Next Article in Journal
Modelling and Estimation in Lithium-Ion Batteries: A Literature Review
Next Article in Special Issue
MEVO: A Metamodel-Based Evolutionary Optimizer for Building Energy Optimization
Previous Article in Journal
Comparative Evaluation of PSA, PVSA, and Twin PSA Processes for Biogas Upgrading: The Purity, Recovery, and Energy Consumption Dilemma
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Airtightness Assessment under Several Low-Pressure Differences in Non-Residential Buildings

Department of Architectural Engineering, College of Engineering, Kangwon National University, Samcheok 25913, Republic of Korea
*
Author to whom correspondence should be addressed.
Energies 2023, 16(19), 6845; https://doi.org/10.3390/en16196845
Submission received: 31 August 2023 / Revised: 18 September 2023 / Accepted: 22 September 2023 / Published: 27 September 2023

Abstract

:
The thermal performance of building envelopes is significantly affected by building insulation and airtightness. However, most studies have focused on improving thermal performance in building envelopes, while few studies on improving airtightness in buildings have been conducted. The present study measured airtightness and infiltration in non-residential buildings using fan pressurization and tracer gas methods. By analyzing the results obtained from both methods, the distribution of the correlation factors was identified, which can be used for the air leakage rates obtained from the blower door test to estimate the infiltration rates under natural airflow conditions. Since it is difficult to get the values of ACH50 through the blower door test in buildings of large volume or where large air leakages occur, the study proposed a method to convert the values of airtightness under several low-pressure differences of 20 Pa, 25 Pa, 30 Pa and 35 Pa into ACH50 using conversion coefficient. By dividing the air leakage rate under 20 Pa pressure difference by the conversion coefficient of 0.60, the values of ACH50 can be estimated. Results converted to ACH50 using conversion coefficient for various pressure differences of 20 Pa, 25 Pa, 30 Pa, and 35 Pa showed an error of 0.1–4.4%, respectively, compared to actual ACH50 measurement results.

1. Introduction

1.1. Background and Objective

With the significant concern for climate change in response to global warming, the Intergovernmental Panel on Climate Change (IPCC) has agreed to achieve the goal of net zero by 2050 to limit temperature increase to 1.5 °C by 2100. Thus, many countries have agreed to reduce greenhouse gas (GHG) emission rates [1]. The building sector in the EU accounts for about 40% of total energy consumption [2,3,4]. In addition, 60–70% of building energy consumption was used for space heating. Among possible strategies to reduce building energy consumption, one of the most effective strategies is to improve the thermal performance of building envelope systems [5]. In residential buildings, the exterior walls contributed about 34% of building energy consumption, which was important in determining the energy demand for indoor thermal comfort [5,6].
In the Energy Conservation Design Standard of buildings in Republic of Korea, the government has strengthened the thermal properties of building envelopes by about 15–20% every two or three years since 2008 [7]. Specifically, the thermal transmittance value from 2008 to 2022 was changed from 0.47 W/m2K to 0.15 W/m2K, respectively. This shows an approximate decrease in thermal transmittance of 70%. Even though building insulation and airtightness are both important for the thermal properties of building envelopes, the Korean government has only focused on building insulation performance. In addition, there have been a few studies of the infiltration in building energy consumption [8]. In the total heat loss of buildings, infiltration accounted for about 15–60%.
Moreover, air leakage has demanded about 25% and 12% of heating and cooling, respectively [9]. The improvement of airtightness in buildings can be considered an effective way to minimize heat loss. In the case of high-performance buildings, the effectiveness of the improved airtightness can be relatively greater [10,11].
Generally, airtightness can play a significant role in building energy efficiency [11,12,13,14,15]. Recently, much attention has been paid to the importance of building airtightness [15,16,17]. Exfiltration is estimated to account for 3–5% and 11–15% of the total energy demand and CO2; emissions in UK housing stock, respectively [1]. Thus, improving airtightness in building envelopes is necessary, which can result in improved building energy efficiency and indoor air quality [18,19].
To assess building airtightness, two methods have been commonly used: the fan pressurization method and the tracer gas method [20,21,22]. The fan pressurization method measures the airflow at an artificial condition of 50 Pa or 10 Pa of pressure difference between indoors and outdoors. In addition, the air leakage rates from the measurement can be used as a metric for the air leakage rates on the unit area of the building envelope [23,24,25]. The airtightness value in natural conditions is quite a bit lower than that under a 50 Pa pressure difference between indoors and outdoors. Specifically, the pressure difference between indoors and outdoors under the natural airflow condition is lower than 10 Pa [26]. Generally, the tracer gas method has been used to measure infiltration under natural air flow conditions, and it can provide a more reliable result than that offered by the fan pressurization method [27,28,29].
For the objectives of the present study, the infiltration rates for non-residential buildings were regularly measured using the tracer gas method and the fan pressurization method to identify the correlation factor. The measurements assessed the airtightness of non-residential buildings, and the correlation factor was recognized by the analyses of the results obtained from the two methods. Since it is difficult to maintain a 50 Pa pressure difference for the blower door test in buildings of large building volume or which are old, the present study also proposed a method to convert the values of airtightness under several low-pressure differences of 20 Pa, 25 Pa, 30 Pa and 35 Pa into A C H 50 . The overall flow of this study is displayed in Figure 1.

