1. Introduction
For the last three decades, the energy efficiency of buildings has been getting much attention due to the substantial energy demands of maintaining indoor thermal comfort in modern buildings [
1,
2]. Generally, it is critical to construct energy-efficient buildings as the increased demand for fossil fuel creates environmental problems like climate change and an increase in the cost of fossil materials [
3]. Previously, buildings were constructed with wider walls that could store a large amount of sensible heat and provide natural conditioning by controlling the temperature variations [
4]. However, in modern buildings, the wall’s thermal mass has been reduced to save materials, time and transportation [
5]. Ultimately, the lightweight buildings are getting huge temperature variations because of this new development, which leads to low thermal storage and extreme internal cooling and heating loads [
6,
7]. Therefore, it is crucial to design and implement efficient energy-saving techniques in buildings. Building envelopes such as walls, roofs, windows and floors isolate the indoor environment from the outside weather conditions to maintain indoor thermal comfort [
8]. Therefore, building envelopes present an opportunity to enhance indoor thermal comfort and reduce energy consumption by influencing the heating and cooling loads of a building [
9]. Many steps have been taken by Heat, ventilation and air condition (HVAC) engineers, such as incorporating facades, hydronic systems, thermal conditioning by radiation, thermal storage devices and many more to reduce energy consumption in buildings [
10]. To ensure the thermal comfort of a building, it is evident that cooling and heating loads will be affected, but recent development in construction materials has changed this phenomenon with the significant use of phase change materials (PCM) [
11,
12].
2. Phase Change Materials
PCM provides additional thermal mass to a building’s envelope to maintain indoor temperature fluctuations by absorbing and releasing heat during the material’s phase change [
13]. These thermal energy storage materials help maintain the indoor ambient temperature within a specific range close to the transition temperature of the PCM [
14]. When PCM attain their melting temperature during the daytime, the indoor ambient temperature increases and the chemical bond in the material breaks (As illustrated in
Figure 1A), causing additional heat to be absorbed by the material and its state changing from solid to liquid [
15]. Similarly, when the temperature drops below the PCM’s freezing temperature at night, the PCM release energy and its state changes from liquid to solid [
16]. If the optimal selection of phase melting and freezing temperature matches, the required indoor comfort temperature can help in reducing the cooling loads by absorbing the extra heat [
15].
PCM is categorized as organic, inorganic and eutectic [
17]. The subcategories of PCM such as paraffin are the most frequently used irrespective of the region, and the maximum frequency of usage is up to 87.5%. This could be because the mixtures of paraffin in different mass proportions have a more comprehensive phase change temperature range and higher phase change latent heat (as illustrated in
Figure 1B) [
18]. Thus, paraffin mixtures can be used in different thermal storage fields through the modification of the mixed proportion [
19].
Paraffin PCM was chosen for this study because they are readily available, inexpensive and melt at different temperatures relating to their carbon chain length with the general formula CnH2n+2 [
20]. Their melting temperature and phase change enthalpy increase with the length of the carbon chain. When the number of carbon atoms in the paraffin molecule is between 13 and 28 [
20,
21], the melting temperature falls within approximately −5 to 60 °C, a temperature range covering building applications in most climates around the world [
22]. They are chemically stable; their volume increase by 10% upon melting, which is similar to many inorganic materials but less critical as paraffin are softer and therefore build up smaller forces upon expansion [
23]. Paraffin is safe and non-reactive; it does not react with the most common chemical reagents [
24]. The latent heat stored to gypsum wallboard during melting and freezing depends on phase change temperature, location, the thickness of the PCM wallboard layer, the shape of the enthalpy curve and the temperature range of phase change [
25].
In a hot climate, the indoor temperature changes quickly because of higher temperatures outside buildings [
15]. In such cases, PCM can be most effective as they have high volumetric heat capacity at the time of phase transition, and it could be 30 times higher than that of concrete or other massive construction materials [
5]. The melting temperature, thermal conductivity and Thermal Energy Storage (TES) density are the best measures to test the thermal performance of PCM’s integration into buildings [
26]. PCM with rapid melting and crystallization/solidification points are suitable for TES applications [
3]. However, designing an efficient heat storage system is challenging because it is not restricted to the system’s thermal performance but also involves costs, safety, and sustainability of materials used and processes employed [
3].
Figure 1.
(
a) Comparison of a building’s indoor temperature profile with and without PCMs. (
b) Comparison of latent heat & sensible heat in material storage [
27].
Figure 1.
(
a) Comparison of a building’s indoor temperature profile with and without PCMs. (
b) Comparison of latent heat & sensible heat in material storage [
27].
2.1. Heat Transfer through a Wall
The total energy utilised by a household is consumed through heating of water, refrigeration, lightening, charging of electronic devices and gadgets. This energy that is consumed through heating and cooling is largely dependent on the type of house, its location and mode of construction. This heat transfer through a building can occur either by conduction, convention or radiation. Heat transfer through building structures such as walls and floor occur whenever a difference exists between the conditioned indoor space of a building and the surrounding outdoor temperature [
28,
29]. To determine the heat transfer through a building, the indoor conditions are assumed to be constant, although it also varies with climates and seasons. For instance, in cold countries and during the winter period, heating load calculations are dependent upon peak or near peak conditions that takes place shortly before sunrise, and there is little or no difference in the surrounding outdoor temperature in cold countries during winter [
30,
31].
In terms of heat transfer, walls are the most prominent source of heat transfer in a building. Generally, walls are exposed to the sun; therefore, calculating the temperature difference is critical. For calculating heat flow, we need to get the area of the wall excluding the area of windows, the transmission coefficient for external walls and the mass flow rate per unit from the ASHRAE tables (ASHRAE, Inc., Peachtree Corners, GA, USA, (n.d.)). Some important parameters should be considered to calculate the heat transfer through walls, for instance, the equivalent temperature difference when the wall is in shade or exposed to the sun, maximum solar heat gain at the direction of the wall facing for a desired month and latitude, wall facing towards north/south/east/west/direction.
The first step in estimating the heat transfer through a wall is to determine the design heat transmission coefficient. Thus, in terms of thermal efficiency, solar and transmission gain through walls can be calculated from the given equation below:
Q = Cooling load (Btu/hr = 0.293 watts);
U = overall heat transfer coefficient (Btu/hr-ft2-F = 5.6783 W/(m2·K);
A = Area (Ft2 = 0.093 m2);
CLTD = Equivalent temperature difference (F = 255.928 K).
Here, Q describes ‘Sensible heat flow’ that affects Heat Ventilation & Air Conditioning equipment size and energy consumption, and the goal is to minimize this value for overall economics and efficiency. Higher Q value imposes high first- and recurring operation costs on the HVAC system [
32]. A is a function of a building’s form. The area values are computed from building plans and elevations drawings. the U-value describes the rate of heat flow through a building element. It is the reciprocal R-value (U = 1/R), where R is the total resistance of the materials used in constructing the wall. The higher the R-value, the higher the insulating value of the material or the lower the U-value, the higher the insulation value of the material. Energy efficiency standards set a maximum U-factor value and are calculated from the material information provided in building drawings. The cooling load temperature difference (CLTD) value is derived from the ASHRAE table for any wall, rood, latitude and hour of the day [
32]. CLTD is a theoretical temperature difference that accounts for the combined effects of inside and outside air temp difference, daily temp range, solar radiation and heat storage in the construction assembly/building mass. It is affected by orientation, tilt, month, day, hour, latitude, etc. CLTD factors are used for adjustment to conductive heat gains from walls, roof, floor and glass [
28].
2.2. Cooling Load Principle
To maintain a uniform thermal condition, the cooling load principle must be applied. The cooling load is the rate at which a cooling system or process must remove heat from a conditioned zone to maintain constant dry bulb temperature and humidity [
33]. The building components which affect the cooling loads are external input (walls, roof, floor, window and ceiling), internal supply or internal load (lightening, occupants, appliances and equipment), infiltration (air leaks, moisture migration), system (duct leakage, heating, ventilation) [
32]. Cooling load calculation methodologies are based on heat transfer by conduction, convection, radiation [
33] and include heat balance, radiant time series, cooling load temperature difference [
33]. Calculation of thermal loads of buildings is altered for cooling in summer for the accuracy of design and appropriate equipment or materials to adapt the thermal comfort and reduce the cooling loads in the selected place.
For standard cooling load calculations, many pieces of software have been designed by HVAC engineers, and the most popular ones include HAP, REVIT and ENERGY PLUS. This software examines each space of a building from the months and daytime. For example, walls are expected to provide thermal comfort within the building and at the same time, the thermal resistance (R-value) of the wall is a critical parameter and highly influences the energy consumption and increases the cooling loads [
34], especially in the buildings where the ratio between the wall and total envelope area is more significant [
35]. Based on the construction materials, walls are classified as wood-based, metal-based, or masonry-based.
To estimate the cooling load of an area or building, four methods have been suggested, including cooling Load by Transfer Function Method (TEM), Total Equivalent Temperature Difference (TETD) method, Cooling Load Temperature Difference (CLTD) method and Transfer Function Method (TFM). In this study, we adopted the CLTD method. This method involves the temperature difference in the case of building components (walls and roofs) and the cooling load factors in the case of solar heat gain through windows and internal heat sources. The following formula is used to estimate cooling loads using the CLTD method
where
Q is the net room conduction heat gain through roof, wall or glass (W);
A is the area of the roof, wall or glass (m2);
U is the overall heat transfer coefficient (kW/m2·K);
CLTDC is the cooling load temperature difference (°C).
2.3. Thermal Comfort
Thermal comfort is a condition of the mind which expresses satisfaction with the thermal environment and is mainly affected by environmental factors such as air temperature, radiant temperature, air velocity and humidity. Thermal comfort also depends on the cooling loads (the amount of heat energy that must be removed from an environment to maintain an optimum temperature) and the heating load (the amount of heat that must be added to an environment to ensure optimum temperature) of a place.
The metabolic rate for specific activity levels and clothing affects our thermal comfort as well. The Predicted Mean Vote (PMV) model from Fanger is the most widely used comfort model [
36]. Generally, PMV is an index with a seven-point scale, where −3 is the cold extremum and +3 is hot. PMV model can be expressed as:
where,
M = metabolic rate;
I = clothing insulation;
Ta = Air temperature;
Tr = radiant temperature;
RH = Relative humidity;
v = Air velocity.
PMV can be directly connected with productivity level in an office while performing basic tasks like typing or thinking. Most of the PMV index studies are based on climate chambers [
37], which can be very different from a normal office or home environment. Another alternative approach is adaptive comfort; thousands of building occupants have been involved in field studies in real buildings, where measurements and questionnaires have been used to correlate the temperature to the thermal sensation experienced by the occupants [
37].
Air and radiant temperatures are critical parameters of thermal comfort in modern buildings, which could be maintained with the use of phase change materials. For example, using phase change materials in the roof and walls can reduce their interior temperature, which will have a direct effect on the convection (linked to the air temperature) and radiation (linked to the radiant temperature) heat transfer, and subsequently improve the thermal comfort of people inside the building. Phase change materials (PCMs) have great potentials to be used in modern building materials to stabilize indoor temperature fluctuations for improving thermal comfort by phase transition occurs between the “cooling” and “heating” temperatures and heat absorbed/emitted without the material changing temperature [
38].
