Air Conditioning Operation Strategies for Comfort and Indoor Air Quality in Taiwan’s Elementary Schools
Abstract
:1. Introduction
2. Analysis
2.1. Numerical Analysis Method
2.2. Student Timetable and Simulation Settings
2.3. A/C Operation Strategies
3. Results and Discussion
3.1. Current Situation (Case 0) and A/C Operated all Day without Mechanical Fresh Air Ventilation (Case 1)
3.2. Installation of Mechanical Fresh Air Ventilation System (Case 2)
3.3. Turn off Air-Conditioning during Certain Periods
3.4. Ranking of Different A/C Operation Strategies
4. Conclusions
- The validity of the numerical model used in the present simulations has been confirmed. It has been shown that the simulated value deviates from the measured value by no more than 3.2%.
- In the case where A/C is not installed, i.e., the classroom is cooled and ventilated by natural ventilation only, the average CO2 within the classroom varies between 583~612 ppm, depending on the proportion of students leaving the classroom at recess. The IAQ is thus consistent with the EPA guideline. However, the thermal comfort is extremely poor.
- The IAQ can be further improved through encouraging the students to leave the classroom and go outdoors every recess.
- To satisfy both the Executive Yuan requirement for thermal comfort over the full school day and the EPA guideline for the IAQ (an 8-h average CO2 concentration in the classroom of less than 1000 ppm), it is necessary to run the A/C system continuously the entire day (08:00~15:50) and to provide mechanical fresh air ventilation at a rate of 5 l/s per person in the classroom of an elementary school.
- As a lower energy consumption alternative, the A/C system can be operated from 08:00 to 15:50, but turned off during every recess period and at lunch time.
- The A/C energy consumption can be reduced by delaying the A/C turn-on time until the 3rd class (10:30) and then turning the A/C off both at lunch time and during the 6th class.
- As a final alternative, the A/C turn-on time can be delayed until the 2nd class (09:35) and then run for the remainder of the school day with the exception of the lunch time period and the 6th class.
Author Contributions
Funding
Data Availability Statement
Conflicts of Interest
References
- Taiwan Executive Yuan Official Website. Available online: https://english.ey.gov.tw/Page/61BF20C3E89B856/4665e854-bfb8-43e0-a975-34d8b4602d33 (accessed on 2 November 2022).
- Chang, T.; Sheu, J.; Huang, J. Vehicle air leakage ventilation and its effect on cabin indoor air quality, Proceedings of the Institution of Mechanical Engineers, Part E. J. Process Mech. Eng. 2017, 231, 1226–1234. [Google Scholar] [CrossRef]
- Tham, K. Indoor air quality and its effects on humans-A review of challenges and developments in the last 30 years. Energy Build. 2016, 130, 637–650. [Google Scholar] [CrossRef]
- Seppanen, O.; Fisk, W.; Mendell, M. Association of ventilation rates and CO2 concentrations with health and other responses in commercial and institutional buildings. Indoor Air 1999, 9, 226–252. [Google Scholar] [CrossRef] [PubMed] [Green Version]
- Szczepanik-Scislo, N.; Antonowicz, A.; Scislo, L. PIV measurement and CFD simulations of an air terminal device with a dynamically adapting geometry. SN Appl. Sci. 2019, 1, 370. [Google Scholar] [CrossRef] [Green Version]
- Szczepanik-Scislo, N.; Flaga-Maryańczyk, A. Indoor air quality modelling and measurements of a studio apartment with a mechanical exhaust system. E3S Web Conf. 2018, 44, 00171. [Google Scholar] [CrossRef] [Green Version]
- Chung, S.-C.; Lin, Y.-P.; Yang, C.; Lai, C.-M. Natural Ventilation Effectiveness of Awning Windows in Restrooms in K-12 Public Schools. Energies 2019, 12, 2414. [Google Scholar] [CrossRef] [Green Version]
- Lin, Y.-P. Natural Ventilation of Toilet Units in K–12 School Restrooms Using CFD. Energies 2021, 14, 4792. [Google Scholar] [CrossRef]
- ASTM. Standard Guide for Using Indoor Carbon Dioxide Concentrations to Evaluate Indoor Air Quality and Ventilation; ASTM International: West Conshohocken, PA, USA, 2012. [Google Scholar]
- Wang, Y.; Zhao, F.; Kuckelkorn, J.; Liu, D.; Liu, L.; Pan, X. Cooling energy efficiency and classroom air environment of a school building operated by the heat recovery air conditioning unit. Energy 2014, 64, 991–1001. [Google Scholar] [CrossRef]
- Kusiak, A.; Tang, F.; Xu, G. Multi-objective optimization of HVAC system with an evolutionary computation algorithm. Energy 2011, 36, 2440–2449. [Google Scholar] [CrossRef]
- Xaman, J.; Ortiz, A.; Alvarez, G.; Chavez, Y. Effect of a contaminant source (CO2) on the air quality in a ventilated room. Energy 2011, 36, 3302–3318. [Google Scholar] [CrossRef]
- ASHRAE Standard 62.1-2019; Ventilation for acceptable indoor air quality. American Society of Heating. Refrigeration and Air conditioning Engineers; ASHRAE: Peachtree Corners, GA, USA, 2019.
- Prill, R.; Blake, D.; Hales, D. School Indoor Air Quality Assessment and Program Impementation; Washington State University: Pullman, WA, USA, 2012. [Google Scholar]
- You, Y.; Bai, Z.; Jia, C.; Hu, X.; Ran, W.; Zhang, J. Ventilation conditions and the related symptoms in selected indoor environments in a University. In Proceedings of the 6th International Conference on Indoor Air Quality, Ventilation & Energy Conservation in Buildings IAQVEC, Sendai, Japan, 28–31 October 2007. [Google Scholar]
- Allen, J.; MacNaughton, P.; Satish, U.; Vallarino, J.; Spengler, J. Associations of congnitive function scores with carbon dioxide, ventilation, and volatile organic compound exposures in office workers: A controlled exposure study of Green and conventional office environments. Environ. Health Perspect. 2016, 124, 805–812. [Google Scholar] [CrossRef] [Green Version]
- Satish, U.; Mendell, M.; Shekhar, K.; Hotchi, T.; Sullivan, D.; Streufert, S.; Fisk, W. Is CO2 an indoor Pollutant? Direct effects of low-to-moderate CO2 concentrations on human decision-making performance. Environ. Health Perspect. 2012, 120, 1671–1677. [Google Scholar] [CrossRef] [PubMed] [Green Version]
- Chuah, Y.K.; Yang, J.J. A Integrated Dedicated Outdoor Air System to Optimize Energy Saving. Sustainability 2020, 12, 1051. [Google Scholar] [CrossRef] [Green Version]
- Haverinen-Shaughnessy, U.; Shaughnessy, R. Effects of classroom ventilation rate and temperature on students’ test scores. PLoS ONE 2015, 10, e0136165. [Google Scholar] [CrossRef] [PubMed]
- Szczepanik-Scislo, N.; Schnotale, J. An Air Terminal Device with a Changing Geometry to Improve Indoor Air Quality for VAV Ventilation Systems. Energies 2020, 13, 4947. [Google Scholar] [CrossRef]
- Bako-Biro, Z.; Clements-Croome, D.; Kochhar, N.; Awbi, H.; Williams, M. Ventilation rates in schools and pupils’ performance. Build. Environ. 2012, 48, 215–223. [Google Scholar] [CrossRef]
- Mendell, M.; Eliseeva, E.; Davies, M.; Lobscheid, A. Do classroom ventilation rates in California elementary schools influence standardized test scores? Results from a prospective study. Indoor Air 2016, 26, 546–557. [Google Scholar] [CrossRef]
- Turanjanin, V.; Vucicevic, B.; Jovanovic, M.; Mirkov, N.; Lazovic, I. Indoor CO2 measurements in Serbian schools and ventilation rate calculation. Inside Energy 2014, 77, 290–296. [Google Scholar] [CrossRef]
- Gao, J.; Wargocki, P.; Wang, Y. Ventilation system type, classroom environmental quality and pupils’ perceptions and symptoms. Build. Environ. 2014, 75, 46–57. [Google Scholar] [CrossRef]
- Chan, W.R.; Li, X.; Singer, B.C.; Pistochini, T.; Vernon, D.; Outcault, S.; Sanguinetti, A.; Modera, M. Ventilation rates in California classrooms: Why many recent HVAC retrofits are not delivering sufficient ventilation. Build. Environ. 2020, 167, 106426. [Google Scholar] [CrossRef]
- Johnson, D.L.; Lynch, R.A.; Floyd, E.L.; Wang, J.; Bartels, J.N.J.B. Indoor air quality in classrooms: Environmental measures and effective ventilation rate modeling in urban elementary schools. Build. Environ. 2018, 136, 185–197. [Google Scholar] [CrossRef]
- Fisk, W.J.J.I.A. The ventilation problem in schools: Literature review. Indoor Air 2017, 27, 1039–1051. [Google Scholar] [CrossRef] [PubMed] [Green Version]
- Persily, A.; de Jonge, L. Carbon dioxide generation rates for building occupants. Indoor Air 2017, 27, 868–879. [Google Scholar] [CrossRef] [PubMed] [Green Version]
- Chang, J.J. The Study of Indoor Air Quality in the Computer Classrooms of Elementary School in Pintung Area. Master’s Thesis, Tajen University, Pingtung, Taiwan, 2015. [Google Scholar]
- Daily Timetable of Elementary School. Available online: https://sites.google.com/a/kyes.tn.edu.tw/kyes104501/ban-ji-ke-biao (accessed on 2 November 2022).
- Ministry of Education of Taiwan, Elementary and Secondary School Class Organization and Staffing Guidelines, National Law Database. Available online: https://law.moj.gov.tw/LawClass/LawAll.aspx?pcode=H0070006 (accessed on 13 March 2021).
- Chang, T.B.; Sheu, J.J.; Huang, J.W.; Lin, Y.S.; Chang, C.C. Development of a CFD model for simulating vehicle cabin indoor air quality. Transp. Res. Part D Transp. Environ. 2018, 62, 433–440. [Google Scholar] [CrossRef]
Period | Program |
---|---|
7:35–8:00 | Student check-in |
8:00–8:40 | Mentor time |
8:40–8:45 | Break time |
8:45–9:25 | 1st class |
9:25–9:35 | Break time |
9:35–10:15 | 2nd class |
10:15–10:30 | Break time |
10:30–11:10 | 3rd class |
11:10–11:20 | Break time |
11:20–12:00 | 4th class |
12:00–12:40 | Lunch & brushing time |
12:40–13:20 | Nap time |
13:20–13:25 | Break time |
13:25–14:05 | 5th class |
14:05–14:15 | Break time |
14:15–14:55 | 6th class |
14:55–15:10 | Break time |
15:10–15:50 | 7th class |
15:50– | End of school/Pickup time |
Parameters | Setting Value | Source of Setting Value |
---|---|---|
Volume of classroom (V) | 248 m3 | Chang [29] |
The natural ventilation flow rates when A/C is turned on (QAC/on) | Chang [29] | |
The natural ventilation flow rates when A/C is turned off (QAC/off) | Chang [29] | |
Number of person in classroom (n) | 29 children and 1 teacher | The regulations of the Ministry of Education of Taiwan 「Regulations governing the establishment of classes and staffs for elementary and secondary schools」 [31] |
The CO2 generation rate per person (Gs) |
| Persily and Jonge [28] |
The initial value of the CO2 concentration in the classroom C0 | 420 ppm | Chang et al. [32] |
The outdoor CO2 | 420 ppm | Chang et al. [32] |
The Beginning Time for Turning-On the A/C | Whether the A/C is on or Not during Lunch & Brushing Time | Whether the A/C is on or Not in the 6th Class | The Proportion of Students Leaving the Classroom to Outdoor Activities during the Break Time | Case Number |
---|---|---|---|---|
Current situation without A/C | --- | --- | 0% | 0a |
50% | 0b | |||
100% | 0c | |||
Mentor time/08:00 (Natural ventilation) | ON | ON | 0% | 1a |
50% | 1b | |||
100% | 1c | |||
Mentor time/08:00 (with additional mechanical ventilation rate at 5 l/s per person, i.e., ) | ON | ON | 0% | 2a |
50% | 2b | |||
100% | 2c | |||
1st class/08:45 | ON | ON | 0% | 3a |
50% | 3b | |||
100% | 3c | |||
2nd class/09:35 | ON | ON | 0% | 4a |
50% | 4b | |||
100% | 4c | |||
3rd class/10:30 | ON | ON | 0% | 5a |
50% | 5b | |||
100% | 5c | |||
Mentor time/08:00 | OFF | ON | 0% | 6a |
50% | 6b | |||
100% | 6c | |||
1st class/08:45 | OFF | ON | 0% | 7a |
50% | 7b | |||
100% | 7c | |||
2nd class/09:35 | OFF | ON | 0% | 8a |
50% | 8b | |||
100% | 8c | |||
3rd class/10:30 | OFF | ON | 0% | 9a |
50% | 9b | |||
100% | 9c | |||
Mentor time/08:00 | OFF | OFF | 0% | 10a |
50% | 10b | |||
100% | 10c | |||
1st class/08:45 | OFF | OFF | 0% | 11a |
50% | 11b | |||
100% | 11c | |||
2nd class/09:35 | OFF | OFF | 0% | 12a |
50% | 12b | |||
100% | 12c | |||
3rd class/10:30 | OFF | OFF | 0% | 13a |
50% | 13b | |||
100% | 13c | |||
Mentor time/08:00 (the A/C was turned on from the beginning of the mentor time (08:00) to the end of the school day (15:50), but was turned off every recess and during the lunch and teeth brushing period) | OFF | ON | 0% | 14a |
50% | 14b | |||
100% | 14c |
Case Number | The Average CO2 Concentration in Classroom | The Average CO2 Concentration Experienced by the Students for the Case Where They Leave the Classroom during the Recess Periods | Total A/C Operation Time |
---|---|---|---|
0a | 612 | -- | 0 |
0b | 597 | 584 | |
0c | 583 | 573 | |
1a | 1818 | -- | 7 h 50 min |
1b | 1715 | 1616 | |
1c | 1612 | 1524 | |
2a | 966 | -- | 7 h 50 min |
2b | 925 | 883 | |
2c | 883 | 847 | |
3a | 1705 | -- | 7 h 5 min |
3b | 1604 | 1524 | |
3c | 1503 | 1432 | |
4a | 1548 | -- | 6 h 15 min |
4b | 1459 | 1407 | |
4c | 1371 | 1326 | |
5a | 1376 | -- | 5 h 20 min |
5b | 1309 | 1283 | |
5c | 1241 | 1220 | |
6a | 1505 | -- | 7 h 10 min |
6b | 1420 | 1322 | |
6c | 1335 | 1247 | |
7a | 1399 | -- | 6 h 25 min |
7b | 1316 | 1235 | |
7c | 1232 | 1161 | |
8a | 1258 | -- | 5 h 35 min |
8b | 1185 | 1132 | |
8c | 1113 | 1068 | |
9a | 1119 | -- | 4 h 40 min |
9b | 1064 | 1038 | |
9c | 1008 | 987 | |
10a | 1283 | -- | 6 h 5 min |
10b | 1217 | 1118 | |
10c | 1151 | 1062 | |
11a | 1176 | -- | 5 h 20 min |
11b | 1112 | 1031 | |
11c | 1048 | 977 | |
12a | 1035 | -- | 4 h 30 min |
12b | 982 | 929 | |
12c | 928 | 883 | |
13a | 897 | -- | 3 h 35 min |
13b | 860 | 835 | |
13c | 824 | 803 | |
14a | 986 | -- | 6 h |
14b | 944 | 905 | |
14c | 902 | 868 |
Index A | Index B | Index C (C = A × B) | Ranking | |
---|---|---|---|---|
Case 0 | 1 | 0 | 0 | Not recommended |
Case 2 | 1 | 1 | 1 | 1st |
Case 12 | 2/3 | 0.574 | 0.383 | 4th |
Case 13 | 1 | 0.457 | 0.457 | 3rd |
Case 14 | 1 | 0.766 | 0.766 | 2nd |
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2023 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).
Share and Cite
Chang, L.-Y.; Chang, T.-B. Air Conditioning Operation Strategies for Comfort and Indoor Air Quality in Taiwan’s Elementary Schools. Energies 2023, 16, 2493. https://doi.org/10.3390/en16052493
Chang L-Y, Chang T-B. Air Conditioning Operation Strategies for Comfort and Indoor Air Quality in Taiwan’s Elementary Schools. Energies. 2023; 16(5):2493. https://doi.org/10.3390/en16052493
Chicago/Turabian StyleChang, Ling-Yi, and Tong-Bou Chang. 2023. "Air Conditioning Operation Strategies for Comfort and Indoor Air Quality in Taiwan’s Elementary Schools" Energies 16, no. 5: 2493. https://doi.org/10.3390/en16052493
APA StyleChang, L. -Y., & Chang, T. -B. (2023). Air Conditioning Operation Strategies for Comfort and Indoor Air Quality in Taiwan’s Elementary Schools. Energies, 16(5), 2493. https://doi.org/10.3390/en16052493