Next Article in Journal
Competition of Dynamic Self-Confidence and Inhomogeneous Individual Influence in Voter Models
Previous Article in Journal
Statistical Mechanics Ideas and Techniques Applied to Selected Problems in Ecology
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Performance Optimization of Generalized Irreversible Refrigerator Based on a New Ecological Criterion

School of Aviation Science and Engineering, Beihang University, Beijing 100191, China
*
Author to whom correspondence should be addressed.
Entropy 2013, 15(12), 5277-5291; https://doi.org/10.3390/e15125277
Submission received: 10 October 2013 / Revised: 10 November 2013 / Accepted: 18 November 2013 / Published: 29 November 2013

Abstract

:
On the basis of the exergy analysis, a performance optimization is carried out for a generalized irreversible refrigerator model, which takes into account the heat resistance, heat leakage and internal irreversibility losses. A new ecological criterion, named coefficient of performance of exergy (COPE), defined as the dimensionless ratio of the exergy output rate to the exergy loss rate, is proposed as an objective function in this paper. The optimal performance factors which maximize the ecological objective function have been discussed. Numerical examples are given to explain the influences of heat leakage and internal irreversibility on the generalized and optimal performances. This new ecological criterion may be beneficial for determining the reasonable design of refrigerators.

1. Introduction

Since the 1970s, many studies on identification of the performance limits and optimization of the thermodynamic cycles for refrigerators have been carried out based on various objective functions [1,2,3,4,5,6,7,8,9,10,11,12,13,14,15,16,17,18,19,20,21,22,23,24,25]. Most of these previous works have chosen the cooling load, power input, coefficient of performance, exergy output rate and entropy generation rate as optimization criteria. Angulo-Brown et al. [26] proposed an ecological objective function, E′ = P − TLσ, for finite-time Carnot heat engines, where TL is the temperature of the cold heat reservoir, P is the power output and σ is the entropy generation rate. Yan [27] modified it to E = P − T0σ, where T0 is environment temperature. It is more reasonable to use E as the criterion function than that proposed by Angulo-Brown, because E is the best compromise between power output, P, and power loss, T0σ, when TLT0.
The ideas used in heat engines can also be applied to study the performance of refrigeration systems. Based on the viewpoint of energy analysis, Chen et al. [28,29] defined an ecological function E" = R − εcTHσ for endoreversible Carnot refrigerators working between two heat reservoirs (the heat sink and the heat source) with temperature TH and TL, where R is cooling load of the refrigerator, εc = TL / (TH − TL) is the reversible coefficient of performance (COP). Ust et al. [30,31] defined a new thermo-ecological objective function called ecological coefficient of performance (ECOP), which is defined as the ratio of cooling load to the loss of the availability, i.e., ECOP = R/T0σ. Furthermore, Chen et al. [32] proposed a unified ecological optimization objective for all thermodynamics cycles based on the view of exergy analysis as follows:
E = A/τ − T0σ
where A/τ is the exergy output of the cycle, T0 is the environment temperature of the cycle, and σ is the rate of the entropy generation of the cycle. When Equation (1) is examined, one can see that the objective function (E) may take negative values. At this condition, the exergy loss rate (second term in the E function) is greater than the exergy output rate (first term in the E function). Therefore, this objective function Equation (1) calls for a thermodynamic interpretation. For this purpose, we modify Equation (1) defined by Chen et al. [32] to the dimensionless ratio of exergy output rate to exergy loss rate (entropy generation rate), named coefficient of performance of exergy (COPE), i.e., COPE = (A/τ)/(T0σ). The COPE gives information about the exergy loss rate and entropy generation rate. Optimizations based on this new ecological criterion function have been performed. Numerical examples are presented to show the effects of heat leakage and internal irreversibility on the optimal performance of a generalized irreversible refrigerator.

2. Model and Basic Assumption

The Temperature-Entropy (T − S) diagram of the irreversible refrigerator is shown in Figure 1. The cycle operates between a heat sink at temperature TH and a heat resource at temperature TL. The working fluid in the cycle works at temperature THC and TLC, respectively. QHC is due to the driving force of (THCTH) in the high-temperature heat exchanger, QLC is due to the driving force of (TLTLC). QH is the net heat rates transferred to the heat source, and QL is the net heat rates transferred from the heat sink, i.e., the cooling load(R). The relationship between THC, TH, TL, TLC satisfies the following inequality:
THC > TH > TL > TLC
The model for the generalized irreversible refrigerator and its surroundings to be considered in this paper is shown in Figure 2.
Figure 1. T − S diagram for the generalized refrigerator model.
Figure 1. T − S diagram for the generalized refrigerator model.
Entropy 15 05277 g001
Figure 2. The model of the generalized refrigerator and its surroundings.
Figure 2. The model of the generalized refrigerator and its surroundings.
Entropy 15 05277 g002
The following assumptions are made for this model [33]:
(1)
The working fluid flows through the cycle at a steady state. The cycle consists of two isothermal processes and two adiabatic processes. All four processes are irreversible.
(2)
The heat transfer surface areas (F1 and F2) of the high- and low- temperature heat exchangers are finite. The total heat transfer surface area (F) of the two heat exchangers is assumed to be a constant:
F = F1 + F2
(3)
There exists heat leakage (q) from the heat sink to the heat source. Thus:
QH = QHC − q
QL = R = QLC − q
(4)
There are various irreversibilities in the refrigeration cycle due to: (i) heat resistance between heat reservoirs and working fluid. (ii) heat leakage between heat reservoirs and (iii) miscellaneous factors such friction, turbulence and non-equilibrium activities inside the refrigerator. Therefore, a larger power input is needed when compared with an endoreversible refrigerator. In other words, the rate of heat rejected to the sink (QHC) of the generalized irreversible refrigerator is higher than that of an endoreversible one (Q′HC). To scale these irreversibilities, we introduce a constant factor, ϕ, to characterize the additional internal miscellaneous irreversibility effect:
Entropy 15 05277 i001
The model described above is a more general one than the endoreversible [28] and irreversible [34,35,36,37,38,39] refrigerator models. If q = 0 and ϕ = 1, the model is reduced to the endoreversible refrigerator [28]. If q > 0 and ϕ = 1, the model is reduced to the irreversible refrigerator with heat resistance and heat leak losses [34,35,36]. If q = 0 and ϕ > 1, the model is reduced to the irreversible refrigerator with heat resistance and internal irreversibilities [37,38,39].

3. Optimization for Irreversible Refrigerator

The second law of thermodynamics for an irreversible refrigerator requires that:
Entropy 15 05277 i002
Combining Equations (6) and (7) yields:
Entropy 15 05277 i003
Consider that the heat transfers between the refrigerator and its surroundings obey Newton’s linear law:
Entropy 15 05277 i004
and:
Entropy 15 05277 i005
We define a heat transfer surface area ratio (f):
Entropy 15 05277 i006
The power input (P) to the refrigerator, according to the first law of thermodynamics, is:
Entropy 15 05277 i007
The coefficient of performance (ε) of the refrigerator is:
Entropy 15 05277 i008
Equations (7)–(13) yield:
Entropy 15 05277 i009
Entropy 15 05277 i010
Combining Equations (8)–(11) gives:
Entropy 15 05277 i011
which then yields:
Entropy 15 05277 i012
Combining Equations (3) and (9)–(11) gives:
Entropy 15 05277 i013
Substituting Equation (18) into Equations (16) and (17), we obtain:
Entropy 15 05277 i014
and:
Entropy 15 05277 i015
Substituting Equations (19) and (20) into Equations (14) and (15) derives the entropy generation rate (σ) and coefficient of performance (ε) of the generalized irreversible refrigerator cycle as follows:
Entropy 15 05277 i016
Entropy 15 05277 i017
Based on the viewpoint of exergy analysis, the objective function of ecological optimization, proposed by Angulo-Brown [26] and modified by Yan [27], is:
Entropy 15 05277 i018
where T0 is the environment temperature.
The ECOP (ecological coefficient of performance) is defined by Ust et al. [31], as the ratio of power output to the loss rate of availability, i.e.,
Entropy 15 05277 i019
Based on the viewpoint of exergy analysis, Chen et al. [32] provide an ecological optimization objective for refrigerator cycles:
Entropy 15 05277 i020
The COPE (coefficient of performance of exergy) is defined as the ratio of the exergy output rate to exergy loss rate (entropy generation rate), thus, COPE is a dimensionless ecological function. It is written as:
Entropy 15 05277 i021
Combining Equations (21), (22) and (26) one obtains:
Entropy 15 05277 i022
where Entropy 15 05277 i023 and Entropy 15 05277 i024.
Equations (21), (22) and (27) indicate that the entropy generation rate (σ), COP(σ) and COPE of the generalized irreversible refrigerator are functions of the heat transfer surface ratio (f) for given TH, TL, T0, R, q, α, β, F, and ϕ. Taking the derivatives of σ, ε and COPE with respect to f and letting them equal to zero (dσ/df = 0, dε/df = 0, dCOPE/df = 0) gives the same optimum surface area ratio:
Entropy 15 05277 i025
The corresponding optimal entropy generation rate, the optimal COP and the optimal COPE are as follows:
Entropy 15 05277 i026
Entropy 15 05277 i027
Entropy 15 05277 i028
where Entropy 15 05277 i029.

4. Discussion

(1)
If q = 0 and ϕ = 1, the model is reduced to the endoreversible refrigerator with external heat resistance as the sole irreversibility in the system, and Equations (29)–(31) become:
Entropy 15 05277 i030
Entropy 15 05277 i031
Entropy 15 05277 i032
where Entropy 15 05277 i033.
(2)
If q > 0 and ϕ = 1, the model is reduced to the irreversible refrigerator with heat resistance and heat leak losses, and Equations (29)–(31) become:
Entropy 15 05277 i034
Entropy 15 05277 i035
Entropy 15 05277 i036
(3)
If q = 0 and ϕ > 1, the model is reduced to the irreversible refrigerator with heat resistance and internal irreversibilities, and Equations (29)–(31) become:
Entropy 15 05277 i037
Entropy 15 05277 i038
Entropy 15 05277 i039
(4)
If q > 0 and ϕ > 1, and in order to find the optimal coefficient of performance of exergy (COPE) for the generalized irreversible refrigerator, letting dCOPE/dR = 0 yields:
Entropy 15 05277 i040
Entropy 15 05277 i041
where:
Entropy 15 05277 i042
Entropy 15 05277 i043
Entropy 15 05277 i044
Entropy 15 05277 i045
Entropy 15 05277 i046
Entropy 15 05277 i047
Entropy 15 05277 i048
Entropy 15 05277 i049
Entropy 15 05277 i050
Entropy 15 05277 i051

5. Numerical Examples

5.1. Calculation Conditions

Assume that heat leakage from the heat sink at temperature TH to the heat source at temperature TL follows a linear law, which was first provided by Bejan [34], and it is given as:
Entropy 15 05277 i052
where Ci is the internal conductance of the refrigerator. Substituting Equation (53) into the above performance equations yields the corresponding optimal relationships.
In the numerical calculation for the performance characteristics of the refrigerator, α = β, αF = 4kWK−1, TH = 300K, TL = 260K, T0 = 290K, ϕ = 1.00 − 1.30 and Ci = 0.00 − 0.03kWK−1 are set.

5.2. The Main Influencing Factors on COPE

5.2.1. Cooling Load and Entropy Generation Rate

The variation of the COPE ecological function with respect to cooling load, COPE − R, and the variation of the COPE ecological function versus entropy generation rate, COPE − σ, for different values of ϕ and Ci are plotted in Figure 3 and Figure 4.
Figure 3. The variation of the COPE ecological function with respect to the cooling load (R) for different values of ϕ and Ci. (a) ϕ = 1.00 (b) ϕ = 1.03 (c) ϕ = 1.07 (d) ϕ = 1.10.
Figure 3. The variation of the COPE ecological function with respect to the cooling load (R) for different values of ϕ and Ci. (a) ϕ = 1.00 (b) ϕ = 1.03 (c) ϕ = 1.07 (d) ϕ = 1.10.
Entropy 15 05277 g003aEntropy 15 05277 g003b
Figure 4. Variation of the COPE ecological function with respect to the entropy generation rate (σ) for different values of ϕ and Ci. (a) ϕ = 1.00 (b) ϕ = 1.03 (c) ϕ = 1.07 (d) ϕ = 1.10.
Figure 4. Variation of the COPE ecological function with respect to the entropy generation rate (σ) for different values of ϕ and Ci. (a) ϕ = 1.00 (b) ϕ = 1.03 (c) ϕ = 1.07 (d) ϕ = 1.10.
Entropy 15 05277 g004
Figure 3 illustrates that the COPE is a monotonic decreasing function while Ci = 0. In other situation, the COPE reaches the maximum point while the cooling load is at the optimal value. The maximum of COPE declines from about 4.5 to less than 1.5 with the growth of irreversibility ϕ. The details can be seen from Table 1. Figure 4 shows that the COPE function follows the similar trend with respect to the entropy generation rate ( ϕ) as it versus the cooling load (R).
Table 1. Performance of irreversible refrigerators.
Table 1. Performance of irreversible refrigerators.
ϕ1.01.01.01.11.11.1
Ci0.010.020.030.010.020.03
T0σE(kW)0.140.270.430.731.171.58
εE5.234.784.463.112.892.73
COPEmax4.312.922.300.980.86440.79
ECOPm27.8718.7714.766.195.394.88
Rm(kW)3.685.26.3564.516.347.72
ϕ1.21.21.21.31.31.3
Ci0.010.020.030.010.020.03
T0σE(kW)1.472.262.922.213.374.36
εE2.222.081.971.731.621.55
COPEmax0.570.520.490.410.380.36
ECOPm3.493.162.932.432.242.10
Rm(kW)5.007.058.585.3767.539.15

5.2.2. The Coefficient of Performance (COP)

Exergy loss rate, COPE, cooling load versus COP characteristic with ϕ = 1.01 and Ci = 0.01kWK−1 is illustrated in Figure 5. It shows that there exists a maximum COP point while the corresponding exergy loss rate, COPE, and cooling load are (T0σ)ε, COPEε, and Rε, respectively [32]. It can be seen from Figure 5 that the optional working field should be on the upper half of the characteristic curves, that is the region lied in T0σ > (T0σ)ε, COPE > COPEε or R > Rε.
Figure 5. Variation of the exergy loss rate, COPE and cooling load (R) with respect to COP (ε) characteristics with ϕ = 1.01 and Ci = 0.01kWK−1.
Figure 5. Variation of the exergy loss rate, COPE and cooling load (R) with respect to COP (ε) characteristics with ϕ = 1.01 and Ci = 0.01kWK−1.
Entropy 15 05277 g005

5.2.3. The Irreversibility and Internal Conductance

One can observe from Figure 6 and Figure 7 that with increase of the irreversibility ϕ or the internal heat conductance of the refrigerator Ci, the COPE function decreases monotonically. It also shows that as the cooling load increases, slope of the COPE function decreases.
Figure 6. Influence of ϕ on COPE with different values of cooling load (R).
Figure 6. Influence of ϕ on COPE with different values of cooling load (R).
Entropy 15 05277 g006
Figure 7. Influence of Ci on COPE with different values of cooling load (R).
Figure 7. Influence of Ci on COPE with different values of cooling load (R).
Entropy 15 05277 g007

5.3. Optimal Matching Criterion

The optimization of the dimensionless COPE ecological function provides a selectable design point which satisfies the condition mentioned above and gives the corresponding optimal selection. In order to judge design point performance, we choose another arbitrary working condition, for example the condition where the cooling load is 6 kW with ϕ = 1.02 and Ci = 0.01. Comparing the chosen working point with the optimal one, the COP decreases about 1%, but the entropy generation rate increases about 21%.
The optimization of the COPE function makes the entropy generation rate of the cycle decrease significantly, and the COP reaches the maximum point when the cooling load is chosen at the optimal point. Therefore, it represents a compromise between the exergy output rate and the exergy loss rate (entropy generation rate) when the cooling load is a constant.

5.4. Comparison between COPE and ECOP

Ust proposed in [40] an ecological function ECOP for irreversible air refrigeration cycles as ECOP = R/T0σ, where R is the cooling load and T0σ is the entropy generation rate of the cycle. In fact, for refrigeration cycles, the exergy output is not the cooling load [28,29]. The exergy output rate of refrigeration cycles should be written as:
Entropy 15 05277 i053
which is just the first term of the right side of Equation (25). ECOP combines the cooling load R, which is a physical quantity based on the energy point, with the entropy generation rate (exergy loss rate) T0σ, which is a physical quantity based on the exergy point. It cannot represent a best compromise between the exergy output rate, A, and the exergy loss rate, T0σ, of the refrigeration cycles, based on the viewpoint of exergy analysis.
Therefore, we propose the COPE function as a unified ecological criterion. It has several advantages to analyze the performance of the refrigeration system. First, the COPE function would not take negative values as equations with the form like E = R − T0σ. The dimensionless form of the COPE guarantees the objective function meaningful both mathematically and thermodynamically. Second, the COPE function is defined purely from the perspective of exergy. It can provide the best compromise between the exergy output rate to the exergy loss rate.

6. Conclusions

A thermo-ecological performance optimization of the generalized irreversible refrigerator models with finite heat transfer ability, heat leakage and internal irreversibilities based on a new objective function named coefficient of performance of exergy (COPE) has been carried out. Numerical examples are given to analyze the influences of heat leakage and internal irreversibilities on the optimal performance of the generalized irreversible refrigerator.
By optimizing the ecological function COPE, we find that: (1) the irreversibility and internal conductance have inverse proportion relationship with the ecological function COPE, that is, both of them contribute to exergy destruction; (2) when the cooling load increases, the effects of irreversibilities and heat leakage on COPE function become weaker; (3) there exists a maximum point of COP at about 5 for a given exergy loss rate or cooling load; (4) the optimization process gives a new criterion on how to match cooling load for given generalized irreversible refrigerator system.
Based on the viewpoint of exergy analysis, we have derived analytically the optimal cooling load, the optimum coefficient of performance and the minimum entropy generation rate. It also represents a compromise between the exergy output rate and the entropy generation rate. Furthermore, it gives a candidate option for refrigerator design. Thus, it is essential to investigate and optimize the ecological function COPE for the generalized irreversible refrigerator by taking account of both the internal irreversibilities and heat leakages.

Acknowledgments

The authors are grateful to the anonymous reviewers for their constructive review of the manuscript. The research is sponsored by the Aviation Science Foundation of China (2011ZC09004).

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Curzon, F.L.; Ahlborn, B. Efficiency of a Carnot engine at maximum power output. Am. J. Phys. 1975, 43, 22–24. [Google Scholar] [CrossRef]
  2. Bejan, A. Entropy Generation through Heat and Fluid Flow, 1st ed.; Wiley: New York, NY, USA, 1982; pp. 118–152. [Google Scholar]
  3. Bejan, A. Entropy Generation Minimization: The Method of Thermodynamic Optimization of Finite-Size Systems and Finite-Time Processes, 1st ed.; CRC Press: Boca Raton, FL, USA, 1996; pp. 70–122. [Google Scholar]
  4. Chen, L.G.; Wu, C.; Sun, F.R. Finite time thermodynamic optimization or entropy generation minimization of energy system. J. Non-Equil. Thermodyn. 2005, 24, 327–359. [Google Scholar] [CrossRef]
  5. Chen, L.G.; Zhang, L.; Sun, F.R. Power, efficiency, entropy-generation rate and ecological optimization for a class of generalized irreversible universal heat-engine cycles. Appl. Energy 2007, 84, 512–525. [Google Scholar] [CrossRef]
  6. Durmayaz, A.; Sogut, O.S.; Sahin, B.; Yavuz, H. Optimization of thermal systems based on finite-time thermodynamics and thermoeconomics. Prog. Energy Combust. Sci. 2004, 30, 175–217. [Google Scholar] [CrossRef]
  7. Chen, C.K.; Su, Y.F. Exergetic efficiency optimization for an irreversible Brayton refrigeration cycle. Int. J. Therm. Sci. 2005, 44, 303–310. [Google Scholar] [CrossRef]
  8. Tu, Y.; Chen, L.G.; Sun, F.R.; Wu, C. Cooling load and efficient of performance optimizations for real air-refrigerators. Appl. Energy 2006, 83, 1289–1306. [Google Scholar] [CrossRef]
  9. Chen, L.G.; Wu, C.; Sun, F.R. Steady flow combined refrigeration cycle performance with heat leak. Appl. Therm. Eng. 1997, 17, 639–645. [Google Scholar] [CrossRef]
  10. Zhu, X.Q.; Chen, L.G.; Sun, F.R.; Wu, C. Effect of heat transfer law on the ecological optimization of a generalized irreversible Carnot heat pump. Int. J. Exergy 2005, 2, 423–436. [Google Scholar] [CrossRef]
  11. Chen, L.G.; Zhu, X.Q.; Sun, F.R.; Wu, C. Ecological optimization of a generalized irreversible Carnot refrigerator for a generalized heat transfer law. Int. J. Ambient Energy 2007, 28, 213–219. [Google Scholar] [CrossRef]
  12. Chen, L.G.; Li, J.; Sun, F.R. Ecological optimization of a generalized irreversible Carnot refrigerator in case of Entropy 15 05277 i054. Int. J. Sustain. Energy 2012, 31, 59–72. [Google Scholar] [CrossRef]
  13. Agnew, B.; Anderson, A.; Frost, T.H. Optimisation of a steady-flow Carnot cycle with external irreversibilities for maximum specific output. Appl. Therm. Eng. 1997, 1, 3–15. [Google Scholar] [CrossRef]
  14. Zhu, X.Q.; Chen, L.G.; Sun, F.R.; Wu, C. Exergy based ecological optimization for a generalized irreversible Carnot refrigerator. J. Energy Inst. 2006, 79, 42–46. [Google Scholar] [CrossRef]
  15. Goktun, S. Coefficient of performance for an irreversible combined refrigeration cycle. Energy 1996, 21, 721–724. [Google Scholar] [CrossRef]
  16. Salah El-Din, M.M. Optimization of totally irreversible refrigerators and heat pumps. Energy Convers. Manag. 1999, 40, 423–436. [Google Scholar] [CrossRef]
  17. Chen, J.; Chen, X.; Wu, C. Ecological optimization of a multi-stage irreversible combined refrigeration system. Energy Convers. Manag. 2002, 43, 2379–2393. [Google Scholar] [CrossRef]
  18. Bhattacharyya, S.; Bose, S.; Sarkar, J. Exergy maximization of cascade refrigeration cycles and its numerical verification for a transcritical CO2-C3H8 system. Int. J. Refrig. 2007, 30, 624–632. [Google Scholar] [CrossRef]
  19. Chen, L.G.; Li, J.; Sun, F.R. Generalized irreversible heat-engine experiencing a complex heat-transfer law. Appl. Energy 2008, 85, 52–60. [Google Scholar] [CrossRef]
  20. Chen, L.G.; Sun, F.R.; Wu, C. Influence of heat-transfer law on the performance of a Carnot engine. Appl. Therm. Eng. 1993, 17, 277–282. [Google Scholar] [CrossRef]
  21. Chen, J.; Chen, X.; Wu, C. Optimisation of rate of exergy output of a multistage endoreversible combined refrigeration system. Exergy 2001, 1, 100–106. [Google Scholar] [CrossRef]
  22. Morosuk, T.; Tsatsaronis, G. Advanced exergetic evaluation of refrigeration machines using different working fluids. Energy 2009, 34, 2248–2258. [Google Scholar] [CrossRef]
  23. Koda, A.; Sahin, B.; Yilmaz, T. Effects of internal irreversibility and heat leakage on the finite-time thermoeconomic performance of refrigerators and heat pumps. Energy Convers. Manag. 2000, 41, 607–619. [Google Scholar] [CrossRef]
  24. Ust, Y. Performance analysis and optimization of irreversible air refrigeration cycles based on ecological coefficient of performance criterion. Appl. Therm. Eng. 2009, 29, 47–55. [Google Scholar] [CrossRef]
  25. Tyagi, S.K.; Kaushik, S.C.; Salhotra, R. Ecological optimization and performance study of irreversible Stirling and Ericsson heat-engines. J. Phys. D 2002, 35, 2668–2675. [Google Scholar] [CrossRef]
  26. Angulo-Brown, F. An ecological optimization criterion for finite-time heat engines. J. Appl. Phys. 1991, 69, 7465–7469. [Google Scholar] [CrossRef]
  27. Yan, Z. Comment on “ecological optimization criterion for finite-time heat-engines”. J. Appl. Phys. 1993, 73, 3583. [Google Scholar] [CrossRef]
  28. Chen, L.G.; Sun, F.R.; Wu, C. Ecological optimization criteria for an endoreversible Carnot refrigerator. Nat. J. 1992, 15. No. 8, (in Chinese). [Google Scholar]
  29. Chen, L.G.; Sun, F.R.; Wu, C. On the ecological figures of merit for thermodynamics cycles. J. Eng. Therm. Energy Power 1994, 9, 374–376. (in Chinese). [Google Scholar]
  30. Ust, Y.; Sahin, B. Performance optimization of irreversible refrigerators based on a new thermo-ecological criterion. Int. J. Refrig. 2007, 30, 527–534. [Google Scholar] [CrossRef]
  31. Ust, Y.; Sahin, B.; Sogut, O.S. Performance analysis and optimization of an irreversible dual-cycle based on an ecological coefficient of performance criterion. Appl. Energy 2005, 82, 23–39. [Google Scholar] [CrossRef]
  32. Chen, L.G.; Zhu, X.; Sun, F.R.; Wu, C. Ecological optimization for generalized irreversible Carnot refrigerators. J. Phys. D 2005, 35, 113–118. [Google Scholar] [CrossRef]
  33. Chen, L.G.; Sun, F.R.; Wu, C. A generalized model of a real refrigerator and its performance. Appl. Therm. Eng. 1997, 17, 401–412. [Google Scholar] [CrossRef]
  34. Bejan, A. Theory of heat transfer-irreversible refrigeration plants. Int. J. Heat Mass Trans. 1989, 32, 1631–1639. [Google Scholar] [CrossRef]
  35. Chen, L.G.; Wu, C.; Sun, F.R. Influence of internal heat leak on the performance of refrigerators. Energy Convers. Manag. 1998, 39, 45–50. [Google Scholar] [CrossRef]
  36. Gordon, J.M.; Ng, K.C. Thermodynamic modeling of reciprocating chillers. J. Appl. Phys. 1994, 75, 2769–2774. [Google Scholar] [CrossRef]
  37. Sun, F.R.; Wu, C.; Chen, L.G. Optimal performance and rate of entropy production for forward and reverse irreversible Carnot cycles. Chin. J. Eng. Thermophys. 1991, 12, 357–360. [Google Scholar]
  38. Ait-Ali, M.M. A class of internally irreversible refrigeration cycles. J. Phys. D 1996, 29, 593–599. [Google Scholar] [CrossRef]
  39. Ait-Ali, M.M. The maximum coefficient of performance of internally irreversible refrigerators and heat pumps. J. Phys. D 1996, 29, 975–980. [Google Scholar] [CrossRef]
  40. Ust, Y. Performance analysis and optimization of irreversible air refrigeration cycles based on ecological coefficient of performance criterion. Appl. Therm. Eng. 2009, 29, 47–55. [Google Scholar] [CrossRef]

Share and Cite

MDPI and ACS Style

Xu, J.; Pang, L.; Wang, J. Performance Optimization of Generalized Irreversible Refrigerator Based on a New Ecological Criterion. Entropy 2013, 15, 5277-5291. https://doi.org/10.3390/e15125277

AMA Style

Xu J, Pang L, Wang J. Performance Optimization of Generalized Irreversible Refrigerator Based on a New Ecological Criterion. Entropy. 2013; 15(12):5277-5291. https://doi.org/10.3390/e15125277

Chicago/Turabian Style

Xu, Jie, Liping Pang, and Jun Wang. 2013. "Performance Optimization of Generalized Irreversible Refrigerator Based on a New Ecological Criterion" Entropy 15, no. 12: 5277-5291. https://doi.org/10.3390/e15125277

Article Metrics

Back to TopTop