Analysis of a CO2 Transcritical Refrigeration Cycle with a Vortex Tube Expansion
Abstract
:1. Introduction
2. Materials and Methods
2.1. CO2 Transcritical Refrigeration System with an Expansion Valve (i.e., a Basic System)
2.2. CO2 Transcritical Refrigeration System with a Vortex Tube (i.e., the Proposed System)
2.3. Mathematical Models and Assumptions
- The heat transfer effectiveness of the desuperheater is 0.8;
- The CO2 compressor isentropic efficiency is 0.8.
3. Results and Discussions
3.1. Effects of Vortex Tube Characteristics and Thermodynamic Parameters on COP Improvement
3.1.1. Results
3.1.2. Discussions
3.2. Regression of Optimal Discharge Pressure Correlation for the Proposed System with a Vortex Tube and a COP Improvement Investigation under Optimal Discharge Pressure
- The cold mass fraction y is 0.5;
- The vortex tube isentropic efficiency ηn is 0.8;
- The water inlet temperature of the desuperheater Twi is 25 °C.
4. Conclusions
- The COP of the proposed system with a vortex tube was higher than that of the basic system with an expansion valve;
- The critical influence factors of COP improvement were the inlet temperature of the vortex tube (i.e., the outlet temperature of the gas cooler) and the discharge pressure. The higher the inlet temperature of the vortex tube, the higher COP improvement was. The lower the discharge pressure, the higher COP improvement was. When the inlet temperature of the vortex tube was 45 °C, the discharge pressure was 9 MPa, and the COP increased by 33.7%;
- The higher the isentropic efficiency of the vortex tube, the higher the COP improvement was. COP improvement could be up to 11.6%;
- The more the cold mass fraction of the vortex tube, the higher the COP improvement was. When the cold mass fraction was 0.8, COP improvement was 11.5%;
- The lower the evaporation temperature, the higher COP improvement was. When the evaporation temperature was −5 °C, COP improvement was 9.2%;
- The lower the inlet water temperature of the desuperheater, the higher COP improvement was. When the inlet water temperature of the desuperheater was 10 °C, COP improvement was 12.0%;
- Under optimal discharge pressures, COP improvement increased gradually with an increase in vortex tube inlet temperature and decreased slightly with an increase in evaporation temperature. When the vortex tube inlet temperature was −10 °C, and the evaporation temperature was 45 °C, COP improvement was 7.1%.
Author Contributions
Funding
Acknowledgments
Conflicts of Interest
Nomenclature
English letters | |
COP | coefficient of performance |
COPb | COP of the basic system |
COPv | COP of the proposed system |
h | specific enthalpy (kJ/kg) |
Imcop | COP improvement of the proposed system over the basic system (%) |
P | discharge pressure (MPa) |
T | temperature (°C) |
x | quality |
y | cold mass fraction |
m | mass flow rate (kg/s) |
Greek letters | |
ε | heat exchanger effectiveness |
η | isentropic efficiency |
Subscript | |
b | basic system with expansion valve |
c | compressor or cold end of vortex tube |
H | hot end of vortex tube |
s | isentropic process |
n | vortex tube nozzle |
wi | water inlet of desuperheater |
v | the proposed system with vortex tube expansion |
opt | optimal |
References
- Maina, P.; Huan, Z. A review of carbon dioxide as a refrigerant in refrigeration technology. S. Afr. J. Sci. 2015, 111. [Google Scholar] [CrossRef]
- Sawalha, S.; Karampour, M.; Rogstam, J. Field measurements of supermarket refrigeration systems. Part I: Analysis of CO2 trans-critical refrigeration systems. Appl. Therm. Eng. 2015, 87, 633–647. [Google Scholar] [CrossRef]
- Robinson, D.M.; Groll, E.A. Efficiencies of CO2 trans-critical cycles with and without an expansion turbine. Int. J. Refrig. 1998, 21, 577–589. [Google Scholar] [CrossRef]
- Li, D.; Back, J.S.; Groll, E.; Lawless, P.B. Thermodynamic analysis of vortex tube and work output expansion devices for the CO2 trans-critical cycle. In Proceedings of the Fourth IIR-Gustav Lorentzen Conference on Natural Working Fluids at Purdue, Lafayette, IN, USA, 25–28 July 2000; pp. 433–440. [Google Scholar]
- Groll, E.A.; Kim, J.-H. Review Article: Review of recent advances toward CO2 trans-critical cycle technology. HVAC R Res. 2007, 13, 499–520. [Google Scholar] [CrossRef]
- Bodys, J.; Smolka, J.; Banasiak, K.; Palacz, M.; Haida, M.; Nowak, A.J. Performance improvement of the R744 two-phase ejector with an implemented suction nozzle bypass. Int. J. Refrig. 2018, 90, 216–228. [Google Scholar] [CrossRef]
- Sawalha, S.; Piscopiello, S.; Karampour, M.; Manickam, L.; Rogstam, J. Field measurements of supermarket refrigeration systems. Part II: Analysis of HFC refrigeration systems and comparison to CO2 trans-critical. Appl. Therm. Eng. 2017, 111, 170–182. [Google Scholar] [CrossRef]
- Yamaguchi, H.; Zhang, X.R. A novel CO2 refrigeration system achieved by CO2 solid–gas two-phase fluid and its basic study on system performance. Int. J. Refrig. 2009, 32, 1683–1693. [Google Scholar] [CrossRef]
- Shamsoddini, R.; Khorasani, A.F. A new approach to study and optimize cooling performance of a Ranque–Hilsch vortex tube. Int. J. Refrig. 2012, 35, 2339–2348. [Google Scholar] [CrossRef]
- Kandil, H.A.; Abdelghany, S.T. Computational investigation of different effects on the performance of the Ranque–Hilsch vortex tube. Energy 2015, 84, 207–218. [Google Scholar] [CrossRef]
- Chen, J.; Zeng, R.; Zhang, W.; Qiu, L.; Zhang, X. Numerical analysis of energy separation in Ranque-Hilsch vortex tube with gaseous hydrogen using real gas model. Appl. Therm. Eng. 2018, 140, 287–294. [Google Scholar] [CrossRef]
- Chang, S.W.; Yu, K.C. Thermal performance of reciprocating two-phase thermo-syphon with nozzle. Int. J. Therm. Sci. 2018, 129, 14–28. [Google Scholar] [CrossRef]
- Han, X.; Li, N.; Wu, K.; Zhang, Z.; Tang, L.; Chen, G.; Xu, X. The influence of working gas characteristics on energy separation of vortex tube. Appl. Therm. Eng. 2013, 61, 171–177. [Google Scholar] [CrossRef]
- Manimaran, R.; Lund, H.; Kaiser, M.J. Computational analysis of energy separation in a counter-flow vortex tube based on inlet shape and aspect ratio. Energy 2016, 107, 17–28. [Google Scholar] [CrossRef]
- Liao, S.M.; Zhao, T.S.; Jakobsen, A. A correlation of optimal heat rejection pressures in CO2 trans-critical cycles. Appl. Therm. Eng. 2000, 20, 831–841. [Google Scholar] [CrossRef]
- Lemmon, E.W.; Huber, M.L.; McLinden, M.O. REFPROP, NIST Standard Reference Database 23, v.9.1; National Institute of Standards: Gaithersburg, MD, USA, 2013.
Parameters | Reference Value | Variation Range |
---|---|---|
Vortex tube inlet temperature T3, °C | 40 | 25–45 |
Evaporation temperature T6, °C | 0 | −10–10 |
Vortex tube isentropic efficiency ηn | 80% | 0%–100% |
Cold mass fraction y | 0.5 | 0.3–0.8 |
Water inlet temperature of the desuperheater Twi, °C | 25 | 10–35 |
Discharge pressure P, MPa | 9 | 8–12 |
© 2019 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (http://creativecommons.org/licenses/by/4.0/).
Share and Cite
Liu, Y.; Sun, Y.; Tang, D. Analysis of a CO2 Transcritical Refrigeration Cycle with a Vortex Tube Expansion. Sustainability 2019, 11, 2021. https://doi.org/10.3390/su11072021
Liu Y, Sun Y, Tang D. Analysis of a CO2 Transcritical Refrigeration Cycle with a Vortex Tube Expansion. Sustainability. 2019; 11(7):2021. https://doi.org/10.3390/su11072021
Chicago/Turabian StyleLiu, Yefeng, Ying Sun, and Danping Tang. 2019. "Analysis of a CO2 Transcritical Refrigeration Cycle with a Vortex Tube Expansion" Sustainability 11, no. 7: 2021. https://doi.org/10.3390/su11072021
APA StyleLiu, Y., Sun, Y., & Tang, D. (2019). Analysis of a CO2 Transcritical Refrigeration Cycle with a Vortex Tube Expansion. Sustainability, 11(7), 2021. https://doi.org/10.3390/su11072021