Aside from the thermal load of a building, another vital parameter is the thermal comfort of a building, and this is the condition of mind which expresses satisfaction with the thermal environment [
39]. It means that a person feels neither too cold nor too warm. It is essential for health, well-being and productivity [
40,
41]. Thermal comfort is vital for buildings, especially in tropical climates where intensive cooling capacity is needed throughout the year [
42]. Therefore, PCM is commonly investigated in passive cooling in buildings to provide thermal comfort by adding construction materials or integrating them into building structures [
43]. In tropical regions such as Darwin in Australia, which is a warm, humid climate that requires long-term conditioning to gain thermal comfort, more heat is usually dissipated into the environment because a hotter environment raises the temperature and demands thermal comfort in the buildings [
44].
Generally, it has been observed that PCM’s efficacy depends on various parameters such as the type of PCM, location, climate, phase change temperature range, enthalpy curve, and thickness [
45,
46]. However, little study has been carried out on building orientation on PCM’s melting temperature. Moreover, the overall efficacy of PCM in hot and humid climates is equally unclear [
47]. Apart from these, there is no evidence of standard thickness of PCM’s layer to optimize the thermal comfort inside a building in different climate zones [
48]. Although some previous studies suggest that during the phase transition, a large amount of heat is absorbed and released by PCM, a phase change takes place in a specific temperature range rather than immediately at one temperature, for example, the specific heat capacity of PCM when used as a function of temperature [
49].
The efficacy of PCM requires sizeable daily temperature variations to obtain melting-freezing cycles, but in Darwin, this could be a challenge [
50]. Finally, various studies have been done in winter and summer climate regions (China, US, Europe, Bangladesh, India), but just a few studies (about 4%) have been published on tropical areas such as Darwin, Australia. Furthermore, just about 13% of review articles focused on the general problem of Thermal Energy Storage (TES) using PCM, 40% dealt with the development and evaluation of PCM in laboratories, 37% focused on numerical simulation, and 10% dealt with both experiment and simulation, while there are very few articles that focused on actual outdoor conditions [
51].
Hence, this research aimed to study phase change materials to optimize indoor thermal comfort and minimize the cooling loads of residential buildings in tropical climates such as Darwin in Australia. The strategy used to achieve this was the incorporation of PCM-based gypsum wallboard on the walls of a single-family building in Wagaman, Darwin, using Energy Plus simulation software (Revit 2021). This work provides a combined modelling and simulation study to quantify the effectiveness of PCM in reducing cooling loads by design strategy of placement of PCM on the lining of the walls.
3. Materials and Methods
The approach used for this study consisted of a qualitative research mechanism that focused on Darwin’s weather study, analysis of cooling loads, building modelling, PCM material selection and energy simulation.
3.1. Approach
This study was aimed at investigating phase change materials (using paraffin wax) to optimize indoor thermal comfort and minimize the cooling loads of residential buildings in tropical climates.
Figure 2 illustrates the three-stage process that was adopted for this study. In the first stage, a single-family residential building was chosen and surveyed for this study.
The orientation, 3-D model structure, surrounding microclimatic properties were studied by simulation using Revit 2021 software. In the second phase, 10% paraffin-based n-octadecane in pouches was used and mixed with gypsum to form the PCM-based gypsum wallboard of 1-centimetre and 2-centimetre-thicknesses.
In the final stage, simulation was used to calculate the cooling loads and analyse the energy consumption of the building. The simulation was performed in two stages. First, the construction of the building and secondly, the introduction of the data such as internal gains, environmental aspects and cooling system.
The cooling load associated with different building envelopes and the energy consumption of the selected building (based on a building’s conceptual masses, building elements, or both depending on the analysis mode selected in the energy setting dialogue) was calculated using the Revit software and Energy Plus, respectively.
3.2. General Simulation Process
Revit 2021 software was used to structure a 3D model of the building located at Wagaman suburb in Darwin, Australia. The 3D model in Revit usually represents 3D geometry as rectangles, lines, and extrusion operations between the geometry. The material properties for the materials used in the construction of the building were conveniently obtained from the material properties browser of the Revit software. The analyse toolbar gave the option to calculate the cooling loads associated with different building envelopes. After modelling the building in Revit2021, the spaces were divided into zones to calculate the cooling load.
In terms of energy consumption analysis for the selected residential building, the project’s geographic location, weather, and site were specified in Revit. Also, the cooling design temperature data for all months of the year as shown in Darwin were specified. Since the location, weather and site data were provided, the 3D structure was converted into the energy analytical model to calculate the yearly energy consumption of the building. The energy analytical model was validated based on conceptual masses and building elements before running the energy simulation using the selected energy mode in the energy setting dialogue.
3.3. Building Survey
A realistic estimation of the thermal load of a building was performed using a building survey which included surveying the orientation, use of spaces, dimensions of spaces, ceiling height, construction materials, surrounding conditions and details about the building envelopes [
52,
53,
54]. A single-family residential building with four spaces was selected for this study. The orientation of the building was 35–180 degrees, as shown in
Figure 3A. The window–wall ratio for southern, western, and eastern interacts with window properties to impact daylight, heating and cooling. The building’s walls were constructed from composite masonry material, including different insulation layers such as the core boundary layer, membrane layer, thermal/air layer, finish layer, brick, and render beige. In addition, a finished surface (gypsum wallboard) was added to the walls, as shown in
Figure 3B below.
The material properties of composite masonry brick walls and the material properties of the PCM are given in
Table 1, while the details of the building’s outdoor design conditions are given in
Table 2.
The floor plan of the building consisted of 4 spaces, as shown in
Figure 4.
The external structured wall (render on brick on block) consists of concrete masonry material with a nominal thickness of 16.42 cm (concrete masonry is 7.48, thermal air is 1.97 and thermal air cavity fill is 1.97, brick is 4.02 and finish 2 render smooth is 0.98 respectively) in which two leaves of undressed stones can be built together. The interior partition wall consists of gypsum with core boundary metal stud layer (135 mm partition (2-h) with total thickness 5.33 mm. The floor and roof structures are designed to represent real buildings with typical construction details as the floor has graphics parameters (callout tag) with a callout head with a 3-millimetre corner radius and a sim reference label, whereas roof is gable type at 30 degrees inclination and floor to roof height is 2743 mm.
3.4. PCM Incorporation
The method used to incorporate the PCM with gypsum was microencapsulation. This method prevented the external environment from contaminating the PCM. Tiny spheres of paraffin (5–10 microns in diameter) were encapsulated in acrylic shells, mixed with the gypsum in wallboard. Only 10% paraffin-based
n-octadecane in pouches was used and mixed with gypsum to form the PCM-based gypsum wallboard. Additionally, to determine the maximum efficiency of the PCM-based gypsum wall, different thicknesses (1 cm and 2 cm) of PCM wallboard were applied at the internal and external sides of the composite masonry wall. The melting temperature of the PCM was set to 24 °C. The solidification temperature was assumed to be 1 K higher than the melting point of 25 °C. The phase change process inside the wallboard allowed a portion of the solar energy to be stored as latent heat [
55].
3.5. Design Conditions
Both indoor and outdoor design conditions were considered in calculating the cooling load of the building. Outdoor design conditions included climatic design information according to latitude, longitude, altitude and atmospheric pressure, statistical analysis of weather data, and data found in handbooks such as ASHRAE Fundamentals Handbook [
32]. Indoor design conditions included basic design parameters such as thermal comfort and indoor air quality, solar gain through glass and structures, infiltration and ventilation, and internal heat gain. All indoor design conditions are represented in
Table 3.
3.6. Modelling of the Building
Revit 2021 software was used to structure a 3D model (
Figure 5) of a building located at Wagaman suburb (GPS—12.3810040, 130.8805245) in Darwin, Australia. The 3D model in Revit usually represents 3D geometry as rectangles, lines, and extrusion operations between the geometry [
56]. Depending on its purpose, the focus moves textured or shaded surfaces to volumes of building envelopes for calculations. With Revit, a building’s 3D model’s different sections and view can be seen straightforward from the wire-frame display. The Revit software was chosen because of its numerous advantages such as visualization, user-friendly, relative ease of understanding, showing depth elevation clearly and visually, and having the flexibility of design changes [
56]. It helps to minimize the field clashes and delay in construction projects as resolution occurs before any work is done.
