4.2. Scenario Comparison and Result Analysis
To verify the cost reduction effect brought by battery storage configuration in a grid containing wind, solar, thermal, and pumped storage units when considering inertia constraints and deep peak regulation of thermal power, we constructed four scenarios for comparison in the case study:
Scenario 1: Without considering inertia constraints and without configuring battery storage;
Scenario 2: Without considering inertia constraints but with configuration of battery storage;
Scenario 3: Considering inertia constraints but without configuring battery storage;
Scenario 4: Considering inertia constraints and configuring battery storage. The comprehensive operating cost results for each scenario are shown in
Table 3.
From
Table 3, the following conclusions can be summarized:
Generation costs account for the largest proportion of long-term scheduling costs. By comparing Scenario 1 and Scenario 3, we find that considering inertia constraints leads to the operation of more thermal power units during periods of low system inertia, increasing their start–stop and operating costs, while also exacerbating wind and solar curtailment. The comparison between Scenario 3 and Scenario 4 shows that integrating inertia constraints into grid operations and investing in battery storage to provide virtual inertia can reduce the frequent start–stop of thermal power units, lower operating costs, and reduce wind and solar curtailment. The comparison between Scenario 2 and Scenario 4 indicates that considering inertia constraints requires configuring higher-capacity battery storage, which not only reduces wind and solar curtailment but also provides the necessary inertia support for grid operation.
From an economic perspective, the method proposed in this paper has several advantages compared to the traditional approach of meeting system inertia requirements by dispatching thermal power units. Firstly, the quick response of battery storage can reduce the need for frequent start–stop operations of thermal power units, thereby lowering the overall operation and maintenance costs of the power system. Secondly, meeting system inertia demands through battery storage can reduce the adjustment requirements of thermal power units, thus decreasing the consumption of fossil fuels, which in turn lowers fuel costs and enhances environmental friendliness. Finally, although the initial investment in storage systems is relatively high, in the long run, battery storage can optimize the integration of renewable energies such as wind and solar, and reduce the reliance on traditional power plants, thereby significantly lowering the total costs of the power system.
However, there are also some disadvantages. Firstly, the initial investment cost of providing virtual inertia through battery storage is relatively high, especially when deployed on a large scale, which may impact economic efficiency in the short term. Secondly, the lifespan of battery storage is shorter compared to traditional thermal power units, so multiple replacements of battery modules are required during the lifecycle of battery storage, increasing the long-term maintenance and replacement costs of battery storage.
Next, we take one of the typical days as an example to observe the operation under each scenario. The start–stop situations of thermal power units for each scenario are shown in
Figure 4.
When battery storage is not considered in the power grid configuration, analyzing
Figure 4,
Figure 5 and
Figure 6 reveals the following.
When inertia constraints are not considered, thermal power units will be scheduled to minimize operating costs throughout the day. This means that units with lower operating costs and higher maximum technical output, such as thermal power units 4 and 8, will be prioritized. However, as shown in
Figure 5, the system inertia during the entire operation process generally does not meet the minimum inertia requirements. Consequently, if a fault occurs, the system frequency minimum point will exceed limits and fail to meet the system’s frequency requirements.
When inertia constraints are included, analyzing
Figure 6 shows that the system frequency will meet the pre-determined requirements at any time of fault occurrence, specifically, the post-fault minimum system frequency will be greater than 49 Hz. By analyzing
Figure 5, it is evident that, to meet the system’s minimum inertia requirements, an additional thermal power unit (unit 7) is operated from midnight to 8:00 AM in Scenario 3, along with units 4 and 8 from Scenario 1. From 9:00 AM to noon, due to the higher load, Scenario 1 operates additional thermal power units 3 and 5 to meet load requirements, but still falls short of the minimum inertia requirements. In this situation, Scenario 3 continues to dispatch thermal power units 6 and 7. After noon, unit 7, which has a lower inertia time constant, is shut down, and unit 6, which has a relatively higher inertia time constant, is kept running to meet both load and inertia requirements. Overall, in Scenario 3, the frequency of thermal power units entering deep peak shaving mode increases significantly, which also increases the wear and tear on these units.
When battery storage is considered in the power grid configuration, analyzing the on–off situations of thermal power units in Scenarios 3 and 4 from
Figure 4 shows that battery storage reduces the frequent start–stop of thermal power units, lowering their operating costs and the costs of wind and solar curtailment. This is because battery storage can provide virtual inertia, working in conjunction with thermal power units and pumped storage units to meet the minimum inertia requirements. Specifically, in Scenario 4, due to the virtual inertia provided by battery storage, unit 7 can be shut down from midnight to 8:00 AM when the inertia demand is not high, with battery storage compensating for the missing inertia. After 9:00 AM, unit 2, which has a low inertia time constant and poor economic performance, can be shut down. The entire system maintains frequency stability through the combined support of thermal power units, pumped storage units, and the virtual inertia provided by battery storage. Overall, this significantly reduces the wear and tear on thermal power units caused by deep peak shaving, as well as the associated environmental pollution.
Next, taking Scenario 4 as an example, we observe the system’s operating output and the SOC (State of Charge) of the battery storage, as shown in
Figure 7 and
Figure 8.
According to
Figure 7 and
Figure 8, it can be seen that by integrating battery storage into a high-proportion renewable power system, two key benefits are achieved. Firstly, battery storage provides the necessary virtual inertia for the system. Secondly, battery storage, in conjunction with pumped storage, enables peak shaving and valley filling for the entire system. For example, during midday when renewable energy generation is high, both battery storage and pumped storage are in a charging state, absorbing excess renewable energy. In the evening, when renewable energy is scarce, battery storage and pumped storage discharge to work with thermal power units to meet the system’s load requirements. Additionally, analysis of the battery storage SOC shows that the SOC remains between 0.1 and 0.9 throughout the day, which meets the safety requirements for battery storage operation. Furthermore, at the end of the day, the SOC of the battery storage returns to the initial 0.5 level, ensuring that the battery storage can meet the dispatching requirements for the next day.
4.5. The Impact of Different Renewable Energy Penetration Levels on the Results
To ensure the reliability and resilience of the model proposed in this paper, we tested the model under scenarios with different renewable energy penetration levels. The results are shown in
Table 6.
From the results in
Table 6, it can be seen that when the renewable energy penetration level is low, the overall cost of meeting the system inertia requirements using traditional methods is lower than that of the method proposed in this paper. This is because, at low penetration levels, the installed capacity of thermal power units is relatively large, and many units operate simultaneously, providing the necessary inertia support. In contrast, the initial investment cost of battery storage is high, making traditional methods more economical in this scenario. However, as the renewable energy penetration level increases, the share of installed capacity and output from thermal power units decreases, leading to a decline in the economic efficiency of traditional methods. Conversely, the economic efficiency of the method proposed in this paper improves with increasing penetration, gradually demonstrating greater economic benefits. The higher the penetration level, the more apparent the advantages.
It is also important to note that the overall operating costs in this study exhibit a trend of first decreasing and then increasing as the renewable energy penetration level rises. This is because, in this paper, penetration is defined as the proportion of installed renewable energy capacity. Changing the penetration level affects the installed capacity, but the overall operating costs in the model do not include the investment costs of renewable energy installations, only considering the costs of wind and solar curtailment. As a result, an initial increase in penetration leads to a reduction in operating costs, but as penetration continues to rise, limitations in grid transmission capacity lead to increased wind and solar curtailment, causing overall operating costs to increase.
4.6. Comparison between Stochastic Optimization and Deterministic Optimization
The comparison of economic costs between the stochastic optimization method adopted in this paper and the deterministic optimization method, which considers only a single typical scenario of wind and solar output, is shown in
Figure 9.
Based on the analysis of the above figure, the following conclusions can be drawn: The deterministic optimization method makes decisions based on a given single wind and solar output scenario without accounting for the uncertainty in wind and solar output throughout the year. Therefore, its planning scheme is greatly affected by the typical daily wind and solar output magnitude and volatility. When the typical daily wind and solar output are high and volatility is low, the configuration cost and overall operating cost are low, whereas, when the typical daily wind and solar output are low and volatility is high, the configuration cost and overall operating cost are high.
In contrast, the stochastic optimization method comprehensively considers the volatility of wind and solar output and load. As a result, its outcomes ensure economic efficiency while meeting operational requirements under the most adverse conditions, thereby reducing overall operating costs. This method balances a degree of conservatism, making the system more robust and resilient.