Next Article in Journal
Real Pseudo-Lidar Point Cloud Fusion for 3D Object Detection
Previous Article in Journal
Enhancing Elderly Health Monitoring: Achieving Autonomous and Secure Living through the Integration of Artificial Intelligence, Autonomous Robots, and Sensors
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

A Hierarchical Control Strategy Based on Dual-Vector Model Predictive Current Control for Railway Energy Router

School of Electrical Engineering, Southwest Jiaotong University, Chengdu 611756, China
*
Author to whom correspondence should be addressed.
Electronics 2023, 12(18), 3919; https://doi.org/10.3390/electronics12183919
Submission received: 14 August 2023 / Revised: 12 September 2023 / Accepted: 13 September 2023 / Published: 18 September 2023

Abstract

:
The multiport and multidirectional energy flow of railway energy routers (RERs) poses a significant challenge when integrating photovoltaic (PV) systems and energy storage systems (ESSs). To address this issue, this paper proposes an improved hierarchical control strategy for RERs with a reference signal generation layer and an inverter control layer. In the reference signal generation layer, a time-segmentation energy allocation strategy based on a state machine is proposed to manage the multidirectional energy flow in RERs resulting from PV systems and ESSs while minimizing peak power demand. In the inverter control layer, a dual-vector model predictive current control (MPCC) strategy is designed for back-to-back inverters. The dual-vector MPCC strategy eliminates the need for individual PWM blocks, thereby enhancing RER current-tracking accuracy and efficiency. The prominent advantage of the dual-vector MPCC strategy is its ability to achieve high current-tracking accuracy while minimizing active power losses. Simulations and hardware-in-the-loop experiments are conducted to validate the feasibility and effectiveness of the proposed method.

1. Introduction

Railways have become a crucial component of the national economy, with China’s railways operating over 150,000 km, including 40,000 km of high-speed railways. Electrified railways commonly utilize traction transformers to convert three-phase grid AC voltage into a single-phase AC-27.5 kV traction power supply system. However, this unique configuration leads to issues such as negative-sequence current and power factor. The energy demand for electrified railways is large. For instance, the total electricity consumption in 2022 alone was as high as 787 billion kWh [1]. To achieve the vision of “carbon neutrality”, it becomes pragmatic to optimize the energy structure of electrified railways and seamlessly integrate new energy sources. On the other hand, electrified railways generate massive regenerative braking energy (RBE) during operation [2]. Unrecycled RBE directly flows to the upstream power grid, which not only leads to a large amount of energy waste but also causes power quality deterioration in the upstream power grid [3,4]. Consequently, enhancing the recovery and reuse rate of RBE emerges as a potent strategy for achieving energy conservation, emission reduction, and the optimization of the energy consumption structure.
To handle these issues, railway energy routers (RERs), which integrate both photovoltaic (PV) systems and energy storage systems (ESSs) into the traction power supply system via back-to-back converters, have been proposed [5,6]. Most of the existing RER research mainly focuses on RER topology [7,8,9], compensation principle [10,11,12], or energy allocation strategy [13,14,15], while fewer studies have delved into the realm of control strategies. Most of these studies have traditionally focused on conventional RERs that lack integration with PV systems and ESSs. However, the multiport and multidirectional energy flow of RERs necessitates a fresh perspective when integrating PV systems and ESSs. Traditional control methods can no longer satisfy the RER requirements. Consequently, the adoption of a layered approach involving energy allocation strategies and device control layers becomes imperative.
For energy allocation, the scheme proposed in [5,13] integrates PV systems with the DC link of back-to-back converters, offering the capability to absorb new energy locally and enhance the flexibility and reliability of the traction power supply system. But these research studies only discuss the architecture design and lack in-depth research on energy management. Deng et al. [6,10,11] propose methods to recycle RBE by integrating ESSs into the DC link of back-to-back converters. These methods solve the problem that RBE returns to the upstream grid when surplus energy exists. But these research studies only discuss the case of integrating ESSs alone. These methods are not suitable for the case of integrating PV systems and ESSs together. The purposes of an energy allocation strategy are peak shaving and valley filling, which in turn reduce the electricity bill. Many of the aforementioned studies employ a traditional peak-shaving energy allocation strategy, capable of reducing energy charges but not both energy charges and power demand charges.
For device control, as a core component of RERs, the control of back-to-back converters determines the quality of RERs. The control methods for converters mainly include the following: (1) Hysteresis control [16,17,18,19], which has a large tracking error and large current ripple. (2) Proportional–integral (PI) control [20], which is simple and easy to use but has large overshoot during the DC-side voltage transition stage and a slow response speed. The steady-state tracking error of the AC-side compensation current is large, which causes errors between the active power/reactive power of back-to-back converter compensation and the reference command value. (3) Proportion resonance (PR) control [21,22], which requires a fundamental wave controller and multiple harmonic controllers and increases the economic cost. (4) Sliding-mode variable structure control [23], which can achieve the fast and accurate tracking of the compensation current but is prone to chattering. The model predictive control technology has been widely used in grid-connected converter control in recent years because of its simple principle, no modulation unit, high robustness, good current-tracking effect, and strong applicability in various nonlinear systems [24,25]. Therefore, this paper designs a dual-vector model predictive current control (MPCC) strategy for back-to-back converters.
To solve the problem of the multiport and multidirectional energy flow of RERs when PV systems and ESSs are integrated, this paper proposes an improved hierarchical control strategy with a reference signal generation layer and a converter control layer.
In the reference signal generation layer, a time-segmentation energy allocation strategy is proposed to solve the multidirectional energy flow brought by PV systems and ESSs, as well as to reduce the maximum power demand.
In the converter control layer, a dual-vector MPCC strategy for back-to-back converters that has flexible control and does not need a separate PWM block is presented. The method improves the current-tracking accuracy and efficiency of RERs.
The remainder of this paper is organized as follows: The structure of RERs is introduced in Section 2. The four operation modes and the time-segmentation energy allocation strategy are analyzed in Section 3. An improved hierarchical control strategy for RERs with a reference signal generation layer and a converter control layer is constructed in Section 4. Simulation verification and HIL experiments are presented in Section 5. Finally, the conclusion is presented in Section 6.

2. System Structure of RERs

The topology of RERs is illustrated in Figure 1. Two-phase traction buses with 27.5 kV voltage are connected to a three-phase grid through a V/V traction transformer. The back-to-back inverter is composed of two single-phase voltage source inverters (VSCα/VSCβ), whose AC sides are connected to the traction buses via step-down transformers Tα and Tβ, respectively. The inverters are interconnected by a buffer capacitor on the DC side. The PV system and ESS are integrated into the traction power supply system through the back-to-back inverter’s DC bus.

3. Results of Operating Modes and Time-Segmentation Energy Allocation Strategy for RERs

3.1. Four Operating Modes of RERs

As shown in Figure 1, many uncertain factors lead to the complexity of energy flow, e.g., whether the two feeder loads are in traction state or in regenerative braking state, whether the PV system is in working state or not, whether the ESS is charging or discharging. For ease of analysis, four typical modes are summarized in Figure 2.
Pg represents the active power of the upstream utility grid; PPV represents the power generated by the PV system; PESS represents the power of the ESS regardless of charging or discharging; P, P denote the active power of α/β traction loads, respectively; P and P (Q and Q) denote the active (reactive) power compensated by VSCα and VSCβ, respectively; SOCmin, SOCmax denote the upper and lower state-of-charge (SOC) limits of the ESS, respectively. PH represents the value of peak-clipping power. Plow represents the value of valley-filling adjustment power.
  • Mode 1: peak-clipping discharge state. In this situation, the loads satisfy (P + PPPV) ≥ PH, and the ESS satisfies SOC > SOCmin. Then, the ESS is in discharge state. The power generated by the PV system or ESS is distributed to both traction buses through the RER. Then, a certain amount of active power is transferred from one traction bus to the other to achieve power balance. Meanwhile, the reactive power of each bus is independently compensated.
  • Mode 2: recovery regenerative braking state. As shown in Figure 2, the loads meet (P + PPPV) < 0, and the ESS satisfies SOC < SOCmax. The ESS enters the charging state. RBE is first absorbed by the load on the same traction bus, and the remaining part is transferred to the other traction bus to be absorbed by the RER. Then, the unconsumed RBE is absorbed by the ESS, and the part that cannot be absorbed is fed back to the upstream utility grid. The energy generated by the PV system is first absorbed by the load, and the excess energy is absorbed by the ESS (if the ESS is still capable), otherwise it is discarded.
  • Mode 3: power transmission state. In this scenario, the ESS does not work. The SOC of the ESS exceeds the effective threshold, or the loads meet Plow ≤ (P + PPPV) < PH, whether in traction state or in regenerative braking state.
  • Mode 4: valley-filling adjustment state. In this mode, the loads meet 0 ≤ (P + PPPV) < Plow. Specifically, if the instantaneous SOC(t) is less than the initial SOCSOC (SOCSOC0), the ESS enters the charging state, otherwise it enters the standby state. The SOC values should be the same during the alternation of the daily cycle to keep the ESS continuously working.

3.2. Time-Segmentation Energy Allocation Strategy

The energy allocation strategy is the optimal approach to solve the control problem of the multiport and multidirectional energy flow when the PV system and the ESS are integrated in an RER. In China, railways have a two-part tariff policy. To reduce the electricity tariff, this subsection proposes a time-segmentation energy allocation strategy, which divides the 24 h into peak-shaving-valley-filling mode, and maximum demand mode. The peak-shaving-valley-filling mode uses lower peak–valley values to minimize the energy charge. The maximum demand mode uses higher peak–valley values to reduce the demand as much as possible, thus reducing the power demand charge. As shown in Figure 3, the time-segmentation energy management strategy is divided into the following three steps:
  • Data processing: This step involves initializing variables, detecting data, and calculating the traction load. The initialized variables include the threshold values of the SOC (SOCmin, SOCmax), the initial value of the SOC (SOC0), the rated capacity of the inverter (Smax), and the maximum discharge power of the ESS (PBM).
  • Judge mode: First, based on the historical measured data, the time period, t ∈ (t1, t2), in which the maximum demand is probable to appear is estimated and set as the maximum demand mode. Then, different peak-valley values are set for the maximum demand mode, and the peak-shaving-valley-filling mode, respectively.
  • Judge state: Based on the instantaneous power of the traction load and PV system, and the instantaneous SOC(t) of the ESS, as well as the peak and valley values obtained in the previous step, the system operation status is judged in real time. Specifically, it is divided into peak-clipping discharge state, recovery regenerative braking state, power transmission state, and valley-filling adjustment state. The specific judgment process is shown in Figure 3, and the transition relationships among different operation states are shown in Figure 4.

4. Hierarchical Control Strategy

The dual intermittency and volatility of PV sources and traction load cause difficulties in system control. Employing an energy allocation strategy is an effective way to solve this problem. This paper constructs a hierarchical control strategy for RERs, as shown in Figure 5, which is divided into reference signal generation layer and converter control layer. To achieve the stable operation of the three-port system of an RER, one port needs to work in master mode to stabilize the DC bus voltage and maintain the energy balance of the RER, while the remaining ports work in slave mode to manage their own output power and complete the corresponding power flow scheduling tasks. In this paper, the ESS works in master mode, and the PV system and the converters on both sides work in slave mode.

4.1. Reference Signal Generation

At the reference signal generation layer, the energy storage output is first calculated based on the time-segmentation energy allocation strategy shown in Figure 3. Then, the reference power of the RER is calculated based on the compensation principle [5].
Finally, according to second-order generalized integrator (SOGI), the αβ0 stationary reference frame is fabricated on the single-phase inverter. After coordinate transformation, the active power and reactive power of the single-phase voltage source converter in the dq0 rotating reference frame can be expressed as
[ P     Q ] = [ e d i d     e d i q ]
Therefore, the reference-current instructions of the back-to-back inverter can be obtained and are
i c α ref = 2 ( P c α ref U α ) sin ( ω t ) + 2 ( Q c α ref U α ) cos ( ω t )
i c β ref = 2 ( P c β ref U β ) sin ( ω t - π 3 ) + 2 ( Q c β ref U β ) cos ( ω t - π 3 )
where Uα and Uβ denote the root-mean-square values of Uα and Uβ, respectively.

4.2. Modeling and Control of Back-to-Back Inverter

Due to the buffer effect of the intermediate DC capacitor, VSCα/VSCβ of the back-to-back inverter can be controlled independently, even when active power exchange is present. This paper takes VSCα as an example to design a current controller, because VSCα and VSCβ have the same structure and function. A dual-vector MPCC strategy is proposed for back-to-back converters to accurately track the reference current and acquire stable and rapid control capability. The basic principle is to seek the voltage vector that minimizes the current-tracking error as the output voltage of the voltage source converter.
Figure 6 shows an equivalent circuit of the single-phase voltage source converter. L (R) denotes the inductor (resistor) of the circuit; u and i denote the output voltage and current of VSCα, respectively; e denotes the output voltage of the grid.
Referring to Figure 6, the following equation can be obtained as
L d i d t = u R i e
The current derivative in the continuous-time domain is described in Equation (4). Correspondingly, the current derivative in the discrete domain is replaced by the first-order forward Euler approximation method with a sampling period Ts, which can be expressed as follows:
d i ( k + 1 ) d t = i ( k + 1 ) i ( k ) T s
Then, in the discrete-time domain, the output current dynamics can be described as
i ( k + 1 ) = i ( k ) + T s L [ u ( k ) e ( k ) R i ( k ) ]
In MPCC, according to (6), the three different output voltages produced by VSCα can predict three different future output currents. At each sampling time point, the voltage that minimizes the cost function is selected from three possible voltages as the output voltage. And the cost function is defined as the absolute error between the present current and the future reference current. Due to the cost function, the actual output current generated by the optimal output voltage is forced to approach the future reference current in the next step. The one-step future reference current (iref(k + 1)) can be calculated using the Lagrange extrapolation formula.
i ref ( k + 1 ) = 3 i ref ( k ) 3 i ref ( k 1 ) + i ref ( k 2 )
where iref(k) denotes the present reference current; iref(k − 1) denotes the one-step past reference current; iref(k − 2) denotes the two-step past reference current.
Due to the large amount of calculation for model predictive control, the control program has an unavoidable calculation delay in practice. Therefore, the output current of the one-step delay is obtained by dynamically moving the output current one step forward in (6), which can be described as shown in (8).
i ( k + 2 ) = i ( k + 1 ) + T s L [ u ( k + 1 ) e ( k + 1 ) R i ( k + 1 ) ]
where i(k + 2) denotes the two-step future current; u(k + 1) denotes three different possible voltage vectors output by VSCα; considering that the grid voltage changes slowly, e(k + 1) is approximately equal to e(k), i.e., e(k + 1) ≈ e(k).
At every sampling instant, the cost function that evaluates the absolute errors between the two-step future reference current (iref(k + 2)) and the predicted output currents is described as
g = | i ref ( k + 2 ) i ( k + 2 ) |
Also, iref(k + 2) can be calculated using the Lagrange extrapolation formula.
i ref ( k + 2 ) = 3 i ref ( k + 1 ) 3 ref ( k ) + i ref ( k 1 )
Due to the fact that VSCα can only produce three different output voltages (i.e., uout1 = 0; uout2 = Udc; uout3 = −Udc), a large current error is generated. And the delay compensation increases the current error and distortion. Although current with high-quality waveforms and smaller errors can be achieved by increasing the sampling frequency, a greater cost is needed in practice. Therefore, this paper proposes a dual-vector MPCC strategy that considers all possible future combinations produced by two voltages of VSCα (i.e., (uout1, uout1), (uout1, uout2), (uout1, uout3), (uout2, uout1), (uout2, uout2), (uout2, uout3), (uout3, uout1), (uout3, uout2), (uout2, uout2)).
The sampling period is assigned to two variable time intervals, corresponding to the first and second voltages in a voltage combination. At every sampling instant, the error between the actual current and the reference current is reduced by changing the variable time interval. The virtual voltage can be expressed as
u m n = t m T s u out m + t n T s u out n
where uoutm, uoun (m, n = 1, 2, 3) denote three different possible output voltages, respectively; tm and tn correspond to the working time of the first voltage (uoutm) and the second voltage (uoutn) during the kth sampling period, respectively, satisfying tm + tn = Ts.
Therefore, another way of expressing the two-step future output current is
i ( k + 2 ) = i ( k + 1 ) + f m ( k ) t m + f n ( k ) t n
where fm(k) and fn(k) denote the derivatives of the output current produced by the first voltage (uoutm) and the second voltage (uoutn) during the kth sampling period, respectively. They can be expressed as
f j ( k ) = u out j e ( k ) R i ( k + 1 ) L , j ( m , n )
To simplify the algorithm, modulation model predictive control is used to calculate the vector application time. The basic idea is that the larger the objective function corresponding to the corresponding vector, the larger the control error. Therefore, its action time should be as short as possible. The distribution of tm and tn satisfies
{ t m = G n G m + G n T s t n = G m G m + G n T s
where Gm and Gn denote the voltage cost function of the first voltage (uoutm) and the second voltage (uoutn) during the kth sampling period, respectively, which are defined as
G p = | u r e f ( k + 1 ) u o u t p | , p ( m , n )
where uref(k + 1) denotes the one-step future reference voltage value, which can be calculated using the deadbeat algorithm as
u ref ( k + 1 ) = L [ i ref ( k + 2 ) i ( k + 1 ) ] T s + R i ( k + 1 ) + e ( k + 1 )
According to (11) and (14)~(16), the virtual vector that minimizes Equation (9) can be solved; then, dual-vector MPCC can be realized.
Figure 6 describes the flow diagram of the dual-vector MPC method.
Comparing the conventional MPCC strategy and the dual-vector MPC method, Figure 7 shows the output current waveforms of VSCα with the same sampling frequency. It can be seen that steady-state current error and current ripple can be reduced by utilizing the dual-vector MPC method without increasing the sampling frequency.

4.3. Control of DC/DC Converter

ESSs play an important role in balancing power and adjusting the DC bus voltage for RERs. In this paper, the voltage outer loop is used to generate a reference value for the current inner loop to maintain DC bus voltage stability and manage the charge and discharge of the ESS, as shown in Figure 5b.
Because the output characteristics are influenced by the environment and climate, a PV system should have two modes: maximum power point tracking (MPPT) mode and non-working mode. To effectively use renewable energy, it generally works in MPPT mode. However, when the environmental factors change so that the PV system cannot continuously supply power, the working mode is turned to non-working mode. The DC/DC converter control structure of the PV system is shown in Figure 5c.

5. Analysis of Simulations and Experiments

5.1. HIL Experimental Verification

In this section, to verify the correctness and effectiveness of the proposed method, an HIL simulation platform consisting of a real controller (TMS320F28335 DSP) and a virtual controlled object is built, as depicted in Figure 8. An RER model and a traction power supply system model are both implemented in the RT-BOX simulator using PLECS software 4.7.5. The voltage and current signals of the converter are transmitted to the DSP controller through the A/D conversion unit. Then, the hierarchical control strategy presented in Section 4 is implemented using the DSP controller. Finally, the control signals are transmitted to the built RER from the D/A conversion unit to the control converters.
In this subsection, the data of four typical moments are selected to constitute two dynamic operating conditions to verify the correctness of the proposed dual-vector MPCC strategy. The HIL platform parameters are specified in Table 1.
  • Power transmission state and recovery regenerative braking state: The experimental waveforms are described in Figure 9.
Before β-side locomotive braking, the loads are −1 MW and 7 MW, respectively, and the system is in power transmission state. The 1 MW active power generated by the PV system is absorbed; the ESS does not work; and the consumption of the upper-grid power is 5 MW. After β-side locomotive braking, the load changes to −1 MW, and the system is in recovery regenerative braking state. The ESS is in charging state, absorbing the regenerative braking energy of the two traction buses. The 1 MW active power generated by the PV system is directly absorbed by the ESS, and no energy is fed back to the upper grid. The DC bus voltage of the RER introduced in Figure 9c remains around its reference value, which ensures the normal operation of the RER. The result of converter α tracking the reference current shows that the dual-vector MPC method can ensure the accurate tracking of current. As shown in Figure 9d, when the RER works in power transmission state, the grid-side currents of the traction transformer are almost symmetric; when the RER works in recovery regenerative braking mode, the primary-side currents of the traction transformer almost become 0.
2.
Peak-clipping discharge state and valley-filling adjustment state: The experimental waveforms are described in Figure 10.
Before β-side locomotive braking, the loads are 2 MW and 10 MW, respectively, and the system is in peak-clipping discharge state. The ESS is in discharging state, providing 1 MW active power to the traction bus; the PV system does not work; and the consumption of the upper-grid power is equal to the preset peak value (11 MW). After β-side locomotive braking, the load changes to −1 MW, and the system is in valley-filling adjustment state. The ESS is in charging state, acting as a load and consuming 1 MW active power, absorbing the regenerative braking energy of the two traction buses. The whole system consumes upper-grid power equal to the preset valley value (2 MW). The DC bus voltage of the RER introduced in Figure 10c remains around its reference value, which ensures the normal operation of the RER. The result of converter α tracking the reference current shows that the dual-vector MPC method can ensure the accurate tracking of current. As shown in Figure 10d, the grid-side currents of the traction transformer are almost symmetric.

5.2. Typical Daily Measured Load Data Verification

Considering the daily periodicity of train operation, this section selects the typical daily measured load data of a traction substation in a high-speed railway section (sampling interval: 1 s/time). Correspondingly, the PV system selects the measured power generation data of the PV power station near the traction substation during a typical summer day (sampling interval: 1 min/time) to further evaluate the engineering capability of the RER.
Figure 11 shows typical daily field data of a traction substation. The traction load of the two arms is quite different, and 16.27 MWh RBE is returned to the upstream grid every day, accounting for 19.82% of the traction energy. It means that the traction substation is suitable for installing an RER system.
Based on a professional economic analysis, the specific parameters of the RER system are as follows: the rate capacity of the RER is 11 × 2 MVA; the capacity of the ESS battery is 1000 kWh; and the PV installed capacity is 1 MWp.
Figure 12 shows the changes in total active power on the traction side without and with RER deployment. Thanks to the addition of a PV system and an ESS, the power consumed by the traction is obviously decreased after RER deployment. The total traction power is reduced from 85.1 MWh to 71.8 MWh, and its rate of decrease is 15.63%. The energy recovery efficiency of RBE is 86.81%. The consumption of the PV system is 5.45 MWh, and the consumption rate is 68.76%.
Figure 13 shows the instantaneous SOC of the ESS. The SOC does not exceed the limit and can be restored to SOC0 during the alternation of the day cycle, ensuring ESS state consistency.
In Figure 14, it is easily inferred that the voltage imbalance degree shows an overall downward trend after RER deployment, and its 95% probability value decreases from 2.83% to 1.24%, which meets the 2% international standard. On the other hand, without RER deployment, the probability of the instantaneous power factor being equal to 1 is 33.89%, while with RER deployment, it is 75%. The power factor shows an overall increasing trend, and the average value rises from 0.61 to 0.91.

5.3. Comparison with Previous Works

  • Comparison of different control strategies: hysteresis control [16,17,18,19], PI control [20], and the proposed dual-vector MPCC strategy. The specific operating conditions involve transitioning from recovery regenerative braking state to peak-clipping discharge state. Figure 15 illustrates the current of inverter α following the application of three different control strategies. It can be observed that during transient processes, when employing the proposed dual-vector MPCC strategy, there is high precision in tracking the reference current with minimal current deviation. Figure 16 shows the current-tracking error when three different control strategies are adopted for converter α. It can be observed that the current error is minimized when employing the dual-vector MPCC strategy. Therefore, the current-tracking error can be employed effectively, and current-tracking accuracy can be improved by using the proposed dual-vector MPCC strategy.
  • Comparison of the proposed time-segmentation energy allocation strategy with the previous strategy: Table 2 shows the simulation results with different energy allocation strategies. With the time-segmentation energy management strategy, the power demand reduction rate increases from 5.51% to 10.36% with the same RBE recovery rate, PV consumption rate, and power quality improvement effect. The results suggest that the time-segmentation energy allocation strategy proposed in this paper can simultaneously reduce the maximum demand and PV consumption, and recover regenerative braking energy, as well as improve power quality.

6. Conclusions

In this paper, a hierarchical control strategy for RERs is proposed. The feasibility and effectiveness of the proposed scheme are verified with the analysis of typical scenarios, comparative studies, and field cases. The paper is concluded as follows.
(1) This paper proposes an improved hierarchical control strategy with a reference signal generation layer and a converter control layer that realize on-site consumption of PV energy, RBE recycling and reuse, and peak shaving and valley filling on the grid side to stabilize grid load fluctuations. Meanwhile, power quality problems such as reactive power compensation and negative-sequence voltage imbalance are solved.
(2) Compared with the existing PI control and hysteresis control, the dual-vector MPCC strategy of back-to-back converters for RERs has high current-tracking accuracy and low active power loss. Additionally, it has flexible control and does not need a separate PWM block.
(3) The simulation of typical daily measured load data validate that the proposed time-segmentation energy allocation strategy can achieve peak shaving and valley filling, as well as reduce maximum power demand.
The fact is that with the installed capacity of ESSs, the recovery rate of RBE and the utilization rate of PV systems increase, but this brings more problems, such as cost and site selection. Hence, how to optimally configure the installed capacity of ESSs to maximize the benefits is another research focus.

Author Contributions

Writing—original draft preparation, J.L.; writing—review and editing, C.D.; investigation, F.Z.; supervision, W.C. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by Beijing Natural Science Foundation (L221002), Sichuan Science and Technology Program (2020YJ0250).

Data Availability Statement

The data that support the findings of this study are available on request from the corresponding author. The data are not publicly available due to privacy or ethical restrictions.

Conflicts of Interest

The authors declare no conflict of interest. The funders had no role in the design of the study; in the collection, analyses, or interpretation of data; in the writing of the manuscript; or in the decision to publish the results.

Nomenclature

RERRailway energy router
PVPhotovoltaic
ESSEnergy storage system
MPCCModel predictive current control
RBERegenerative braking energy
PIProportional–integral
PRProportion resonance
SOCState of charge of the ESS
SOGISecond-order generalized integrator
MPPTMaximum power point tracking
Variables and Symbols
VSCα, VSCβSingle-phase voltage source inverters of railway energy router
Tα, TβStep-down transformers
PgActive power of the upstream utility grid (MW)
PPVPower generated by a PV system (MW)
P, PActive power of α/β traction loads (MW)
P, PActive power compensated by VSCα and VSCβ (MW)
PHPeak-clipping power value (MW)
PlowValley-filling adjustment power value (MW)
PBMMaximum discharge power of the ESS (MW)
PLTotal active power of load (MW)
PESSPower generated by the ESS (MW)
Q, QReactive power compensated by VSCα and VSCβ (MVar)
SOCmin, SOCmaxThe upper and lower SOC limits of the ESS (%)
SOC0Initial SOC of the ESS (%)
Uα(t), Uβ(t)Voltages of α- and β-phase traction feeders (kV)
Iα(t), Iβ(t)Currents of α- and β-phase traction feeders (kA)
L, RInductor and resistor of the circuit (mF/Ω)
u, iOutput voltage and current of VSCα (kV/kA)
eOutput voltage of grid (kV)
iref(k)Present reference current (kA)
iref(k + 1)One-step future reference current (kA)
i(k + 2)Two-step future current (kA)
iref(k − 1)One-step past reference current (kA)
iref(k − 2)Two-step past reference current (kA)
u(k + 1)One-step future voltage (kV)
uoutm, uounFirst voltage and second voltage (kV)
tm, tnWorking time of uoutm and uoun (s)
TsSampling period (s)
fm(k), fn(k)Derivatives of the output current produced by uoutm and uoun
Gm, GnVoltage cost function of uoutm and uoutn

References

  1. Hu, H.; Ge, Y.; Huang, Y.; Ai, L.; Zhou, Y.; He, Z.; Gao, S. A novel “Source-Network-Train-Storage” integrated power supply system for electric railways. Proc. CSEE 2022, 42, 4374–4391. [Google Scholar]
  2. Khayyam, S.; Ponci, F.; Goikoetxea, J.; Recagno, V.; Baglinano, V.; Monti, A. Railway energy management system: Centralized-decentralized automation architecture. IEEE Trans. Smart Grid 2016, 7, 1164–1175. [Google Scholar] [CrossRef]
  3. Ceraolo, M.; Lutzemberger, G.; Meli, E.; Pugi, L.; Rindi, A.; Pancari, G. Energy storage systems to exploit regenerative braking in DC railway systems: Different approaches to improve efficiency of modern high-speed trains. J. Energy Storage 2018, 16, 269–279. [Google Scholar] [CrossRef]
  4. Song, Y.; Song, W. A novel dual speed-curve optimization based approach for energy-saving operation of high-speed trains. IEEE Trans. Intell. Transp. Syst. 2016, 17, 1564–1575. [Google Scholar] [CrossRef]
  5. Wu, M.; Dai, C.; Deng, W.; Gao, Y.; Chen, H.; Chen, W. Back-to-back PV generation system and its control strategy for electrified railway. Power Syst. Technol. 2018, 42, 541–547. [Google Scholar]
  6. Deng, W.; Deng, C.; Han, C.; Chen, W. Back-to-back hybrid energy storage system of electric railway and its control method considering regenerative braking energy recovery and power quality improvement. Proc. CSEE 2019, 39, 2914–2924. [Google Scholar]
  7. Deng, W.; Dai, C. A multifunctional energy storage system with fault-tolerance and its hierarchical optimization control in AC-fed railways. IEEE Trans. Power Del. 2022, 37, 2440–2452. [Google Scholar] [CrossRef]
  8. Guo, P.; Xu, Q.; Yue, X.; Ma, F.; He, Z.; Luo, A.; Guerrero, J.M. Analysis and control of modular multilevel inverter with split energy storage for railway traction power conditioner. IEEE Trans. Power Electron. 2020, 35, 1239–1255. [Google Scholar] [CrossRef]
  9. Ma, F.; Wang, X.; Deng, L.; Zhu, Z.; Xu, Q.; Xie, N. Multiport railway power conditioner and its management control strategy with renewable energy access. IEEE J. Emerg. Sel. Top. Power 2020, 8, 1405–1418. [Google Scholar] [CrossRef]
  10. Cui, G.; Luo, L.; Liang, C.; Hu, S.; Wang, T. Supercapacitor integrated railway static power conditioner for regenerative braking energy recycling and power quality improvement of high-speed railway system. IEEE Trans. Transp. Electrif. 2019, 5, 702–714. [Google Scholar] [CrossRef]
  11. Chen, J.; Hu, H.; Ge, Y.; Wang, K.; He, Z. An energy storage system for recycling regenerative braking energy in high-speed railway. IEEE Trans. Power Del. 2021, 36, 320–330. [Google Scholar] [CrossRef]
  12. Chen, H.; Che, Y.; Fu, R.; Wang, X.; Zhu, H. Study on regenerative braking energy utilization and power quality control in electrified railways. In Proceedings of the 2018 IEEE International Power Electronics and Application Conference and Exposition (PEAC), Shenzhen, China, 4–7 November 2018. [Google Scholar]
  13. Deng, W.; Dai, C.; Zhang, H.; Zhang, L.; Li, M.; Wu, Z. Research on comprehensive optimization control method for traction photovoltaic generation system of complex electrified railway. Proc. CSEE 2020, 40, 5849–5865. [Google Scholar]
  14. Luo, P.; Li, Q.; Zhou, Y.; Ma, Q.; Sun, J. Multi-application strategy based on railway static power conditioner with energy storage system. IEEE Trans. Intell. Transp. Syst. 2021, 22, 2140–2152. [Google Scholar] [CrossRef]
  15. Zhang, Y.; Hu, H.; Geng, A.; Cheng, J.; Ge, Y.; Wang, K. Capacity optimization configuration of hybrid energy storage system for electrified railway considering peak shaving and valley filling. Electr. Power Autom. Equip. 2023, 43, 44–50. [Google Scholar]
  16. Luo, A.; Wu, C.; Shen, J.; Shuai, Z.; Ma, F.J. Railway static power conditioners for high-speed train traction power supply systems using three-phase V/V transformers. IEEE Trans. Power Electron. 2011, 26, 2844–2856. [Google Scholar] [CrossRef]
  17. Ma, F.; Luo, A.; Xu, X.; Xiao, H.; Wu, C.; Wang, W. A simplified power conditioner based on half-bridge inverter for high-speed railway system. IEEE Trans. Ind. Electron. 2013, 60, 728–738. [Google Scholar] [CrossRef]
  18. Wu, C.; Luo, A.; Shen, J.; Ma, F.J.; Peng, S. A negative sequence compensation method based on a two-phase three-wire inverter for a high-speed railway traction power supply system. IEEE Trans. Power Electron. 2012, 27, 706–717. [Google Scholar] [CrossRef]
  19. Joseph, V.P.; Thomas, J. Power quality improvement of AC railway traction using railway static power conditioner a comparative study. In Proceedings of the 2014 International Conference on Power Signals Control and Computations (EPSCICON), Thrissur, India, 6–11 January 2014; pp. 1–6. [Google Scholar]
  20. Tian, M.; Zhang, J.; Dong, X.; Yang, X.; Hui, L. Simulation research on control method based on parallel railway static power conditioner of electrified railway. High Volt. Eng. 2016, 42, 3533–3538. [Google Scholar]
  21. Jiang, Y.; Liu, X.; Zhao, L.; Wang, Z.; Cao, Y. Research on stability and control strategy of railway power conditioner. Power Syst. Technol. 2018, 42, 1620–1627. [Google Scholar]
  22. Yang, P.; Kang, Y.; Miao, S.; Zhen, T.; Wang, J.; Han, J. Improved sliding mode control strategy for railway static power conditioner in V/v traction power supply system. High Volt. Eng. 2020, 46, 2218–2229. [Google Scholar]
  23. Kwak, S.; Kim, S.-E. Model predictive control methods to reduce common-mode voltage for three-phase voltage source inverters. IEEE Trans. Power Electron. 2015, 30, 5019–5035. [Google Scholar] [CrossRef]
  24. Li, X.; Zhang, H.; Shadmand, M.B.; Balog, R.S. Model predictive control of a voltage-source inverter with seamless transition between islanded and grid-connected operations. IEEE Trans. Ind. Electron. 2017, 64, 7906–7918. [Google Scholar] [CrossRef]
  25. Kwak, S.; Kim, S.-E.; Park, J.-C. Predictive current control methods with reduced current errors and ripples for single-phase voltage source inverters. IEEE Trans. Ind. Inform. 2015, 11, 1006–1016. [Google Scholar] [CrossRef]
Figure 1. The typical structure of RERs.
Figure 1. The typical structure of RERs.
Electronics 12 03919 g001
Figure 2. Four operating modes of RERs. (a) Peak-clipping discharge mode; (b) recovery regenerative braking mode; (c) power transmission mode; (d) valley-filling adjustment mode.
Figure 2. Four operating modes of RERs. (a) Peak-clipping discharge mode; (b) recovery regenerative braking mode; (c) power transmission mode; (d) valley-filling adjustment mode.
Electronics 12 03919 g002
Figure 3. The architecture of the hierarchical control strategy.
Figure 3. The architecture of the hierarchical control strategy.
Electronics 12 03919 g003
Figure 4. The transition relationships among different operation states.
Figure 4. The transition relationships among different operation states.
Electronics 12 03919 g004
Figure 5. The proposed architecture of the hierarchical control strategy.
Figure 5. The proposed architecture of the hierarchical control strategy.
Electronics 12 03919 g005
Figure 6. The proposed dual-vector model predictive current control.
Figure 6. The proposed dual-vector model predictive current control.
Electronics 12 03919 g006
Figure 7. The output current waveforms of VSCα with different control. (a) Conventional model predictive current control; (b) proposed dual-vector model predictive current control.
Figure 7. The output current waveforms of VSCα with different control. (a) Conventional model predictive current control; (b) proposed dual-vector model predictive current control.
Electronics 12 03919 g007
Figure 8. The structure of the established HIL experimental platform.
Figure 8. The structure of the established HIL experimental platform.
Electronics 12 03919 g008
Figure 9. Experimental results of power transmission state and recovery regenerative braking state. (a,b) Power balance. (c) DC bus voltage (Vdc) and inverter current (i/icαref). (d) Three-phase grid-side current (iABC).
Figure 9. Experimental results of power transmission state and recovery regenerative braking state. (a,b) Power balance. (c) DC bus voltage (Vdc) and inverter current (i/icαref). (d) Three-phase grid-side current (iABC).
Electronics 12 03919 g009
Figure 10. Experimental results of peak-clipping discharge state and valley-filling adjustment state. (a,b) Power balance. (c) DC bus voltage (Vdc) and inverter current (i/icαref). (d) Three-phase grid-side current (iABC).
Figure 10. Experimental results of peak-clipping discharge state and valley-filling adjustment state. (a,b) Power balance. (c) DC bus voltage (Vdc) and inverter current (i/icαref). (d) Three-phase grid-side current (iABC).
Electronics 12 03919 g010
Figure 11. Daily power profiles of traction load and PV unit.
Figure 11. Daily power profiles of traction load and PV unit.
Electronics 12 03919 g011
Figure 12. Changes in total active power on traction side without and with RER deployment.
Figure 12. Changes in total active power on traction side without and with RER deployment.
Electronics 12 03919 g012
Figure 13. Instantaneous SOC of the ESS.
Figure 13. Instantaneous SOC of the ESS.
Electronics 12 03919 g013
Figure 14. Improved results of power quality without and with RER deployment. (a) The 95% probability value of the voltage imbalance degree; (b) power factor.
Figure 14. Improved results of power quality without and with RER deployment. (a) The 95% probability value of the voltage imbalance degree; (b) power factor.
Electronics 12 03919 g014
Figure 15. Inverter α current following application of three control strategies. (a) hysteresis control; (b) PI control; (c) the proposed dual-vector MPCC strategy.
Figure 15. Inverter α current following application of three control strategies. (a) hysteresis control; (b) PI control; (c) the proposed dual-vector MPCC strategy.
Electronics 12 03919 g015
Figure 16. Inverter α current-tracking error following application of three control strategies. (a) hysteresis control; (b) PI control; (c) the proposed dual-vector MPCC strategy.
Figure 16. Inverter α current-tracking error following application of three control strategies. (a) hysteresis control; (b) PI control; (c) the proposed dual-vector MPCC strategy.
Electronics 12 03919 g016
Table 1. HIL experimental parameters.
Table 1. HIL experimental parameters.
ItemParameterValue
Three-phase power gridPhase-to-phase voltage (kV)220
Short-circuit capacity (MVA)2000
V/V transformerTransformer ratio (kV/kV)220/27.5
Back-to-back inverterTransformer ratio (kV/kV)27.5/2
Nominal capacity (MVA)12
DC bus voltage (V)4000
ESSEnergy storage medium typeLithium–iron–phosphate battery
Nominal capacity (kWh)1000
Nominal power (MVA)10
PV systemNominal power (MVA)5
Table 2. Simulation results with different energy allocation strategies.
Table 2. Simulation results with different energy allocation strategies.
SchemeDevice CapacityThresholdRBE Utilization
Rate (%)
PV Absorption Rate (%)Power QualityMaximum Demand with/without Access (MW)
BTB-RER
(MVA)
ESS
(kWh)
Peak PH
(MW)
Valley Plow
(MW)
95% εu *Power Factor
Without any devices------------------2.830.6121.23
traditional peak-shaving energy
allocation strategy [7,10]
11 × 210004.741.4287.4668.691.210.90820.06 (↓5.51%)
The proposed time-segmentation
energy allocation strategy
11 × 210004.74
29.4 (11–13 h)
1.42
2.37 (11–13 h)
86.8168.761.240.9119.03 (↓10.36%)
* The 95% probability value of voltage imbalance degree.
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Lian, J.; Dai, C.; Zhou, F.; Chen, W. A Hierarchical Control Strategy Based on Dual-Vector Model Predictive Current Control for Railway Energy Router. Electronics 2023, 12, 3919. https://doi.org/10.3390/electronics12183919

AMA Style

Lian J, Dai C, Zhou F, Chen W. A Hierarchical Control Strategy Based on Dual-Vector Model Predictive Current Control for Railway Energy Router. Electronics. 2023; 12(18):3919. https://doi.org/10.3390/electronics12183919

Chicago/Turabian Style

Lian, Jingru, Chaohua Dai, Fulin Zhou, and Weirong Chen. 2023. "A Hierarchical Control Strategy Based on Dual-Vector Model Predictive Current Control for Railway Energy Router" Electronics 12, no. 18: 3919. https://doi.org/10.3390/electronics12183919

APA Style

Lian, J., Dai, C., Zhou, F., & Chen, W. (2023). A Hierarchical Control Strategy Based on Dual-Vector Model Predictive Current Control for Railway Energy Router. Electronics, 12(18), 3919. https://doi.org/10.3390/electronics12183919

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop