaini, H. Spatial optimization of an underhood cooling module–Towards an innovative control approach. Appl. Energy 2011, 88, 3841–3849. [Google Scholar] [CrossRef]
  31. Khaled, M.; Ramadan, M.; Shaito, A.; El Hage, H.; Harambat, F.; Peerhossaini, H. Parametric analysis of heat exchanger thermal performance in complex geometries—Effect of air velocity and water flow distributions. Heat Transf. Eng. 2016, 37, 1027–1037. [Google Scholar] [CrossRef]
  32. Ferguson, C.R.; Kirkpatrick, A.T. Internal Combustion Engines: Applied Thermosciences, 2nd ed.; John Wiley & Sons: Hoboken, NJ, USA, 2001. [Google Scholar]
Figure 1. Design of air intakes.
Figure 1. Design of air intakes.
Energies 15 07917 g001
Figure 2. New suggested design: use of a diffuser in the cooling module.
Figure 2. New suggested design: use of a diffuser in the cooling module.
Energies 15 07917 g002
Figure 3. The vehicle cooling module with the suggested diffuser integration.
Figure 3. The vehicle cooling module with the suggested diffuser integration.
Energies 15 07917 g003
Figure 4. Splitting of the heat exchanger area into multiple RCs.
Figure 4. Splitting of the heat exchanger area into multiple RCs.
Energies 15 07917 g004
Figure 5. Schematic of the method of obtaining the overall U value from nodal experimental data.
Figure 5. Schematic of the method of obtaining the overall U value from nodal experimental data.
Energies 15 07917 g005
Figure 6. Flow chart of the U-value estimation with the developed code.
Figure 6. Flow chart of the U-value estimation with the developed code.
Energies 15 07917 g006
Figure 7. Schematic of the experimental setup used to measure the thermal performance of a heat exchanger.
Figure 7. Schematic of the experimental setup used to measure the thermal performance of a heat exchanger.
Energies 15 07917 g007
Figure 8. Structure and characteristics of the heat exchanger used in the experiment.
Figure 8. Structure and characteristics of the heat exchanger used in the experiment.
Energies 15 07917 g008
Figure 9. Variation versus water flow rate of (a) experimental and rational overall heat transfer coefficients and (b) relative error of extrapolation.
Figure 9. Variation versus water flow rate of (a) experimental and rational overall heat transfer coefficients and (b) relative error of extrapolation.
Energies 15 07917 g009
Figure 10. Variation versus airflow velocities of (a) exchanger’s performance obtained experimentally and using the computational code and (b) relative error of the computational code.
Figure 10. Variation versus airflow velocities of (a) exchanger’s performance obtained experimentally and using the computational code and (b) relative error of the computational code.
Energies 15 07917 g010
Figure 11. Elements of the parametric analysis.
Figure 11. Elements of the parametric analysis.
Energies 15 07917 g011
Figure 12. Thermal performance and its enhancement versus (a) axial and (b) lateral distances.
Figure 12. Thermal performance and its enhancement versus (a) axial and (b) lateral distances.
Energies 15 07917 g012
Figure 13. Variation of the HX thermal performance enhancement in function of the air velocity for different water flow rates.
Figure 13. Variation of the HX thermal performance enhancement in function of the air velocity for different water flow rates.
Energies 15 07917 g013
Figure 14. Performance enhancement evolution versus diffuser angle for multiple X.
Figure 14. Performance enhancement evolution versus diffuser angle for multiple X.
Energies 15 07917 g014
Figure 15. Variation of the fuel consumption and carbon dioxide emission rates in function of the enhancement percentage of the HX thermal performance.
Figure 15. Variation of the fuel consumption and carbon dioxide emission rates in function of the enhancement percentage of the HX thermal performance.
Energies 15 07917 g015
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Faraj, J.; Chahine, K.; Mortada, M.; Lemenand, T.; Ramadan, H.S.; Khaled, M. Eco-Efficient Vehicle Cooling Modules with Integrated Diffusers—Thermal, Energy, and Environmental Analyses. Energies 2022, 15, 7917. https://doi.org/10.3390/en15217917

AMA Style

Faraj J, Chahine K, Mortada M, Lemenand T, Ramadan HS, Khaled M. Eco-Efficient Vehicle Cooling Modules with Integrated Diffusers—Thermal, Energy, and Environmental Analyses. Energies. 2022; 15(21):7917. https://doi.org/10.3390/en15217917

Chicago/Turabian Style

Faraj, Jalal, Khaled Chahine, Mostafa Mortada, Thierry Lemenand, Haitham S. Ramadan, and Mahmoud Khaled. 2022. "Eco-Efficient Vehicle Cooling Modules with Integrated Diffusers—Thermal, Energy, and Environmental Analyses" Energies 15, no. 21: 7917. https://doi.org/10.3390/en15217917

APA Style

Faraj, J., Chahine, K., Mortada, M., Lemenand, T., Ramadan, H. S., & Khaled, M. (2022). Eco-Efficient Vehicle Cooling Modules with Integrated Diffusers—Thermal, Energy, and Environmental Analyses. Energies, 15(21), 7917. https://doi.org/10.3390/en15217917

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop