1. Introduction
About 50% of the consumed energy in many regions of the world are attributed to heating, ventilation, and air conditioning (HVAC) systems, especially in hot tropical countries such as Singapore, Saudi Arabia, Malaysia, etc. [
1]. Conventional cooling systems, such as split AC units and chillers installed in the basement of buildings, are commonly used to satisfy cooling demands, globally [
2]. On the other hand, a well managed district cooling (DC) technique, to supply air conditioning services to a network of buildings in cities, is 50% more efficient than conventional techniques. However, researchers have developed several methods to optimize district energy performance in terms of higher system efficiency, lower operation cost, integrating cleaner fuels for GHG reduction, etc. [
3,
4].
In recent times, the integration of storage systems technologies into DC setups has gained worldwide implementation. In various DC facilities, thermal energy storage (TES) systems have been installed to optimize the operation of DC plants and meet the fluctuating demand for the supply of chilled water for air conditioning purposes. Although the vapor compression chiller (VCC) accounts for about 40% of the total electricity supplied to the DC plant [
5], studies have shown that integrating the functionalities of VCC and TES into the DC plant leads to a 35% reduction in electricity consumption, compared to conventional DC systems without TES. Different electricity tariffs during various times of the day benefit the integration of TES technology. The TES tank assists with load levelling and peak shaving. Peak load shaving is achieved by charging the TES tanks during the off peak period (at night), with the VCC operating at full capacity when it exhibits maximum performance. The stored chilled water satisfies the district cooling load during the day (on peak), while the VCC systems are shut down. This setup allows the cooling technologies in the central cooling station to be sized closer to the average load than the peak load. In addition, the electricity used for pumping water through the district network and operating electricity based chillers can be shifted to off peak hours.
Several qualitative and quantitative methodologies have been developed and adopted to assess the environmental performance of energy systems. The classified quantitative or qualitative techniques commonly used include environmental benchmarking; a simplified LCA checklist; a material, energy, toxic emissions matrix; life cycle assessment (LCA); etc. However, amongst these options, the LCA methodology stands out as the most preferred tool for analyzing the environmental performance of energy intensive systems [
6,
7].
A few notable reviews are available addressing the environmental impact implications of chiller systems. The available literature reviews of the chiller systems are addressed below.
Bukoski et al. [
8] used the LCA methodology to assess the environmental impact of installing a solid hybrid cooling system in a 15,000-seat Thai stadium. The baseline research compares a solar powered absorption chiller system against an electric powered vapor compression chiller system. The solar system saved around 26–40%, in terms of environmental effect, compared to the other two systems.
Using the life cycle assessment (LCA) approach, Sonia Longo et al. [
9] investigated the life cycle energy and environmental performance of a small solar space heating and cooling (SHC) system, with an adsorption chiller in different European locations. The new system was compared to the old one, which used a vapor compression unit. According to the study, the conventional system outperforms the SHC system over its entire life cycle (10 years). Furthermore, while the production phase of the SHC system has the greatest impact on the life cycle phase, the operating phase is the most crucial.
Hampo et al. [
5] used a gate to gate LCA methodology to analyze the environmental performance of four electric chillers. The authors investigated the environmental performance of the chiller systems based on the composition of the 2020 Malaysia’s fuel mix and the proposed optimized electricity mix by 2030. The authors recorded an average of a 33% reduction across all the selected environmental categories, as the optimized fuel mix option (2030) was introduced into the electricity mix.
Nan Xie et al. [
10] evaluated the environmental advantages of combining a LiBr/H
2O absorption chiller and Kalina cycle (KC) with an individual KC, using the LCA approach. They discovered that energy production during the operation stage is a more environmentally friendly option. Furthermore, the combined system displayed a significantly higher number of ecological indexes compared with the individual KC, increasing by 46.17%.
To analyze the influence of energy systems on environmental profiles, Catrini et al. [
11] presented a combined technique based on thermoeconomics and life cycle assessment. This approach was used to assess a water cooled scroll compression chiller built to cool a big office building. The authors used an IMST-ART simulator to model the operation of the chiller system and compare different chiller designs to their associated environmental improvements. According to the authors, the use phase has the most significant influence on the environment. They also claimed that the electricity production mix utilized to power the chiller (the Italian grid energy mix) presented more substantial trade offs between efficiency and cost.
In separate research, K. Almutairi et al. [
12] reported on an LCA and economic analysis of a VCC placed in residential structures in Saudi Arabia. According to the findings, the use phase has the most significant environmental effect. In addition, the quantity of the effects assessed was impacted by the type of main fuel utilized to power the facility. According to the government, installing and using more energy efficient air conditioner systems is always advantageous, economically and environmentally.
In the study of Emillo et al. [
13], the LCA methodology was used to evaluate the global warming potentials of two 500-ton capacity water chiller systems, focusing on the manufacturing stage, one with an oil lubricated bearing system and the other with a magnetic bearing system. The study found that over 90% of the emissions from the water chiller system’s operating stage are due to power consumption, with the most significant emissions coming from material extraction and production. As a result, magnetic bearing systems recorded reduced GHG emissions, more than oil lubricated bearings. However, according to sensitivity and uncertainty analysis, both electrical energy generation factor and chiller efficiency NPLV can strongly affect GHG emissions, though a more significant reduction in emissions can occur when the power supply for chillers is mixed with clean energy resources.
The energy consumption and emissions related to the operation of a chiller and other chiller plant components installed in a university building powered by fossil fuels were examined by Saidur et al. [
14]. The authors estimated the emissions and energy savings associated with incorporating variable speed drives (VSDs) into chillers and motors in their study. They also stated that integrating VSDs into chiller systems resulted in a 60 percent reduction in speed and a 2,426,769 kg reduction in total carbon emissions.
The review of the life cycle analysis of the studies conducted in this project includes assessing the environmental impacts resulting from the life cycle energy and material usage of various chiller systems. However, despite the range of modelling options available in the literature, several gaps exist. From the general overview of the literature, some research gaps are drawn.
First, other LCA studies on HVAC systems are mostly carried out for European, American, and China case scenarios. A probable reason for this can be due to the relative presence of stricter environmental laws and higher energy costs in these countries. On the other hand, similar research for countries in southeast Asia with tropical weather conditions, such as Malaysia, is extremely rare to find. Since LCA results are largely affected by geographical location, energy source, and building types, this raises the need to conduct more case study research that reflects the peculiarity of Malaysia (and southeast Asia in general) in terms of its temperate weather condition, cooling demands and commercial grid mix.
Secondly, the VCC analyzed in most case studies operated separately, in various building attachments, to satisfy the cooling demands. However, no available research addresses integrating the functionalities of a VCS in a DC plant, especially as it involves pairing the functionalities of the TES and VCC in optimizing the economic and environmental performance of the DC plant.
Thirdly, only a few studies were found to evaluate or optimize the VCS by combining two aspects, addressing the energy and environment. Therefore, a methodology that assesses the life cycle energy and environmental performance of VCS systems is desirable.
Based on these gaps, mentioned above, the primary objectives of this paper are listed below;
To develop a cradle to grave LCA model to investigate the environmental impact of a vapor compression system integrated into a DC plant.
To identify several design options to reduce the environmental impact of the vapor compression system during the operation phase.
To estimate the environmental gains resulting from the integration of TES tanks in a DC setup, compared to the conventional system designs.
This study provides an in depth version of the previous work by Hampo et al. [
5], however, this document adds depth to that content. For example, Hampo et al. [
5] did not conduct a cradle to grave life cycle impacts assessment, as their model was limited only to the gate to gate approach. Secondly, their research did not include TES tanks in their research scope. Thirdly, the use of LCA software, in this study, allowed for a wider variety of impact categories to be assessed, compared to the just four impact categories considered in the study of Hampo et al. Lastly, this study assessed the possibility of integrating several optimized system designs into the case study, to estimate the environmental reaction. In contrast, Hampo et al. [
5] only addressed the environmental implications of switching the 2020 Malaysia fuel mix with the proposed 2030 fuel mix.
3. Results and Discussion
In fulfilling the objectives of this project, the results of the environmental sustainability assessments of the VCS are presented and discussed. This includes identifying the most environmental pathway in terms of the influence of the material flow, electricity mix, and system configuration.
3.1. Life Cycle Inventory Result
Figure 7 shows the monthly contribution of each VCC to the generation of chilled water for the DC networks. According to the analysis, the months with the largest and lowest cooling demands are April and June. The impact of climatic weather conditions on refrigeration demands is demonstrated by the average monthly temperature trend on the figure. This demonstrates that, as the globe continues to warm, the need for air conditioning will continue to rise. However, this analogy is inconsistent throughout the year, as November and December experienced the lowest temperature recorded higher cooling load. This phenomenon can best be explained as a result of the end of year festivities which causes increased human activities observed during these times in Malaysia.
The results presented in
Figure 7 indicate that VCC A and B consumed more electricity than VCC C and D, in their overall operation. The total estimate of energy used by the VCS system is estimated to be 17,412,439,194 kWh.
Figure 7 shows the percentage contribution of specific VCC systems to meeting monthly and annual cooling demands, respectively. From the analysis as presented in the graph, VCC A and B fulfilled about 79 percent of the annual cooling load, while VCC C and D handled the remaining 21 percent throughout the systems annual use.
Figure 8 shows the VCC systems’ estimated monthly EP consumption in producing chilled water for the DC networks. April and June, as expected, consumed the most and least electrical energy during the research year, in proportion to their consumption rate over time.
Due to the performance degradation experienced by the four installed VCC systems over time, the COP of the oiled centrifugal chiller tends to reduce with time. According to the study of Ref. [
34], conventional oiled compressors, such as in VCC systems, are prone to significant performance degradation resulting from excessive bearing wear, oil impurities, rotor tip contact, poor system maintenance, and other factors. Refs [
30,
35] suggested a 10% loss in efficiency of the VCS system after every five years. This assumption was applied to the case study to determine the performance degradation to energy consumption over a lifetime period of 25 years. The result of this analysis is presented in
Figure 9.
As shown in
Figure 9, after an operation period of 10 years, the percentage increase in performance degradation would amount to about 21.4%. However, this percentage would increase progressively from 33.1% through 46.4% to 61.1% after an operation of 15, 20, and 25 years, respectively. By implication, the subsequent performance degradation is observed to increase progressively, to 11.4%, 11.7%, 13.3%, and 14.7% after 10, 15, 20, and 25 years, respectively. This also implies that, after a period of 25 years of usage, the performance efficiency of the system would have decreased to about 40% of the initial efficiency value. However, such degradation is minimal in magnetic nonoiled centrifugal chillers, and the efficiency is almost constant throughout their lifetime usage [
13].
3.2. Result of the Life Cycle Impact Assessment
In understanding the dynamic trend of the life cycle environmental impact of the VCS, the result of the carbon footprint per functional unit of 1 Ton of refrigeration is given as 0.72 kg CO
2 eq/RTh. The result of the contribution of each process to the overall carbon footprint of the LCA analysis is presented in
Table 7. From the result, about 98% of the overall carbon footprint per FU is caused by the indirect emission from commercial electricity usage to drive the VCS during its 25 years of operation.
In
Table 8, the proportion of the indirect GHG emissions to the overall environmental footprint is presented. From the result, about 90% of the recorded GHG emission is occupied by carbon dioxide gases. This is mainly due to the high proportion of fossil fuels (nonrenewable energy) present in the country’s (Malaysia) commercial electricity mix. This is closely followed by methane gas (recording about 3%), primarily due to fossil and nonfossil fuel usage.
The LCIA result per FU of the selected impact categories is presented in
Figure 10. From the result, GWP recorded the highest impact, of about 60% of the overall result. This is followed by human toxicity (HT) and fossil depletion (FD), with 19% and 18% impact contributions. The result of other selected impact categories had little or no significance to the overall result. The high GWP recorded is due to the nature of the GHG emission, largely composed of CO
2 gases, as revealed in
Table 8 above.
Figure 11 indicates the contribution of different life cycle stages to the selected impact categories. The major contributor is the operation phase, contributing an overall average of 95% in all categories, with human toxicity (HT) and freshwater ecotoxicity (FET) recording the highest (98.6%) and lowest (91.6%) readings, respectively. The strong influence of the operation phase on the LCAI result is primarily linked to the high energy consumption and the high ratio of fossil fuel in the grid commercial mix used to drive the plants. On the other hand, the manufacture phase contributes an average of 0.15%, with the highest and lowest contribution of 0.26% and 0.05% to the photochemical oxidant formation (POF) and ozone depletion (OD), respectively. Likewise, the raw material phase contributes an average of 4%, with the highest and lowest contribution, of 8.12% and 1.26%, to the ozone depletion (OD) and human toxicity (HT), respectively. Finally, the disposal/recycling phase contributes an average of 0.38%, with the highest and lowest contribution, of 1.7% and 0.0013%, to the freshwater ecotoxicity (FET) and water depletion (WT). The result of the overall impact of the phases is presented in
Figure 12. From the result, the operation phase accounted for the highest environmental impact (about 98%), with other life cycle phases making minor or insignificant contributions.
3.3. Model Optimization: Comparison of Scenarios (Scenarios A, B, and the Base Case)
Since the use phase has shown to make the most significant contribution to the system’s environmental impacts, measures targeted at lowering energy consumption and utilizing cleaner fuels during VCS operation may improve the whole system’s environmental profile.
Keeping other variables constant,
Figure 13 presents the environmental implications of switching countries’ commercial electricity mix and upgrading the plant compressors in the system use phase. The result indicates that integrating the Sweden commercial electricity mix produced the most sustainable option of the five considered scenarios. The carbon footprint per refrigeration for the Sweden fuel mix option recorded a 0.04 kg CO
2eq/RTh, occupying just 6% of the base case carbon contribution. This implies that a 94% decrease in the environmental footprint, to the base case, is achieved by adopting the Sweden mix. This is followed by the Singapore grid mix option, which records a carbon footprint per refrigeration of 0.43 kg CO
2eq/RTh, which is about 60% of the carbon contribution of the base case scenario. This implies that integrating the Singapore grid mix option will result in an estimated 40% decrease in the environmental footprint of the base case. In using energy distributed and generated solely from natural gas, the carbon footprint per refrigeration of 0.47 kg CO
2eq/RTh is recorded, which is about 65% of the carbon contribution of the base case and a 35% decrease in the environmental footprint to the base scenario.
This result indicates the significant influence the country’s fuel mix has on the overall environmental impact of energy systems, stressing the need for countries (e.g., Malaysia) to reduce the presence of nonrenewable energy sources, while increasing the ratio of clean energy in the commercial grid electricity mix. This finding also correlates with the author’s previous research [
5], which reported a 33% reduction across all selected environmental impact categories using the proposed 2030 Malaysia optimized electricity mix suggested by Rina et al. [
36].
In assuming the base scenario while improving the design of the electric chiller component by incorporating a more efficient compressor (oilless magnetic compressor), a 0.16 kg CO2eq/RTh of the carbon footprint per refrigeration is recorded. This accounts for about 22% of the carbon contribution of the base case and a 78% decrease in the environmental footprint to the base scenario.
In
Table 9, the result of the indirect GHG emissions to the overall environmental footprint for integrating the Singapore mix. From the result, about 60% of the recorded GHG emission is occupied by carbon dioxide gases, representing about a 30% decrease from the result recorded for the base case study. An increased allocation of renewable energy sources in Singapore’s grid mix compared to the base case resulted in this decrement.
The result presented in
Table 10 shows the contribution of indirect GHG emissions to the overall environmental footprint for integrating the Sweden commercial electricity mix to the base case. From the result, about 30% of the recorded GHG emission is occupied by carbon dioxide gases, representing about 60% reduction from the result of the base scenario. This reduction is attributed to the higher proportion of renewable energy sources in the country’s grid mix than the base case scenario.
The result presented in
Table 11 shows the contribution of the indirect GHG emissions to the overall environmental footprint for integrating natural gas to generate electricity for the base case. From the result, about 60% of the recorded GHG emission is occupied by carbon dioxide gases, representing about a 30% reduction from the result of the base scenario.
The result presented in
Table 12 shows the contribution of the indirect GHG emissions to the overall environmental footprint for installing the oilless magnetic compressor to the electric chiller compartment. From the result, about 60% of the recorded GHG emission is occupied by carbon dioxide gases, representing about a 26% reduction from the result of the base scenario. This phenomenon is due to the reduction in energy consumed by the chiller system as a result of integrating a more stable and efficient nonlubricating compressor system.
The LCIA result per refrigeration based on the selected impact categories of all the considered scenarios is presented in
Table 13. The total of their environmental impacts per refrigeration for the base case, Singapore, Sweden, natural gas, and the oilless chiller options are given by 1.17, 0.63, 0.09, 0.68, and 0.26, respectively. The Singapore, Sweden, natural gas, and oilless chiller options all had GWP as the highest impact category, with an average of 60% impact contribution. This is followed by fossil depletion (FD) and human toxicity (HT), with an average contribution of 21% and 16%, respectively. The result of other selected impact categories had little or no influence on the overall result. However, the Sweden and oilless chiller options recorded a lower FD contribution of 9% and 18% and a higher HT contribution of 39% and 19%, respectively.
The percentage change of all considered scenarios to the base case study is presented in
Table 14. In analyzing the results, the case of the Sweden mix again provided the most sustainable option with an average of 81% environmental savings across all selected impact categories, having its highest (96%) and lowest (49%) impact savings on GWP and WD, respectively. This is followed by the oilless magnetic compressor design scenario, with an average environmental savings of 76% across all selected impact categories, having its highest (78.38%) and lowest (72.84%) impact savings on HT and FET, respectively. This is followed by the Singapore and natural gas case scenarios, with an average of 57% and 32% environmental savings. However, the Singapore mix recorded its highest savings (about 92%) on HT, while it made an extra 5% to the base case on the OD impact category. On the other hand, the natural gas case scenario recorded its highest environmental savings of 87% on HT and made an extra 69% to the base case on the OD impact category.
3.4. Comparison of the Base Study with Literature
A few studies on the LCA of VCC systems have been carried out in the literature [
11,
13]. However, owing to numerous assumptions, such as plant capacity, use time, refrigeration outputs, load factors, longevity, and geographic locations where VCC systems are built, a direct comparison of the various outcomes is problematic. In addition, various background data, such as national commercial electricity blends expected for VCS operation, result in different outcomes.
In this section, a comparison of the study conducted by Byrd et al. [
13] with the case study is conducted, to analyze the environmental gains resulting from integrating TES tanks into the operation of a DC system.
A VCC system placed directly in commercial buildings in the United States is examined in the study by Byrd et al. [
13]. The study’s functional unit is a 500-ton chiller that can cool a 150,000-square-foot office building. The cradle to cradle LCA, which encompasses raw material extraction, production, consumption, and end of life phases, is covered by the system boundary of their study. The amount of electrical energy consumed by the chiller system is estimated at 31,478,174 kWh throughout its lifetime. The calculated emissions of the chiller system (considering the USA electricity mix) throughout its lifecycle are estimated at 16,654,097.46 kgCO
2eq. This implies that, for every 1 kW of energy used to drive the VCC system, 1.9 kg of CO
2 is emitted.
For the base study with TES tanks installed, the total amount of energy used by the VCS is estimated at 17,412,439,194 kWh throughout its lifetime. For the sake of comparison, the US electricity mix is assumed for the base system analysis. As a result, the calculated emissions of the chiller system throughout its lifecycle are estimated at 15,518,780,377 kgCO
2eq. This result implies that, for every 1 kW of energy used to drive the VCS, 1.1 kg of CO
2 is emitted. The result of this analysis is presented in
Figure 14, and it shows that about 40% of the CO
2 emission is avoided by TES tanks integration, thereby making their incorporation in a DC setup a more sustainable option.
The results and findings of the life cycle environmental assessment of the VCS in this study can be summarized as follows:
The result of the cradle to grave life cycle analysis of the VCS is given as 0.72 kg CO2 eq/RTh, and about 98% is as a result of indirect emission from commercial electricity usage to drive the system throughout its use life.
In the LCIA result of the case study, GWP recorded the highest impact contribution of about 60% of the overall selection. This is followed by human toxicity (HT) and fossil depletion (FD), with 19% and 18% impact contributions.
In comparing the contributions of the life cycle phases to the overall LCIA result, the operation phase made an average of a 95% contribution in all selected impact categories, with HT and FET recording the highest (98.6%) and lowest (91.6%) readings, respectively. This is due to the high ratio of fossil fuels in the electricity grid mix used to drive the plants.
Integrating the Sweden commercial electricity mix produced the most sustainable option compared to other scenarios, with an estimated 94% environmental savings to the base case. It also made the least CO2 contribution, of about 30% to the total GHG emissions compared to 90% and 60% of the base case and other scenarios. This result is directly proportional to the ratio of fossil fuel in the country’s fuel mix. Implying that reducing the presence of nonrenewable energy sources while increasing the ratio of clean energy in Malaysia’s grid electricity mix would generally improve the system’s environmental performance.
In analyzing the LCIA result of all the considered scenarios, GWP accounted for the highest impact category, with an average of 60% impact contribution. This is followed by FD and HT, with an average contribution of 21% and 16%, respectively. However, the Sweden and oilless chiller options recorded a lower FD, of 9% and 18%, and a higher HT, of 39% and 19%, respectively.
In analyzing the LCIA result, switching the grid electricity to the Sweden mix option resulted in an average of 81% environmental savings across all selected impact categories, having its highest (96%) and lowest (49%) savings on GWP and WD, respectively. This is followed by the oilless chiller, Singapore, and natural gas case scenarios, with an average of 76%, 57%, and 32% savings across all selected impact categories, respectively.
In estimating the environmental gains resulting from the integration of TES tanks in the VCS operation, the base study result is compared with the literature. In analyzing the result, a 40% environmental saving is recorded with TES integration.