1.2. Literature Review

Sherman proposed a simple rule-of-thumb of the “air changes per hour under 50 Pa” (hereafter A C H 50 /N (N = the correlation factor, 20), divided-by-20 rule) [30,31] and correlation factor simply consists of the assumption that the infiltration in a building is 1/20th of its airtightness [32]. However, recent studies have revealed that the correlation factor can differ by building location and climate conditions and that a correlation factor greater than 20 was analyzed [19,33,34]. For example, Alan et al. measured the infiltration rates of 19 residential buildings by the blower door test and the tracer gas method. Since the ratio of the volume to the envelope area of the buildings was about 1:1, the correlation factor was calculated using the envelope area. As a result, the correlation factor ranged from 21 to 55, and the average value was 37 (divide-by-37 rule) [19]. To extrapolate the correlation between the fan pressurization-measured airtightness and the tracer gas-measured infiltration, it is necessary to perform the blower door test in advance. However, it is difficult to maintain a 50 Pa pressure difference between indoors and outdoors in some situations, such as large-scale or leaky buildings. While additional fans or a combination of blower door equipment and air handler units can overcome the problem, it is still difficult to maintain a 50 Pa pressure difference in reality [24,35,36,37]. Previous studies have used air handle units to maintain a 50 Pa pressure difference between indoors and outdoors for airtightness measurements in large-scale buildings that cannot establish a 50 Pa pressure difference [24,38]. However, there are limitations in measuring airtightness performance in large-scale buildings or buildings with numerous leakage points.

2. Methodology

2.1. Fan Pressure Method—Blower Door Test

Among various methods for airtightness measurements, the fan pressurization method employs artificial pressure conditions between indoor and outdoor fans. Figure 2 shows that the airtightness was measured using a blower door system. Specifically, the airflow rate was monitored to induce a particular pressure between the interior and exterior of the building. To set up the pressure–leakage relationship, the airflow rate passing the fans was also measured [37].
Q = C(Δp)n
where Q [ m 3 / h ] is the airflow rate through the opening, and C [ m 3 / ( h · P a n )] is the flow coefficient. In addition, n is the pressure exponent.
While there are several airtightness metrics available, such as A C H 50 ( h · 1 ), ELA ( m 2 ), EqLA ( m 2 ), and Air permeability ( m 3 / h · m 2 ), A C H 50 was used for the present study as the metric to analyze the result obtained from the airtightness measurements. To present the metric of ACH in a natural ventilation state, it was expressed as ACH50. In addition, the blower door tests were conducted in accordance with ISO Standard 9972:2015 method 3 [39]. The windows and doors were closed for the measurements, but nothing was sealed, including the window frames and the wall.
Moreover, a blower door system was installed at the main entrance. The measurements were conducted at intervals of 5 Pa–10 Pa indoors and outdoors pressure difference by pressurizing or depressurizing from 10 Pa–65 Pa. In accordance with ISO Standard 9972, they were required that the indoor/outdoor air temperature difference should not exceed 25 °C (when the height of a building is 10 m) and the wind speed should not exceed 6 m/s. Therefore, during the Blower Door test, indoor and outdoor temperatures, humidity, and wind speed were monitored and confirmed [39].

2.2. Tracer Gas—Decay Method

The tracer gas method is one of the most highly regarded methods for infiltration measurements in buildings [40]. Three tracer gas techniques exist concentration decay, constant injection, and constant concentration [25]. Among them, the decay method is the most widespread technique for infiltration measurements due to its convenience, and compared with other techniques, it produces relatively accurate results [41,42,43]. While SF6 gas or CO2 were mainly used as a tracer gas, the use of SF6 is limited due to its environmental effects [44]. Thus, CO2 has been increasingly used [45].
For the measurement in the study, CO2 was injected into the selected building room where the windows and doors remained closed, with the same conditions as those of the blower door method. As shown in Figure 3, the infiltration rates obtained from the decay method were calculated using Equation (2):
ACH = (lnC0 − lnC(t))/t
where C (t) is the tracer gas concentration at time (t), C 0 is the concentration of the tracer in the space at t = 0, t is time, and A C H is the air change rate ( h 1 ).
Based on the CO2 concentration in each room, the tracer gas was measured in the center of the room for 6 h–12 h.

2.3. Airtightness under Several Low-Pressure Differences

As a representative airtightness metric, the A C H 50 can be calculated using Equation (3):
ACH50 = Q50/V
where, Q 50 is the air leakage rate under the 50 Pa indoor/outdoor pressure difference ( m 3 / h ), and V is the volume ( m 3 ).
The present study proposed a method to predict the A C H 50 by analysing the airtightness measurements with several indoor/outdoor pressure differences of 20 Pa, 25 Pa, 30 Pa and 35 Pa. In addition, the measured values of A C H 50 were compared with the predicted A C H 50 . The specific methods are below:
Step 1. According to the analyses of the measured data at an interval of 5 Pa–10 Pa from 10 Pa to 65 Pa through the airtightness measurements in accordance with ISO 9972:2015, the value of A C H 50 was compared with the measured data at several indoor/outdoor pressure differences of 20 Pa, 25 Pa, 30 Pa and 35 Pa.
Step 2. Using Equation (4), the conversion coefficient can be calculated with measured data when the value is at the A C H 50 is assumed to be 1. For the conversion coefficient, the average values obtained from the airtightness measurements under four low-pressure differences in 6 rooms in buildings A, B, and C were used:
Npr = ACHpr/ACH50
where, A C H 50 is the air change per hour under 50 Pa ( h 1 ), and p r is the pressure difference (Pa). In addition, A C H p r is the air change per hour under the various pressure differences ( h 1 ), and N p r is the conversion coefficient under the various pressure differences.
Step 3. To validate the conversion coefficient, the airtightness was measured to obtain the values of A C H p r (pr = 20 Pa, 25 Pa, 30 Pa and 35 Pa) in four different rooms. Moreover, the A C H 50 was measured for the same four rooms for validation in accordance with ISO 9972:2015—method 3. The calculated A C H 50 values (by using the measured, A C H p r and Equation (4)) were compared with the measured A C H 50 values. The difference from the comparison was identified.
The data to maintain the four pressure differences of 20 Pa, 25 Pa, 30 Pa and 35 Pa without sealing any parts in the room was measured twice. To reduce the effect of different environmental conditions, the airtightness measurement under a 50 Pa pressure difference was immediately conducted for validation.

2.4. Building Description

According to previous studies, airtightness measurements have mainly been conducted in residential buildings [10,19,46,47]. However, there have been few studies of airtightness in non-residential buildings, such as offices, schools, etc. The present study focuses on the airtightness in school buildings (Buildings A, B, and C).
Table 1 presents a description of the selected buildings. The selection of buildings was based on their building age, i.e., 1987, 1994, and 2007. The structure of all the buildings was made of reinforced concrete, and two window frames, of PVC and Aluminum, were used. In all rooms in these selected buildings, the blower door tests were performed, and both pressurization and depressurization test modes were applied twice. The tracer gas tests were also conducted in all the rooms of the selected buildings. For validation of the A C H p r at 20 Pa, 25 Pa, 30 Pa, and 35 Pa, the measurements were performed in 4 rooms (A3, A4, B3, and C3).

3. Results

3.1. Blower Door Test Results

For both the fan pressurization method and tracer gas method, the indoor and outdoor temperatures were measured. The wind data were based on the weather data [48].
In Table 2, the indoor and outdoor temperatures ranged from 8.1 °C–25.1 °C and 1.9 °C–22.6 °C, respectively. The in/outdoor temperature difference ranged 0.9 °C–14.8 °C. In addition, the wind speed ranged from 0.68 m/s to 6.79 m/s, which was considered a “Moderate breeze” on the Beaufort scale of wind in ISO 9972 standard Annex D [39].
Figure 4 shows the results of the blower door tests in two rooms in each building. Four pressurization and depressurization tests were performed in each room. As a result, the A C H 50 values for pressurization in the room A1 were 18.50 h−1–18.51 h−1, while the values for depressurization were 17.42 h−1–17.65 h−1. The average value of A C H 50 was 17.8 h−1.
By comparing the average values of all buildings, the air leakages for buildings A, B, and C under A C H 50 were (21.1 h−1, 10.9 h−1 and 6.6 h−1, respectively. The difference in the air leakage rates was caused by the building age [10]. Specifically, the air leakage rate of Building A, constructed in 1980, was about three times higher than that of Building C in 2000.

3.2. Tracer Gas Results and Distribution of the Correlation Factor

Figure 5 shows the measurement results obtained from the decay method.
According to the result of the decay method, the averaging infiltration rates for buildings A, B, and C were 0.3 h−1, 0.16 h−1 and 0.09 h−1, respectively. Similarly, the lowest infiltration rate was observed in building C, as with the blower door test results. The averaging infiltration rates of building A were about three times higher than that of building C due to the blower door method.
Table 3 shows the infiltration rates obtained from the decay method and the blower door test that were analyzed to determine the distribution of the correlation factors in non-residential buildings in Republic of Korea.
Table 3 presents measurement results and the correlation factors. In Table 3, the infiltration rates for room A1 were 0.22 h−1 and 0.29 h−1, while the values under the A C H 50 from the blower door test were 18.02 h−1 and 17.57 h−1, respectively. In addition, the calculated correlation factor was 81.91 based on the measurement results obtained from the blower door test and the decay method.
When estimating the correlation factors based on the measurement results of the blower door test and the decay method, the factors ranged from 40.29−117.31. The average correlation factor was 73.14, about 3.6 times higher than that suggested by Sherman (divided-by-20 rule). Alan et al. estimated the distribution of correlation factors through the comparison between the measurement of air permeability ( m 3 / h · m 2 ) and the results of the tracer gas method in residential buildings in the UK [19]. As a result, the factors were distributed in the range of 20.54−55.06, and the average value was 36.53.
Comparing the averaging correlation factors of each building, the values for buildings A, B, and C were 86.6, 68.93, and 65.3, respectively. The highest correlation factor can be caused by the highest air leakage rates in a building.

4. Results ACH of Several Low-Pressure Differences

In this study, the air leakage rates under several pressure differences ( A C H p r , p r = 20 Pa, 25 Pa, 30 Pa, 35 Pa and 50 Pa) and Equation (4) for the calculation of N p r were analyzed. Equation (4) was used to convert the data obtained from the blower door test in the selected buildings into A C H 50 values. In addition, the value of conversion coefficients was calculated.
In this chapter, the A C H p r was measured in rooms A3, A4, B3, and C3 in the selected buildings. The conversion coefficients ( N p r ) were calculated through comparison with the measured A C H 50 values.
A C H 50 P was predicted based on the conversion coefficients and the measured A C H p r values using Equation (5):
ACHpr/Npr = ACH50P
where, p r = 20 Pa, 25 Pa, 30 Pa and 35 Pa.
Figure 6 shows the distribution of the conversion coefficients obtained from the blower door test, which were calculated under four low-pressure differences of 20 Pa, 25 Pa, 30 Pa and 35 Pa, assuming that the A C H 50 was 1.
The distribution of the conversion coefficients under the 20 Pa indoor and outdoor pressure difference was from 0.55 to 0.73, in which the average value was 0.60. For this study, the average conversion coefficient was used, and the values of A C H p r 20 Pa, 25 Pa, 30 Pa and 35 Pa were 0.60, 0.68, 0.76, and 0.84, respectively. Figure 7 presents the results obtained to verify the conversion coefficient in Room A3. To validate this, the airtightness performance (ACH 20, ACH 25, ACH 30, ACH 35) at the corresponding pressure differences was divided by the conversion coefficient (20 Pa = 0.60, 25 Pa = 0.68, 30 Pa = 0.76, 35 Pa = 0.84) presented in Figure 6 to calculate ACH 50. According to the result obtained in room A3, the depressurization and pressurization values under A C H 20 were 8.2 h−1 and 9.2 h−1, respectively, as shown in Figure 7. Moreover, the same measurements under the pressure differences of 25 Pa, 30 Pa and 35 Pa were performed in rooms A4, B3, and C3.
The values of A C H 50 P can be calculated using Equation (5). The values of A C H 50 P were compared with the values of A C H 50 M for validation, which was obtained from the measurements in the rooms in accordance with ISO 9972: Method 3. Figure 8 presents the values of A C H 50 P and A C H 50 M . To calculate the values of A C H 50 P , the measured data under the 20 Pa pressure difference was divided by the conversion coefficient 0.60 in Figure 6. As a result, the A C H 50 P ( A C H 20 / N 20 ) was 14.6 h−1, while the A C H 50 M obtained from the measurement in the same room was 15.2 h−1. The difference between these values was 4.4%. By comparing the difference between A C H 50 M and A C H 50 P in Table 4, the results are 3–4.4%, 0.1–4.4% and 0.4–2.9% for buildings A, B, and C, respectively. For comparison under the indicated pressure differences in Table 4, they were 0.7–4.4%, 1.0–3.2%, 0.1–3.1% and 0.9–4.1% for A C H 20 , A C H 25 , A C H 30 , and A C H 35 , respectively.
A comparison of the values under several pressure differences shows that the results are evenly distributed. In addition, the conversion coefficients are evenly distributed and seem not to be affected by the building age. Therefore, it is shown that the conversion coefficients can be used to convert the measured data under a lower pressure difference than 50 Pa in the building where large air leakages occur or which has a large volume into ACH50 values.

5. Discussion and Conclusions

The present study identified the airtightness and distribution of the correlation factors for non-residential buildings in Republic of Korea. In addition, the study also proposed a method to calculate the airtightness under the low-pressure difference caused by large air leakage in the building or large building volume.
The distribution of the values of A C H 50 obtained from the blower door test in non-residential buildings in Republic of Korea increased according to the increase in building age. The average values in two rooms in buildings A and C, built in 1987 and 2007, were 21.1 h−1 and 6.6 h−1, respectively. The air leakage rates in Building A were about three times higher than in Building C.
The correlation factors through the comparison of the results obtained from the blower door test and the tracer gas method ranged from 40.29 to 117.31. A comparison of these values with the factor (N = 20, dived-by-20 rule) proposed by Sherman showed the high difference between them. In addition, they also showed a high difference compared with the value of 36.53 determined by Alan et al. Specifically, the correlation factors for buildings A, B, and C were 86.60, 68.93, and 65.30, respectively. In this study, it was difficult to determine the value of the correlation factor properly. There was a limit in that the value was larger than other studies. Further, determining the representative correlation factor for various buildings is necessary, considering the construction year, WWR (window-to-wall ratio), locations, etc.
The conversion coefficient N p r was proposed to convert values under low-pressure differences of 20 Pa, 25 Pa, 30 Pa and 35 Pa into the A C H 50 value. To verify the conversion coefficient, the measurements under low-pressure differences of 20 Pa, 25 Pa, 30 Pa and 35 Pa were performed. The values of A C H 50 P were calculated using the conversion coefficient ( N p r ). As a result, the differences between the A C H 50 P and the A C H 50 M values were less than 5%.
In the future, it is necessary to investigate the accuracy of conversion coefficients through measurements for residential buildings and buildings with various purposes. In addition, a study will be conducted to confirm the possibility of measurement at a lower pressure difference. This will be achieved by calculating the conversion coefficient based on measurement results at a pressure difference lower than 20 Pa and comparing it with ACH50 measurement results.

Author Contributions

Conceptualization, G.H.; Methodology, C.S.; Data curation, C.S.; Writing—original draft, C.S.; Writing—review & editing G.H.; Visualization, C.S.; Supervision, G.H.; Funding acquisition, G.H. All authors have read and agreed to the published version of the manuscript.

Funding

This study was supported by a 2021 Research Grant from Kangwon National University and the National Research Foundation of Korea (NRF) grant funded by the Korean government (MSIT) (NRF-2020R1C1C1010801).

Data Availability Statement

The data presented in this study are available on request from the first author. Data sharing is not applicable.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Jones, B.; Das, P.; Chalabi, Z.; Davies, M.; Hamilton, I.; Lowe, R.; Mavrogianni, A.; Robinson, D.; Taylor, J. Assessing Uncertainty in Housing Stock Infiltration Rates Andassociated Heat Loss: English and UK Case Studies. Build. Environ. 2015, 92, 644–656. [Google Scholar] [CrossRef]
  2. Al-Sakkaf, A.; Bagchi, A.; Zayed, T. Evaluating Life-Cycle Energy Costs of Heritage Buildings. Buildings 2022, 12, 1271. [Google Scholar] [CrossRef]
  3. Economidou, M.; Todeschi, V.; Bertoldi, P.; D’Agostino, D.; Zangheri, P.; Castellazzi, L. Review of 50 years of EU Energy Efficiency Policies for Buildings. Energy Build. 2020, 225, 110322. [Google Scholar] [CrossRef]
  4. Lapillonne, B.; Pollier, K.; Samci, N. Energy Efficiency Trends for Households in the EU. Enerdata 2014, 22, 2015. [Google Scholar]
  5. Li, T.; Xia, J.; Chin, C.S.; Song, P. Investigation of the Thermal Performance of Lightweight Assembled Exterior Wall Panel (LAEWP) with Stud Connections. Buildings 2022, 12, 473. [Google Scholar] [CrossRef]
  6. Lee, J.; Kim, J.; Song, D.; Kim, J.; Jang, C. Impact of External Insulation and Internal Thermal Density upon Energy Consumption of Buildings in a Temperate Climate with Four Distinct Seasons. Renew. Sustain. Energy Rev. 2017, 75, 1081–1088. [Google Scholar] [CrossRef]
  7. Korea Energy Agency (KEA). Commentaries for Building Energy Code; Korea Energy Agency (KEA): Ulsan, Republic of Korea, 2018. [Google Scholar]
  8. Shim, C.; Seong, N.; Hong, G. An Analysis of ACHn for Improving the Performance of Green Remodeling through the Airtightness Measurements. KIEAE J. 2021, 21, 7–12. [Google Scholar] [CrossRef]
  9. Poza-Casado, I.; Meiss, A.; Padilla-Marcos, M.Á.; Feijó-Muñoz, J. Airtightness and Energy Impact of Air Infiltration in Residential Buildings in Spain. Int. J. Vent. 2021, 20, 258–264. [Google Scholar] [CrossRef]
  10. Hong, G.; Kim, C. Experimental Analysis of Airtightness Performance in High-Rise Residential Buildings for Improved Code-Compliant Simulations. Energy Build. 2022, 261, 111980. [Google Scholar] [CrossRef]
  11. Erhorn-Kluttig, H.; Erhorn, H.; Lahmidi, H. Airtightness Requirements for High Performance Building Envelopes. EPBD Build. Platf. 2009, 157, 1–6. [Google Scholar]
  12. Etheridge, D. A Perspective on Fifty Years of Natural Ventilation Research. Build. Environ. 2015, 91, 51–60. [Google Scholar] [CrossRef]
  13. Miszczuk, A. Influence of Air Tightness of the Building on Its Energy-Efficiency in Single-Family Buildings in Poland. In MATEC Web of Conferences; EDP Sciences: Les Ulis, France, 2017; Volume 117. [Google Scholar] [CrossRef]
  14. Jing, J.; Lee, D.S.; Joe, J.; Kim, E.J.; Cho, Y.H.; Jo, J.H. A Sensing-Based Visualization Method for Representing Pressure Distribution in a Multi-Zone Building by Floor. Sensors 2023, 23, 4116. [Google Scholar] [CrossRef] [PubMed]
  15. Kravchenko, I.; Kosonen, R.; Jokisalo, J.; Kilpeläinen, S. Performance of Modern Passive Stack Ventilation in a Retrofitted Nordic Apartment Building. Buildings 2022, 12, 96. [Google Scholar] [CrossRef]
  16. Ji, Y.; Duanmu, L. Airtightness Field Tests of Residential Buildings in Dalian, China. Build. Environ. 2017, 119, 20–30. [Google Scholar] [CrossRef]
  17. Vinha, J.; Manelius, E.; Korpi, M.; Salminen, K.; Kurnitski, J.; Kiviste, M.; Laukkarinen, A. Airtightness of Residential Buildings in Finland. Build. Environ. 2015, 93, 128–140. [Google Scholar] [CrossRef]
  18. Miszczuk, A.; Heim, D. Parametric Study of Air Infiltration in Residential Buildings—The Effect of Local Conditions on Energy Demand. Energies 2021, 14, 127. [Google Scholar] [CrossRef]
  19. Pasos, A.V.; Zheng, X.; Smith, L.; Wood, C. Estimation of the Infiltration Rate of UK Homes with the Divide-by-20 Rule and Its Comparison with Site Measurements. Build. Environ. 2020, 185, 107275. [Google Scholar] [CrossRef]
  20. Hong, G.; Kim, D.D. Airtightness of Electrical, Mechanical and Architectural Components in South Korean Apartment Buildings Using the Fan Pressurization and Tracer Gas Method. Build. Environ. 2018, 132, 21–29. [Google Scholar] [CrossRef]
  21. Cheong, K.W. Airflow Measurements for Balancing of Air Distribution Systems—Tracer-Gas Technique as an Alternative? Build. Environ. 2001, 36, 955–964. [Google Scholar] [CrossRef]
  22. Goubran, S.; Qi, D.; Saleh, W.F.; Wang, L. Comparing Methods of Modeling Air Infiltration through Building Entrances and Their Impact on Building Energy Simulations. Energy Build. 2017, 138, 579–590. [Google Scholar] [CrossRef]
  23. Martín-Garín, A.; Millán-García, J.A.; Hidalgo-Betanzos, J.M.; Hernández-Minguillón, R.J.; Baïri, A. Airtightness Analysis of the Built Heritage field Measurements of Nineteenth Century Buildings through Blower Door Tests. Energies 2020, 13, 6726. [Google Scholar] [CrossRef]
  24. Kim, M.H.; Jo, J.H.; Jeong, J.W. Feasibility of Building Envelope Air Leakage Measurement Using Combination of Air-Handler and Blower Door. Energy Build. 2013, 62, 436–441. [Google Scholar] [CrossRef]
  25. Resources, R.C. F16 SI: Ventilation and Infiltration. In Ashrae Handbook; ASHRAE: Norfolk, VA, USA, 2009. [Google Scholar]
  26. Li, X.; Zhou, W.; Duanmu, L. Research on Air Infiltration Predictive Models for Residential Building at Different Pressure. Build. Simul. 2021, 14, 737–748. [Google Scholar] [CrossRef]
  27. Sherman, M.H. Tracer-Gas Techniques for Measuring Ventilation in a Single Zone. Build. Environ. 1990, 25, 365–374. [Google Scholar] [CrossRef]
  28. Lee, D.S.; Jeong, J.W.; Jo, J.H. Experimental Study on Airtightness Test Methods in Large Buildings; Proposal of Averaging Pressure Difference Method. Build. Environ. 2017, 122, 61–71. [Google Scholar] [CrossRef]
  29. Cui, S.; Cohen, M.; Stabat, P.; Marchio, D. CO2 Tracer Gas Concentration Decay Method for Measuring Air Change Rate. Build. Environ. 2015, 84, 162–169. [Google Scholar] [CrossRef]
  30. Sherman, M.H.; Dickerhoff, D.J. Airtightness of U.S. Dwellings. ASHRAE Trans. 1998, 104, 1359–1367. [Google Scholar]
  31. Sherman, M.H. Estimation of Infiltration from Leakage and Climate Indicators. Energy Build. 1987, 10, 81–86. [Google Scholar] [CrossRef]
  32. Lutzkendorf, T.; Balouktsi, M. Energy Conservation in Buildings and Community Systems Programme; IEA: Paris, France, 2016; pp. 35–42, Annex 57; Available online: http://www.annex57.org/wp/wp-content/uploads/2017/05/ST2_Repor.pdf (accessed on 5 October 2022).
  33. Kang, K.; Lee, S.-W.; Lee, E.-J.; Park, M.-J.; Lim, J.-H.; Jo, B.-R.; Lee, J.-C. Infiltration : Just ACH50 Divided by 20? Concentrated on a Residential Building. SAREK Summer Conf. 2015, 6, 435–439. [Google Scholar]
  34. Hyon, M.J.; Ik, L.J.; Sung, K.M. Study on Estimation of Infiltration Rate (ACH Natural) Using Blower Door Test Results. J. KIAEBS 2020, 14, 687–698. [Google Scholar]
  35. Erin, L.; Max, H. Blower-Door Techniques for Measuring Interzonal Leakage: A Preliminary Report; Ernest Orlando Lawrence Berkeley National Laboratory: Berkeley, CA, USA, 2013. [Google Scholar]
  36. Bahnfleth, W.P.; Yuill, G.K.; Lee, B.W. Protocol for Field Testing of Tall Buildings to Determine Envelope Air Leakage Rate. ASHRAE Trans. 1999, 105, 27. [Google Scholar]
  37. Zheng, X.; Cooper, E.; Gillott, M.; Wood, C. A Practical Review of Alternatives to the Steady Pressurisation Method for Determining Building Airtightness. Renew. Sustain. Energy Rev. 2020, 132, 110049. [Google Scholar] [CrossRef] [PubMed]
  38. Jeong, J.W.; Firrantello, J.; Bahnfleth, W.P.; Freihaut, J.D.; Musser, A. Case Studies of Building Envelope Leakage Measurement Using an Air-Handler Fan Pressurisation Approach. Build. Serv. Eng. Res. Technol. 2008, 29, 137–155. [Google Scholar] [CrossRef]
  39. EN ISO 9972:2015; Thermal Performance of Buildings—Determination of Air Permeability of Buildings—Fan Pressurization Method. Standards Australia: Sydney, Australia, 2015.
  40. Frattolillo, A.; Stabile, L.; Dell’Isola, M. Natural Ventilation Measurements in a Multi-Room Dwelling: Critical Aspects and Comparability of Pressurization and Tracer Gas Decay Tests. J. Build. Eng. 2021, 42, 102478. [Google Scholar] [CrossRef]
  41. Lo, L.J.; Novoselac, A. Cross Ventilation with Small Openings: Measurements in a Multi-Zone Test Building. Build. Environ. 2012, 57, 377–386. [Google Scholar] [CrossRef]
  42. Nikolopoulos, N.; Nikolopoulos, A.; Larsen, T.S.; Nikas, K.S.P. Experimental and Numerical Investigation of the Tracer Gas Methodology in the Case of a Naturally Cross-Ventilated Building. Build. Environ. 2012, 56, 379–388. [Google Scholar] [CrossRef]
  43. Jankovic, A.; Gennaro, G.; Chaudhary, G.; Goia, F.; Favoino, F. Tracer Gas Techniques for Airflow Characterization in Double Skin Facades. Build. Environ. 2022, 212, 108803. [Google Scholar] [CrossRef]
  44. Almeida, R.M.S.F.; Barreira, E.; Moreira, P. A Discussion Regarding the Measurement of Ventilation Rates Using Tracer Gas and Decay Technique. Infrastructures 2020, 5, 85. [Google Scholar] [CrossRef]
  45. Batterman, S. Review and Extension of CO2-Based Methods to Determine Ventilation Rates with Application to School Classrooms. Int. J. Environ. Res. Public Health 2017, 14, 145. [Google Scholar] [CrossRef]
  46. Sinnott, D. Dwelling Airtightness: A Socio-Technical Evaluation in an Irish Context. Build. Environ. 2016, 95, 264–271. [Google Scholar] [CrossRef]
  47. Shin, H.K.; Jo, J.H. Air Leakage Characteristics and Leakage Distribution of Dwellings in High-Rise Residential Buildings in Korea. J. Asian Archit. Build. Eng. 2013, 12, 87–92. [Google Scholar] [CrossRef]
  48. KMA, Daily Data, (2021–2022). Available online: https://Www.Weather.Go.Kr/w/Obs-Climate/Land/Past-Obs/Obs-by-Day.Do (accessed on 5 October 2022).
Figure 1. Research Framework.
Figure 1. Research Framework.
Energies 16 06845 g001
Figure 2. Blower door test.
Figure 2. Blower door test.
Energies 16 06845 g002
Figure 3. Tracer gas measurement.
Figure 3. Tracer gas measurement.
Energies 16 06845 g003
Figure 4. Airtightness performance of building rooms.
Figure 4. Airtightness performance of building rooms.
Energies 16 06845 g004
Figure 5. Concentration of the rooms through tracer gas measurement.
Figure 5. Concentration of the rooms through tracer gas measurement.
Energies 16 06845 g005
Figure 6. Distribution of conversion coefficients at several pressure differences.
Figure 6. Distribution of conversion coefficients at several pressure differences.
Energies 16 06845 g006
Figure 7. ACHpr under four low-pressure differences in room A3.
Figure 7. ACHpr under four low-pressure differences in room A3.
Energies 16 06845 g007
Figure 8. Comparison of ACHpr divided by conversion coefficient with measurement ACH50.
Figure 8. Comparison of ACHpr divided by conversion coefficient with measurement ACH50.
Energies 16 06845 g008
Table 1. Building description.
Table 1. Building description.
Building ABuilding BBuilding C
Energies 16 06845 i001Energies 16 06845 i002Energies 16 06845 i003
Construction Year198719942007
RoomA1A2A3A4B1B2B3C1C2C3
Floor planEnergies 16 06845 i004Energies 16 06845 i005Energies 16 06845 i006Energies 16 06845 i007Energies 16 06845 i008Energies 16 06845 i009Energies 16 06845 i010Energies 16 06845 i011Energies 16 06845 i012Energies 16 06845 i013
Floor area (m2)33.6100.833.6100.822.758.358.349.774.274.2
Volume (m3)90.7272.290.7272.251.0157.5157.5134.1200.3200.3
Window framePVCPVCALALPVCPVCALPVCPVCPVC
Table 2. Indoor and outdoor climate parameters during the experiment period.
Table 2. Indoor and outdoor climate parameters during the experiment period.
RoomMeasurement DateIndoor Temp [°C]Outdoor Temp [°C]Indoor/Outdoor Temperature Difference [°C]Outdoor Wind Speed [m/s]
A116 April 2021
29 September 2021
22.3
24.8
14.8
22.6
7.5
2.2
1.3
3.8
A218 April 2021
30 September 2021
17.0
23.1
13.4
22.2
3.6
0.9
2.6
1.0
A317 December 2021
8 April 2022
17.1
16.3
2.3
10.1
14.8
6.2
6.8
1.3
A417 December 2021
8 April 2022
15.0
18.7
2.7
10.1
12.3
8.6
4.5
1.5
B130 April 2021
23 December 2021
20.5
16.3
18.3
4.8
2.2
11.5
3.6
4.1
B24 May 2021
23 December 2021
21.5
17.4
19.3
4.8
2.2
12.6
1.7
3.6
B323 December 202116.64.911.73.6
C117 September 2021
7 January 2022
25.1
8.1
20.9
2.4
4.2
5.7
0.7
1.7
C27 January 2022
15 April 2022
8.4
20.1
1.9
14.9
6.5
5.2
1.1
3.9
C37 January 2022
15 April 2022
8.7
19.0
2.2
13.2
6.5
5.8
1.9
3.9
Table 3. Airtightness performance measurement results and distribution of the correlation factor.
Table 3. Airtightness performance measurement results and distribution of the correlation factor.
RoomAir Change per Hour (h−1, ACH) Using the Decay MethodAir Change per Hour at 50 Pa (ACH50) Using the Blower Door TestACH50/ACH
A10.22
0.29
18.02
17.57
81.91
60.58
A20.2124.64117.31
B10.16
0.15
14.02
12.91
87.59
86.08
B20.15
0.18
9.26
7.25
61.73
40.29
C10.09
0.09
5.21
5.64
57.83
62.64
C20.096.7975.42
Table 4. Results of ACHpr divided by Npr and errors.
Table 4. Results of ACHpr divided by Npr and errors.
ACH50MACH20/N20
(ACH50P)
Error (%)ACH25/N25
(ACH50P)
Error (%)ACH30/N30
(ACH50P)
Error (%)ACH35/N35
(ACH50P)
Error (%)
A315.2
14.1
14.6
13.7
4.4
2.5
14.8
13.7
3.2
2.8
14.8
13.6
3.1
3.2
14.8
13.6
3.1
3.2
A419.6
19.6
19.4
19.8
0.8
1.3
19.3
19.2
1.2
2.1
19.1
19.6
2.4
0.3
19.1
19.6
2.4
0.3
B318.519.34.418.91.918.50.118.50.1
C39.1
8.9
9.2
8.7
0.7
2.1
9.2
8.7
1.0
1.8
9.1
8.6
0.4
2.3
9.1
8.6
0.4
2.3
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Shim, C.; Hong, G. Airtightness Assessment under Several Low-Pressure Differences in Non-Residential Buildings. Energies 2023, 16, 6845. https://doi.org/10.3390/en16196845

AMA Style

Shim C, Hong G. Airtightness Assessment under Several Low-Pressure Differences in Non-Residential Buildings. Energies. 2023; 16(19):6845. https://doi.org/10.3390/en16196845

Chicago/Turabian Style

Shim, Chanhyung, and Goopyo Hong. 2023. "Airtightness Assessment under Several Low-Pressure Differences in Non-Residential Buildings" Energies 16, no. 19: 6845. https://doi.org/10.3390/en16196845

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop