1. Introduction
Recently, as interest in eco-friendly distributed power using solar power, wind power, batteries, etc. has increased, the trend of product development and research is rapidly changing from the AC system to the DC system [
1,
2,
3]. These changes in R&D trends are accelerating as each country’s carbon-neutral policies and ESG (environmental, social and governance) management of companies. Particularly, in the case of DC distribution products where the electrical resistance is more fragile than that of the AC distribution products, it is necessary to interrupt the inflow of over-current more quickly. Therefore, various studies are being conducted to improve performance, such as introducing a new structure to improve the performance of existing breakers [
4,
5,
6,
7,
8,
9,
10,
11,
12].
The circuit breaker basically consists of a trip unit that detects the inflow of over-current, a driving unit that separates electrodes that are conducted, and an arc extinguishing unit that directly removes the arc [
13]. Even if the environment installed with the DC distribution system changes, these are essential components of the distribution circuit breaker with over-current protection. Therefore, in order to improve the performance of the circuit breaker, it is recommended that the above-mentioned three components (trip unit, driving unit, arc extinguishing unit) are improved.
Sang-Jae Choi et al. proposed the direct current fault current limitation and interruption process of hybrid DC circuit breaker by using double quench [
14]. Yaqobi et al. studied a low-voltage solid-state circuit breaker for a DC micro-grid cluster using a bidirectional insulated-gate bipolar transistor (IGBT) for rapid detecting the fault current. [
15]. In our precious research, the dielectric recovery strength according to materials of the splitter plate was studied and it was confirmed that the thermal conductivity of the material had a dominant effect on initial dielectric recovery [
16].
Currently, research on DC breakers is being conducted based on AC breakers. In the industry, AC breakers are also used as alternatives. In this paper, existing AC breakers are used for technical research applicable to DC breakers.
The blocking phase can be divided into before and after current-zero, as shown in
Figure 1. First of all, before current-zero, the current limitation effect that limits over-current and the arc phenomenon that occurs between the operation of the moving electrode and a fixed electrode mainly. When the over-current inflows, the moving electrode of the circuit breaker begins to be separated from the fixed electrode and arc is generated between the electrodes. The generated arc is extended and moved toward the splitter plate by the pressure of the hot-gas generated by the arc and the arc runner. As opening of the moving electrode. After that, the arc that reaches the splitter plate is stretched, divided, and cooled to be extinguished, and at this time, current-zero is formed [
17].
After current-zero, the re-ignition phenomenon occurs by hot gas. Hot gas generated by interruption is residual inside an arc extinguishing chamber, and this may decrease the dielectric strength between two open electrodes. Due to this reduced dielectric strength, arc is formed again between the two electrodes, and re-ignition occurs, resulting in a failure of interruption. To carry out the experiment, a structure is made for applying magnetic field to the circuit breaker. Using the structure, the effect of external magnetic field on the arc between electrodes are verified through finite element analysis (FEA) and pre-experiment. Through this process, the effect of the external magnetic field applied to a molded case circuit breaker (MCCB) on the short-circuit characteristics before the current-zero and the dielectric strength performance after the current-zero have been analyzed.
The composition of this paper is as follows.
Section 2 deals with finite element analysis and experimental verification to analyze the effect of external magnetic fields on arcs formed between electrodes. In
Section 3, short-circuit characteristics and dielectric recovery voltage are measured after being applied to the actual circuit breaker based on the previous verification. Finally, in
Section 4, the effects of external magnetic fields are analyzed and conclusions were drawn based on the experimental results.
3. Experimental Studies According to External Magnetic Field
3.1. Experimental Set-Ups
The circuit used in the experiment is shown in
Figure 7. The charged capacitor C
S generates an over-current and the frequency is adjusted through L. The frequency used in the experiment is 60 Hz, which is the commercial frequency. Thereafter, an over-current flows to the circuit breaker by applying a gate signal to the thyristor. A capacitor C
0 connected in parallel to a circuit breaker was installed to model the recovery voltage of the system applied to the circuit breaker after current zero. By adjusting the capacitance of C
0, re-ignition for measuring the dielectric recovery voltage between electrodes after current zero can be arbitrarily generated [
13]. The capacitor C
S is charged with 600 V, and the over-current flowing into the breaker is 2.5 kA. All experiments are performed in a laboratory maintaining the conditions of temperature 20~25 °C and humidity 45~55 %R.H using an air conditioner in order to exclude the effect of environmental conditions.
3.2. Short-Circuit Characteristics
In order to analyze the short-circuit characteristics of the circuit breaker by an external magnetic field, the measurement period is determined from a representative waveform.
Figure 8 shows for these periods.
Here, t
10 is the section where an over-current flows into the breaker and the moving electrode starts to be separated from the fixed electrode due to the Lorentz force between the electrodes. t
21 is a section where, after two electrodes are separated, the moving electrode is opened, and the arc generated between the electrodes moves to the splitter plate. A t
32 is a section in which arc energy is consumed after reaching the splitter plate. As a circuit breaker, Schneider’s EZC100H model is used in the experiment. To apply an external magnetic field to the arc generated between two electrodes, the core used in the pre-experiment is installed the circuit breaker, as shown in
Figure 9.
The conditions of each experiment are as follows:
- (1)
When there is no external magnetic field (I = 0 A);
- (2)
When external magnetic field is applied (I = 5 A).
Table 1 shows each repeated experimental values and arithmetic mean values.
Figure 10 shows the resulting waveform of no external magnetic field, and
Figure 11 shows the waveform when the external magnetic field is applied.
The results are as follows. First, in t10 period, there is little difference in the presence or absence of a magnetic field of about +0.02 ms. This means that the external magnetic field does not affect the internal Lorentz force determining t10. This internal Lorentz force is generated when the over-current flowing into the fixed electrode reciprocates, and in order to generate a large Lorentz force, the interval between the paths through which the current reciprocates should be narrow. Applying this experiment, in order for the external magnetic field to affect the Lorentz force, many magnetic fields must pass due to the wide gap in the passage, but it is difficult to have a significant impact because the gap in this passage must be small.
In addition, the generation position of the external magnetic field is not a fixed electrode with a gap in the path but occurs between the fixed electrode and the movable electrode, so it is judged to have an insignificant effect.
In t21 period, there is significant difference of −0.13 ms. The arc current moves fast by receiving a force in the direction of the splitter plate by an external magnetic field. It is faster than the case of no external magnetic field. From the experimental results, it can be seen that the sum of t10 and t21 has a relatively constant value regardless of the deviation. It is about 7.1 ms for the case without external field and 7.0 ms for the case with external field. The difference above is a significant difference in that this sum is a value that is difficult to replace with another factor. Time reduction at t21 is important to relate to the extinguish time of the arc current afterwards. This time can be adjusted by the external magnetic field.
Even in the t32 period, there is a small difference of 0.01 ms. Factors influencing t32 include the size and number of splitter plates, the value and temperature of arc current, and the temperature of external air, but there is no significant influence on this.
3.3. Dielectric Recovery Strength Performance
The dielectric recovery voltage after current-zero is measured by repeatedly performing an experiment that intentionally generates re-ignition through adjusting the C
0 value.
Figure 12 shows a schematic diagram of the re-ignition that occurs after current-zero. When re-ignition occurs, the waveform of the arc voltage shows a form in which the dielectric breakdown occurs and the arc current is re-formed.
In order to measure the dielectric recovery voltage between electrodes, the time and voltage of the position where the re-ignition occurs are measured three times each to derive an arithmetic average value. At this time, the C
0 capacities are 0.47 μF, 1 μF, and 10 μF, respectively, and are related to the time when re-ignition occurs. The experimental waveform according to each C
0 capacitance is shown in
Figure 13 and
Figure 14.
Table 2 shows the DRV (dielectric recovery voltage) without an external magnetic field (I = 0 A) and with an external magnetic field (I = 5 A). Each C
0 value (0.47, 1, 10 μF) shows the average voltage and average time. Using this voltage and time values,
Figure 15 shows the V-t curve of the DRV without external magnetic field (I = 0 A) and with external magnetic field (I = 5 A)
DRV characteristics can be largely divided into initial state and latter state. The initial state is affected by the cooling performance of the splitter plate, and the latter state is affected by the emission of hot gas generated by arc extinguishing, etc. The results of this paper are as follows. The differences in dielectric recovery voltages corresponding to C0 values (0.47 μF, 1 μF, 10 μF) are 39.0 V, 33.7 V, and 64.0 V, respectively. It is difficult to accurately compare the voltage values (y-axis) because the average time of each state is slightly different. However, the values of the initial state and the latter state are about twice different. This is interpreted in that the ionized hot gas generated in the process of extinguishing the arc receives a force from an external magnetic field in the direction of the exhaust port.
4. Conclusions
In this paper, the analysis of characteristics of low-voltage circuit breaker by the external magnetic field is performed. First, the FEA and the pre-experiment were performed to confirm the movement of the arc current by the magnetic field. In this experimental condition, the force acted in the targeted direction when 2.7 A, and its distribution was determined. Based on this, the performance of the low voltage circuit breaker for external magnetic fields was investigated through two experiments. These assessed short circuit characteristics before current-zero and dielectric recovery strength afterwards. In terms of short-circuit characteristics, it shows a significant decrease in t21 period in which the arc current generated between the fixed and moving electrodes moves to the splitter plate. This reduces the overall cutoff time and helps to improve reliability in that it secures a t32 time when the arc current is extinguished. In terms of dielectric recovery strength, there is an improvement of 13.3% in the latter state of the DRV V-t curve. Since the initial state performance can be improved by changing the material of the splitter plate, increasing the surface area, and decreasing a temperature decrease, the result can be applied in more various ways. This study confirms the improvement of the interruption performance before and after current-zero due to the presence or absence of an external magnetic field. Therefore, it is judged that the external magnetic field can be utilized when additional performance improvement is required depending on the environment or surrounding environmental conditions. For example, by adding a high-end product lineup with a built-in generator or devising a form that attaches to an existing circuit breaker in a modular way, it is expected to be possible to generate additional income and gain competitiveness in business. Additional research on the control of external magnetic fields is required in the future. In addition, if time control and spatial control are performed, it can help to improve the breaker’s interruption performance.