1. Introduction
Air leakage is one of the major sources of energy gain and loss in buildings. Typically, the pressure gradient induced by wind blowing on the sides of a building can cause air to enter the building on the windward side and exit on the leeward side, resulting in the significant energy consumption of buildings. Traditionally, the energy impact of infiltration has been calculated based on the infiltration flow rate and the enthalpy difference between indoor and outdoor air [
1]. However, this calculation method assumes that the air entering the building remains unchanged as it passes through the building envelope. Therefore, standard methods of calculating infiltration ignore the thermal coupling between infiltration and conduction heat transfer through the building envelope, leading to potentially inaccurate estimations of heating and cooling loads.
On the other hand, the exchange of heat between infiltrating (or exfiltrating) air and building envelope materials is referred to as infiltration heat recovery (IHR). This exchange results in a reduction in the impact that the infiltrating air has on the energy required to condition the building. As the infiltrating air passes through the envelope, it exchanges heat with the materials, causing the air entering the building to be at a temperature that is not equal to that of the outdoor environment. Additionally, the air leaving the building tends to bring the interior surface closer to the indoor temperature, thereby reducing the heat transfer through the envelope [
2]. In essence, the building envelope functions as a heat exchanger for infiltrating and exfiltrating air, resulting in a net reduction in the energy impact of the airflow. Hence, the thermal properties of the building envelope could be considered as one of the main factors that influence the heat exchange performance of IHR. This heat recovery effect can reduce energy consumption in some climates. One study indicated that IHR is responsible for reducing the thermal load of infiltration by 10% to 20% in cold climates [
3].
Additionally, the direction and amount of airflow, whether from warm to cold or vice versa, significantly impacts the temperature gradient within the wall. In heating climates, infiltration refers to cold air entering a warm space. As the amount of airflow increases, the effects of infiltration heat recovery cause the gradient to become more convex. This results in a lower impact of infiltration energy due to a lower overall wall temperature but an increase in conduction due to a steeper temperature gradient. Conversely, in cooling climates, warm air enters a cooler space, creating a concave temperature gradient within the wall with increasing airflow and decreasing conduction [
4].
Recent studies, both experimental and numerical, highlighted the presence of significant thermal coupling between air leakage and wall elements, leading to modifications in heat transmission. Furthermore, several models were developed to investigate the behavior of IHR, for instance, Anderlind [
5] created a basic model to assess the thermal coupling between air infiltration and heat conduction in a wall. The model assumes that the infiltration is uniformly distributed across the wall surface. Liu [
6] developed a model that considers the influence of solar gains on infiltration heat recovery. The effect of solar heat transfer is believed to be magnified by changes in the exterior surface air temperature. When the solar gains are not considered, the solution provided by the Liu model is equivalent to that of the Anderlind model. Moreover, Krarti [
7] presented an analytical steady-state model of the IHR that considers heat convection along wall surfaces and assumes that diffuse air enters the wall at the surface temperature rather than the ambient temperature. The study concluded that temperature profiles and heat flux along the inner and outer wall surfaces demonstrate the effect of airflow on heat transmission through building envelopes. In addition, Buchanan and Sherman [
8] proposed a model with a wall participation factor to account for air leakage only happening in a portion of the wall area, which decreases the infiltration heat recovery effect as the wall participation factor decreases. The study conducted a thorough numerical analysis of the heat exchange between the wall and infiltration, utilizing both two-dimensional and three-dimensional simulations and validating their results with experimental data. Later, Solupe and Krarti [
3] discussed the implementation of the steady-state infiltration heat recovery (IHR) models mentioned above. Inter-model and experimental comparisons were performed to assess the accuracy of the predictions of these models. Sensitivity analyses were performed and showed that implementing IHR models in a whole-building simulation environment reduced heating consumption by 5% to 30% for four audited residential homes.
Conversely, Solupe [
4] conducted a thorough assessment of IHR, revealing a prevalent issue with most IHR models: they are represented by the absence of information concerning the quantity of diffuse airflow and the factor of IHR that normally occurs within a wall. The study stated that the flow exponent from a blower door test can be used to characterize airflow through an envelope and estimate infiltration heat recovery. A higher flow exponent indicates that building air leakage has more diffuse characteristics, potentially resulting in greater infiltration heat recovery. Nevertheless, several researchers, such as Buchanan and Sherman [
8], Abadie et al. [
9], and Qiu and Haghighat [
10], used computational fluid dynamics (CFD) models to calculate the IHR factor. However, this method can be computationally expensive in terms of CPU time. Similarly, Sherman and Walker [
2] worked on improving the prediction of energy load due to infiltration by introducing a correction factor that multiplies the expression for the conventional load. The study included simplified analytical modeling and CFD simulations to examine the infiltration heat recovery (IHR) effect on typical building envelopes. The results of the study show that IHR is negligible in buildings with insulated walls due to the small fraction of the envelope that participates in heat exchange with the infiltrating air. However, higher participation in dynamic walls/ceilings or uninsulated walls has the potential for a significant IHR effect. Later, in a recent study, Tallet et al. [
11] introduced a reduced-order model (ROM) technique that uses proper orthogonal decomposition (POD) to analyze the impact of energy balance permeability in buildings. The proposed ROM was developed in Modelica and applied to a case study that focused on air infiltration in a low-energy-consumption building. The results demonstrate the ROM approach’s effectiveness in evaluating buildings’ energy performance. It should be noted that in the steady-state analysis of IHR, as with the analysis presented in most previous studies, energy is neither created nor stored within the wall, and the temperature derived defines the conditions of the wall and air, assuming local thermal equilibrium.
On the other hand, several experimental studies were conducted to evaluate the thermal coupling of infiltration and heat conduction in walls. One of the first experiments in this area was conducted by Bhattacharyya and Claridge [
12]. In this experiment, the heat exchange between infiltrating air and an insulated test cell was studied, and it showed that heat conducting through the envelope of a building can warm the air that is leaking into the building, resulting in an infiltration energy loss that is less than the enthalpy difference between the inside and outside air. The experimental study also stated that infiltration heat exchange effectiveness strongly depends on three variables: flow rate, path length, and hole size. The results of the study show that infiltration heat recovery is higher at lower flow rates and lower at higher flow rates. Furthermore, Janssens [
13] presented a hot box experiment to investigate the heat recovery effect for air infiltration through a crack in an insulated wall. The experiment used a two-dimensional calculation model for combined heat and mass transfer to measure the steady-state transmission and infiltration heat loss through a wall. The experiment also employed a tracer gas technique to measure the infiltration flow rate. Numerical simulations were carried out to derive the proper test conditions and the results of the experiment were used to determine the infiltration heat recovery effectiveness by comparing the measured transmission and infiltration losses to the steady-state transmission loss through the wall with sealed cracks. Moreover, Ackerman et al. [
14] conducted a laboratory experiment to investigate the effect of airflow through a wall test panel. Two identical panels were constructed using a wood frame, fiberglass insulation, plywood, and gypsum. The panels were designed with specific entry and exit points through the gypsum and plywood, enabling air to flow through the insulation. The experiment showed that the heat recovery potential of infiltration strongly depends on the heat exchange participation fraction of the building envelope. Finally, in the most recent experiment conducted for IHR, Brownell [
15] examined the relationship between heat loss and infiltration flow rate in a test cell, focusing on the high flow rate regime. A 3.5 m
3 test cell was constructed using standard light-frame construction and a removable panel to test wall sections with varying flow path lengths. Two different wall sections were tested, and six different infiltration flow rates were utilized. The study compared experimentally determined heat recovery factors to computational fluid dynamics, and the results were consistent within an approximate 15% margin of error.
Breathing walls are construction elements made of porous materials that serve as insulation components and heat recovery exchangers [
16]. Wall porosity is a fundamental property of materials; it describes the proportion of void space within the material’s volume. This void space can permit the passage of air. In the context of building materials, porosity can influence the thermal and ventilation properties of walls. On the other hand, a breathing wall is a term often used to describe walls with intentionally high porosity that are designed for specific purposes. These walls allow for regulated air movement, facilitating natural ventilation and potentially contributing to the building’s thermal performance. It is essential to understand that while all breathing walls exhibit high porosity, not all walls with high porosity are designed or function as breathing walls.
The concept of air-permeable concrete (APC) was also introduced as a dynamic breathing wall system [
17]. Breathing walls, often referred to as permodynamic walls, have been extensively studied, especially the coupling effect between air leakage and conduction heat transfer through the wall. A recent review paper presented by Fawaier and Bokor [
18] classified and discussed various studies on dynamic insulation structures, highlighting the use of breathing walls to enhance indoor air quality and minimize the cooling or heating energy in buildings. Recent research studies focused on the performance of breathing walls. For example, Zhang and Wang [
19] analyzed the critical insulation thickness of breathing walls under different scenarios to minimize the pressure drop and reduce convective heat loss. Alongi et al. [
20] developed a steady periodic analytical model for breathing walls. They validated the model with experimental data by investigating temperature profiles and heat flux across sample wall blocks at varying air velocities. Zhang et al. [
21] developed and validated a network heat transfer model for exhaust air insulation walls (EAIWs) to optimize their design and increase the energy-saving potential for different climates. Alongi et al. [
22] presented a one-dimensional numerical model of breathing walls using the finite difference method, validating it with experimental data and dynamic analytical models under sinusoidal and periodic boundary conditions. The study examined the wall’s temperature distribution and heat flux for different air velocities and time durations. Alongi et al. [
23] investigated the optimal operation strategies for breathing walls using a transient numerical model coupled with TRNSYS. They analyzed the energy savings of an office room in Milan, Italy.
While IHR has been explored extensively, as discussed above, most research studies have focused on the steady-state performance of IHR while ignoring the thermal energy storage of the wall. Only a few studies investigated the IHR transient effect of dynamic insulation breathing walls. However, no research studies were found that evaluated the heat recovery factor of the wall in the context of the transient behavior of the convection-diffusion model of the IHR phenomena. Specifically, the interrelationship effects between the wall’s thermal conductivity, thermal mass, airflow rate, airflow direction, wall thickness, and wall porosity concerning the heat recovery factor have not been adequately analyzed. Therefore, this study aimed to fill this research gap by developing and analyzing a transient convection–diffusion numerical model representing the IHR phenomena and investigating the impact of the heat capacity of the building’s exterior walls on the performance of IHR under various conditions. The findings of this study will provide insights into the transient behavior of IHR for various design conditions and contribute to the ongoing efforts to improve the modeling accuracy of building physics.
To provide a comprehensive understanding of the study’s approach and findings, this paper is structured as follows:
Section 2 details the “Materials and Methods,” encompassing the analysis methods employed, the transient and steady-state IHR models, and the derivation of the heat recovery factor. In
Section 3, “Results and Discussion” are presented. This section provides an in-depth look into the analysis of the temperature distribution within the wall, discussing the effects of heat capacity (HC) and airflow rate under varying conditions, alongside an extensive analysis of the infiltration heat recovery (IHR) factor, exploring its relationship with parameters, such as the Peclet number (Pe), heat capacity, wall thickness, and wall porosity. Finally,
Section 4 concludes the study, summarizing the key findings and their implications.
2. Materials and Methods
2.1. Analysis Methods
The objective of this research study was to provide a detailed understanding of the impact of the building’s thermal mass on IHR performance by investigating the transient effect of the wall’s heat capacity on the performance of infiltration heat recovery for various conditions. It is important to note that most investigations into IHR have mainly focused on its performance in the context of porous insulation materials, which are recognized for their low thermal conductivity and minimal thermal mass. Consequently, one of the principal objectives of this research study was to expand the analysis of IHR to include broader wall systems while considering the impact of both thermal conductivity and heat capacity.
As documented in the prior research studies discussed earlier, the steady-state convection–diffusion IHR model is employed to analyze the temperature distribution within the wall and determine the heat recovery factor of dynamic or porous insulation walls. As explored in these studies, temperature profiles within the wall are altered due to the influence of air leakage through the wall. The amount of this distortion of temperature distribution depends on the rate of airflow and the direction of the air leakage within the wall (i.e., infiltration or exfiltration). In the absence of airflow leakage, a linear steady-state profile is observed. However, in the case of infiltration, or the movement of air through the wall from outdoors to indoors, a concave temperature distribution is observed within the wall, which influences the level of heat gain due to conduction heat transfer through the wall. The opposite effect is observed when the direction of air leakage is reversed, which is a situation referred to as exfiltration: the movement of air through the wall from indoors to outdoors.
Figure 1 illustrates the impact of infiltration and exfiltration on the deformation of temperature profiles within the wall, where L is the thickness of the wall, T
in is the indoor wall surface temperature, and T
out is the outdoor wall surface temperature.
The initial step involved presenting the mathematical partial differential equation (PDE) model of the IHR phenomena and discussing the numerical method employed to solve this model. The IHR model took into consideration the thermal attributes of the wall, including the heat capacity and thermal conductivity, along with the effects of external and internal conditions. The numerical model of IHR was then verified against results derived from a steady-state analytical solution. A comprehensive analysis, including sensitivity analysis, was subsequently performed by running simulations of the model under broad design conditions, including different values of the wall’s heat capacity, thermal conductivity, airflow rate through the wall, direction of airflow, and wall porosity. Sensitivity analysis, by definition, is a technique used to determine how different values of an independent variable impact a particular dependent variable under a given set of assumptions. In the context of this study, sensitivity analysis was employed to determine the complex interactions between several key parameters and their collective influence on the infiltration heat recovery factor. Parameters such as heat capacity, Peclet number, wall porosity, and wall thickness were anticipated to significantly influence the IHR’s effectiveness. While each parameter has its distinct effect on the IHR factor, it is their collective and potentially non-linear interactions that offer insights into the behavior of the system. Specifically, variations in the wall thickness can significantly modulate the effects of other parameters. Consequently, a multi-variable sensitivity analysis was conducted to provide a comprehensive understanding of the combined impact of these variables on the IHR factor. This approach ensures a more robust grasp of the variables’ dynamics and contributes to a more accurate prediction of IHR behavior.
Though an explicit time-dependent analysis of infiltration heat recovery (IHR) behavior was not directly undertaken in this study, it is essential to highlight the inherent considerations incorporated into the analysis. Specifically, insights into the influence of time are provided by exploring delays in the temperature profiles, which are attributed to differences in wall heat capacities. In walls with a low heat capacity, an immediate heat transfer behavior is observed, resulting in a near-instantaneous response in temperature profiles. Conversely, a delayed response is noted in walls with a high heat capacity due to their inherent thermal energy storage capacity, leading to divergent temperature profiles over an elapsed period. This behavior emphasizes the time-dependent nuances of IHR. Moreover, the relationship between the IHR factor, heat capacity, and air velocity, as characterized by the Peclet number, further demonstrates the indirect effects of time on the heat recovery dynamics. Thus, while direct analysis may not have been undertaken, the influence of time on IHR was thoroughly addressed through these indirect examinations. The upcoming section describes the numerical modeling of the transient IHR model.
2.2. IHR Transient Model
The approach employed to model the infiltration heat recovery (IHR) phenomenon used a one-dimensional, single-layer wall model to represent the transient convection-diffusion system governed by energy conservation. As outlined in Equation (1) [
7], conduction heat transfer exists through the wall due to the temperature difference between the indoor and outdoor environments, along with air leakage through the wall at a velocity denoted as V
a, as illustrated in
Figure 2. Additionally, uniform heat and mass flows were assumed in the one-dimensional model. The temperature, denoted as T in Equation (1), represents the temperature of both the air and the wall material at a given position (x) and time (t). In Equation (1), a positive value is assigned to the velocity V
a when air flows in the direction of the
x-axis, representing exfiltration or the movement of air from indoors to outdoors. Conversely, a negative value is given for V
a when air flows from outdoors to indoors, which represents infiltration in this case. Furthermore, the term ρ⋅C
p expressed in Equation (1) signifies the wall’s and air’s heat capacity, reflecting the amount of heat storage per unit volume, where ρ represents the density and C
p represents the specific heat.
The heat capacity of the wall and air, denoted as (ρ⋅C
p)
wa in Equation (1), is expressed in Equation (2) [
7], where ε is the wall porosity (%) characterizing the amount of air flowing through the wall:
The finite difference method was used as a numerical modeling approach to solve the IHR model, as represented by Equation (1). The discretized form of this equation is presented in Equation (3) as an approximate linear algebraic equation as follows:
The subscript i in Equation (3) represents the position x, and the superscript n denotes the time. Meanwhile, Δt and Δx represent the time step and wall thickness, respectively. Equation (3) is then rearranged and simplified, as shown in Equation (4), to be employed in a matrix form:
where the symbols φ and μ are defined as follows:
The boundary conditions for Equation (1) are defined in Equations (7) and (8), which represent the boundaries at x = 0 and x = L respectively. The right-hand side of Equations (7) and (8) depicts the discretized form of the boundary conditions. In these equations, hi and ho express the convection heat transfer coefficients of the interior and exterior films on the wall surfaces, respectively. Additionally, Twi represents the temperature of the interior surface of the wall, Tin is the indoor air temperature, Two is the temperature of the outdoor surface of the wall, and Tout is the outdoor air temperature.
The numerical scheme presented above, which represents the interior nodes and the boundary nodes of the wall, was developed in Matlab, presented in a tridiagonal matrix, and solved using the L-U decomposition numerical approach. The finite difference method was chosen in this study for its efficiency and accuracy in handling the complex partial differential equation representing the relationship between advection and conduction heat transfer in the infiltration heat recovery phenomena. While numerous methods are available for solving such equations, the L-U decomposition was selected due to its efficient computational cost. To guarantee the accuracy of the numerical approach, verification analysis was performed by comparing the numerical results with the analytical solution of the IHR steady-state model. The numerical method results were found to align well with the analytical solutions, indicating its reliability for this problem, as presented in the next section.
2.3. IHR Steady-State Model
The analytical solution of the IHR steady-state model was utilized to verify the accuracy of the IHR numerical model. When assuming steady-state conditions for conduction and infiltration rates through the wall, where no energy storage is considered, the total thermal energy through the wall is defined in Equation (9) [
3]:
The prospective influence of infiltration heat recovery can be represented as a function of a dimensionless term called the Peclet number. This number characterizes the connection between advection and conduction heat transfer within a body experiencing airflow. In the context of a building application, for instance, this relationship could be identified as the proportion between infiltration and conduction loss coefficients for the part of the wall where airflow is present. Furthermore, the impacts of heat recovery on the overall building load become negligible when the Peclet number is extremely small or exceptionally large. The only exception is when the amount of conduction heat transfer through the wall is minor. This leads to a situation where the infiltration heat recovery increases to its theoretical maximum of one. Accordingly, the analytical solution of the steady-state second-order differential equation presented in Equation (9) can be derived using both the Peclet number and Biot number [
3], as shown in Equation (10) [
3]:
where Bi is the Biot number and Pe is the Peclet number of the airflow and are estimated as follows [
3]:
The value of the infiltration rate determines the Peclet value, where a Peclet value of zero means there is no infiltration, and a value of infinity indicates very high infiltration. Indeed, the Peclet number is considered negative when exfiltration occurs.
On the other hand, the film resistance of the wall’s surface will influence the air temperature just before it enters and immediately after it exits the wall. This is where the role of the Biot number becomes apparent. The Biot number, calculated for interior and exterior surfaces, reveals the convective characteristics of the wall surface, given that the conduction remains constant. The Biot number typically ranges from 1 to 10 in practical building scenarios. When the Biot number is zero for either surface, the wall surface film resistance becomes infinite, behaving like an adiabatic layer. Conversely, if the Biot number is infinitely large, the surface film heat transfer resistance becomes insignificant.
To verify the outcomes of the IHR numerical model, a comparison was performed with the analytical solution of the IHR steady-state model. The graph shown in
Figure 3 presents a comparative analysis of the results from the two models across various Peclet number values. The numerical model was specifically configured for a wall with an extremely low heat capacity, while a constant thermal conductivity of 0.04 W/m⋅K was fixed for both models. The boundary conditions presumed an indoor air temperature of 20 °C and an outdoor air temperature of 40 °C. Further, the convection heat transfer coefficient was assumed to be 5 W/m
2⋅K and 15 W/m
2⋅K for the indoor and outdoor wall surfaces [
24], respectively. As indicated in
Figure 3, the outcomes of the numerical model align closely with the analytical solution. Therefore, it can be concluded that the developed IHR numerical model demonstrated notable accuracy and is suitable for further detailed analysis.
2.4. Heat Recovery Factor
Certain research studies proposed the infiltration heat recovery factor (f) [
7,
15] to easily describe the impact of IHR. Theoretically, the IHR factor oscillates between zero and one. The maximum value of the IHR factor (f = 1) signifies instances where infiltration approaches zero. In contrast, at its minimum (f = 0), it signifies a situation where the mass flow rate of infiltration increases to such an extent that it surpasses the conduction heat transfer load, typically seen at very high Peclet numbers. To characterize the impact of IHR, the heat recovery factor (f) is calculated as follows [
3]:
where Q
recov is the heat recovery rate, Q
cond is the conduction heat transfer rate through the wall, and Q
inf is the classical infiltration rate where no heat recovery is considered. The heat recovery rate can be expressed as follows [
3]:
where
is the mass flow rate of infiltration, C
p is the specific heat of air, T
in is the indoor air temperature, and T
out is the outdoor air temperature. It is worth noting that the second part on the right-hand side of Equation (13) represents the effective thermal load impact associated with infiltration. The infiltration rate that takes into account the heat recovery is estimated using Equations (15) and (16) [
4]:
where T
surf_in in Equation (16) is the wall’s indoor surface temperature. Therefore, based on the above equations, the heat recovery factor presented in Equation (13) can be modified as shown in Equation (17) [
4]:
The overall effect of infiltration heat recovery becomes significant only when substantial heat transfer through the wall is present. As the IHR factor approaches unity, the infiltration load decreases significantly compared with the conduction load, yielding an almost negligible overall impact. While the IHR factor tends to decline at higher airflow rates, the absolute effect becomes more evident under higher loads. Theoretically, energy savings due to infiltration heat recovery can significantly increase until the loads of infiltration and conduction reach a similar magnitude. However, when infiltration predominantly governs the total heat transfer within a space, the influence of infiltration heat recovery diminishes until it once again becomes negligible.
4. Conclusions
This study addressed the lack of analysis on the transient behavior of the convection-diffusion model for infiltration heat recovery (IHR) and the impact of the wall’s heat capacity, along with other factors. Understanding this relationship is crucial for accurate predictions of the energy performance of buildings. Therefore, the findings of this research study aimed to provide valuable insights into the performance of IHR and the impact of several factors, including the wall’s heat capacity, thermal conductivity, airflow rate across the wall, airflow direction, and wall porosity, in influencing the temperature distribution and heat recovery factor within the wall.
The results of this study indicated that the heat capacity of the wall plays a crucial role in delaying the temperature rise within the wall, with higher heat capacity walls exhibiting a greater delay. Conversely, walls with very low thermal conductivity, such as super-insulated walls, minimize the rate of conduction heat transfer, reducing the overall heat recovery rate and increasing the IHR factor. The impact of the wall’s heat capacity on the IHR factor became insignificant when very low thermal conductivity walls were considered. However, heat capacity’s influence became more evident for high thermal conductivity walls, especially as the Peclet number increased. The sensitivity analysis revealed that the IHR factor generally increased as the wall thickness increased, with thicker walls providing enhanced heat retention and better heat recovery potential. Additionally, the influence of the airflow rate on the IHR factor diminished with thicker walls, further enhancing the heat recovery. A higher IHR factor was generally associated with thicker walls, lower Peclet numbers, and higher heat capacities. Wall porosity also played a role in determining the effectiveness of infiltration heat recovery, with more porous walls experiencing increased heat loss through the material, resulting in lower IHR factors. However, the influence of wall porosity appeared to be less significant, particularly for low Peclet numbers, compared with other factors. These findings highlight the importance of considering heat capacity, thermal conductivity, wall thickness, and wall porosity in understanding the performance of the infiltration heat recovery. Incorporating these insights into energy-efficient building design and energy simulation models can lead to more accurate predictions, enhanced energy management strategies, and reduced cooling energy consumption.
By considering the transient behavior of IHR and the thermal energy storage of walls, designers can optimize energy consumption patterns and enhance the performance of buildings. Future research in this area could further explore additional factors and optimize building design to maximize the benefits of infiltration heat recovery. In addition, beyond the immediate focus of infiltration heat recovery, future research should also consider the broader implications of uncontrolled airflow in buildings. This includes drafts, pollutant transport, moisture challenges, and potential mold growth. Addressing these concerns will offer a more comprehensive perspective on building performance, merging energy efficiency with occupant well-being. Finally, this study contributes to the field of building physics by providing a detailed understanding of the interactions between IHR, thermal mass, and other influential factors, in addition to enhancing the accuracy of building energy modeling and prediction of building energy performance.