Furthermore, any changes in size or materials do not create any additional cost and the material properties for the materials used in the construction of the building were conveniently obtained from the material properties browser of the Revit software. In addition, the analyse toolbar gave the facility to calculate the cooling loads associated with different building envelopes. After modelling the building in Revit2021, the spaces were divided into zones to calculate the cooling load (
Figure 6). Asides from the cooling load, the software also provided options for energy analysis in Analyze Tab Energy Optimization panel, based on a building’s conceptual masses.
3.7. Energy Consumption Analysis
To analyse the energy consumption for the selected residential building, Revit gave an option to specify the project’s geographic location, weather, and site. In addition, the selection of Darwin, NT gave cooling design temperature data for all months of the year, as shown in
Table 4. Since the location, weather and site data were provided, the 3D structure was converted into the energy analytical model to calculate the yearly energy consumption of the building. This feature allowed inspection of the energy analytical model to validate it before running the energy simulation. The energy analytical model was based on conceptual masses, building elements, or both depending on the analysis mode selected in the energy setting dialogue.
3.8. Energy Simulation of the PCMs
In this study, energy simulation for the PCM was carried out using Energy Plus 9.5. The software tested the building energy performance using construction materials and the software equally had features that simulated the heating and cooling loads, cooling, lighting, ventilation, air conditioning, and energy flow [
57]. The principal used parameters to determine the efficiency of phase change materials were material property, location, climate, sizing period and design day. Additional properties such as temperature-dependent thermal conductivity and enthalpy were used and solved by Heat Balance Algorithm (Conduction Finite Difference). The design day object in Energy Plus created the parameters for the program to create the 24-h weather profile that was used for sizing and running to test the other simulation parameters. Parameters in design day included a month and day; a day type consists of appropriate schedules for either sizing or simple tests, minimum or maximum temperature, wind speed and solar radiation values. In this study, simulation was performed in two stages. First, the construction of the building and secondly, the introduction of the data such as internal gains, environmental aspects and cooling system.
5. Discussion
The average temperature of Darwin lies between 19 °C to 38 °C throughout the whole year. Despite this temperature range, the average relative humidity is approximately 38% to 75%. These weather patterns demand high conditioned space inside buildings to meet the required thermal comfort. Ultimately, it increases the energy consumption of buildings and cooling loads vice-versa. According to ASHRAE Standard 55-1992, the Human Comfort Zone diagrammed onto a Psychometric Chart lies between 24 °C (75.2 °F) to 27 °C (80.6 °F). However, Darwin’s weather results compared to the ASHRAE Standard 55-1992 human comfort zone indicates that the indoor building environment of Darwin needs reduced temperature.
Thus, in this study, PCM was used to optimize the indoor thermal comfort and minimize the cooling loads using PCM-based gypsum wallboard which was incorporated into the walls of a single-family building in Wagaman, Darwin Australia.
5.1. Effect of PCM on the Total Cooling Load of the Building
Overall, the cooling load of the building with and without PCM was calculated and the total cooling load without PCM was 7259 W, whereas with PCM (1-centimetre and 2-centimetre-thicknesses), the total cooling load was 7151 W; this gave a 1.49% reduction in total cooling load. This decreased cooling load is due to the PCM-based gypsum wallboard that stored thermal heat due to the phase change mechanism. This slight cooling load percentage reduction could be increased by increasing the quantity of PCM during encapsulation, but the PCM that can be used is limited by the structural integrity of the gypsum board [
58]. In addition, Darwin has a similar temperature during the day and night, thus restricting the PCM’s ability to give an optimal performance [
59].
5.2. Thermal Mass and Effect of PCM Thickness on Thermal Properties and Cooling Load
In this study, the thermal mass was developed by embedding PCM with gypsum wallboards and impregnated on the interior side of the walls. The PCM embedded gypsum wallboard used the energy associated with the material’s phase change from solid to liquid. The PCM with a melting point of 24 °C added a significant equivalent thermal mass. Thus, embedded PCM specifically paraffin waxes can be designed with a melting point suitable for retrofitting in conventional buildings [
60]. It was observed that the thermal mass of the walls increased with the PCM layer thickness increment, while thermal conductivity decreased with the PCM-based gypsum wallboard thickness increment. This increment in thermal mass increased the adequate heat capacity during the phase transition and stored more heat, consequently reducing the cooling load inside the space. Therefore, the use of PCM is an efficient passive measure to lower the cooling loads and cooling energy demands in buildings [
61].
Usually, it is advantageous to use materials with low thermal conductivity to save building energy [
62]. However, their low thermal conductivity can be a challenge since PCM stores large amounts of heat and cold in small volumes and because it is necessary to transfer this heat to the outside of the storage to use it. Consequently, there is a limitation in its use without instant heat transfer when required, no matter how large a capacity of heat storage the PCM has. These deficiencies could potentially reduce the rate of heat storage and release during the melting and solidification cycles and restrict their extensive applicability [
63].
5.3. Effect on Cooling Load by Varying Thickness and Position of the PCM Layer
The total cooling load of the building decreased by increasing the thickness of the PCM-based gypsum wallboard. For example, the total cooling load decreased by 1.1% when 1 cm in thickness was applied to the wall, whereas a 1.5% reduction was obtained when 2 cm of PCM layer was applied. Therefore, a lower amount of energy to transfer indoors with increased thickness [
64]. The highest reduction in total cooling load was obtained when PCM gypsum wallboard was installed at the internal linings of the walls and successful in capturing solar energy, which helps in performing the phase-change mechanism [
58]. The total site energy and energy cost both decreased with increasing the PCM layer’s thickness. Moreover, a 2-centimetre-thick PCM layer gave a 7.6% reduction in total site energy, and 4.76% energy saving in USD/m
2/year was achieved.
5.4. Thermal Resistance and Heat Transfer Coefficient
The thermal resistance of the wallboard increased with the increase in the thickness of the PCM layer. The higher thermal resistance of walls material was considered to restrict heat transfer. Furthermore, due to the higher thermal resistance of PCM, heat transfer was lower towards the inside surface. This phenomenon indicated that the lesser the heat transfer to the indoor, the lesser cooling load would be required to maintain the thermal comfort. Additionally, the heat transfer coefficient decreased with an increase in PCM wallboard thickness. As mentioned in the introduction section, heat transfer through the wall of resistance is the reciprocal of heat transfer coefficient (U = 1/R), where R is the total resistance of the material used in constructing the walls. Therefore, the higher the R-value, the higher the insulating value of the material or the lower the U-value, the higher the insulation value of the material [
32]. Hence, decreased value of the heat transfer coefficient gave higher insulation and less heat transfer to the indoor space.
5.5. Insights into Future Research
This study focused on the building walls component, which contributes less percentage toward the total cooling load of a building; however, the study on other parameters such as windows and roofs can provide more efficient results as they contribute more towards building total cooling load thus, additional research is required in this area.
Additionally, a small percentage of Cooling load reduction was obtained with organic PCM-based gypsum wallboard during this study, however, other PCM materials could be used for maximum results.
This research is simulation-based; some of the parameters are by default in Energy Plus software which cannot be changed; however, in a real-life experiment, we can use the actual parameters such as ground surface temperature to analyze the performance of PCMs.
In this study, the microencapsulation method was used to apply to the PCM. This is expansive, so other methods such as direct incorporation, shape stabilization could be tried for better performance and energy savings.