Next Article in Journal
Unilateral Route Method to Estimate Practical Mutual Inductance for Multi-Coil WPT System
Next Article in Special Issue
Design and Control of a DC Collection System for Modular-Based Direct Electromechanical Drive Turbines in High Voltage Direct Current Transmission
Previous Article in Journal
A 1 GS/s 12-Bit Pipelined/SAR Hybrid ADC in 40 nm CMOS Technology
Previous Article in Special Issue
A Novel Self-Powered Dynamic System Using a Quasi-Z-Source Inverter-Based Piezoelectric Vibration Energy Harvester
 
 
Article
Peer-Review Record

Analysis of Three-Phase Inverter Parallel Operation with Network-Based Control Having Strong Robustness and Wide Time-Scale Compatibility in Droop-Controlled AC Microgrid

Electronics 2020, 9(2), 376; https://doi.org/10.3390/electronics9020376
by Yao Zhang 1,*, Fan Zhang 1, Yu Quan 1 and Pengfei Zhang 2
Reviewer 1: Anonymous
Reviewer 2: Anonymous
Electronics 2020, 9(2), 376; https://doi.org/10.3390/electronics9020376
Submission received: 18 January 2020 / Revised: 13 February 2020 / Accepted: 20 February 2020 / Published: 24 February 2020
(This article belongs to the Special Issue Applications of Power Electronic Circuits and Systems for Future Grid)

Round 1

Reviewer 1 Report

The paper proposed a network-based droop control for parallel inverters. While there are many works of literature have been studied for the same object, the authors should clarify the contribution of the paper on both theory and experiment comparing with the other works. There are some issues as below need to be clarified to evaluate the paper. 

-The control block diagram of the proposed network-based control method should be presented to compare with the conventional method presented by fig. 4.

-The colour scale of fig. 8 needs to be explained.

-The contribution of the paper presented in section 4 should be presented more explicitly such as by in the form of a theorem.

-The network used for experimental assess should include at least 3 inverters to ensure that the proposed method is usable for the general case of the parallel inverters.

-A figure describes the environment of the experiment should be provided.

-How the proposed can be used with the inverters, which have different rated powers and different time delay levels?

-How the proposed system be operated when trouble occurs with the communication network?

-How about the THD of currents presented in section 5.3?

 

Author Response

Please see the attachment.

Author Response File: Author Response.pdf

Reviewer 2 Report

Dear authors,

The paper proposes an interesting analysis of three-phase inverter parallel operation in AC microgrids. The paper extension is quite large but the appendix can help readers to understand the formulation.


In my modest point of view, there are several general questions that need more clarification:

1. What are the requirements of the network from the point of view of the latency and real-time response? In lines 340-341 you include a comment explaining that the system has a strong robustness towards time-delay but. You summarize this question in fig. 8 but a more detailed explanation is needed.

2. How robust is the proposed approach if network experiences communication problems?


From a more specific point of view:

Line 155. The first Zn is a complex magnitude. Please update the representation.
Line 167. "angel" should be "angle"
Line 176 and 343. Please, review table numeration. The first two tables are numbered as 1.

Line 224. Eq. (9) right term Qn has an extra prime

Line 294, 295 and 296. Please, review notation in equations (11), (12) and (13). The mutiplication/time symbol is a dot while in previous equations you don't use any symbol.

Line 421. Fig. 11. Please, review the input and output power flows in the inverter #2. Does the input to the Inverter #2 should be Pcom1 and Qcom1 and the output Pcal2 and Qcal2?

Line 474. The fonts of the legends included in figures 12 and 14 is too small. Please consider to increase it in order to improve the readability.

Line 619. Please review the numeration of the equations included in the appendix. There are two equations numbered as A18.

 

Thank you very much for your contribution

Best Regards

 

Author Response

Please see the attachment.

Author Response File: Author Response.pdf

Round 2

Reviewer 2 Report

Dear authors,

I really appreciate so much your effort improving the paper.

Best Regards

 

Back to TopTop