1. Introduction
Innovative irrigation practices and new design techniques can enhance water efficiency, gaining an economic advantage and reducing environmental burdens [
1]. Nowadays, reducing water and energy consumption while maintaining high levels of crop yields is imperative for sustainability [
2]. In small areas, where the topography is not necessarily flat, micro-irrigation is currently considered one of the most efficient and widely applied methods, since it reduces water losses due to evaporation. Many studies have focused on simple methods to design drip irrigation systems [
3,
4,
5] and even to minimize the water and the energy consumption [
4,
6]. However, to optimize capital and operating costs, many private companies are investing in the mechanization of irrigation [
7]. Especially in the last few decades, the use of Center-Pivot irrigation systems (
CPIS) has significantly increased when almost flat areas to irrigate are available, since it makes farm management easier, allows much larger coverage, and is less time-consuming compared to the other irrigation systems.
Thus, CPISs are replacing currently used irrigation systems in reasonably flat areas thanks to their automation, reliability, application uniformity, and ability to operate on relatively rough topography. In fact, CPISs are easily automated, and can require much lower labor costs than mobile sprinkler systems that need to be displaced in different sectors of the farm, according to irrigation scheduling.
Several studies have been performed on
CPIS hydraulics [
8,
9,
10,
11], with the aim to increase the uniformity of the water application rate and limiting the peak of instantaneous precipitation rates, which may determine soil erosion [
12]. Reddy and Apolayo [
13] derived a correction factor to be used to estimate the friction losses along
CPISs. Scaloppi and Allen [
14] developed analytical equations to characterize the hydraulics of Center-Pivot laterals with and without an end-gun sprinkler. By comparing the performance of fixed and rotating spray plate sprinklers, Faci et al. [
15] stated that the latter installed at larger spacing along the pivot’s lateral are characterized by higher uniformity coefficients, with smaller local peaks of instantaneous precipitation rates. Moreover, larger spacing favors the reduction in undesired runoff, determining water losses and erosion, which occur when the water application rate exceeds the soil’s infiltration capacity [
16].
The design problem could be complicated by the fact that machines must be designed to match each site and information must be collected to characterize the variability of the soils [
17], topography, infiltration rates, microclimates across a field, and expected crop water use patterns over the season [
18].
Valin et al. [
19] developed a software application, named DEPIVOT, which the
CPIS design possible according to five sub-models. Users can verify initial target design values and then compare alternative sprinkler packages until appropriate conditions are established.
In order to optimize water use efficiency, de Almeida et al. [
20] proposed a new system called localized mobile drip irrigation (IRGMO) in the attempt to combine the practicality and benefits of a Center-Pivot system with the efficiency and water savings of drip irrigation systems, which, however, due to the small-sized drippers, can be affected by plugging more than sprinklers.
Instead of common
CPISs, equipped with drippers (IRGMO) or sprinklers, Baiamonte and Baiamonte [
21] analyzed the ‘geometry’ of the irrigated areas of a
CPIS equipped with rotating sprinkler guns, which provide a solution to the plugging phenomena due to the larger-sized nozzles, where water use efficiency and uniformity distribution have not been investigated yet.
To ensure the uniformity of the water application rate,
CPISs commonly equipped by sprinklers require increasing the flow rates along the lateral because the sprinklers farther from the pivot move faster, and therefore, their instantaneous application rates must be greater. Thus, the irrigated area under a
CPIS expands substantially with the increasing system length. To irrigate the increasing area along the pipe, while maintaining a constant water application rate, different methodologies have been proposed, for example: an increasing flow rate of equally spaced sprinklers, a gradually decreasing sprinkler spacing of equal-flow sprinklers along the Center-Pivot lateral [
8,
22,
23], or a semi-uniform spacing [
24], which is a combination of the first two methods.
Although the most common approach is to have equally spaced sprinklers with increasing flow rates (nozzle sizes) along the Center-Pivot lateral [
23], probably because it is easy to provide from a practical point of view, a variable spacing system allows arranging the sprinklers at strategic locations on the lateral so that the distribution of water along the lateral is uniform [
25].
Following this line of thinking, recently, a simple analytical design procedure was introduced [
26]. The method is based on a gradually decreasing sprinkler spacing along a pivot lateral with constant diameter and sprinkler flow rate, allowing to set favorable and uniformly distributed water application rates. The need for changing the inside diameter and the sprinkler flow rate to fully cover the center pivot irrigated area was emphasized. However, no suggestions were given to design multiple diameter laterals characterized by different values of the inside pipe diameter. The use of multiple diameter size, sometimes denoted as telescoping pipes, is a method of planning a center pivot for minimum water flow friction loss and low operating pressure, and thus, lower pumping costs. Multiple diameter size uses a combination of pipe sizes [
27] based on the amount of water flowing through, and it is usually accomplished in the whole span lengths. Usually, dealers use computer telescoping programs based on numerical and time-consuming solutions to select mainline pipe sizes for the lowest purchase price and operating costs [
28].
The objective of this paper is to extend to
CPIS design the procedure introduced by Baiamonte et al. [
26] to laterals with multiple size diameters, according to a gradually decreased spacing of equal-flow sprinklers. The procedure makes it possible to set any water application rate and assures water application uniformity.
The paper is organized as follows. Following this introduction, first, the design procedure proposed by Baiamonte et al. [
26] is briefly summarized. For multiple size diameters, the new design procedure is introduced, which makes it possible to choose different pipe diameters in order to save water and energy. In
Section 3, several applications based on the proposed hydraulic design procedure were performed, by varying the number of sprinklers in the inner and in the outer laterals and by varying the corresponding pressure head tolerances.
2. Theory
For constant lateral diameter and sprinkler flow rate, and for gradually decreased sprinkler spacing, Baiamonte et al. [
26] proposed a simple
CPIS design procedure, where a uniform water application rate was imposed. This procedure is briefly summarized in the following and helps describe the new suggested approach for designing telescoping pipe laterals.
Along a given
CPIS with radius,
r0 (m), Baiamonte et al. [
26] considered a lateral where
N sprinklers,
j = 1, 2, …
N, with gradually decreased sprinkler spacing,
s1,
s2, …
sN, are installed (
Figure 1).
During the lateral rotation, with angular velocity ω, each sprinkler
j fully irrigates an annulus area with gradually decreased width,
w0,
w1, …
wN-1. The annulus area irrigated by each sprinkler
j,
A, was imposed equal for all the sprinklers, and it was expressed by the ratio between the design sprinkler flow rate,
qn, and the desired water application rate,
i:
Once a constant
qn is fixed, Equation (1) states that for a uniform water application rate,
i, a constant irrigated annulus area
A, for each sprinkler installed with variable spacing (
Figure 1), needs to be imposed. One parameter,
A*, i.e., the annulus area,
A, normalized with respect to the pivot irrigated area,
, can be used to fully describe the
CPIS geometric and the sprinkler flow rate characteristics:
For different values of
r0 and
qn parameters,
Figure 2 shows
A* as a function of the water application rate,
i, indicating the high variability of
A* (four orders of magnitude). The figure also reports the
A* values corresponding to the applications, run #1 and run #2, that will be discussed later.
According to Equation (1), Baiamonte et al. [
26] found the variable decreased sprinkler spacing sequence that needs to be imposed for a uniform water application rate, which, in this work, will be associated with the
A* parameter (Equation (2)). For the first annulus, where the first outer sprinkler,
j = 1, is installed (
Figure 1), the width,
w0, normalized with respect the
CPIS radius,
r0, can be expressed by using
A* (Equation (2)), which Baiamonte et al. [
26] did not consider:
Once
w*0 is established, the normalized annulus width of the sprinklers after the first one (
j > 1,
Figure 1) was determined by imposing for each sprinkler a constant annulus area (
A*), according to a recurrence relation that recursively defines a sequence of gradually decreasing annulus widths, associated with
A*. The distance between the edge of each width and the center-pivot,
rj (
Figure 1), normalized with respect to
r0, is denoted as
r*j. Therefore, for the first annulus width, wide
w0, the initial terms,
r*0 =
r0/
r0 = 1 and
w*0 (and
A*, Equation (3)), are established, and the
w*j sequence can be derived:
where
r*j,
w*j,
r*j−1, and
w*j−1 are the radius and annulus width corresponding to the sprinkler
j and
j−1, normalized with respect to lateral length,
r0. Thus, each further term of the
w*j sequence is defined as a function of the preceding terms and corresponds to a sequence of annuli characterized by a constant area,
A, irrigated by each sprinkler, thus assuring a uniform water application rate.
Equation (4) also makes it possible to derive the sprinkler spacing sequence, which needs for the hydraulic design of the
CPIS lateral. Indeed, considering that each sprinkler is in the middle of the annulus width (
Figure 1) yields:
where
s*j is the sprinkler spacing between the sprinkler
j and
j−1, normalized with respect to lateral length,
r0. For
N sprinklers, the corresponding normalized lateral length,
L*, which is referred to the distal end of the lateral, starting from the outer sprinkler (
Figure 1), equals to:
For different
A* values, the cumulated
w*j, ∑
w*j and the cumulated
s*j, ∑
s*j are graphed in
Figure 3a and in
Figure 3b, respectively, as a function of the sprinkler number
j, illustrating an expected monotonically increasing trend. Moreover, for a fixed
A*, because of the radicand constrain in Equation (4), depending on the geometric and hydraulic
CPIS characteristics, a lateral length fully covering the
CPIS radius (∑
w*j = 1) cannot always be achieved. Indeed, to fully cover the lateral length, different sprinkler characteristics, i.e.,
qn, should be considered. However, the latter issue is beyond the purpose of this paper, which aims to design
CPIS laterals by only using different inside diameters.
Therefore, the cumulated sprinkler interspace displayed in
Figure 3b can be applied to any pair or triplet of diameters of the
CPIS lateral, and the two or more sectors in which the irrigated area is subdivided are only determined by the changes in lateral diameters.
Of course, the number of sprinklers,
N, which can be installed along the lateral is also affected by
A*. For a high number of simulations performed for reasonable values of the triplet (
i,
r0,
qn),
N is graphed in
Figure 4 versus
A*, together with (see
Figure 5): (i) the normalized width irrigated by the first sprinkler
w*0 (Equation (3)), (ii) the normalized width irrigated by the last sprinkler
w*N, and (iii) the normalized width irrigated by the total number of sprinklers,
W*N:
Figure 4 shows that
N versus
A* (solid line) is fitted by a power law well, and, of course, so is
w*0 (Equation (3)). Contrarily,
W*N and
w*N show a worse power-law fitting than
N and
w*0, which is due to the sequence annuli randomness in fully covering or not fully covering the entire pivot area, already discussed for
Figure 3. However, it seems that the lower
A* is, the more the total annuli width,
W*N (blue circles), approaches the unity (fully coverage).
High values of
A* values, greater than those displayed in
Figure 4, could be not recommended because the corresponding high widths,
w*0 and
w*N, even for high spray distance (
Figure 1b), might not be covered by one sprinkler, and thus, they should be preliminarily checked [
26].
Figure 4 also illustrates the values corresponding to the applications run #1 and run #2 that will be performed later.
Telescoping laterals do not require to use the total number of sprinklers installed in the same pipe diameter, since the pipe diameter could be changed after a number of sprinkler
NI <
N, according to two or more than two sectors. For a clear legibility of the considered sketch, for the case of two sectors, i.e., dual-diameter lateral,
Figure 5 illustrates the aforementioned parameters,
w*0,
w*N,
W*N, where the subscript I refers to the sector I (outer lateral), whereas the subscript II refers to the sector II (inner lateral). The last sprinkler width,
w*N, which belongs to a common
w*j sequence of the two sectors (green circles in
Figure 4), is associated with the total number of sprinklers,
N =
NI +
NII.
As an example, for run #1, where a number of sprinklers in sector I,
NI = 28, was imposed (
Table 1),
Figure 6 shows the corresponding two sectors that could be geometrically designed with a dual-diameter lateral.
Hydraulic Design
Once the geometry of the center-pivot was designed, Baiamonte et al. [
26] also provided an easy to apply hydraulic design procedure, starting from a simplified approach that Baiamonte [
4] developed for drip laterals, according to the energy balance. Baiamonte et al. [
26] described the pressure head distribution (PHD) line of the
N sprinklers, under the assumption to neglect the variation of sprinkler flow rate,
qn, along the lateral [
29,
30] and local losses, as generally assumed for the pivot laterals [
31], which contrarily have to be considered in the drip laterals design.
The
CPIS design procedure suggested by Baiamonte et al. [
26] for one-diameter lateral could be extended for three or more sectors, but for a simplified description of the procedure, only two sectors will be considered here. Under constant
qn, for sector I and for sector II, i.e., for the outer lateral and for the inner laterals (
Figure 5 and
Figure 6), the PHD line can be expressed as:
respectively, where
h*j is the pressure head at the sprinkler
j;
h*min is the minimum pressure head to be imposed at the first sprinkler
j = 1, both normalized with respect to
r0,
hj/
r0 and
hmin/
r0, respectively; and
KI and
KII denote the parameters of sector I and of sector II, accounting for the friction losses (friction head loss gradient) and according to the well-accepted Hazen–Williams’s resistance equation [
5,
32], also recently considered for
CPIS [
33]:
where
DI (m) and
DII (m) are the inside diameters of the outer lateral and of the inner laterals (sector I and II), respectively, and
C is a pipe smoothness factor, which is a function of the pipe material’s characteristics [
32,
34].
For drip laterals, Baiamonte [
4] showed that based on the energy balance equation, where the hypothesis to neglect the variation of sprinkler flow rate was assumed, the design problem of drip laterals can be solved by imposing a fixed pressure head tolerance, δ, which depends on the desired emission uniformity coefficient of Keller and Karmeli [
35]. Baiamonte [
4] also derived analytical solutions that facilitate the micro-irrigation design for one-lateral units [
4,
36] as well as for rectangular micro-irrigation units [
37].
For
CPIS, a similar approach as that described for drip laterals, for a fixed minimum normalized pressure head,
h*min, the maximum pressure head at
j =
NI, normalized with respect to
r0 and denoted as
h*n (
Figure 7a), can be imposed to delimit the PHD line in the range
h*min ≤
h*j ≤
h*
n:
Denoting δ
I the pressure head tolerance assumed for sector I, the normalized average pressure
h*n,I (
Figure 7a) can be used to express
h*min and
h*n, respectively:
Using Equations (13) and (14),
h*n can be expressed as a function of
h*min:
Substituting Equation (15) into Equation (10) provides:
For sector II, denoting
h*max and δ
ΙΙ, the maximum normalized pressure and the pressure head tolerance for the inner lateral, a similar relationship to Equation (16) can be derived, if considering that the maximum normalized pressure of sector I,
h*n, corresponds the minimum normalized pressure head of sector II (
Figure 7a), providing:
where
h*n,II is the average normalized pressure head for the inner lateral (
Figure 7a). Using Equations (17) and (18),
h*max can be expressed as a function of
h*n:
The normalized maximum pressure head (Equation (19)) can also be expressed as a function of
h*min by using Equation (15):
For run #1, where δ
I = 0.02 was imposed,
h*min,
h*nI,
h*n,
h*nII, and
h*max values are also reported in
Figure 7a, together with their average
h*av = 0.5 (
h*max +
h*min), which will be considered later to evaluate the corresponding coefficient of variation of the pressure heads around
hav,
CVav.
To delimit the PHD variation in sector II (
h*n ≤
h*j ≤
h*max,
Figure 7a), and thus the sprinkler flow rate variations, as for sector I,
h*max can be imposed at the distal end of the lateral (
j =
N =
NI +
NII) in the corresponding energy balance equation (Equation (9)), which by using Equation (12) provides:
Equation (21) makes it possible to determine the
KII relationship:
Finally, substituting Equations (15) and (20) into Equation (22), the
KII parameter as a function of
h*min can be obtained:
Since
h*max also represents the normalized pressure head that the pump system has to provide at the inlet,
h*max ≡
h*min, by using Equation (20), it is also useful to express
KI and
KII as a function of
h*in:
In conclusion, for fixed δI and δII, the K values for the inner and the outer lateral, KI and KII, can be expressed according to any fixed h*min value (Equations (16) and (23)) or to any fixed h*in value (Equations (24) and (25)), once A* (Equation (2)) and any pair of pressure head tolerances (δI, δII), are assumed. Of course, the CPIS pressure head tolerance, δ, is equal to δI + δII. Importantly, for any input data, in the K relationships, the mathematical formulation of the principle of the conservation of energy for the lateral of a Center-Pivot is satisfied, so that the pressure head variation is balanced by the sum of friction losses in between the sprinklers.
Knowledge of
KI and
KII values allows for designing the inner and the outer lateral diameters, by inverting Equations (10) and (11):
The hypothesis to neglect the variation of sprinkler flow rate,
qn, when deriving
K relationships, agrees with the assumption to impose a pressure head tolerance δ
I and δ
II. In fact, along a lateral where sprinklers are installed, it is under limited pressure head variations established by the pressure head tolerances that the ratio between the sprinkler flow rate variation (
qmax–
qmin), and its average,
qn, is low (for
x = 0.5, it equals to 5%, when δ = 10 %), providing a good approximation of this assumption [
38,
39].
3. Applications
For run #1, where
A* = 0.0149 and
r0 = 400 m (
Table 1) were assumed; for fixed pressure heads tolerances δ
I = 0.02 and δ
II = 0.08, so that the
CPIS pressure head tolerance δ = δ
I + δ
II = 10%, as it is usual; for a fixed
hmin = 13.5 m (
h*
min = 0.0338); and for
NI = 28,
Table 2 reports all the design variables previously introduced, in particular the cumulated sprinkler spacing ∑
s*j,I and ∑
s*j,II and the corresponding terms ∑
s*j,I (
j − 1)
1.852 and ∑
s*j,II (
j − 1)
1.852, which are required into the
K relationships (Equations (24) and (25)).
The latter parameters make it possible to calculate the inside diameters of the telescoping lateral,
DI and
DII (
Table 2), by Equations (26) and (27), which resulted in 82.79 mm and 120.58 mm, respectively. Thus, as it is commonly accepted in practice, this dual-diameter case involves using a larger diameter pipe at the beginning of the lateral and then a lower diameter, as the flow rate decreases starting from the pivot axes.
Table 2 also reports the same parameters for the one-diameter lateral (
K and
D), where only Equation (16) was applied to the total number of sprinklers (
N = 67) in order to make a comparison between one-diameter and dual-diameter
CPISs. Towards this aim, for a dual-diameter lateral, the mean weight diameter,
Dm, which could be considered as an index of the investment costs, is also reported in
Table 2.
Dm was calculated as:
where
L*,I =
LI/
L and
L*II =
LII/
L. Of course, for a
CPIS irrigated area fully covered by the sprinklers, the denominator of Equation (28) is equal to the unity.
To compare one-diameter and dual-diameter
CPISs, the corresponding relative difference between one-diameter (
D) and dual diameter (
Dm) laterals, RE
D, was calculated as:
For run #1,
Table 2 shows that
Dm is 4.5% less than the diameter,
D, corresponding to a one-diameter lateral design. Of course,
Dm could be used to roughly detect the most convenient choice of the diameter pair to be considered in the design by an economic point of view, since the lower
Dm is, the lower the telescoping pipe cost will be [
40,
41]. However, a deeper economic analysis should be recommended, since the cost pipe does not necessary vary linearly with the diameter and for the best choice of the lateral diameters, the cost of reducing coupling or adapter should also be considered.
3.1. Numerical Validation
Testing the derived
KI and
KII relationships requires the corresponding PHD lines to be determined, by considering that, for the outer lateral, the PHD line can be expressed by (Equation (8)), whereas the inner lateral requires the application of Equation (9). For run #1,
Figure 7 shows the corresponding PHD lines for both one-diameter and dual-diameter laterals in dimensionless (
Figure 7a) and dimensional terms (
Figure 7b), together with the PHD derived by the commonly used step-by-step (SBS) procedure (dots), which is rigorous since it considers the continuity and the motion equations repetitively applied to the consecutive sprinkler outlets and the actual sprinkler flow rate–pressure head relationship. The comparison showed in
Figure 7 indicates the reliability of the described procedure.
Indeed, for the fixed h*min = 0. 0338, the PHD line achieves the normalized pressure head in the changing section (h*n = 0.0351) calculated by Equation (16), and then the maximum normalized pressure, h*max = 0.0412, is achieved at the distal sprinkler of the lateral.
The comparison was performed for an exponent
x = 0.5 of the sprinkler flow rate–pressure head relationship, commonly assumed for sprinklers, thus for a coefficient
ke =
qn/√
hn = 200.08 l h
−1 m
−0.5, which was set equal for both dual- and one-diameter laterals (
Table 2). Of course, for
x = 0, the solutions provided by the suggested procedure matches that provided by SBS, and it has no sense to be compared.
Figure 7 also reports the PHD derived by the suggested procedure and by the SBS method, in the case of a one-lateral diameter.
It is interesting to consider that the pivot radius is a scale factor of the aforementioned relationships; thus, the results presented here could be referred to any pressure head–pivot radius pair, providing the same normalized values. Indeed, once the telescoping pipe is designed and the normalized PHD line determined, the PHD line in dimensional terms can be simply derived by multiplying the normalized pressure heads for the selected r0 value.
3.2. Varying the Pressure Head Tolerances
In order to investigate the influence of pressure head tolerances δ
I (and δ
II) and of the number of sprinklers installed in the first (
NI) and in the second sectors (
NII), for run #1, further applications have been performed. By varying the pressure tolerances, δ
I = 0.02, 0.04, 0.05, 0.06, and 0.08, and
NI (and
NII),
Figure 8a–e show the corresponding PHDs, all laying in the admitted range (
h*min ≤
h*j ≤
h*max), indicating that different pairs of the inside diameters could be selected, providing suitable behaviors in terms of sprinkler pressure head distribution.
For δ
I = 0.05, i.e.,
h*n ≡
h*av, which could be a good choice for constant interspace sprinklers,
Figure 8c shows that for an equally distributed number of sprinklers (e.g.,
NI = 35), the PHD is not uniform. This because of the high variability in the sprinklers’ interspace,
s (
Figure 3), which needs to be imposed in
CPISs for a uniform water application rate.
Before comparing the output design diameters for dual- and one-lateral
CPISs, an error analysis on pressure heads, aimed at detecting the suitability of the suggested procedure, has been performed. In particular, relative errors, RE, corresponding to the normalized pressure according to the suggested procedure and according to SBS were calculated for dual-diameter laterals at the changing diameter section, RE(
h*n)
dual, and at the inlet, RE(
h*max)
dual, whereas for one-diameter laterals, REs were calculated at the maximum pressure section, RE(
h*max)
one:
where
h*PS is the normalized pressure head according to the present solution, and
h*SBS is the corresponding value according to the SBS procedure, where
x = 0.5 was imposed.
For run #1, by varying
NI and δ
I,
Table 3 reports RE(
h*n)
dual, RE(
h*max)
dual, and RE(
h*max)
one, which, of course, does not depend on
NI and δ
I. The results show that for dual-diameter, REs are almost slight (generally lower than for one-diameter), and for any
NI, REs decrease at decreasing δ
I. Bold values refer to the maximum RE, which was less than 2.28%, thus demonstrating a good approximation of the exact SBS procedure.
Once the error analysis has been performed, for run #1 (
Figure 8), the design diameters have been compared. For run #1,
Table 4 reports
DI and
DII values together with the mean weight diameters
Dm (Equation (28)), which generally resulted in being lower than those corresponding to one lateral diameter (
D = 116.45 mm).
Dm values that resulted in being higher than
D (116.45 mm,
Table 2) are in bold, whereas the lowest
Dm value (
Dm,min = 111.26 mm, bold and underline) is obtained for
NI,min = 28 and δ
I,min = 0.02, indicating that the application illustrated in
Figure 7 could be the most convenient choice from an investment cost point of view. For a few cases, for high
NI values, uncommon
DI <
DII conditions occur, and the corresponding
DI values are highlighted by an asterisk. These cases can be observed in the corresponding PHD slopes (
Figure 8). For example, compare the case δ
I = 0.06 and
NI = 65 with the corresponding PHD line reported in
Figure 8d.
The minimum mean weight diameter,
Dm,min, can also be observed in
Figure 9a, where
Dm is plotted as a function of
NI, for different δ
I values.
Figure 9a shows that for some of the considered
NI and δ
I values,
Dm is higher than
D (116.45 mm, dashed line), and that the higher
Dm values are associated with low and high
NI values. Thus,
NI and δ
I need to be accurately selected to obtain a desirable design. The latter could also be analyzed in terms of the coefficient of variation of the pressure heads, as it is described in the following.
Figure 9b plots the coefficient of variation of pressure heads with respect to the mean of the PHD values (
h*j), indicating that, contrarily to
Figure 9a, the lowest
CV values, which are lower than the
CV = 0.0498 obtained for one lateral diameter (dashed line), occur for low and high
NI values. However, it needs considering that for dual-diameter laterals,
CV values that are higher than for a one-diameter lateral is an expected issue, since it is associated with the abrupt modification of the PHD due to the changing diameter (
Figure 7 and
Figure 8). A more suitable comparison in terms of the coefficient of variation could be performed with respect to the average pressure head,
h*av, calculated according to the minimum and maximum values,
h*av = 0.5 (
h*max +
h*min):
where
CVav is the variation coefficient calculated with respect to
hav. This because
hav refers to a linear PHD providing a uniform distribution of sprinkler flow rate and can be selected as a reference to evidence the benefit of the dual-diameter laterals.
Towards this aim,
Figure 9c graphs
CVav as a function of
NI for the same δ
I previously considered, evidencing the benefit of a dual-lateral diameter in terms of PHD around the average
h*av value. Indeed, with exception of few cases, the
CVav calculated for dual-diameter lay below that for one-diameter lateral (dashed line).
Of course, these results have to be referred to the corresponding A* value selected (0.0149), and further applications are needed to investigate the suggested procedure for a wider range of the input parameters.
Therefore, a generalization of the results illustrated in
Figure 9 was performed for a very high number of simulations (15,000) characterized by different values of the
A* parameter, which describes the geometry of the
CPIS. The triplet of values (
qn,
r0,
i) was selected according to their common ranges also considered in Baiamonte et al. [
26] in order to arrange a whole reliable dataset. For each simulation, the
Dm,min value was calculated according to an objective function by minimizing
Dm and by varying
NI and δ
I:
Figure 10a illustrates that at increasing
A*, a slight increase in δ
min,I occurs, and that δ
I is close to 0.02 (
Figure 8a), which is reasonable, if considering that the outer laterals are characterized by larger areas to irrigate than the inner laterals. Thus, δ
I = 0.02 could be a good approximation of the recommended value to obtain the lowest
Dm. The number of sprinklers to be installed in the first sector,
NI,min (and in the second sector,
NII,min), are power-laws, as illustrated in
Figure 10b; thus, they could be used for an easy
CPIS design.
For the whole dataset considered in
Figure 10,
Figure 11a shows that by varying
A* (different
CPIS geometries), RE
D varies in a narrow range (0.043–0.047). Thus,
Dm results in being almost 4.5 % lower than
D, thereby confirming the result obtained for run #1 (
Table 2).
Figure 11b plots the relative errors in pressure heads, RE(
h*n)
dual and RE(
h*max)
dual (Equation (30)) versus
A*, which makes it possible to conclude that the previous RE range (<2.28%,
Table 3) is much lower and almost negligible (<0.3 %), if referred to the considered
Dm,min (Equation (32)). For the maximum pressure head in the case of one-diameter lateral, RE(
h*max)
one, a bit higher RE values were obtained (
Figure 11b).
Although low RE
D were observed (
Figure 11a), a more significant effect of the dual-diameter can be observed in terms of CV
av (Equation (31)). For both one and dual-diameters and for the whole dataset, in
Figure 11c, CV
av is plotted versus
A*. The figure shows that for one-diameter laterals, CV
av is higher (≅0.083) than for dual-diameters laterals (≅0.068), indicating more suitable PHDs for the latter.
Figure 11 also indicates the dots corresponding to the applications run #1 and run #2 that will be performed in
Section 3.4.
3.3. Varying the Inlet Pressure Head
The normalized inlet pressure,
h*in, which was set equal for the whole dataset (
h*in = 0.0412,
Table 2), also plays an important role in the suggested
CPIS design procedure. Using Equations (24) and (25), it can be easily observed that
h*in is a scale factor of the
K relationships. For run #1 (
A* = 0.0149),
Figure 12a,b plot the diameter of sector I,
DI, and sector II,
DII, by varying
h*in with
qn as a parameter. As expected, lower
DI and
DII values could be selected for normalized inlet pressures higher than that considered for run #1 (dot circles), and these values further decrease with decreasing
qn.
3.4. Application for Run #2
Finally, for a different set of the input parameters reported in
Table 1 (run #2), another application aimed at summarizing the suggested procedure was performed. Due to the higher lateral length (
r0 = 700 m) than run #1 (
r0 = 400 m), an inlet pressure,
hin = 25 m, higher than 16.5 m (fixed for run #1) was set. For the selected
qn = 300 l/h and
i = 0.15 mm/h,
A* equals 0.0013 (Equation (2),
Table 1). First, for
A* = 0.0013, the annulus width sequence irrigated by each sprinkler (Equations (3) and (4)) was derived. Second, the number of sprinklers in the first sector
NI has to be determined by the equation displayed in
Figure 10b, and approximating to the integer, 316 sprinklers were obtained.
According to the results shown in
Figure 10a, which suggests that the pressure head tolerance of the outer lateral is close to 0.02, when the minimum weight diameter is imposed, δ
I = 0.02 and δ
II = 0.08 were selected, in order to set the pressure head tolerance of the dual-diameter lateral δ = δ
I + δ
II = 0.1. Once the parameter ∑
s*j,I (
j − 1)
1.852 and ∑
s*j,II (
j − 1)
1.852, which are required in
K relationships are calculated (
Table 2), for
C = 135, the corresponding sectors’ diameters were determined by Equations (26) and (27), providing
DI = 152.1 mm and
DII = 224.8 mm. Of course, these diameter values do not match the available commercial ones; however, commercial pipe diameters immediately larger than the design ones could be selected, which will provide δ < 0.1. Since the latter is beyond the purpose of this study, in the following, the design diameter values (
DI = 152.1 mm and
DII = 224.8 mm) are considered to compare the suggested procedure and the exact one provided by the numerical step-by-step (SBS) method.
For run #2,
Figure 13 plots the PHD lines obtained for dual-diameter laterals and for the one-diameter lateral for the suggested procedure and by the SBS method, confirming that, for fixed pressure-head tolerances δ
I and δ
II, neglecting the flow variation in the approximate design procedure determines very moderate errors in PHD lines and makes it possible to achieve the established pressure head extremes (
hmin and
hmax,
Table 2). The suggested procedure also provides convenient solutions from an energy-saving point of view. Indeed, it was observed that confining the sprinkler pressure heads into an admitted range, and thus the sprinkler flow rates, favors high emission uniformity and, as for drip laterals, allows one to also save energy [
6].