Review

Energy Efficiency Indicators for Hotel Buildings

by
Luis Martin Dibene-Arriola
1,2,
Fátima Maciel Carrillo-González
3,*,
Sandra Quijas
4 and
María Carolina Rodríguez-Uribe
3
1
Doctorado en Biosistemática, Ecología y Manejo de Recursos Naturales y Agrícolas (BEMARENA), Centro Universitario de la Costa, Universidad de Guadalajara, Puerto Vallarta, Jalisco 48280, Mexico
2
División Ingenierías Energías Renovables y Mantenimiento Industrial, Universidad Tecnológica de Bahía de Banderas, Nuevo Vallarta, Nayarit 63732, Mexico
3
Departamento de Ciencias Exactas, Centro Universitario de la Costa, Universidad de Guadalajara, Puerto Vallarta, Jalisco 48280, Mexico
4
Centro de Investigaciones Costeras, Centro Universitario de la Costa, Universidad de Guadalajara, Puerto Vallarta, Jalisco 48280, Mexico
*
Author to whom correspondence should be addressed.
Sustainability 2021, 13(4), 1754; https://doi.org/10.3390/su13041754
Submission received: 20 November 2020 / Revised: 29 January 2021 / Accepted: 2 February 2021 / Published: 6 February 2021
(This article belongs to the Special Issue Energy Efficiency in Buildings and Districts)

Abstract

:
Hotels are energy-intensive buildings; therefore, in this study, we investigate the indicators used for measuring the energy efficiency of one- to five-star hotels, in temperate and tropical regions of Asia, Europe, and Africa. There are several indicators for measuring energy intensity, but we found that the “total average annual energy use intensity index”, measured in kilowatt-hours per square meter per year (kWh/m2 year), was most often used. Surveys and energy audits are the methods used most often to collect the indicator data. Hotels in the tropics tend to consume more energy than those located in temperate zones, with four- and five-star hotels consuming the most energy.

1. Introduction

According to [1], hotel buildings are classified as one of the highest energy consumption building categories. Hotels, together with offices and retail, consume the most energy; for example, in the UK, these represent more than 50% of the total energy consumption; in the USA, 64%; and in Spain, 85% [2].
Hotel buildings make intensive use of energy [1,3,4,5,6,7,8,9,10,11,12,13,14,15,16,17,18], which generally comes from the burning of fossil fuels, such as oil and liquefied petroleum gas (LPG). Almost all of them offer services such as air conditioning, hot water, and laundry, which in many cases are provided by inefficient equipment [6,14]; the aforementioned aggravates the problem of environmental pollution. The majority of these hotel buildings were designed to be used throughout the year and with different schedules, and they also offer other services such as restaurants, swimming pools, spa, and conference rooms [1,4,6,7,8,10,11,14,15,17,18,19,20,21]. It should be noted that hotel guests tend to be very demanding in terms of thermal and visual comfort, since they are paying for these services, and sometimes they indiscriminately use these services offered in their rooms [5]. Therefore, hotels generate large amounts of CO2, which leads to negative impacts on the environment [4,12] and also diminishes the companies’ profits [14] due to the high energy costs.
Effective and objective energy benchmarking for hotels comprises a meaningful and useful method of ensuring the sustainable development of the lodging sector [22]. Monitoring energy consumption in hotel buildings can be carried out by an energy audit [23], and it is therefore important to identify the indicators that can be used to measure the intensity of energy consumption in hotels and identify if the same indicators are being used or if they are different.

Core Question and Specific Questions

The aim of this study was to identify the indicators that can be used to measure the energy efficiency of all areas in a hotel building, and their behavior in different climatic regions, as well as in different categories of hotels (Table 1). Studies have indicated that the following three specific questions should be considered:
  • Which indicators are used to measure the energy efficiency of hotel buildings?
  • Is there a relationship between hotel classification and energy efficiency?
  • Is there a relationship between the climatic region of the hotel and energy efficiency?

2. Methods

2.1. Strategy for Information Search

The bibliographical search for this review mainly consisted of primary documents (original scientific papers), and the contributions from some conferences proceeding reports were also considered. The multidisciplinary ISI Web of Knowledge database was used since it is a system that offers a high-quality content platform and the tools to access, analyze, and manage research information. The Scopus database and Google Scholar were also used. The process is shown in Figure 1. Papers that were reviews, theoretical simulations, or that only reported some hotel services, such as air conditioning, laundry, and kitchen services, were not selected; only original papers that reported energy efficiency in all areas of the hotel were selected for this study.
The following main keywords in the subject and title, in English, were used in the search: energy, hotel buildings, energy consumption, indicator, use, and intensity. The scope of this review was from 1995, which is when the indicator that measures energy efficiency in all areas of a hotel was published for the first time, until the beginning of 2019.

2.2. Compilation of Information

Once the scientific papers were defined, we proceeded to collect the information in a database, which contained the bibliographic information, keywords, abstracts, support details, and other information (based on Scopus criteria). Additional information that was added included the number of authors, continent, climatic zone (temperate, tropical, or cold), number of hotels studied, the place where the study was conducted, years of data, type of hotel, and all the indices that were found. Finally, the type of method to collect the data was considered since it could be helpful to similar studies.

3. Results and Discussion

3.1. Characteristics of Publications

Only 26 scientific publications met the search criteria for this study. In Figure 2, publications per year and accumulated are shown. For the review period (1995 to 2019), the first publication was in 1995, and there were 9 years without publications, 10 years with one publication per year, 2 years with four publications per year, 2 years with three publications per year, and 1 year with two publications. The reasons for this behavior are unknown.
In Figure 3, the publications by type of document and source are shown. Among the 26 publications in this review, 22 are original scientific papers and four are conference proceeding reports. About the publications in indexed journals, 12 are published in the journal Energy and Buildings, while 10 are published in the following journals: Energy, HKIE Transactions, Hospitality Management, IEEE ICBEST, International Journal of Hospitality Management, Journal of Cleaner Production, and Journal of Science and Technology in Civil Engineering, and Renewable Energy and Sustainability (Switzerland). Finally, four of the publications were presented at the following conferences: Proceedings of the 15th IBPSA Conference, San Francisco, CA, USA, 7–9 August 2017; ICEAMM 2017 IOP Conference Series: Materials Science and Engineering, Proceedings of the 28th Chinese Control and Decision Conference, CCDC 2016, 9th International Symposium on Heating, Ventilation and Air Conditioning (ISHVAC); and Proceedings of the ICETCE 2011 International Conference on Electric Technology and Civil Engineering.
Figure 4 shows the publications by climate region and country. It should be noted that China has 38.46% of the publications, followed by Taiwan and Greece with 11.54% of the publications each. The remaining 38.46% of publications is distributed among the other countries. There are 13 publications on tropical regions and 13 on temperate regions. Among the 26 scientific papers used for this study, 65.38% are papers from Asia, 30.77% from Europe, and 3.85% from Africa. No scientific papers were found for America or Oceania, based on the criteria of this review.

3.2. Indicators, Units, and Their Description

It was found that the indicator most often used is the total average annual energy use intensity index (avg EUI total) in kWh/m2 per year (kWh/m2 year), defined as the annual energy consumption per gross floor area (energy use intensity (EUI)), used in 20 of the 26 reviewed publications [1,3,4,7,9,10,12,13,14,15,16,18,20,21,23,24,25,26,27,28] (Table 2); and it is also the indicator that is used by governmental instances in their guidelines [1,24,25]. The range of EUI varies from 621.14 [23] to 70.2 kWh/m2 year [15], which shows that there is a huge variation in the index values. Four scientific papers presented their results for avg EUI totals in kWh/room and three presented their results for avg EUI totals in kWh/overnight stay. Another 19 indicators are also reported, but these show partial indices.

3.3. Methods Used to Collect the Data in the 26 Scientific Papers

Figure 5 shows the methods that were used in the publications to collect the data. Surveys were the most frequently used method in 42.30% of the publications, followed by energy audits in 30.77%, both cases and interviews in 11.54%, and an audit with software in 3.85% of the publications.

3.4. Average Energy Use Index for Hotels from 1 to 5 Stars

The average energy use index for hotels by category (one to five stars) is shown in Figure 6. Hotels in the tropics have higher average annual energy use intensity (avg EUI) rates than those in the temperate zones; the range of indexes in the tropical zone varies from 143.6 kWh/m2 year in one-star hotels to 621.14 kWh/m2 year in four-star hotels; while in the temperate zone the range is of 70.2 kWh/m2 year for one-star hotels and 237.15 kWh/m2 year for four-star hotels. The index of the four-star hotels was higher than that of the five-star hotels for the two climatic regions, temperate and tropical. The reason for this behavior was that the four-star hotels studied were older than 20 years; therefore, most of their HVCA systems and electrical installations were obsolete, which caused reduced performance and high energy consumption [23]. Regardless of the climate zone, the highest category hotels (i.e., five-star hotels) have a higher energy use index (429.1 kWh/m2 per year) than the one-star hotels (106.9 kWh/m2 year).

3.5. Average Energy Use Index for All the Studied Hotels

Figure 7 and Figure 8 show the results for all publications that reported the total average annual energy intensity use index by hotel type and climate zone, in kWh/m2 year. Various combinations of hotels were included, such as four- and five-star luxury hotels, hotels used all year, seasonal hotels, and averages by climate zone in general, which were reported in this way in the publications studied.
The behavior of the energy consumption index of hotels in the tropics is determined by the average monthly temperature, which, in turn, influences the use of air conditioning systems [1,4,7,11,16,18,19,20,21]. The air conditioning, ventilation, and heating (HVAC) systems are usually powered by electrical power, and the highest consumption is in hotels located in tropical areas (Figure 9).
Hotels in tropical climates used more electricity than hotels in temperate zones since hotels in temperate zones use less air conditioning than hotels in tropical zones, but hotels in temperate zones use more heating than those in the tropics, which is usually obtained through burning fuel. Hence, in the temperate zones, the use of electrical energy decreases, but the use of thermal energy increases.

4. Conclusions

The energy efficiency of hotel buildings is measured by energy use intensity (EUI) indicators; 21 indicators were found in the 26 publications and used for this review (Table 2). The most widely used indicator is measured in kWh/m2 year. A wide interval was observed between the measurements of these indicators ranging from 60 to 700 kWh/m2 year, which is explained by the fact that they are found in two climatic regions, that is, temperate and tropical, in addition to the fact that categories from one- to five-star hotels were considered.
The selection criteria for this review only resulted in the use of 26 publications for this study, which reported studies carried out only in Asia, Europe, and Africa. We did not find scientific publications for the other continents, which indicates an area of opportunity for future studies.
The most widely used indicator for measuring energy efficiency in hotel buildings is the total average energy use intensity index measured in kWh/m2 year. This represents a base indicator and is recommended for future studies in the area of energy efficiency in hotel buildings.

Author Contributions

Conceptualization, L.M.D.-A., S.Q., and F.M.C.-G.; methodology, L.M.D.-A., and S.Q.; investigation, L.M.D.-A., F.M.C.-G., and M.C.R.-U.; resources, L.M.D.-A.; writing—original draft preparation, L.M.D.-A.; writing—review and editing, M.C.R.-U.; supervision, S.Q. and F.M.C.-G. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

Not applicable.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Van Dat, M.; Quang, T.N. A study on energy consumption of hotel buildings in Vietnam. J. Sci. Technol. Civ. Eng. NUCE 2018, 12, 109–116. [Google Scholar]
  2. Pérez-Lombard, L.; Ortiz, J.; Pout, C. A review on buildings energy consumption information. Energy Build. 2008, 40, 394–398. [Google Scholar] [CrossRef]
  3. Qi, M.; Shi, Y.; Li, X. A Bottom-up Method to Assess Energy Consumption of Main Departments in Five-star Hotels in China. In Proceedings of the 15th IBPSA Conference, San Francisco, CA, USA, 7–9 August 2017; pp. 1347–1357. [Google Scholar]
  4. Priyadarsini, R.; Xuchao, W.; Eang, L.S. A study on energy performance of hotel buildings in Singapore. Energy Build. 2009, 41, 1319–1324. [Google Scholar] [CrossRef]
  5. Sheng, Y.; Miao, Z.; Zhang, J.; Lin, X.; Ma, H. Energy consumption model and energy benchmarks of five-star hotels in China. Energy Build. 2018, 165, 286–292. [Google Scholar] [CrossRef]
  6. Beccali, M.; La Gennusa, M.; Lo Coco, L.; Rizzo, G. An empirical approach for ranking environmental and energy saving measures in the hotel sector. Renew. Energy 2009, 34, 82–90. [Google Scholar] [CrossRef]
  7. Huang, K.T.; Wang, J.C.; Wang, Y.C. Analysis and benchmarking of greenhouse gas emissions of luxury hotels. Int. J. Hosp. Manag. 2015, 51, 56–66. [Google Scholar] [CrossRef]
  8. Gao, X.; Zhang, D. Analysis of the rule of influence of hotel occupancy ratio on energy consumption. In Proceedings of the 2011 International Conference on Electric Technology and Civil Engineering (ICETCE), Lushan, China, 22–24 April 2011; pp. 1009–1014. [Google Scholar]
  9. Oluseyi, P.O.; Babatunde, O.M.; Babatunde, O.A. Assessment of energy consumption and carbon footprint from the hotel sector within Lagos, Nigeria. Energy Build. 2016, 118, 106–113. [Google Scholar] [CrossRef]
  10. Pieri, S.P.; Tzouvadakis, I.; Santamouris, M. Identifying energy consumption patterns in the Attica hotel sector using cluster analysis techniques with the aim of reducing hotels’ CO2 footprint. Energy Build. 2015, 94, 252–262. [Google Scholar] [CrossRef]
  11. Deng, S.M.; Burnett, J.; Yik, F.W.H. Audit of electricity use for hotels in hong kong. HKIE Trans. Hong Kong Inst. Eng. 1999, 6, 75–78. [Google Scholar] [CrossRef]
  12. Bohdanowicz, P.; Martinac, I. Determinants and benchmarking of resource consumption in hotels-Case study of Hilton International and Scandic in Europe. Energy Build. 2007, 39, 82–95. [Google Scholar] [CrossRef]
  13. Santamouris, M.; Balaras, C.A.; Dascalaki, E.; Argiriou, A.; Gaglia, A. Energy conservation and retrofitting potential in Hellenic hotels. Energy Build. 1996, 24, 65–75. [Google Scholar] [CrossRef]
  14. Wang, J.C.; Huang, K.T. Energy consumption characteristics of hotel’s marketing preference for guests from regions perspective. Energy 2013, 52, 173–184. [Google Scholar] [CrossRef]
  15. Tang, M.; Fu, X.; Cao, H.; Shen, Y.; Deng, H.; Wu, G. Energy performance of hotel buildings in Lijiang, China. Sustainability 2016, 8, 780. [Google Scholar] [CrossRef] [Green Version]
  16. Shiming, D.; Burnett, J. Energy use and management in hotels in Hong Kong. Int. J. Hosp. Manag. 2002, 21, 371–380. [Google Scholar] [CrossRef]
  17. Dascalaki, E.; Balaras, C.A. XENIOS—A methodology for assessing refurbishment scenarios and the potential of application of RES and RUE in hotels. Energy Build. 2004, 36, 1091–1105. [Google Scholar] [CrossRef]
  18. Deng, S.M.; Burnett, J. Study of energy performance of hotel buildings in Hong Kong. Energy Build. 2000, 31, 7–12. [Google Scholar] [CrossRef]
  19. Trung, D.N.; Kumar, S. Resource use and waste management in Vietnam hotel industry. J. Clean. Prod. 2005, 13, 109–116. [Google Scholar] [CrossRef]
  20. Yao, Z.; Zhuang, Z.; Gu, W. Study on Energy Use Characteristics of Hotel Buildings in Shanghai. Procedia Eng. 2015, 121, 1977–1982. [Google Scholar] [CrossRef] [Green Version]
  21. Wang, J.C. A study on the energy performance of hotel buildings in Taiwan. Energy Build. 2012, 49, 268–275. [Google Scholar] [CrossRef]
  22. Chan, W. Energy benchmarking in support of low carbon hotels: Developments, challenges, and approaches in China. Int. J. Hosp. Manag. 2012, 31, 1130–1142. [Google Scholar] [CrossRef]
  23. Biantoro, A.W. Analysis of electrical audit and energy efficiency in building Hotel BC, North Jakarta. IOP Conf. Ser. Mater. Sci. Eng. 2018, 343, 012033. [Google Scholar] [CrossRef]
  24. Farrou, I.; Kolokotroni, M.; Santamouris, M. A method for energy classification of hotels: A case-study of Greece. Energy Build. 2012, 55, 553–562. [Google Scholar] [CrossRef]
  25. Gonçalves, P.; Gaspar, A.R.; Silva, M.G. Da Energy and exergy-based indicators for the energy performance assessment of a hotel building. Energy Build. 2012, 52, 181–188. [Google Scholar] [CrossRef]
  26. Rosselló-Batle, B.; Moià, A.; Cladera, A.; Martínez, V. Energy use, CO2 emissions and waste throughout the life cycle of a sample of hotels in the Balearic Islands. Energy Build. 2010, 42, 547–558. [Google Scholar] [CrossRef]
  27. Zongjie, D.; Shanliang, Z.; Wei, S.; Shulin, S. Study on energy consumption of hotel based on extended STIRPAT model. In Proceedings of the 28th Chinese Control and Decision Conference (CCDC 2016), Yinchuan, China, 28–30 May 2016; pp. 2052–2056. [Google Scholar]
  28. Lai, J.H.K. Energy use and maintenance costs of upmarket hotels. Int. J. Hosp. Manag. 2016, 56, 33–43. [Google Scholar] [CrossRef]
Figure 1. Flow chart showing the procedure used for the selection of the studies considered for this review.
Figure 1. Flow chart showing the procedure used for the selection of the studies considered for this review.
Sustainability 13 01754 g001
Figure 2. Publications per year and accumulated during the study period (1995–2019). The gray line indicates the frequency of accumulated publications and the black line the number of publications per year. The x-axis indicates the year, and the y-axis indicates the number of publications.
Figure 2. Publications per year and accumulated during the study period (1995–2019). The gray line indicates the frequency of accumulated publications and the black line the number of publications per year. The x-axis indicates the year, and the y-axis indicates the number of publications.
Sustainability 13 01754 g002
Figure 3. Publications by type of document and source. The x-axis indicates the type of publications and the y-axis indicates the number of publications during the period from 1995 to 2019.
Figure 3. Publications by type of document and source. The x-axis indicates the type of publications and the y-axis indicates the number of publications during the period from 1995 to 2019.
Sustainability 13 01754 g003
Figure 4. Publications by climate region (temperate and tropical) and country. The x-axis indicates the number of publications and the y-axis indicates the country by climate region.
Figure 4. Publications by climate region (temperate and tropical) and country. The x-axis indicates the number of publications and the y-axis indicates the country by climate region.
Sustainability 13 01754 g004
Figure 5. Methods used to collect data. The x-axis indicates the method used and the y-axis indicates the number of publications.
Figure 5. Methods used to collect data. The x-axis indicates the method used and the y-axis indicates the number of publications.
Sustainability 13 01754 g005
Figure 6. Total average annual energy intensity use index for hotels from 1 to 5 stars per climate zone. The black bars show the value of one standard deviation. For hotels without standard deviation, only one hotel was considered in the evaluation. The x-axis indicates the average annual energy use intensity (avg EUI) measured in kWh/m2 year, and the y-axis indicates the category of the hotels by climatic zone.
Figure 6. Total average annual energy intensity use index for hotels from 1 to 5 stars per climate zone. The black bars show the value of one standard deviation. For hotels without standard deviation, only one hotel was considered in the evaluation. The x-axis indicates the average annual energy use intensity (avg EUI) measured in kWh/m2 year, and the y-axis indicates the category of the hotels by climatic zone.
Sustainability 13 01754 g006
Figure 7. Total average annual energy intensity use index by hotel type and climate zone. Hotels without a standard deviation line included one case. The black bars show the value of one standard deviation. The x-axis indicates the total average annual energy use intensity index (avg EUI total) measured in kWh/m2 year, and the y-axis indicates the category of all the studied hotels by climatic zone.
Figure 7. Total average annual energy intensity use index by hotel type and climate zone. Hotels without a standard deviation line included one case. The black bars show the value of one standard deviation. The x-axis indicates the total average annual energy use intensity index (avg EUI total) measured in kWh/m2 year, and the y-axis indicates the category of all the studied hotels by climatic zone.
Sustainability 13 01754 g007
Figure 8. Total average annual energy use intensity index by climate zone. The gray bars show the value of one standard deviation. The x-axis indicates the climate zone, and the y-axis indicates the total average annual energy use intensity index (avg EUI total) measured in kWh/m2 year.
Figure 8. Total average annual energy use intensity index by climate zone. The gray bars show the value of one standard deviation. The x-axis indicates the climate zone, and the y-axis indicates the total average annual energy use intensity index (avg EUI total) measured in kWh/m2 year.
Sustainability 13 01754 g008
Figure 9. Relationship between the electric energy consumption (i.e., electrical power (EE)) with respect to the total consumption (%) for the temperate and tropical zones, as well as the general average. The x-axis indicates the climate zone and the y-axis indicates the electrical power (EE).
Figure 9. Relationship between the electric energy consumption (i.e., electrical power (EE)) with respect to the total consumption (%) for the temperate and tropical zones, as well as the general average. The x-axis indicates the climate zone and the y-axis indicates the electrical power (EE).
Sustainability 13 01754 g009
Table 1. Indicators for measuring hotel energy efficiency, central question, specific questions, and response variables. The response variables of each of the specific questions are shown in the row of variables or indicators.
Table 1. Indicators for measuring hotel energy efficiency, central question, specific questions, and response variables. The response variables of each of the specific questions are shown in the row of variables or indicators.
Central Question: What Are the Indicators to Measure the Energy Efficiency of a Hotel Building from 1995 to 2019?
Specific QuestionsWhat types of indicators are used to measure energy efficiency in hotels?Is there a relationship between hotel classification and energy efficiency?Is there a relationship between the climatic region of the hotels and energy efficiency?
Variables or IndicatorsTotal energy consumption vs. Floor area
Consumption of Electric Energy (EE) vs. floor area
Consumption of Thermic Energy (TE) vs. Floor area
Consumption of EE vs. beds
Consumption of TE vs. beds
EE consumption vs. overnight stays
TE consumption vs. overnight stays
EE consumption vs. rooms
TE Consumption vs. rooms
Total energy consumption vs. hotel classificationTotal consumption vs. climatic region
Table 2. Indicators, units, and the description of the terms related to energy efficiency. The first column shows the indicators and their units, and the second column lists the description of terms.
Table 2. Indicators, units, and the description of the terms related to energy efficiency. The first column shows the indicators and their units, and the second column lists the description of terms.
List of Indicators and Their UnitsDescription of Terms
  • Avg EUI EE (kWh/room)
  • Avg EUI EE (kWh/bed)
  • Avg EUI EE (kWh/overnight stays year)
  • Avg EUI ET (kWh/room)
  • Avg EUI ET (kWh/bed)
  • Avg EUI ET (kWh/overnight stays)
  • Avg EUI EE (kWh/m2 year)
  • Avg EUI HVAC/EE (%)
  • Avg EUI lighting/EE (%)
  • Avg EUI Vertical transport/EE (%)
  • Avg EUI Miscellaneous/EE (%)
  • Ratio of EE to total (%)
  • Ratio of ET to total (%)
  • Avg EUI Total (kWh/room)
  • Avg EUI Total (kWh/overnight stays year)
  • Avg EUI Total (kWh/m2 year)
  • Avg EUI HVAC/Total (%)
  • Avg EUI lighting/Total (%)
  • Avg EUI Vertical transport/Total (%)
  • Avg EUI Miscellaneous/Total (%)
  • EUI ET (kWh/m2 year)
Avg EUI = Average Energy Use Index (Average Energy Usage Index, for its acronym in English)
EE = Electric Power
ET = Thermal Energy
m2 = gross floor area
HVAC = Heating, ventilation and air conditioning
Hotel classification:
1 star,
2 stars,
3 star,
4 stars,
5 stars,
seasonal,
annual

Climatic region:
Tropical
Temperate
Cold
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Dibene-Arriola, L.M.; Carrillo-González, F.M.; Quijas, S.; Rodríguez-Uribe, M.C. Energy Efficiency Indicators for Hotel Buildings. Sustainability 2021, 13, 1754. https://doi.org/10.3390/su13041754

AMA Style

Dibene-Arriola LM, Carrillo-González FM, Quijas S, Rodríguez-Uribe MC. Energy Efficiency Indicators for Hotel Buildings. Sustainability. 2021; 13(4):1754. https://doi.org/10.3390/su13041754

Chicago/Turabian Style

Dibene-Arriola, Luis Martin, Fátima Maciel Carrillo-González, Sandra Quijas, and María Carolina Rodríguez-Uribe. 2021. "Energy Efficiency Indicators for Hotel Buildings" Sustainability 13, no. 4: 1754. https://doi.org/10.3390/su13041754

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop