1. Introduction
In road lighting installations, a number of individual lighting fixtures are used with a relatively low specific active power of a single fixture. One lighting circuit may contain from several to several dozen luminaires, which in turn means that it can be treated as an electrical energy receiver with relatively high active power. The maximum reduction in energy consumption costs can be achieved by using modern lighting fixtures with adjustable power, for example, by using autonomous intelligent lighting fixtures. Savings are achieved by adjusting the luminous flux in accordance with changes in traffic intensity. Regulating the flux by reducing the active power consumption of luminaires saves electricity, but unfortunately it also has a side effect. This is an increase in capacitive reactive power in the network, which has already been described quite extensively [
1,
2,
3,
4,
5,
6].
The authors in papers [
7,
8] presented the results of the analysis of energy savings levels when replacing high-pressure sodium luminaires with LED luminaires in street lighting. The results of measurements of the luminous flux as a function of the active power of high-pressure sodium and LED luminaires used in road lighting are described, unfortunately focusing only on determining the power factor values—without providing information on the reactive power values. In publications [
9,
10,
11], the authors, analyzing the operation of lighting installations made of LED fixtures, discuss the energy efficiency of these installations as well as the impact of their control on the power factor values, also without providing information on the reactive power values. In the subsequent analyzed publications [
12,
13,
14,
15,
16,
17,
18], the authors present the approach that the values of capacitive reactive power generated by circuits characterized by capacitive reactive energy flows with the “+” sign can be given, with the addition of the comment “capacitive” in some of these publications. In these publications, the values of
coefficients are also given with a “+” sign. This is contrary to the findings known in power theory, which require that the values of both of these values be given with a “−” sign. As is known, capacitive reactive power compensation can be achieved by introducing additional elements that are attached to individual luminaires or to the power grid [
19,
20,
21,
22,
23,
24,
25].
The selection of these elements can be made at the design stage or after measuring energy quality parameters. Such a task is quite complicated when using many different power lighting fixtures with LED sources. In articles [
19,
20,
21,
22], the authors describe the selection of devices (compensation chokes) for capacitive reactive power compensation, providing the values of their inductance. There are chokes available on the market described in a series of types; hence, providing the designated inductance values as used by the authors [
22] seems to be insufficient. Grading of the emitted light flux described in publications [
26,
27,
28,
29] and in accordance with regulations [
30,
31,
32,
33,
34] causes changes in the value of capacitive reactive power flows, which necessitates the use of choke batteries with a system for switching them on.
2. The Problem of Reactive Power in Lighting Installations
Energy efficiency is one of the overarching slogans that drive the development and implementation of EU directives and regulations. One such regulation is Directive [
35] laying down general principles for establishing ecodesign requirements for energy-using products. This provision applies to electricity-based products, which account for a large share of the EU’s natural resource and energy consumption. The essence of the analyzed regulation is to improve energy efficiency, where one of the available options is better use of electricity by end users. Electricity demand is one of the fastest growing categories of energy end use and is expected to increase in the coming years.
Reactive power in alternating current systems and circuits is a quantity that describes the pulsation of electric energy between the components of an electric circuit. This energy is necessary for the functioning of, among others, electrical machines but also electronic systems. It is not converted into useful work or heat. For sinusoidal waveforms, the reactive power is presented by the formula:
where:
—reactive power [var],
—effective value of voltage [V],
—effective value of current [A],
—phase shift between voltage and current.
In the case of a purely resistive load, the phase angle between voltage and current is 0°. In the case of a purely inductive load, the phase angle between voltage and current is 90°. However, in the case of a purely capacitive load, the phase angle between voltage and current is −90°. Due to their very complex structure, most devices (loads) that are powered from a single-phase 230 V network become capacitive or inductive loads (or their type may change with a change in the operating mode). Such loads are reactance loads. These are most often electronic systems that cooperate with various devices, including: with lighting fixtures, including LED.
The regulations regulating the electrical parameters of LED converters specify only the minimum values of power factors depending on the power range of the receiver
(
Table 1). This factor is called the phase shift factor DF in current regulations [
36,
37,
38].
Figure 1 gives a graphical interpretation of the phase shift factor DF.
This definition correctly suggests the inductive or capacitive nature of, among others, electrical energy receivers such as lighting fixtures. Determining the value of the power factor of lighting sources and fixtures in the manner given in the table, with the possible inductive or capacitive nature of the receiver, may mean a negative or positive value of the coefficient determining the ratio of reactive power to active power of the circuit
.
where:
P—active power [W],
—reactive power [var],
—phase shift between voltage and current.
Possible values of the
coefficient are presented in
Table 2.
In the power systems of various countries around the world [
15], different permissible ranges of power factors
, and therefore also
, are adopted. The values of the power factor
, if exceeded, that determine the fee for the use of reactive energy in Poland are in the range (0.00; 0.40).The situation is similar in Belgium, France, Latvia and Romania. In the power systems of Italy, Bulgaria, Iceland and Luxembourg, these values are in the range (0.00; 0.48). In the Netherlands they are in the range (0.00; 0.75). However, in the former Yugoslav countries: Bosnia–Herzegovina, Croatia, North Macedonia, Serbia and Slovenia, the value of
should be in the range (0.00; 0.33). In Spain and Portugal, this range is (0.00; 0.29). As you can see in the description presented, no fees apply only to recipients of passive inductive energy.
In some countries, fees are charged for values outside the range; in the UK, there is a range (0.43; −0.20), and in California in the USA, there is a range (0.48; −0.33). In some countries, several thresholds (ranges of coefficient values during energy consumption) with progressive rates for reactive energy have been adopted. The method of determining rates for the use of reactive power may also depend on the supply voltage levels depending on the amount of power consumption, capacity, time of consumption or location of the billed entity. Additionally, the methods of calculating fees are varied. In some countries, fees are charged on the entire reactive energy consumption in [varh] (e.g., Estonia, Ireland, Lithuania), while in others, the fee depends on the active power and the value of the coefficients: contractual and measured (Poland). As presented above, the value of the coefficient for the designated power of a lighting circuit used in Poland should be in the range (in the case of capacitive luminaires, it is necessary to use compensating chokes). The methodology for limiting reactive power flows in other countries is similar, but other limit values will be adopted.
3. Analysis of the Operation of Road Lighting Fixtures with LED Sources
In modern solutions, the LEDs (power) are supplied from the 230 V/50 Hz network using appropriately designed switching power supplies using specialized integrated circuits. These types of power supplies have high energy efficiency >80% and are characterized by power factor values . Thanks to the passive PF correctors used, the power supplies are resistant to electromagnetic (conducted) interference and are not themselves a source of interference sent to the power supply network. Unfortunately, lighting devices still use PFC-free power supplies. This is a version of the power supply that is theoretically banned in the EU.
As presented in
Section 1, lighting receivers only have permissible values of phase shift coefficients
(
) specified in the regulations. The authors are not aware of any regulations that would include permissible values of
coefficients for lighting fixtures or power supplies used in them. The design of switching power supplies means that they are capacitive in nature, and because they meet the requirements for the
value (
), their designers and manufacturers do not attach importance to compensating reactive power directly in the light source–power supply system. The existence of such a requirement would eliminate the problem of the need to compensate for reactive power in lighting installations.
Table 3 shows selected electrical parameters of lighting fixtures with LED sources equipped with capacitive power supplies.
The luminaires are equipped with a “fluid” control system implemented via GSM network control. The converter system cooperating with the LED matrix changes its supply current values and, consequently, the value of the emitted light flux. The obtained results of measurements of the electrical parameters of the luminaire with a rated power of 41.5 W on the test stand confirm that the expected decrease in the active power of the entire luminaire also causes a change in the parameters
,
and
. These changes are shown in the form of characteristics of the values
P,
,
and
as a function of time in
Figure 2 and
Figure 3.
As can be observed in
Figure 2, the value of active power P decreased from 41.00 W to 2.00 W, and reactive power
varied in the range from −3.28 var to −10.74 var. In the case of the
and
coefficients presented in
Figure 3, their values varied accordingly: for
the range was from 0.97 to 0.4, and for
from −0.265 to −2.4.
Then, the electrical parameters of the same luminaires were determined with individual power reduction implemented by the manufacturer in the converters of each luminaire. The power reduction was carried out according to the proposed schedule:
No power reduction from turning on the lighting until 7 p.m. and from 6 a.m. until turning off the lighting;
Reduction of specific power to 80%—4 h a day: from 7 p.m. to 9 p.m. and from 4 a.m. to 6 a.m.;
Reduction of specific power to 60%—4 h a day: from 9 p.m. to 11 p.m. and from 2 a.m. to 4 a.m.;
Reduction of specific power to 40%—3 h a day: from from 11 p.m. to 12 p.m. and from 12 p.m to 2 a.m.;
The control scheme is shown below in
Figure 4.
Lighting installations are switched on using light sensors implemented in each lighting circuit. The need to use these sensors results from changes in sunrise and sunset times.
Table 4 below shows data for 4 characteristic days a year for a town located in central Poland.
Determining the lighting operation time required analyzing all sunset and sunrise hours. After its determination, it was determined that the total average operating time of lighting fixtures is 4150 h per year and is consistent with the value specified in the regulations [
39]. The total saving predicted using the control diagram presented in
Figure 4 may be approximately 27% [
40].
Table 5 shows the rated and measured selected values of electrical parameters for three selected lighting fixtures with power-reducing LED sources.
The measurements were carried out in laboratory conditions at a station containing: a reference voltage source, a system for measuring electrical parameters and energy quality, and fixtures with LED sources. The results of the active power values
and the corresponding values of power factors depending on the control level are shown in
Figure 5 and
Figure 6. Such characteristics should be developed by manufacturers of lighting fixtures intended for lighting installations [
28,
29], in which it is planned to control the value of the emitted luminous flux.
4. Audit of Road Lighting Installations
The system power (
P) is calculated from the sum of the active power of the light sources, control gear and any other electrical devices (light point control units, switches, photovoltaic cell, etc.) that are directly related to the lighting of the area to be illuminated and installed to operate or adjust the installation. The system power (
P) should be calculated for the entire lighting installation or a representative section used during lighting design according to the formula:
where:
—total power of the lighting installation system or its representative part;
—active power of the kth lighting point (light source, fixture, any other devices such as the lighting point control unit, switch or photocell and component that are associated with the lighting point and necessary for its operation);
—total active power of all devices not included in but necessary for the operation of the road installation, such as a remote switch or photocell, centralized light flux controller or centralized management system;
—the number of lighting points associated with the lighting installation or representative section, whichever is used in the calculation.
If the system power is calculated for a representative area, the total active power of the
should be proportional to the number of luminaires used to illuminate the area (luminaires powered by the devices represented by the
). A road lighting audit should include among others [
28,
29]:
Analysis of the existing condition based on the inventory.
Selection of new luminaires taking into account the requirements based on road categories with the indication of at least three different and independent luminaire manufacturers.
Comparison of investment project options in relation to energy efficiency:
option 1—replacement of existing luminaires (luminaires without power reduction);
option 2—replacement of existing luminaires (luminaires with power reduction);
option 3—replacement of the entire installation including the control (luminaires with dynamic power reduction).
Tabular summary of the existing state, the planned state, ecological analysis before and after modernization.
Photometric calculations–lighting design.
Detailed analysis of the results of road and street lighting measurements in relation to the photometric calculations made using the computer method.
Catalog cards and test reports of proposed lighting fixtures.
Technical and technological analysis of the proposed lighting fixtures.
Analysis of forecasted reactive power flows, taking into account its compensation at control points.
Based on the audit, the authors of the article:
The audit was prepared on the basis of the methodology specified in [
39] regarding the detailed scope and method of preparing an energy efficiency audit and methods of calculating energy savings. The audit included improvements enabling energy savings through the use of energy-saving lighting fixtures with LED sources. An inventory was made and a vision was made of the location and assessment of the condition of lighting fixtures in 24 circuits. The inventory included an assessment of the technical condition of the lighting fixtures in use. The actual status was checked and later compared with the available reports. The arrangement of poles and fixtures was also checked. A total of 979 luminaires with discharge sources with a rated power of 70W were inventoried. Photometric projects and analysis of lighting standards were also carried out to ensure appropriate conditions on the roads.
Figure 7 shows only a fragment of the complex lighting installation.
Based on the measurement data of the luminaires, the values of active and reactive powers in the analyzed circuits were determined. The results of the analysis taking into account control are presented in
Table 6 and
Table 7.
The chokes were implemented in switchboards supplying individual lighting circuits in accordance with the schematic diagram shown in
Figure 8.
Based on the measured values of selected parameters of electrical lighting fixtures, compensating chokes were selected in the analyzed circuits and the values of the obtained
coefficients were determined.
Table 8 and
Table 9 present the measured values of reactive power in the tested lighting installations for selected compensation chokes and the values of the determined
coefficients in these installations.
As is commonly known, connecting compensation chokes means introducing a resistive-inductive receiver into the installation, characterized not only by useful inductive reactive power but also by active power defined as active power losses
. A summary of the resistance values of
chokes and their rated active power losses is presented in
Table 10.
After selecting the compensation chokes, the percentage power losses were determined in the analyzed 24 lighting circuits.
Figure 9 graphically shows the percentage increase in active power consumption in selected lighting circuits marked with Roman numbers (II, IX, XIV, XVI and XIX).
As can be seen from the diagram presented, the increases in active power are the highest when the lighting fixtures are controlled at 40%. Active power losses resulting from connecting chokes in lighting circuits ranged from 0.56% to 2.82% depending on the power level of the analyzed circuit and the control level. This means small losses of active power in relation to the fees charged by electricity distributors for capacitive reactive power [
15].
The constantly growing number of non-linear receivers, including those in lighting installations, causes increasing problems with distortion of current waveforms. Moreover, in the power supply systems for LED luminaires, there is a problem of maintaining the parameters determining the quality of electricity required by regulations [
41]. Unfortunately, the analyzed luminaires contain power supplies that cause distortions in the supply currents.
Figure 10 graphically shows the values of individual harmonics of the supply current of luminaires operated in circuit No. V after determining the operating parameters for control: 100% and with reductions of 80%, 60% and 40% [
39,
40,
41]. The aquamarine bars indicate the permissible values of harmonics in the supply current of
luminaires.
Current distortions are mostly smaller (harmonics numbers 2, 3, 5, 7 and 27–39) than those permitted by the currently applicable regulations [
40,
41]. Unfortunately, in the case of harmonics numbers 9 to 25, the permissible values are exceeded. From the point of view of the selection and operation of compensation chokes, the values of the 3.5th and 7th harmonics [
40] are important as they have the greatest impact on determining the choke parameters.