Next Article in Journal
Thermal and Economic Analysis of Heat Exchangers as Part of a Geothermal District Heating Scheme in the Cheshire Basin, UK
Previous Article in Journal
Vibration Converter with Passive Energy Management for Battery-Less Wireless Sensor Nodes in Predictive Maintenance
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Robust Predictive Control with Three-Vector Modulation Connected to the Power Grid

by
Angelo Lunardi
1,†,
Eliomar R. Conde D.
2,†,
Renato M. Monaro
1,†,
Darlan A. Fernandes
3,† and
Alfeu J. Sguarezi Filho
2,*,†
1
Department of Electrical and Computer Engineering, University of São Paulo, São Paulo 05508-060, Brazil
2
The Engineering, Modeling and Applied Social Sciences Center (CECS), Federal University of ABC, Santo André 09.210-170, Brazil
3
Department of Electrical Engineering, Federal University of Paraíba, João Pessoa 58059900, Brazil
*
Author to whom correspondence should be addressed.
These authors contributed equally to this work.
Energies 2022, 15(6), 1979; https://doi.org/10.3390/en15061979
Submission received: 8 December 2021 / Revised: 24 January 2022 / Accepted: 8 February 2022 / Published: 9 March 2022

Abstract

:
Robust predictive control is presented in this article using a three-vector modulation for a grid-connected three-phase inverter. The aims of this article are proposing a robust controller that is able to deal with some variations of parameters that occur in practical systems and demonstrating the performance of the controller with experimental tests that change the inductance and consequently the parasitic resistance of the plant; the same controller can predictive the changes to obtain the optimal performance. The article also presents mathematical modeling for plants and controllers and a modulation method to solve the variable frequency problem. Experimental tests corroborate the expected results and validate the controller’s efficiency according to the control system analysis requirements and the IEEE 1547.2-2008 standard.

1. Introduction

In recent years, the decrease of CO 2 emissions from power generation has been the main concern to improve the environment [1]. In common with the many ways to generate energy, grid-connected inverters are frequently found in this type of system to regulate the grid voltage or frequency. The grid-connected inverters are devices that can integrate the electrical grid to the renewable energy source for distributed generation (DG) systems [2].
In [3], a proportional resonant (PR) control approach is used through a dual-loop current to link the inverter to the electrical grid. The model is based on a grid with an LCL-filter connected between the grid and the inverter in discrete domain under a stationary frame; this presents the practicality and robustness of the proportional PR. The authors in [4] propose a controller that through grid current feedback active damping can provide the desired bandwidth and robustness against the parameter variation. Another type of controller that can be considered uses a proportional and integral controller with the resonant part that can achieve zero steady-state error [5]. These examples of controllers are part of countless types of controllers that can be divided into classic controllers, predictive controllers, repetitive controllers, robust controllers, and non-linear controllers. All of them can be single-input and single-output (SISO) and multiple-input-multiple-output (MIMO) [6].
The model predictive control (MPC) is a class of controllers that predicts the behavior of specific variables of the system through the model and chooses the controller outputs minimizing the cost function [7]. This type of controller is limited in the number of voltage vectors, which results in a variable switching frequency that interferes with the filters for grid-connected systems [8]. The MPC can be implemented using a pulse width modulation (PWM) to solve the variation frequency problem that exists in the finite control set (FCS). The MPC technique has been proposed for induction motor drives [9], doubly-fed induction generators [10], or inverters.
Repetitive control (RC) [11] is based on the internal model [12] using a transfer function (TF), which is a mathematical representation of the system relating the output and the input in the frequency domain. Another way to represent the system is the state-space (SS) model using the input to output the state variables correlated to the first-order differential of the states (most commonly uses the current and voltage); in the cases of both TF or SS, it is using a periodic signal as a reference [6]. The internal model can provide a zero-error tracking of the reference. For this, it is necessary to include a polynomial equation for the controller [13]. Applications for robotic and power electronics can use this controller [14,15,16].
A conventional MPC can be susceptible to parameter variation. To improve the robustness of an MPC, a compensated RC scheme is combined to the system as in [17]. The idea of parameter variation can also be solved through robust control as in [18], where the approach focuses on robust predictive control with space vector modulation (SVM).
In contrast, ref. [19] features robust predictive control, but using discrete space vector modulation (DSVM), which provides a finite combination of the eight inverter voltage vectors. Still discussing robust control for grid connected systems in [20], the authors analyze the robustness of the controller for possible grid-impedance variations, which justify the effort to study this subject. One of the application examples is in [21,22]. These articles demonstrated the use of robust controls in a doubly fed induction generator (DFIG), which can be found in wind energy systems. When a robust control is applied in this kind of system, the benefits can be the guarantee of a good performance from uncertain parameter values and disturbances that occur in practical situations. These disturbances may include an unbalanced and distorted voltage, which is the focus of [23]. In addition to robust control, the authors use a phase locked loop (PLL) scheme to extract a filtered wave form to use as a reference.
This article focuses on the union of predictive and robust control techniques that can provide an effective combination to obtain a controller that has robustness to the parametric uncertainties of the system and the optimization of the cost function that will provide the voltage value to be applied to the grid to obtain the smallest error between reference and control signal. The predictive portion of the controller is based on future values and on the converter model, which simplifies the control design by being model-based, as long as the mathematical model is compatible with the physical plant. In addition to being able to follow the reference sinusoidal signal and show robustness to parameter variation, this type of controller allows for the rejection of disturbances in the network, such as a weak grid where harmonics can be found due to non-linear loads. The experimental results present the performance of the controller, which was evaluated according to the IEEE Std 1547.2-2008 [24].

2. Modeling of the Grid-Connected Inverter

In the model for the grid-connected inverter, there is the filter between the inverter and the grid, which is an inductance and resistance; this resistance is parasitic due to the physical performance of the inductor. The model is based on the amplitude of grid voltage and current.
This is represented in the following equation [25].
v g , α β = v i n v , α β R g i g , α β L g d i g , α β d t
where, v i n v , α β and v g , α β are the voltage vectors of the converter and the grid, respectively; i g , α β is the grid current vector; and L g and R g are the inductances and resistances of the filter, respectively.
One of the important parts of the system is the filter L g , which filters the high-frequency noise present in the grid current. The filter can be calculated by the following equation [26]:
L g = V R M S 2 Δ I 6 f 0 ,
where f 0 represents the switching frequency, V R M S expresses the effective value of the mains voltage, and Δ I represents the current variation in the inductor. Equation (2) represents what inductance in henries (H) the filter must have to obtain a low-pass filter for the high frequency provided by the inverter commutation. The choice of values for each variable of the equation must be done carefully so that the filter operates with the right cut-off frequency so that only the fundamental frequencies are delivered to the grid.
Active (P) and reactive (Q) power are expressed by:
P = 3 2 e [ v g , α β · i g , α β * ]
Q = 3 2 m [ v g , α β · i g , α β * ]
The superscript * represents the conjugate complex.

3. Finite Control Set for the Grid Side

Finite control set (FCS) is based on the model to obtain the future behavior of the system and then minimize the error through a cost function [10]. The control aims to control the active and reactive power injected into the grid through the inverter voltage vectors according to Table 1.
Figure 1 presents the block diagram of the control system for the grid.
The discrete form of the system model in the stationary reference frame ( α β ) can be obtained by the discretization of (1) using a zero-order-hold (ZOH) technique [27]. Equation (9) presents the discretized model.
v i n v , α β ( k ) = R g i g , α β ( k ) + L g T s Δ P i g , α β ( k ) + v g , α β ( k )
where,
Δ P i g , α β ( k ) = i g , α β R e f i g , α β ( k ) .
The elements i g , α R e f and i g , β R e f of the grid current vector references in the fundamental frequency. The active and reactive power references P r , Q r and the fundamental frequency of the grid voltage vector v α , β are use to compose the current references [28]:
i g , α R e f i g , β R e f = 2 3 [ v g , α 2 ( k ) + v g , β 2 ( k ) ] v g , α ( k ) v g , β ( k ) v g , β ( k ) v g , α ( k ) P r e f Q r e f
The fundamental component frequency of grid voltage is considered to calculate the voltage vector of the inverter in a stationary reference frame using Equation (1).
This voltage vector is the input of the three vector modulation algorithm as space vector modulation that will be presented in the following sections [29].
Finally, Equation (8) has the system control law and when minimized, the optimal solution is obtained.
g F C S = | v α v i n v , α | + | v β v i n v , β |

4. Robust Finite Control Set (RFCS)

The voltage vector is selected by the finite control set and applied to the inverter. In order to guarantee that the system reaches the current reference provided by the matrices in (7), the cost function is minimized to obtain the optimal control signal.
As presented in (1), the inverter voltage in the stationary frame can be used to predict the grid current i g , α β p ( k + 1 ) using the same discretization process of (9) [27]:
i g , α β p ( k + 1 ) = 1 T s R g L g i g , α β ( k ) + T s L g ( v i n v , α β v g , α β )
The errors due to parameter variations are considered in this proposed finite control set robust control formulation. The first step is obtaining the portion responsible to compensate the possible parameter variation.

The Robust Portion for Grid Connected

In order to obtain the robust portion, Equation (9) can be manipulated considering the variation portion. The grid current is presented in (10) in the instant ( k ) and (11) in the instant ( k 1 ) .
v i n v , α β ( k ) = R g i g , α β ( k ) + L g T s Δ i g , α β ( k ) + v g , α β ( k )
v i n v , α β ( k 1 ) = R g i g , α β ( k 1 ) + L g T s Δ i g , α β ( k 1 ) + v g , α β ( k 1 )
The Δ i g , α β ( k ) and Δ i g , α β ( k 1 ) are the grid current variations in different instants for a discrete domain.
Δ i g , α β ( k ) = i g , α β ( k + 1 ) i g , α β ( k )
Δ i g , α β ( k 1 ) = i g , α β ( k ) i g , α β ( k 1 )
For a short sampling time, due to the dynamics of the grid voltage, v g , α β ( k ) v g , α β ( k 1 ) can be considered; therefore if (10) minus (11) is obtained,
v i n v , α β ( k ) v i n v , α β ( k 1 ) = v g f ,
continuing the algebraic manipulation,
v g f , α β = R g i g , α β ( k ) i g , α β ( k 1 ) + L g T s Δ i g , α β ( k ) L g T s Δ i g , α β ( k 1 )
where i g , α β ( k ) i g , α β ( k 1 ) can be substituted by Δ i g , α β ( k 1 ) and the following equation is reached:
v g f , α β = R g Δ i g , α β ( k 1 ) + L g T s Δ i g , α β ( k ) L g T s Δ i g , α β ( k 1 )
at last, for Δ i g , α β ( k ) = 0 , the portion to compensate the parameter variation is
v g f , α β = ( R g L g T s ) Δ i g , α β ( k 1 ) .
After the equation of the robust portion is calculated, the real grid voltage that will be applied is a combination of the predictive plus the robust portion as presented in (18).
v G , α β = v g f , α β + v g , α β .
Finally, Equation (19) has the system control law and when minimized, the optimal solution is obtained.
g R F C S = | v G , α v i n v , α | + | v G , β v i n v , β |

5. Three Vector Modulation (TVM)

The first cost function that should be solved for each pair of vectors corresponding to the sextant in Figure 2 and Table 1 is (19).
Figure 2 refers to the voltage vectors available for the VSI in the α β plane. Figure 2 is divided into six sectors with their related two adjacent vectors; the first sector, as an example, is between vector v i n v ( 1 ) and vector v i n v ( 2 ) presented in Table 1 and their respective voltage generated vectors.
Based on the classical predictive control method, Figure 1 presents a method that uses the same prediction of the load current indicated in (10). In addition to the main contribution, the proposed techniques use two active vectors in order to maintain a fixed switching frequency. For this to be achieved it is necessary to solve the predictive cost functions separately.
First, the cost function g F C S is solved for each vector existing in VSI according to Table 1. As an example, for sector II, the cost function is evaluated for both vectors v i n v ( 2 ) and v i n v ( 3 ) based on (10) that will change according to the grid voltage. Finally, the duty cycle for each vector is calculated by solving:
d 0 = K g 0 ; d 1 = K g 1 ; d 2 = K g 2
d 0 + d 1 + d 2 = T s
where d 0 is the duty cycle of a null vector ( v i n v ( 1 ) or v i n v ( 8 ) ) that must be solved only once; d 1 and d 2 are the duty cycles for the adjacent vectors referring to the sector chosen by the algorithm. The duty cycle unit in this case is seconds (s), as the sampling time ( T s ) is equal to the sum of the duty cycles so that the entire switching period has some voltage vector selected. It is possible to obtain the equation for K solving the system of (20), and they are presented below:
d 0 = T s g 1 g 2 ( g 0 g 1 + g 0 g 2 + g 1 g 2 ) d 1 = T s g 0 g 2 ( g 0 g 1 + g 0 g 2 + g 1 g 2 ) d 2 = T s g 0 g 1 ( g 0 g 1 + g 0 g 2 + g 1 g 2 )
From the predicted actions of the power employing Equation (10), the cost function is calculated in order to select the voltage vectors of the inverter that allows the modulated MPC-FCS as presented before:
g ( k + 1 ) = d 1 g 1 + d 2 g 2
where g 1 and g 2 are the cost function with minor values and d 1 and d 2 are the duty clyces computed using Equation (23).

6. Results Obtained in Experimental Setup

Figure 3 presents the experimental workbench used to evaluate the proposed grid current control using the control robust strategy, which is composed of electronic boards to acquire the voltage (v) and current (i) variables, a digital signal processor (DSP) Texas Instruments model TMS320F28335 to implement the controller proposed here and a back-to-back inverter of the model “Semikron SKS20F (B6CI)2P+E1CIF+B6U 14V12” connected to the grid. The parameters of the system are presented in Table 2.

6.1. Results Obtained in Experimental Setup

The first tests were carried out using a degree of active power from 500 W to 750 W with a focus on analyses of the current α β and the reference. Notice that the controller is capable of tracking the reference successfully and there is little oscillation around the reference. Figure 4 presents this first test.
The second test is performed with the same degree of active power, but now it is presented in Figure 5 with the active and reactive power together with the voltage and current signal.
The following test is a step of reactive power reference Q r from 300 var to 0 var, and the active power reference P r is maintained at 750 W, as depicted in Figure 6.
All the tests performed in this subsection present the controller in normal operation connected to the grid. It is noted that the performance of the controller presents satisfactory results and produces a quality current. The following subsections will approach the parameter variation to demonstrate the controller robustness and the total harmonic distortion (THD) to evaluate the quality current injected to the grid.

6.2. Current Test Performance Parameter Variation

This subsection presents the experimental test for parameter variation. The test consists of the parameter change from 100 % ( 1 × ) to 300 % ( 3 × ) in five steps, increasing 40 % in each step. Figure 7 depicts the ( α β ) current under parameter variation.
Notice that even under parameter variation, the current signal maintains a sinusoidal shape; the quality is affected but the controller is still capable of tracking the reference. The next subsection will present a fixed parameter variation to make a deeper analysis of the dynamic response and the quality of the current signal injected into the grid.
Figure 8 presents a simulation of the controller proposed in MATALB for a variation from 100% to 600%. In addition to the alpha current ( i g , α ), the robust plots are presented, demonstrating that as a variation appears between the plant and the estimated model, this plot increases and compensates for the variation.

6.3. Test as 160% of Nominal Parameter

This subsection focuses on observing the behavior of the proposed control with 60 % increase of inductance and resistance. Figure 9 shows the current and the reference under parameter variation.
It is possible to observe that the controller achieves the reference; however, it is also noticeable that there is a small increase in the oscillation around the reference due to the variation in the parameters. The next result in Figure 10 presents the same test in Figure 5, but now the inductance and the reference are increased by 60 % .
The dynamic response of the system is apparently not affected, as observed in Figure 10. To obtain a deeper analysis of the result, the CSV data were extracted and plotted using MATLAB to observe the details and the comparison between the system in normal operation and the operation under parameter variation. This comparison is presented in Figure 11. To represent a 60% increase in the parameter value, the ×1.6 multiplier (blue line) was used, in the same way the ×1.0 multiplier (red line) represents the parameters in nominal values.
Notice that in both cases the rise time is approximately 1.8 ms. This value of dynamic response is considered good when compared to the same dynamic response presented in [30]. The only visible difference is in the fact that there is a different minimum stationary error in the two cases due to the variation of the parameters, but still not enough to affect the system performance. The result supports the idea that the proposed controller is capable of maintaining the system dynamic response even under parameter variation. Figure 12 presents the dynamic response from the CSV data obtained through the test bench for MPC and the RFCS to illustrate the performance for both controllers. For the same test conditions, the RFCS achieved 1.8 ms and the MPC 2.1 ms, which demonstrates the acceptable dynamic response for the proposed controller.

6.4. Test as 60% of Nominal Parameter

To evaluate the behavior of the system when the inductance is 40%, Figure 13 presents the system response with the variation. It is noticeable that there is greater noise reproduced in the systems because, with a smaller inductance, the filter has a smaller effect on the system, and the switching noise is less attenuated. However, even with the variation of the parameters, the system still operates efficiently.

6.5. Total Harmonic Distortion (THD)

To analyze the quality of current injected to the grid, the CSV data obtained by the experimental test was used to plot the THD graphic using MATLAB tools. Figure 14 presents the THD result for the current produced by the system in normal operation.
The THD result for the current is 3.75 % , in accordance with the grid requirements of IEEE Std 1547.2-2008 [24], for which it is necessary to be below 5 % . The next THD analysis is for the current with the system under parameter variation, for which the resistance and inductance were increased in 60 % , presented in Figure 15.
Notice that the THD value increases to 4.60 % , but it is still in accordance with IEEE Std 1547.2-2008. To conclude the evaluation about the quality of current injected to the grid in both cases, normal operation and parameter variation, the controller is robust enough to produce the current under 5 % , which is required by the standard.

7. Conclusions

A predictive robust controller and its practical implementation were presented in the article. To evaluate the controller performance, dynamic response analyses and THD graphics were presented. The methodology to implement the proposed controller step by step was presented in each section. Furthermore, the mathematical elaboration of the robust portion and plant modeling were also presented so the reader can understand the theory used to elaborate the controller. The proposal is based on the robust controllers handling systems with possible parameter variation, which is a daily problem for control systems.
The experimental results of the system connected to the grid show that the rise time for normal operation and under parameter variation have almost the same values, approximately 1.8 ms, with no overshoot and a low stationary error. The robustness of the controller was validated when the results for normal operation and under parameter variation were still in accordance with IEEE Std 1547.2-2008 for current injected to the grid.
Finally, it is conclusive that this proposed controller has great performance, which makes it eligible for energy application for solar or wind energy systems, which are the trends for environmentally friendly systems. The biggest disadvantage of the controller that should be highlighted is that it is a limited controller in its prediction and control horizons, being only a prediction step in the present proposed control. For future work, it may be possible to change the predictive controller to another type that uses the state-space model and other control and prediction horizons.

Author Contributions

Conceptualization, A.L., E.R.C.D. and A.J.S.F.; methodology, A.L., R.M.M. and A.J.S.F.; software, A.L. and E.R.C.D.; validation, A.L., E.R.C.D., D.A.F. and A.J.S.F.; formal analysis, A.J.S.F.; resources, D.A.F. and A.J.S.F.; data curation, A.L. and E.R.C.D.; writing—original draft preparation, A.L. and E.R.C.D.; writing—review and editing, D.A.F. and A.J.S.F.; visualization, D.A.F.; supervision, A.J.S.F.; project administration, A.J.S.F.; funding acquisition, D.A.F. and A.J.S.F. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Institutional Review Board Statement

A.L. and A.J.S.F.

Data Availability Statement

A.L. and A.J.S.F.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Bersalli, G.; Menanteau, P.; El-Methni, J. Renewable energy policy effectiveness: A panel data analysis across Europe and Latin America. Renew. Sustain. Energy Rev. 2020, 133, 110351. [Google Scholar] [CrossRef]
  2. Razavi, S.E.; Rahimi, E.; Javadi, M.S.; Nezhad, A.E.; Lotfi, M.; Shafie-khah, M.; Catalão, J.P. Impact of distributed generation on protection and voltage regulation of distribution systems: A review. Renew. Sustain. Energy Rev. 2019, 105, 157–167. [Google Scholar] [CrossRef]
  3. Li, B.; Yao, W.; Hang, L.; Tolbert, L. Robust proportional resonant regulator for grid-connected voltage source inverter (VSI) using direct pole placement design method. IET Power Electron. 2012, 5, 1367–1373. [Google Scholar] [CrossRef]
  4. Xu, J.; Xie, S.; Zhang, B.; Qian, Q. Robust grid current control with impedance-phase shaping for LCL-filtered inverters in weak and distorted grid. IEEE Trans. Power Electron. 2018, 33, 10240–10250. [Google Scholar] [CrossRef]
  5. Liserre, M.; Teodorescu, R.; Blaabjerg, F. Multiple harmonics control for three-phase grid converter systems with the use of PI-RES current controller in a rotating frame. IEEE Trans. Power Electron. 2006, 21, 836–841. [Google Scholar] [CrossRef]
  6. Ogata, K. Modern Control Engineering; Prentice Hall: Hoboken, NJ, USA, 2010. [Google Scholar]
  7. Vazquez, S.; Leon, J.I.; Franquelo, L.G.; Rodriguez, J.; Young, H.A.; Marquez, A.; Zanchetta, P. Model Predictive Control: A Review of Its Applications in Power Electronics. IEEE Ind. Electron. Mag. 2014, 8, 16–31. [Google Scholar] [CrossRef]
  8. Rodriguez, J.; Kazmierkowski, M.P.; Espinoza, J.R.; Zanchetta, P.; Abu-Rub, H.; Young, H.A.; Rojas, C.A. State of the art of finite control set model predictive control in power electronics. IEEE Trans. Ind. Inform. 2012, 9, 1003–1016. [Google Scholar] [CrossRef]
  9. Amiri, M.; Milimonfared, J.; Khaburi, D.A. Predictive Torque Control Implementation for Induction Motors Based on Discrete Space Vector Modulation. IEEE Trans. Ind. Electron. 2018, 65, 6881–6889. [Google Scholar] [CrossRef]
  10. Sguarezi Filho, A.J.; Filho, E.R. Model-Based Predictive Control Applied to the Doubly-Fed Induction Generator Direct Power Control. IEEE Trans. Sustain. Energy 2012, 3, 398–406. [Google Scholar] [CrossRef]
  11. Hara, S.; Yamamoto, Y.; Omata, T.; Nakano, M. Repetitive control system: A new type servo system for periodic exogenous signals. IEEE Trans. Autom. Control 1988, 33, 659–668. [Google Scholar] [CrossRef] [Green Version]
  12. Francis, B.A.; Wonham, W.M. The internal model principle of control theory. Automatica 1976, 12, 457–465. [Google Scholar] [CrossRef]
  13. Wei, F.; Zhang, X.; Vilathgamuwa, D.M.; Choi, S.S.; Wang, S. Mitigation of distorted and unbalanced stator voltage of stand-alone doubly fed induction generators using repetitive control technique. IET Electr. Power Appl. 2013, 7, 654–663. [Google Scholar] [CrossRef]
  14. Kaneko, K.; Horowitz, R. Repetitive and adaptive control of robot manipulators with velocity estimation. IEEE Trans. Robot. Autom. 1997, 13, 204–217. [Google Scholar] [CrossRef]
  15. Gao, Y.G.; Jiang, F.Y.; Song, J.C.; Zheng, L.J.; Tian, F.Y.; Geng, P.L. A novel dual closed-loop control scheme based on repetitive control for grid-connected inverters with an LCL filter. ISA Trans. 2018, 74, 194–208. [Google Scholar] [CrossRef] [PubMed]
  16. Zhou, K.; Wang, D.; Yang, Y.; Blaabjerg, F. Periodic Control of Power Electronic Converters; Institution of Engineering and Technology: London, UK, 2017. [Google Scholar]
  17. Liu, Y.; Cheng, S.; Ning, B.; Li, Y. Robust Model Predictive Control With Simplified Repetitive Control for Electrical Machine Drives. IEEE Trans. Power Electron. 2019, 34, 4524–4535. [Google Scholar] [CrossRef]
  18. Fischer, J.R.; González, S.A.; Carugati, I.; Herrán, M.A.; Judewicz, M.G.; Carrica, D.O. Robust predictive control of grid-tied converters based on direct power control. IEEE Trans. Power Electron. 2013, 29, 5634–5643. [Google Scholar] [CrossRef]
  19. Moon, H.C.; Lee, J.S.; Lee, K.B. A robust deadbeat finite set model predictive current control based on discrete space vector modulation for a grid-connected voltage source inverter. IEEE Trans. Energy Convers. 2018, 33, 1719–1728. [Google Scholar] [CrossRef]
  20. Yang, S.; Lei, Q.; Peng, F.Z.; Qian, Z. A robust control scheme for grid-connected voltage-source inverters. IEEE Trans. Ind. Electron. 2010, 58, 202–212. [Google Scholar] [CrossRef]
  21. Da Costa, J.P.; Pinheiro, H.; Degner, T.; Arnold, G. Robust controller for DFIGs of grid-connected wind turbines. IEEE Trans. Ind. Electron. 2010, 58, 4023–4038. [Google Scholar] [CrossRef]
  22. Sguarezi Filho, A.J.; de Oliveira, A.L.; Rodrigues, L.L.; Costa, E.C.M.; Jacomini, R.V. A robust finite control set applied to the DFIG power control. IEEE J. Emerg. Sel. Top. Power Electron. 2018, 6, 1692–1698. [Google Scholar] [CrossRef]
  23. Lai, N.B.; Kim, K.H. Robust control scheme for three-phase grid-connected inverters with LCL-filter under unbalanced and distorted grid conditions. IEEE Trans. Energy Convers. 2017, 33, 506–515. [Google Scholar] [CrossRef]
  24. IEEE Std 1547.2-2008; IEEE Application Guide for IEEE Std 1547(TM), IEEE Standard for Interconnecting Distributed Resources with Electric Power Systems. IEEE: Piscataway, NJ, USA, 2009; pp. 1–217. [CrossRef]
  25. Alepuz, S.; Busquets-Monge, S.; Bordonau, J.; Cortes, P.; Rodriguez, J.; Vargas, R. Predictive current control of grid-connected neutral-point-clamped converters to meet low voltage ride-through requirements. In Proceedings of the IEEE Power Electronics Specialists Conference, Rhodes, Greece, 15–19 June 2008; pp. 2423–2428. [Google Scholar]
  26. Beres, R.N.; Wang, X.; Liserre, M.; Blaabjerg, F.; Bak, C.L. A review of passive power filters for three-phase grid-connected voltage-source converters. IEEE J. Emerg. Sel. Top. Power Electron. 2015, 4, 54–69. [Google Scholar] [CrossRef] [Green Version]
  27. Rodriguez, J.; Cortes, P. Predictive Control of Power Converters and Electrical Drives; John Wiley & Sons: Hoboken, NJ, USA, 2012; Volume 40. [Google Scholar]
  28. Akagi, H.; Kanazawa, Y.; Nabae, A. Instantaneous Reactive Power Compensators Comprising Switching Devices without Energy Storage Components. IEEE Trans. Ind. Appl. 1984, IA-20, 625–630. [Google Scholar] [CrossRef]
  29. Rossiter, J.A. Model-Based Predictive Control: A Practical Approach; CRC Press: Boca Raton, FL, USA, 2003. [Google Scholar]
  30. Lunardi, A.; Conde D, E.R.; de Assis, J.; Fernandes, D.A.; Sguarezi Filho, A.J. Model predictive control with modulator applied to grid inverter under voltage distorted. Energies 2021, 14, 4953. [Google Scholar] [CrossRef]
Figure 1. Grid current control using robust finite control set with three vector modulation.
Figure 1. Grid current control using robust finite control set with three vector modulation.
Energies 15 01979 g001
Figure 2. VSI sextant.
Figure 2. VSI sextant.
Energies 15 01979 g002
Figure 3. Experimental bank setup.
Figure 3. Experimental bank setup.
Energies 15 01979 g003
Figure 4. Step test for current ( α β ) and the reference.The purple line is the alpha current reference and the blue line is the alpha grid current signal. The yellow line is the beta current reference and the green line is the beta grid current signal.
Figure 4. Step test for current ( α β ) and the reference.The purple line is the alpha current reference and the blue line is the alpha grid current signal. The yellow line is the beta current reference and the green line is the beta grid current signal.
Energies 15 01979 g004
Figure 5. Grid current and voltage behavior during active power step test with normal operation.
Figure 5. Grid current and voltage behavior during active power step test with normal operation.
Energies 15 01979 g005
Figure 6. Grid current and voltage behavior during reactive power step test with normal operation.
Figure 6. Grid current and voltage behavior during reactive power step test with normal operation.
Energies 15 01979 g006
Figure 7. Parameter variation test from 100 % to 300 % for inductance and resistance.
Figure 7. Parameter variation test from 100 % to 300 % for inductance and resistance.
Energies 15 01979 g007
Figure 8. Parameter variation simulation test from 100 % to 600 % for inductance and resistance. (a) Represents the current ia injected into the grid. (b) Represents the parameter variation multiplier. (c) The red signal is v g f , α and the blue signal is v g f , β .
Figure 8. Parameter variation simulation test from 100 % to 600 % for inductance and resistance. (a) Represents the current ia injected into the grid. (b) Represents the parameter variation multiplier. (c) The red signal is v g f , α and the blue signal is v g f , β .
Energies 15 01979 g008
Figure 9. Step test for current ( α β ) and the reference with 60 % increase of inductance and resistance. The purple line is the alpha current reference and the blue line is the alpha grid current signal. The yellow line is the beta current reference and the green line is the beta grid current signal.
Figure 9. Step test for current ( α β ) and the reference with 60 % increase of inductance and resistance. The purple line is the alpha current reference and the blue line is the alpha grid current signal. The yellow line is the beta current reference and the green line is the beta grid current signal.
Energies 15 01979 g009
Figure 10. Grid current and voltage behavior during active power step test with 60 % increase of inductance and resistance.
Figure 10. Grid current and voltage behavior during active power step test with 60 % increase of inductance and resistance.
Energies 15 01979 g010
Figure 11. Grid current and voltage behavior during active power step test using RFCS.
Figure 11. Grid current and voltage behavior during active power step test using RFCS.
Energies 15 01979 g011
Figure 12. Dynamic comparison between RFCS and MPC.
Figure 12. Dynamic comparison between RFCS and MPC.
Energies 15 01979 g012
Figure 13. Grid current and voltage behavior during active power step test using RFCS.
Figure 13. Grid current and voltage behavior during active power step test using RFCS.
Energies 15 01979 g013
Figure 14. THD of the grid current using robust predictive control normal operation.
Figure 14. THD of the grid current using robust predictive control normal operation.
Energies 15 01979 g014
Figure 15. THD of the grid current using robust predictive control with 60 % increase of inductance and resistance.
Figure 15. THD of the grid current using robust predictive control with 60 % increase of inductance and resistance.
Energies 15 01979 g015
Table 1. Voltage vectors and switching state.
Table 1. Voltage vectors and switching state.
S a S b S c Vector Voltage v inv ( j )
000 v i n v ( 1 ) = 0
100 v i n v ( 2 ) = 2 3 V d c
110 v i n v ( 3 ) = 1 3 V d c + j 3 3 V d c
010 v i n v ( 4 ) = 1 3 V d c + j 3 3 V d c
011 v i n v ( 5 ) = 2 3 V d c
001 v i n v ( 6 ) = 1 3 V d c j 3 3 V d c
101 v i n v ( 7 ) = 1 3 V d c j 3 3 V d c
111 v i n v ( 8 ) = 0
Table 2. Three phase power inverter parameters.
Table 2. Three phase power inverter parameters.
ParameterValue
Inductor internal resistance per phase ( R g ) 0.10 Ω
Inductance per phase ( L g )22 mH
Nominal grid frequency60 Hz
Nominal grid voltage ( V g ) 78 3 V
Sampling frequency20 kHz
Switching frequency ( f s w )20 kHz
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Lunardi, A.; Conde D., E.R.; Monaro, R.M.; Fernandes, D.A.; Sguarezi Filho, A.J. Robust Predictive Control with Three-Vector Modulation Connected to the Power Grid. Energies 2022, 15, 1979. https://doi.org/10.3390/en15061979

AMA Style

Lunardi A, Conde D. ER, Monaro RM, Fernandes DA, Sguarezi Filho AJ. Robust Predictive Control with Three-Vector Modulation Connected to the Power Grid. Energies. 2022; 15(6):1979. https://doi.org/10.3390/en15061979

Chicago/Turabian Style

Lunardi, Angelo, Eliomar R. Conde D., Renato M. Monaro, Darlan A. Fernandes, and Alfeu J. Sguarezi Filho. 2022. "Robust Predictive Control with Three-Vector Modulation Connected to the Power Grid" Energies 15, no. 6: 1979. https://doi.org/10.3390/en15061979

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop