Next Article in Journal
Corporate Philanthropy Affecting Consumer Patronage Behavior: The Effect of Reciprocity and the Moderating Roles of Vicarious Licensing and Strategic Fit
Previous Article in Journal
Use of Video and 3D Scenario Visualisation to Rate Vegetation Screens for Integrating Buildings into the Landscape
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Energy Efficiency for Airtightness and Exterior Wall Insulation of Passive Houses in Hot Summer and Cold Winter Zone of China

College of Civil Engineering and Architecture, Zhejiang University, 866 Yuhangtang Road, Hangzhou 310058, China
*
Author to whom correspondence should be addressed.
Sustainability 2017, 9(7), 1097; https://doi.org/10.3390/su9071097
Submission received: 26 May 2017 / Revised: 19 June 2017 / Accepted: 19 June 2017 / Published: 23 June 2017
(This article belongs to the Section Sustainable Engineering and Science)

Abstract

:
There exists huge differences in climatic conditions and occupant energy-consuming behavior between Berlin and the “hot summer and cold winter zone of China” (HSCW), which implies that the building energy consumption compositions of two regions are completely different. In this paper, dynamic energy consumption simulation for passive houses with Design Builder software was performed. The results indicated that the improvement of building airtightness and exterior wall insulation can reduce annual heating and cooling load effectively, and more importantly the effect is much stronger on heating load than cooling load. Because of this, the paper proposed that the ratio of heating and cooling electricity consumption (r) should be adopted as an important index in energy efficiency evaluation of passive houses. It would contribute to the reasonable selection of ventilation modes and the exterior wall heat transfer coefficient, and benefit the healthy development of passive houses in HSCW.

1. Introduction

The hot summer and cold winter zone of China (HSCW) refers to the middle and lower reaches of the Yangtze River and surrounding area. The climate here is severe: the mean temperature of the hottest month is between 25 °C and 30 °C, about 2 °C higher than other places of the same latitude in the world, while the mean temperature of the coldest month is between 2 °C and 7 °C, about 8–10 °C lower than other places of the same latitude in the world [1], and the length of summer and winter is significantly longer than that of transient seasons [2]. Because of these, great demands for cooling in summer and heating in winter exist simultaneously for buildings in HSCW, which brings a certain difficulty to constructing energy efficient buildings in this region. The operation of air condition systems accounts for 50~60% of residential annual energy consumption and the ownership of air conditioners is still rising rapidly [3]. It has long been discussed, how to reduce building energy consumption in HSCW effectively using different technologies. Many researchers have offered their opinions on optimum insulation thickness of exterior walls, window–wall ratio, external shading, heating and cooling system, etc. [3,4,5,6].
The “passive house” is a kind of technical architecture which could achieve nearly zero heating and cooling energy consumption, as well as high levels of indoor environmental comfort. It has very strict requirements on insulation, airtightness, high-quality windows, ventilation systems (heat recovery equipment), and the avoidance of thermal bridges, in order to limit the annual per unit area heating (cooling) demand to less than 15 kW·h/(m2·a) and a total primary energy (natural energy that has not been subjected to any conversion or transformation process) demand to less than 120 kW·h/(m2·a) [7]. In contrast to the earlier low-energy buildings, passive houses place much emphasis on building airtightness after noticing that the heat loss by air infiltration accounts for 25 to 50% of the total heating load [8]. The concept of passive houses was practiced for the first time in Darmstadt, Germany, and since then it has become more and more popular. By the end of 2014, more than 1 million square meters of useful floor area had undergone the certification scheme set by the Passive House Institute (PHI) [9]. So far, studies on passive houses are mainly distributed in Germany, Switzerland, Austria and Central Europe, etc. [10]. Mihai et al. [10] analyzed the energy performance of a passive house located in Bucharest, Romania, which had building system that had the earth–air heat exchange technology combined with photovoltaic panels. Both the Energy Plus simulation and actual measurement were used in this work. Persson et al. [11] studied a case of a passive house in Sweden using the DEROBLTH software to evaluate the feasibility of new technologies, such as windows. The results showed that the solar heat gain through windows can contribute well to the heating of space in passive houses. Audenaert et al. [12] and Dan et al. [13] both analyzed the economic aspect of passive houses and calculated the period of recovery of investment. Georges et al. [14] studied the application of wooden stoves in passive houses under cold climates, using dynamic simulation (TRNSYS) on a typical Norwegian house. Projects in Germany and similar climates demonstrated that passive houses generally make 80 to 90% less heating energy than conventional new buildings, at additional building costs of 5 to 20% [9].
In 2007 passive houses were formally introduced to China. Since then several trial projects have been completed or under construction, as shown in Figure 1 [15]. It confirms that China is capable of building passive houses. However, it can be seen that most practices are located in severe cold or cold zones in China. The passive house concept is based on reducing heating losses [16], not in accordance with the fact that in HSCW, cooling load accounts for a considerable proportion of building consumption. It is still worth deep discussion on whether passive houses can be a feasible solution to building energy efficiency problems in HSCW, and what adjustments should be made to the passive house standards, on account of the special climatic conditions in HSCW. This paper presents the dynamic energy consumption simulation results for passives houses, analyzes the effect of building airtightness and insulation on energy consumption, and aims to evaluate the adaptability of passive houses in HSCW from an energy consumption point of view.

2. Program and Experimental Verification

Energy-Plus is a building energy simulation program that builds on the strengths of BLAST and DOE-2. It is based on the Transfer Function Method (TFM) [17]. Design Builder is the first graphic user interface software developed specifically for Energy-Plus in order to resolve the inefficiency of an unfriendly interface [18].
In order to test the accuracy of Design Builder results, a full scale experimental building in Hangzhou was examined under real-time temperature monitoring and the results are used for comparison with the simulation on the corresponding model. Figure 2 shows the experimental building. The configuration of the exterior wall is 240 mm ceramsite aerated concrete block + 15 mm thermal mortar + ceramic tiles. The surface temperature of the envelope was measured by platinum resistance temperature sensor and the step size is 20 min. A meteorological station was erected on the roof to measure ambient temperature, relative humidity, solar radiation, wind speed and direction, etc. The actual measured data was imported into Design Builder for this part of simulation. Figure 3 and Figure 4 show the temperature reading module and station. The internal and external surface temperature (TIS and TES) on the south exterior wall of a room on the second floor has been chosen for illustration. Figure 5 shows the measured and calculated values on 14–16 January and 6–8 July 2016. It can be seen that there are overall good agreements between simulation and measurement results.

3. Simulation Arrangement

The simulation model is a three-floor residential building. Only the results of the central floor have been reported. The standard floor area is 260.64 m2 and the floor height is 3 m, as shown in Figure 6. External insulation is applied to the building envelope. For passive houses the thermal parameters of envelope takes from the passive house standard (“Certification Criteria for Residential Passive House Buildings”) [7]. A reference case is set for comparison, whose envelope thermal parameters takes from the industry standard in HSCW (“Design standard for energy efficiency of residential buildings in hot summer and cold winter zone”) [19], shown in Table 1. The air conditioning (AC) system operates continuously. The heating setpoint temperature is 18 °C and the coefficient of performance (COP) is 1.9. The cooling setpoint temperature is 26 °C and the COP is 2.3. Average internal heat gain intensity is 4.3 W/m2 [19]. Five typical cities in HSCW were selected for simulation and the Chinese Standard Weather Data (CSWD) was used for climate data. In addition, for comparison with the regions where the passive house technology is well established, Berlin was selected as a typical German city. DEU_BERLIN_IWEC was used as the climatic data.

4. Results and Discussion

4.1. Climatic Condition

Figure 7 shows the daily average temperature in typical meteorological years for six cities. It is obvious that Berlin has lower temperatures all year round than any of the cities in HSCW. To further demonstrate this difference, the average temperature in the coldest and hottest month (TC and TH) and the numbers of days in which the daily average temperature is less than or equal to 5 °C (more than or equal to 25 °C) (XC and XH) are compared in Figure 8 and Figure 9 respectively. All of the above four indexes are the basis for climatic division in relevant standards of China [20]. It is found that TC of Berlin is 1.9 °C, while those of five HSCW cities range from 2.0 to 7.5 °C. Only in Hanzhong and Nanjing were the values close to Berlin. TH of Berlin is merely 19.1 °C, far lower than those of five HSCW cities which range from 25.6 to 27.4 °C. In addition, Berlin’s XC is 116 d while XH is merely 5 d, the ratio of the two can reach 23.2. But for HSCW cities, the maximum ratio is merely 1.4 for Hanzhong, the minimum is 0.1 for Guilin. Therefore, there exists huge difference of climatic conditions between Berlin and HSCW. Summer and winter are both cooler in Berlin, and in summer it would be more significant.
Climatic conditions have a deep influence on actual occupant heating and cooling behaviors, and furthermore, will affect the building energy consumption composition. So it should be noted that just because passive houses can achieve excellent energy-saving effects, it does not mean that they are applicable in HSCW too. Detailed analysis combined with actual climatic conditions is necessary on the adaptability of passive houses in this region.

4.2. Airtightness

Passive houses have strict requirements for building airtightness. In order to find the optimal airtightness for passive houses in HSCW, three different ventilation modes are considered here: (1) Mode 1: 1.0 ac/h for average natural infiltration rate (ACH). This value comes from the industry standard in HSCW, which reflects the current situation that the airtightness of existing buildings is poor due to the late start of building energy-saving in HSCW. For the reference case the ACH is 1.0 ac/h as well; (2) Mode 2: 0.5 ac/h for ACH. Previous studies have shown that when indoor air exchange rate is below 0.5 ac/h, many health problems would occur [21]. For this reason many European relevant standards limit the ACH to not lower than 0.5 ac/h [22]. In severe cold and cold zones of China, the ACH is 0.5 ac/h as well [23]. For Mode 1 and 2, since the natural infiltration can satisfy the basic indoor fresh air demand, mechanical ventilation is no longer needed; (3) Mode 3: 0.6 ac/h for average natural infiltration rate when the building envelope is subjected to a 50 Pa pressure (ACH50). This value comes from the passive house standard, which recognizes that naturally, the pressure subjected to the envelope would not reach 50 Pa, and it can be converted between ACH and ACH50 with Equation (1):
ACH50 = ACH/n,
where n is correlation factor related with the climate, stack effect, etc. For Chinese buildings n = 17 [24]. So 0.6 ac/h for ACH50 is equal to 0.035 ac/h for ACH (close to 0). For Mode 3 mechanical ventilation must be employed to satisfy fresh air demand. In the simulation, the strength of mechanical ventilation is set to 0.5 ac/h and the electrical efficiency is 0.45 Wh/m3 with 75% heat recover efficiency. It would operates all the day.
The distribution of annual indoor heat gain and loss in different modes is first analyzed, and Hangzhou is used as an example. If natural ventilation is not carried out, it is shown in Figure 10a that in heating period, the ACH decreasing heat loss for natural infiltration (QINF) can be reduced significantly. When compared to Mode 2, even the heat loss for mechanical ventilation (QMV) is additional, and in Mode 3, the total heat loss is still less. Considering that the solar heat gain through windows and internal heat gain (QSO and QI) are identical in three modes, the annual heating load (QAC) would be reduced. Compared with Mode 1, QAC is reduced by 63.0% in Mode 2 and 94.4% in Mode 3. It is very close to 0 in Mode 3, which means in this condition QSO and QI can basically satisfy the indoor heating demand. As for cooling period, it can be found in Figure 10b that the effect on QINF of ACH is much weaker than in heating period. As a result, when compared with Mode 1, QAC is reduced by 5.8% in Mode 2 and 11.3% in Mode 3, much lower than heating load. In conclusion, annual heating and cooling load are both reduced with decreasing ACH, and the effect on the heating load is more significant.
For buildings in HSCW, during night and early morning in summer, outdoor temperature might drop to lower than indoor temperature. In this period residents can open exterior windows, and take full advantage of natural ventilation to lower the indoor temperature. Adding natural ventilation in the Design Builder program, the air exchange rate during natural ventilation is 0–5.0 ac/h and it operates only when outdoor temperature is lower than indoor temperature in summer. From the comparison of Figure 10b and Figure 11, it can be seen that with natural ventilation operating the annual cooling load can be reduced significantly in all cases. The reduction percent is 6.3%, 14.0%, 20.8% and 23.7% for reference case and three modes respectively. The heat dissipation effect by natural ventilation operating in a certain period is much better than that by mechanical ventilation. So natural ventilation has an excellent effect on cooling energy-saving and should be made good use of.
Secondly the total annual electricity consumption (only including heating, cooling and mechanical ventilation) in different modes is analyzed. Equation (2) is the transformation formula of heating or cooling load and electricity consumption:
HE or CE = QAC/COP,
where HE is the annual heating electricity consumption and CE is the annual cooling electricity consumption, COP is 1.9 for heating and 2.3 for cooling. As shown in Figure 12, the comparative result of annual total electricity consumption in different modes is: Reference case > Mode 3 > Mode 1 > Mode 2. Compared with Mode 1 and Mode 2, although there is a certain reduction of annual heating and cooling consumption in Mode 3, this reduction is still not enough to neutralize the accompanying annual mechanical ventilation consumption. As for other cities, shown in Figure 13, the total consumption in Mode 3 is always higher than in Mode 2, except for Berlin. In Berlin, the reduction of annual heating and cooling consumption can reach 6.01 kW·h/(m2·a), much higher than five HSCW cities, and this value exceeds mechanical ventilation consumption. So only in Berlin the annual total consumption in Mode 3 is lower than Mode 2. The reason lies in the difference of building energy consumption composition between Berlin and HSCW. Since summer and winter are both cooler in Berlin, annual heating demand is higher and cooling demand is lower. The ratio of heating and cooling electricity consumption (r) is used to characterize this energy consumption composition. The calculation formula is:
r = HE/CE,
As seen in Figure 14, for Berlin the r value can reach 42.4 and 13.1 in Mode 2 and Mode 3, while for HSCW cities, the average is only 0.7 and 0.1. It has been confirmed that the effect of ACH on heating load is more significant than cooling load, which means in cities with a bigger r value, the improvement of building airtightness can achieve better energy efficiency. However, for HSCW cities the r is generally small, therefore the total electricity consumption in Mode 3 is higher instead due to adding mechanical ventilation electricity consumption.
In conclusion, although it could not be ignored that mechanical ventilation may generate improvement of indoor air environment, from an energy-saving point of view, Mode 3 is not the most applicable ventilation mode for passive houses in HSCW, which is required by the passive house standard.

4.3 Exterior Wall Insulation

Besides ventilation, the envelope insulation is another important content in the passive house standard. In this part of simulation, the ventilation mode is set as Mode 2 and Mode 3 respectively, and exterior wall heat transfer coefficient (U) varies from 0.15 to 1.50 W/(m2·K) by each 0.15 gap. 0.15 W/(m2·K) is the value in the passive house standard for HSCW.
Natural indoor temperature (TNA) can reflect the comprehensive regulation of envelope to ambient climatic conditions and occupant behavior without air-conditioning. Hangzhou as an example, as shown in Figure 15, with the U value decreasing, the average TNA in the coldest month rises gradually and in the hottest month it drops. The effect on the former is much more remarkable. When U is equal to 0.15 W/(m2·K), compared with the reference case, average TNA in the coldest month rises up to 5.7 °C in Mode 2 and 14.9 °C in Mode 3, and it rises faster with U decreasing. In the hottest month the average TNA merely drops 0.8 °C. So it can be concluded that the improvement of exterior wall insulation can enhance indoor thermal environment of passive houses in both summer and winter.
When air-conditioning operates, Figure 16 shows that the numbers of annual heating and cooling hours decrease simultaneously with the U value decreasing. When U is equal to 0.15 W/(m2·K), compared with the reference case, the number of annual heating hours decreases by 234 h (18.1%) in Mode 2 and 738 h (57.1%) in Mode 3, and it decreases faster with U decreasing. The number of annual cooling hours merely decreases by about 3%.
On the basis that the improvement of exterior wall insulation can enhance indoor thermal environment and reduce annual heating and cooling hours, it generates a certain reduction of annual heating and cooling electricity consumption, as shown in Figure 17. Energy saving rate (R) is used to characterize the energy saving effect. For the reference case the R value is 50% [10]. It actually means that when compared with traditional buildings without insulation, the annual energy consumption of reference case is 50% lower. Therefore, R can be calculated by Equation (4):
R = (AE0/50% − AEi)/(AE0/50%) × 100%,
where AEi is annual total electricity consumption at a certain U value and AE0 is annual total electricity consumption of the reference case. When U is equal to 0.15 W/(m2·K), R can reach 84.2% in Mode 2 and 74.8% in Mode 3. Figure 18 shows the distribution of heat gain and loss in Mode 2 in Hangzhou. In heating period, compared with the case U = 1.50 W/(m2·K), QE is 10.69 kW·h/(m2·a) lower when U is equal to 0.15 W/(m2·K), which results in about a 75% reduction of annual heating load. In the cooling period, the variation of QE comes to 6.09 kW·h/(m2·a), and results in about 35% reduction of annual cooling load. The effect on heating load is more remarkable.
Therefore, the improvement of exterior wall insulation can generate a significant reduction of annual total energy consumption. Besides, there exists difference among different cities. As shown in Figure 19 and Figure 20, when the ventilation mode and U value is certain, R is always highest in Hanzhong, the coldest city of the five and lowest in Guilin, the hottest city. The relationship of R and U is nearly linear. In the same ventilation mode, the slope of U-R line is biggest for Hanzhong and smallest for Guilin. It means the improvement of exterior wall insulation can achieve better energy-saving effects in colder cities. The reason lies in the different ratio of heating and cooling electricity consumption (r) as well. It has been confirmed that the effect of exterior wall insulation on heating load is more significant than cooling load, in colder cities the r value is smaller, the annual energy-saving effect caused by exterior wall insulation is better consequently. Additionally, the R value is always bigger in Mode 2 than Mode 3, which again evidences the conclusion of Section 4.2.
From the analysis in Section 4.2 and Section 4.3, it can be seen that the ratio of heating and cooling electricity consumption (r) becomes an important index in energy efficiency evaluation of passive houses. Considering that improvement of building airtightness and exterior wall insulation, both have a better energy-saving effect on heating load, it actually implies that passive houses can achieve higher energy efficiency in the region with a bigger r value like Berlin. However, in HSCW the r value is generally small, and therefore, the adaptability of the passive house standard should be reevaluated. Climatic conditions would affect actual occupant heating and cooling behaviors, and become a critical factor of r. It is beneficial to the healthy development of passive houses in HSCW if taking r into consideration when selecting the most reasonable airtightness level and insulation construction.
Recently passive houses have become one of the hotspot issues in building of energy-saving houses in China. This paper analyzed the effect airtightness and exterior wall insulation on energy consumption of passive houses in HSCW. Future research could focus on the economic efficiency and indoor environmental comfort, and from these two aspects, the adaptability of passive houses in this region can be evaluated more completely.

5. Conclusions

  • Summer and winter are both cooler in Berlin, and that would be more significant in summer. It will generate a significant difference in actual occupant energy-consuming behaviors and building energy consumption composition.
  • Decrease of ACH can reduce annual heating and cooling load, and the effect on heating load is more remarkable. Well-organized natural ventilation is quite beneficial to cooling and energy-saving. Superb airtightness (ACH50 = 0.6 ac/h) with mechanical ventilation may generate higher electricity consumption because the reduction of heating and cooling consumption is not enough to neutralize the accompanying mechanical ventilation consumption. The most energy-saving ventilation mode in HSCW is 0.5 ac/h for ACH with well-organized natural ventilation.
  • Improvement of exterior wall insulation can reduce annual heating and cooling load, and the effect on heating load is more remarkable. In colder cities the energy-saving effect is heightened by decreasing the exterior wall heat transfer coefficient.
  • This paper proposes that the ratio of heating and cooling electricity consumption (r) should be an important index in passive house energy-saving effect evaluation, as it would contribute to reasonable selection of ventilation mode and exterior wall heat transfer coefficient, and benefit the healthy development of passive houses in HSCW.

Author Contributions

Xiaoqian Qian contributed to the conception of this study and the development of its methodology. Xin Fu and Lina Wang performed the experiments. Xin Fu performed the simulation calculation, analyzed the data and wrote the manuscript. All authors have read and approved the final manuscript.

Conflicts of Interest

The authors declare no conflict of interest.

Abbreviations

The following abbreviations are used in this manuscript:
HSCWhot summer and cold winter zone in China
rthe ratio of heating and cooling electricity consumption
PHIPassive House Institute
TISinternal surface temperature of exterior wall (°C)
TESexternal surface temperature of exterior wall (°C)
ACair conditioning
SHGCsolar heat gain coefficient
Uheat transfer coefficient (W/m2·K)
COPthe coefficient of performance
TCthe average temperature in the coldest month
THthe average temperature in the hottest month
XCthe numbers of days in which the daily average temperature is less than or equal to 5 °C
XHthe numbers of days in which the daily average temperature is more than or equal to 25 °C
ACHaverage natural infiltration rate (ac/h)
ACH50average natural infiltration rate when the building envelope is subjected to a 50 Pa pressure(ac/h)
QACannual heating or cooling load (kW·h/m2·a)
QSOsolar heat gain through exterior windows (kW·h/m2·a)
QIinternal heat gain (kW·h/m2·a)
QMVheat gain or loss for mechanical ventilation (kW·h/m2·a)
QNVheat gain or loss for natural ventilation (kW·h/m2·a)
QINFheat gain or loss for natural infiltration (kW·h/m2·a)
QEheat gain or loss through envelope (kW·h/m2·a)
HEannual heating electricity consumption (kW·h/m2·a)
CEannual cooling electricity consumption (kW·h/m2·a)
AEannual total electricity consumption (kW·h/m2·a)
TNAnatural indoor temperature (°C)
Renergy saving rate

References

  1. Yu, J.; Yang, C.; Tian, L.; Liao, D. A study on optimum insulation thicknesses of external walls in hot summer and cold winter zone of China. Appl. Energy 2009, 86, 2520–2529. [Google Scholar] [CrossRef]
  2. Chow, D.H.C.; Li, Z.; Darkwa, J. The effectiveness of retrofitting existing public buildings in face of future climate change in the hot summer and cold winter region of China. Energy Build. 2013, 57, 176–186. [Google Scholar] [CrossRef]
  3. Ichinose, T.; Lei, L.; Lin, Y. Impacts of shading effect from nearby buildings on heating and cooling energy consumption in hot summer and cold winter zone of China. Energy Build. 2017, 136, 199–210. [Google Scholar] [CrossRef]
  4. Zhang, S.; Zhang, L.; Wei, H.; Jing, J.; Zhou, X.; Zhang, X. Field testing and performance analyses of ground source heat pump systems for residential applications in Hot Summer and Cold Winter area in China. Energy Build. 2016, 133, 615–627. [Google Scholar] [CrossRef]
  5. Lu, S.; Tang, X.; Ji, L.; Tu, D. Research on energy-saving optimization for the performance parameters of rural-building shape and envelopee by TRNSYS-GenOpt in hot summer and cold winter zone of China. Sustainability 2017, 9, 294. [Google Scholar] [CrossRef]
  6. Chen, X.; Wen, Y.; Li, N. Energy efficiency and sustainability evaluation of space and water heating in urban residential buildings of the hot summer and cold winter zone in China. Sustainability 2016, 8, 989. [Google Scholar] [CrossRef]
  7. Passive House Institute. Certification Criteria for Residential Passive House Buildings. 2015. Available online: http://passiv.de/downloads/03_certification_criteria_residential_en.pdf (accessed on 15 January 2015).
  8. Younes, C.; Abi Shdid, C.; Bitsuamlak, G. Air infiltration through building envelopees: A review. J. Build. Phys. 2012, 35, 267–302. [Google Scholar] [CrossRef]
  9. Schnieders, J.; Feist, W.; Rongen, L. Passive houses for different climate zones. Energy Build. 2015, 105, 71–87. [Google Scholar] [CrossRef]
  10. Mihai, M.; Tanasiev, V.; Dinca, C.; Badea, A.; Vidu, R. Passive house analysis in terms of energy performance. Energy Build. 2017, 144, 74–86. [Google Scholar] [CrossRef]
  11. Persson, M.-L.; Roos, A.; Wall, M. Influence of window size on the energy balance of low energy houses. Energy Build. 2006, 38, 181–188. [Google Scholar] [CrossRef]
  12. Audenaert, A.; De Cleyn, S.H.; Vankerckhove, B. Economic analysis of passive houses and low-energy houses compared with standard houses. Energy Policy 2008, 36, 47–55. [Google Scholar] [CrossRef]
  13. Dan, D.; Tanasa, C.; Stoian, V.; Brata, S.; Stoian, D.; Nagy Gyorgy, T.; Florut, S.C. Passive house design—An efficient solution for residential buildings in Romania. Energy Sustain. 2016, 32, 99–109. [Google Scholar] [CrossRef]
  14. Georges, L.; Skreiberg, Ø.; Novakovic, V. On the proper integration of wood stoves in passive houses under cold climates. Energy Build. 2014, 72, 87–95. [Google Scholar] [CrossRef]
  15. Zhang, X. Passive House Construction Situation in China. Available online: http://www.passivehouse.org.cn/al/ (accessed on 23 June 2017). (In Chinese).
  16. Feist, W.; Schnieders, J.; Dorer, V.; Haas, A. Re-inventing air heating: Convenient and comfortable within the frame of the passive house concept. Energy Build. 2005, 37, 1186–1203. [Google Scholar] [CrossRef]
  17. Crawley, D.B.; Lawrie, L.K.; Winkelmann, F.C.; Buhl, W.F.; Huang, Y.J.; Pedersen, C.O.; Strand, R.K.; Liesen, R.J.; Fisher, D.E.; White, M.J.; et al. EnergyPlus: Creating a new-generation building energy simulation program. Energy Build. 2001, 33, 319–331. [Google Scholar] [CrossRef]
  18. Tindale, A. Designbuilder and energyplus. Build. Energy Simul. User News 2004, 25, 2–5. [Google Scholar]
  19. Ministry of Housing and Urban-Rural development of China. Design Standard for Energy Efficiency of Residential Buildings in Hot Summer and Cold Winter Zone; JGJ 134-2010; China Architecture and Building Press: Beijing, China, 2010. (In Chinese)
  20. Bureau of Quality and Technical Supervision of China; Ministry of Construction of China. Standard of Climatic Regionalization for Architecture; GB 50178-93; China Planning Press: Beijing, China, 2001. (In Chinese)
  21. Oie, L.; Nafstad, P.; Botten, G.; Magnus, P.; Jaakkola, J.K. Ventilation in homes and bronchial obstruction in young children. Epidemiology 1999, 10, 294–299. [Google Scholar] [CrossRef] [PubMed]
  22. Dimitroulopoulou, C. Ventilation in European dwellings: A review. Build. Environ. 2012, 47, 109–125. [Google Scholar] [CrossRef]
  23. China Architecture Science Institute. Design Standard for Energy Efficiency of Residential Buildings in Cold and Severe Cold Zone; JGJ 26-2010; China Architecture and Building Press: Beijing, China, 2010. (In Chinese) [Google Scholar]
  24. Chen, S.; Levine, M.D.; Li, H.; Yowargana, P.; Xie, L. Measured air tightness performance of residential buildings in North China and its influence on district space heating energy use. Energy Build. 2012, 51, 157–164. [Google Scholar] [CrossRef]
Figure 1. Passive house projects in China.
Figure 1. Passive house projects in China.
Sustainability 09 01097 g001
Figure 2. The experimental building.
Figure 2. The experimental building.
Sustainability 09 01097 g002
Figure 3. Temperature reading module.
Figure 3. Temperature reading module.
Sustainability 09 01097 g003
Figure 4. The meteorological station.
Figure 4. The meteorological station.
Sustainability 09 01097 g004
Figure 5. Internal and external surface temperature of exterior wall in simulation and measurement (a) 14 to 16 January 2016; (b) 6 to 8 July 2016.
Figure 5. Internal and external surface temperature of exterior wall in simulation and measurement (a) 14 to 16 January 2016; (b) 6 to 8 July 2016.
Sustainability 09 01097 g005
Figure 6. Standard floor plan.
Figure 6. Standard floor plan.
Sustainability 09 01097 g006
Figure 7. Daily average temperature.
Figure 7. Daily average temperature.
Sustainability 09 01097 g007
Figure 8. Average temperature in the coldest and hottest month.
Figure 8. Average temperature in the coldest and hottest month.
Sustainability 09 01097 g008
Figure 9. Numbers of days in which daily average temperature is ≤5 °C for winter period and ≥25 °C for summer period.
Figure 9. Numbers of days in which daily average temperature is ≤5 °C for winter period and ≥25 °C for summer period.
Sustainability 09 01097 g009
Figure 10. Distribution of heat gain and loss without natural ventilation in Hangzhou (a) heating period; (b) cooling period (In one case, former column represents heat loss, latter column represents heat gain, the same below).
Figure 10. Distribution of heat gain and loss without natural ventilation in Hangzhou (a) heating period; (b) cooling period (In one case, former column represents heat loss, latter column represents heat gain, the same below).
Sustainability 09 01097 g010
Figure 11. Effect of natural ventilation on cooling load.
Figure 11. Effect of natural ventilation on cooling load.
Sustainability 09 01097 g011
Figure 12. Annual electricity consumption in Hangzhou.
Figure 12. Annual electricity consumption in Hangzhou.
Sustainability 09 01097 g012
Figure 13. Annual electricity consumption in Mode 2 and Mode 3 in different cities (with natural ventilation).
Figure 13. Annual electricity consumption in Mode 2 and Mode 3 in different cities (with natural ventilation).
Sustainability 09 01097 g013
Figure 14. The ratio of heating and cooling electricity consumption.
Figure 14. The ratio of heating and cooling electricity consumption.
Sustainability 09 01097 g014
Figure 15. Average natural indoor temperature in the hottest and coldest month.
Figure 15. Average natural indoor temperature in the hottest and coldest month.
Sustainability 09 01097 g015
Figure 16. Annual heating and cooling hours.
Figure 16. Annual heating and cooling hours.
Sustainability 09 01097 g016
Figure 17. Annual electricity consumption in Hangzhou.
Figure 17. Annual electricity consumption in Hangzhou.
Sustainability 09 01097 g017
Figure 18. Distribution of heat gain and loss when U = 0.15 and 1.50 (Mode 2 in Hangzhou).
Figure 18. Distribution of heat gain and loss when U = 0.15 and 1.50 (Mode 2 in Hangzhou).
Sustainability 09 01097 g018
Figure 19. Annual electricity consumption in other cities (a) Hanzhong; (b) Nanjing; (c) Changsha; (d) Guilin. (At a certain U value, former column represents Mode 2, latter column represents Mode 3).
Figure 19. Annual electricity consumption in other cities (a) Hanzhong; (b) Nanjing; (c) Changsha; (d) Guilin. (At a certain U value, former column represents Mode 2, latter column represents Mode 3).
Sustainability 09 01097 g019
Figure 20. Energy saving rate variation with exterior wall heat transfer coefficient.
Figure 20. Energy saving rate variation with exterior wall heat transfer coefficient.
Sustainability 09 01097 g020
Table 1. Thermal parameters of envelope.
Table 1. Thermal parameters of envelope.
EnvelopeConfigurationHeat Transfer Coefficient (W/(m2·K))
Passive HousesReference Case
Exterior wall10 mm cement plaster + 240 mm brick + a certain thickness of polystyrene board + 10 mm cement plaster0.151.5
Roof10 mm cement plaster + a certain thickness of polystyrene board + 100 mm reinforced concrete + 10 mm cement plaster0.151.0
Exterior windowsdouble-layer hollow glass0.85 (SHGC = 0.40)4.0 (SHGC = 0.75)

Share and Cite

MDPI and ACS Style

Fu, X.; Qian, X.; Wang, L. Energy Efficiency for Airtightness and Exterior Wall Insulation of Passive Houses in Hot Summer and Cold Winter Zone of China. Sustainability 2017, 9, 1097. https://doi.org/10.3390/su9071097

AMA Style

Fu X, Qian X, Wang L. Energy Efficiency for Airtightness and Exterior Wall Insulation of Passive Houses in Hot Summer and Cold Winter Zone of China. Sustainability. 2017; 9(7):1097. https://doi.org/10.3390/su9071097

Chicago/Turabian Style

Fu, Xin, Xiaoqian Qian, and Lina Wang. 2017. "Energy Efficiency for Airtightness and Exterior Wall Insulation of Passive Houses in Hot Summer and Cold Winter Zone of China" Sustainability 9, no. 7: 1097. https://doi.org/10.3390/su9071097

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop