3.1. Power Frequency Startup
In power frequency starting mode, the frequency of the AC power was 50 Hz. The test results of seven valve openings are shown in
Figure 2,
Figure 3,
Figure 4 and
Figure 5.
Figure 2 shows the rising characteristics of the transient rotational speed during the power frequency startup. For a centrifugal pump, as its outlet valve opening increases, the output torque needs to increase, which theoretically affects the rising characteristics of the motor speed. It can be seen from
Figure 2a that the rising trend of the rotational speed was approximately linear at seven valve openings, while the differences among them were very tiny, and seven rotational speed curves rose to the final stable values at about 0.20 s. When the flow ratio
Q/Qr was 0.158 (
Qr is the rated flow rate), the rotational speed was the highest, about 1480 r/min; and when the flow ratio
Q/Qr was 1.312, the rotational speed was the lowest, about 1464 r/min. The intermediate range was approximately linear; i.e., the stable rotational speed at the end of the starting process showed a gradual and slight downward trend with the increase of the valve opening. This can be seen more clearly in
Figure 2b, which also illustrates that there was a slight lag in the time node at which the speed reached stability as the valve opening increased. In short, the change in rotational speed was not obvious, despite the valve opening.
The transient flow characteristics during the power frequency startup are shown in
Figure 3. It can be seen that the rising trend of each flow curve was basically the same but smoother compared to the rising trend of the rotational speed curve. Compared with the rising of the rotational speed in
Figure 2, it is easy to see that the rising of the flow was behind that of the rotational speed. This could be attributed to the fact that the transferred medium was static before starting; namely, the water body was static in the whole system.
The basic characteristics shown in
Figure 3 are that the rise rating was relatively slow at the beginning of the startup period and then rose rapidly. As the flow approached the stable value, the rising rate decreased again and finally reached a stable level. When the flow ratio
Q/Qr was 0.158, 0.312, 0.518, 0.708, 0.904, 1.100, and 1.312, the time required for the flow to rise to a stable value was about 0.70 s, 1.0 s, 1.10 s, 1.30 s, 1.40 s, 1.40 s, and 1.60 s, respectively. It can be seen that the time required for the flow to rise to the stable value was significantly greater than the time required for the rotational speed to rise to the stable value. Furthermore, with the increase of the valve opening, the time required for the flow to rise to the stable value also showed a gradually increasing trend. The rising characteristics of the head during the power frequency startup are shown in
Figure 4. Under seven different valve openings, the head curves rose to a stable value of approximately 9.76 m, 9.67 m, 9.55 m, 9.27 m, 8.83 m, 8.03 m, and 6.87 m respectively. As can be seen, the stable head decreased gradually with the increase of the valve opening.
It can be seen from
Figure 4 that at the end of startup, the steady head decreased gradually with the increase of the flow ratio. At the beginning of startup, the rise in head was relatively smooth, but then the rising rate increased rapidly. After 0.5 s, when the flow ratio
Q/Qr was 0.158, 0.312, 1.10, and 1.312, respectively, the four head curves showed a more obvious shock phenomenon. The maximum values in heads corresponding to the four valve openings were about 10.21 m, 10.05 m, 8.23 m, and 8.02 m, respectively, and the time of head impact was about 0.60 s, 0.70 s, 0.50 s, and 0.50 s, respectively. The impact head (defined as the difference between the maximum head and the stable head) corresponding to each valve opening was 0.45 m, 0.38 m, 0.20 m, and 1.15 m, respectively. It can be seen that when the flow ratio was from 0.158 to 0.518, the shock head gradually decreased with the increase of the valve opening; when the flow ratio was from 0.518 to 1.312, the shock head gradually increased with the increase of the valve opening. When the flow ratio was 0.518, 0.708, and 0.904, respectively, there was no obvious pressure shock phenomenon.
In the present experiment, a JC0-type torque speed sensor with a rated torque of 5 N·m was installed between the model pump and the motor to measure the transient rotational speed and transient torque. The shaft power of the centrifugal pump was calculated using the measured rotational speed and torque, as shown in
Figure 5. It was found that, except for the flow ratio of 1.312, the other six shaft power curves showed a relatively obvious power shock phenomenon. When the flow ratio was 0.158, 0.312, 0.518, 0.708, 0.904, and 1.100, respectively, the time of shaft power impact was about 0.30 s, and the corresponding maximum shaft powers were about 0.325 kW, 0.347 kW, 0.314 kW, 0.345 kW, 0.358 kW, and 0.407 kW, respectively. They all dropped to the stable value at about 0.60 s, and the corresponding stable shaft power values were about 0.242 kW, 0.258 kW, 0.278 kW, 0.308 kW, 0.331 kW, and 0.361 kW, respectively. The corresponding shock power (defined as the difference between the maximum shaft power and the stable shaft power) was 0.083 kW, 0.089 kW, 0.036 kW, 0.037 kW, 0.027 kW, and 0.046 kW, respectively. When the flow ratio was 1.312, there was no obvious shaft power impact phenomenon, and the shaft power curve rapidly rose at the beginning of startup; the final stable value was about 0.386 kW.
3.2. Frequency Conversion Startup
Frequency conversion startup means using a frequency converter to change the current frequency. By converting the current frequency, the motor speed can be controlled, so that the motor can start smoothly and reduce the impact on the local power grid.
The experimental results for the frequency conversion startup are shown in
Figure 6,
Figure 7,
Figure 8 and
Figure 9.
Figure 6 shows the measured transient rotational speed. The rising characteristics of the rotational speed curves at seven valve openings were basically the same. When the flow ratio was 0.155, 0.308, 0.504, 0.701, 0.902, 1.095, and 1.296, respectively, the difference in the rising of the rotational speeds to the respective stable values was very small. At 0.50 s, the corresponding transient rotational speeds were 531 r/min, 543 r/min, 541 r/min, 531 r/min, 515 r/min, 518 r/min, and 533 r/min, respectively. At the initial stage of startup, the rotational speed curves rose relatively rapidly, and after about 0.50 s, the rising rate tended to slow down. Within 0.5 s–2.3 s, seven rotational speed curves rose to the stable value at a slightly slower rate, and the rising trend was basically the same and showed a linear pattern. All rotational speed curves rose to the stable value at about 2.30 s, corresponding to the final stable values of about 1471 r/min, 1469 r/min, 1468 r/min, 1465 r/min, 1460 r/min, 1458 r/min, and 1455 r/min, respectively. The rotational speed at the end of the frequency conversion startup tended to decrease slightly with the increase of the valve opening, and this characteristic was the same as for the power frequency startup.
The transient flow characteristics during frequency conversion startup are shown in
Figure 7. The steady flow values corresponding to the seven valve openings were 0.90 m
3/h, 1.80 m
3/h, 3.0 m
3/h, 4.20 m
3/h, 5.40 m
3/h, 6.60 m
3/h, and 7.80 m
3/h, respectively. At the beginning of the frequency conversion startup, although the rotational speed rose rapidly, the rising rate of the flow curve was relatively slow. This was the same as for the power frequency startup; the reason for this phenomenon was that the water volume in the whole system before startup was in a static state, with large inertia. With the increase of the valve opening, the time required for the flow to rise to a stable value gradually increased. The flow curves rose to their respective stable values at approximately 0.94 s, 3.43 s, 4.13 s, 4.36 s, 4.53 s, 4.59 s, and 4.62 s for seven different valve openings. During the rising of each flow curve, the flow curves all rose at a more moderate rate at the beginning of startup and then rose rapidly. Of these, when the stable flow ratios were 0.155, 0.308, and 0.504, three flow curves showed a more obvious slowdown of the rising rate, and the time points corresponding to the phenomenon appearance were 0.62 s, 0.67 s, and 0.73 s, respectively. For the other four cases, a tendency towards slowing down was also found, but the transition curve was smoother and there was no more obvious mutation. The rising rates of the flow curves become very slow when rising close to the steady value at the end of startup. In short, the rising characteristics were different for different valve openings. Compared with the flow curves in power frequency startup, the rising rule in frequency conversion startup displayed an obvious distinction.
Figure 8 shows the transient head characteristics during the frequency conversion startup. The head curves also rose gradually with the increased rotational speed. The rising rate of the head curve was relatively slow up to about 1.20 s. At 1.20 s, the transient heads corresponding to seven different valve openings were 2.18 m, 2.13 m, 2.07 m, 2.03 m, 1.99 m, 1.86 m, and 1.72 m, respectively. After about 1.2 s, the rising rate of the head curves increased slightly. After the startup process, seven head curves rose to stable values at about 5.0 s. The corresponding stable values were 9.61 m, 9.56 m, 9.46 m, 9.24 m, 8.71 m, 7.95 m, and 6.85 m respectively. Compared with the flow ratio of 0.155, the drop in head was 0.05 m when the ratio was 0.308, which represented a drop of 0.52% relative to the former. Similarly, the relative values of the head drops were 1.05%, 2.33%, 5.74%, 8.73%, and 13.84% in the other cases. It can be seen from
Figure 8, that at the end of the frequency conversion startup, the degree of head drop increased gradually with the increase of the valve opening. It is easy to see that the head impact phenomenon is the maximum difference between the two startup modes.
The transient shaft power test results during the frequency conversion startup, are shown in
Figure 9. Combined with the rotational speed curves in
Figure 6, the variation characteristics of the shaft power curves is synchronized well in time; this was mainly because both of the physical quantities were measured by the same instrument. After frequency conversion startup, the shaft power curves rose rapidly; the rising rate of the shaft power curves slowed down slightly after about 0.50 s. Until about 2.40 s, all the curves had shaft power shock phenomenon to different degrees; i.e., the shaft power rose to the maximum value and then decreased to fluctuate around the steady value. For the seven valve opening cases, the maximum shaft power values were 0.262 kW, 0.279 kW, 0.292 kW, 0.322 kW, 0.348 kW, 0.367 kW, and 0.388 kW, respectively. When the rotational speeds rose to stable values, the shaft powers were characterized by periodic fluctuations as a whole, and the corresponding average values were about 0.233 kW, 0.249 kW, 0.271 kW, 0.302 kW, 0.327 kW, 0.351 kW, and 0.379 kW, respectively. The shock powers (i.e., the difference between the maximum value and the stable value) were 0.029 kW, 0.030 kW, 0.021 kW, 0.020 kW, 0.021 kW, 0.016 kW, and 0.009 kW, respectively. It can be seen from
Figure 9, that both the steady average values and the maximum values showed an increasing trend with the increase of the valve opening, although the shock powers showed an opposite trend overall; i.e., they gradually decreased with the increase of the valve opening. Therefore, the shock phenomenon of shaft power was more obvious when the outlet valve opening was relatively small. In conclusion, the impact phenomenon of shaft power was more obvious in the power frequency startup than in the frequency conversion startup. This indicates that the frequency conversion startup mode is safer.