Review

Intelligent Systems for Building Energy and Occupant Comfort Optimization: A State of the Art Review and Recommendations

1
Laboratoire d’Innovation Numérique pour les Entreprises et les Apprentissages au service de la Compétitivité des Territoires, Centre des Études Supérieures Industrielles, 2 Avenue de Provence, 29200 Brest, France
2
Institut de Recherche Dupuy de Lôme (UMR CNRS 6027 IRDL), University of Brest, 29238 Brest, France
3
Institut de Recherche Dupuy de Lôme (UMR CNRS 6027 IRDL), ISEN Yncréa Ouest, 29200 Brest, France
4
Logistics Engineering College, Shanghai Maritime University, Shanghai 201306, China
*
Author to whom correspondence should be addressed.
Energies 2018, 11(10), 2604; https://doi.org/10.3390/en11102604
Submission received: 28 August 2018 / Revised: 13 September 2018 / Accepted: 28 September 2018 / Published: 29 September 2018
(This article belongs to the Special Issue 10 Years Energies - Horizon 2028)

Abstract

:
Today, buildings consume more than 40% of primary energy in and produce more than 36% of CO2. So, an intelligent controller applied to the buildings for energy and comfort management could achieve significant reduction in energy consumption while improving occupant’s comfort. Conventional on/off controllers were only able to automate the tasks in building and were not well suited for energy optimization tasks. Therefore, building energy management has become a focal point in recent years, promising the development of various technologies for various scenarios. This paper deals with a state of the art review on recent developments in building energy management system (BEMS) and occupants comfort, focusing on three model types: white box, black box, and gray box models. Through a comparative study, this paper presents pros and cons of each model.

1. Introduction

Currently, buildings are responsible for preeminent amount of world’s energy consumption and CO2 emission. According to the European Energy Efficiency Commission (EEEC), buildings in the EU represent 40% of total primary energy consumption [1] and nearly 36% of CO2 emission [2]. The energy generated from fossil fuels contributes considerable CO2 emission and causes global warming. Consequently, the government authorities, regulators and policy makers have been influencing people in the direction of sustainable buildings by introducing energy efficiency policies. The International Energy Agency (IEA) specifies: “Globally, the wide deployment of best available technologies and energy efficiency policies could yield annual savings in buildings final energy use of roughly 53 exajoules (EJ) by 2050” [3]. This amount is equivalent to cumulative energy consumption by buildings in China, France, Germany, Russia, the United Kingdom and the United States in 2012 [4]. Therefore, optimization of energy consumption is crucial for healthy environment and sustainable development. Integration of renewable energies [5] and intelligent systems [6] to the buildings could achieve the estimated savings in energy consumption. However, efficient building energy consumption optimization is still a challenging task because of various parameters that affecting building energy consumption. These influential factors can be divided into major five types:
  • Building physical and thermal properties (thermal conductivity, specific heat, thickness, density, etc.) [7].
  • Occupancy behaviour (occupancy activities, interaction with the building, etc.) [8].
  • Building sector type and building energy policies (type of building, location, respective regional policies, etc.) [9].
  • Population size (number of occupants presence, indoor activities) [10].
  • Climatic conditions (outdoor dry bulb temperature, wind speed, outdoor relative humidity, solar radiation, etc.) [3].
Among these five influential factors, building physical properties, climatic conditions and occupancy behaviour have a direct impact on energy consumption. At the same time other parameters represents slightly minimal effect on the energy consumption. A study conducted on university buildings to evaluate the relationship between energy consumption and population size, user activities, and demand profiles reveals population size have a minimal impact on electrical energy consumption as compared to other parameters [10]. Generally, people spend 90% of their life in buildings [11], hence the maintenance of comfortable environment is important to assure occupants’ health and productivity. The quality of occupants’ living is determined by three comfort parameters: thermal comfort, indoor air quality and visual comfort. These three comforts are achievable by exploiting Heating, Ventilation and Air-Conditioning (HVAC) controller and lighting systems with natural resources (day lighting, outside temperature, etc.).
A Building Energy Management System (BEMS) is required to improve energy performance meanwhile ensuring improved occupants’ comfort. Conversely, realisation of indoor comfort environments draws more energy to achieve and maintain the optimal comfort. Therefore a proper trade-off is required between energy and indoor comfort [12]. In this context, recent developments in the BEMS are focusing on smart technologies to address the gap between energy consumption and occupants’ comfort.

1.1. Building Modelling Approach

Three main approaches have been used for building energy management systems: white box models, black box models and gray box models. White box models [13,14] are a physical modelling approach relying on thermodynamic and/or mathematical equations and engineering methods for energy modelling, analysis and control. White box-based modelling approach examples are the building energy analysis simulation software such as: EnergyPlus [15], Transient System Simulation Tool (TRNSYS) [16], eQuest [17], etc. These software tools basically are used during building planning and designing phases, prior to the building construction. They calculate overall energy consumption [18], HVAC design [19], operation scheduling, lighting information [20], etc., based on the detailed building physical properties [21], occupancy schedule, geographical conditions, and type of building and climatic parameters. However, availability of such precise data for the simulation is troublesome and in some cases impossible to obtain. Also, due to the non-linear behaviour of building parameters, white box models are suitable for simple models and as when applied to complex buildings, the model tends to be thermodynamically complex.
Black box models are data driven building energy models, which are built on data basis [22,23,24,25,26] often considered as easy to model over physics-based white box models. Generally, black box models are applied for prediction of energy consumption [25], HVAC operation scheduling [27], and adaptive control systems [28]. Black box models methods examples are Artificial Neural Networks (ANNs), Support Vector Machine (SVM), Genetic Algorithms (GAs), Reinforcement Learning (RL), deep machine learning [29], etc. Aside from the ease to apply, black box models require large input data to train the model [30]. This data may not be available in buildings in which sensors are not installed, thereby limiting their application to the few buildings with installed sensors.
To overcome white box and black box models drawbacks, hybrid models were introduced [31]. Hybrid models (gray box models) are combination of physics-based models (white box models) and statistical methods (black box models). Gray box modelling is found out as robust and accurate for building systems modelling and in building performance improvement [31].

1.2. Indoor Comfort Parameters

People spend most of their time in buildings. Maintenance of indoor comfort parameters is therefore significant to improve occupants productivity, health, and comfort feeling [32]. Thermal comfort in indoor environment is the principal component for ensuring indoor environment quality. Thermal comfort is generally expressed as the satisfaction of thermal environment, usually referred as psychological sensation of thermal environment [33]. Visual comfort is another parameter affecting the indoor environment quality. Basically, proper illumination level is essential for commercial, institutional, and industrial buildings to preserve inhabitants working efficiency.

1.3. Objectives and Motivation

Several literature reviews have been previously published in building energy and comfort management context. Dounis and Caraiscos [34], reviewed advanced control systems for energy and comfort optimization covering various control strategies, whereas Lombard et al. [35] detailed building energy consumption by building types and HVAC systems. Zhao and Magoulès [36] summarized various building energy consumption prediction methods based on classification; engineering model, statistical model, neural networks, support vector machines, and gray models. Amasyali and El-Gohary [37] elaborated data driven prediction methods and in addition, Wei et al. [38] discussed classification of building energy consumption. Previous literature studies have discussed various building energy management systems, prediction of energy consumption, and occupancy relation with buildings. However, a clear gap is observed for the consideration of recent developments in control strategies for optimal energy and comfort management in buildings. In this state of the art paper, the recent developments in BEMS methods along with indoor comfort conditions were discussed in detail and critically reviewed. Besides, the review papers are selected from the year 2013 onwards (around 80% papers) for clearly focus on recent developments. An elementary related research was conducted by using search engine and scientific websites: Google scholar, Science Direct and IEE explore digital library. The keywords ’building energy management’, ’building comfort management’, ’intelligent systems for buildings’, and ’building control’ were used for filtering papers to perform the review process. Papers were only selected from top international journals and indexed conference proceedings. Based on the selection criteria, 90 papers were further considered for this state of the art review.
The content of the paper is organised as follows: Section 2 reviews studies of recent developments in building energy management systems based on their model type, Section 3 details and discusses the literature review observations. Main conclusions and future investigations are described in Section 4.

2. Building Energy Management Systems—BEMS

BEMS are generally installed in buildings to monitor and control indoor comfort conditions and energy consumption [18]. These systems are mainly based on sensors, actuators, software, and hardware networks [6,39]. Normally, buildings with few occupants (residential, and office buildings) may permit to interact with BEMS technologies via a human machine interface (HMI) [40] to control electrical appliances and HVAC system operation. These interactions could be restricted in institutional, commercial, and industrial buildings because of the large number of occupants, where each may posses a unique set point, resulting in higher energy consumption. Hence, HVAC system operating values are set to a standard range to maintain indoor comfort in such buildings. However, heterogeneous parameters affecting building energy and comfort hinder the performance of BEMS models.

2.1. White Box Models

White box models are thermal dynamics modelling, which are based on fundamental laws of physics, thermodynamics, and heat transfer. Generally this approach can be roughly classified into two types: physics-based models using simulation tools such as: TRNSYS, EnergyPlus, etc., and physics governing laws-based thermal dynamics state-space equation or lumped capacitance model [41].
Due to the diversified and heterogeneous behaviour of building parameters, complexity of hardware network (sensors, and actuators), and occupants interaction with buildings, it is difficult to carry out full scale experiments. Hence, software tools are affordable and ease-to-use platforms that can be used for building dynamics evaluation and analysis. Numerous software tools have been developed over the last few decades for the analysis of energy consumption, HVAC design, operation scheduling, lighting information, renewable energies, etc., Regular up-gradation is performed on these simulation tools to improve the performance efficiency and decreasing computational cost. The list of US Department of Energy (DOE) organisation approved building simulation tools is available in [42].
EnergyPlus is a building energy performance analysis simulation software and console-based program that reads inputs and writes outputs in text files, developed based on DOE-2 [43] and the Building Loads Analysis and System Thermodynamics (BLAST) by National Renewable Energy Laboratory(NREL) and U.S. DOE Building Technologies Office (BTO) [15]. Zhao et al. [44] used EnergyPlus to procure raw data for commercial building to perform overall energy performance and dynamic pricing by using Cyber Physical Systems (CPS)—enabled BEMS [45]. Furthermore, a fuzzy logic controller (FLC) is initially designed based on the data probation from EnergyPlus and a GA method applied to FLC for evolution of improved member functions population for improved comfort control energy optimization of a food service center. The results were compared with stand-alone EnergyPlus output and investigated that the GA-FLC-based method resulted notable decrease in energy consumption during both cooling and heating [46]. This shows that EnergyPlus lacks interactive control optimization techniques and would be coupled with other dynamic computational software (Matlab, Modelica [47]) via co-simulation software building controls virtual test bed (BCVTB). Kim et al. [19] used EnergyPlus for training ANNs and coupled GA for optimization of integrated daylighting and HVAC systems. This was performed to ensure large database available for training ANNs in less time, otherwise 3 months would have been needed to procure data from sensors. A multi-objective optimization strategy is validated using non-dominated sorting genetic algorithm (NSGA), implemented in the GenOpt [48] optimization engine through the Java genetic algorithms package, to instruct the EnergyPlus simulation tool [12]. Meanwhile, Huh et al. [49] developed a system to generate predicted real-time weather data for 24 h duration using EnergyPlus coupled with GenOpt through BCVTB [50]. This approach improves the building energy control optimization based on real time prediction control.
TRNSYS (Transient systems simulation program) is a dynamic computational software for building energy performance analysis [16]. It is incorporated with Matlab for database generation to train 2 ANNs used for predictive and adaptive approach applied to hotel building. The developed model efficiently improved thermal comfort and building energy optimization during summer season resulting in 18–38% energy savings over the simulation period [28]. TRNSYS was used for determining building cooling load needed from the chiller plant, Later, these data were fed to Matlab for performing optimization analysis [51].
BCVTB is used for coupling various simulation tools for co-simulation and co-simulation to hardware. Refs. [13,46,52] used BCVTB to ease the simulation process by coupling EnergyPlus, Matlab in their model for building energy performance analysis. Meanwhile, BCVTB was coupled with EnergyPlus to generate real-time weather data file for energy consumption prediction in one day [49]. Figure 1 shows the process of generating a weather data file based on the forecasted weather using BCVTB as a coupling platform between EnergyPlus and other tools. The weather elements from weather forecast by national weather station, calculated weather parameters, measured weather elements, and default parameters are coupled together in BCVTB platform for generating weather forecast.
Although simulation tools are the first choice for building energy performance analysis because of accuracy and effectiveness, they require proper data of building, weather parameters, and physical properties. However, collecting appropriate data is always difficult and in some cases these data are not available. This is the major challenge in retrofitting existing buildings. In addition, these tools lack controller development flexibility and absence of high performance controller systems in their libraries yields difficulty to develop and integrate in practical application/implementation [53].

2.2. Black Box Models

These are also known as data-driven models and are developed based on statistical models by quantifying historical data parameters and correlating between building performance and data to find optimal pattern. Data-driven model approach is often considered as less complex with high accuracy and low computational cost. However, the inner process is mostly unknown, leading to reduced control flexibility of the overall process. The primary requirement of black box models are pre-collected data. These can be obtained from following sources:
  • Real data collected from existing building through sensors, smart meters, and other smart systems [54].
  • Simulated data collected from the simulation tools such as EnergyPlus, BCVTB, etc., [30].
  • Standard data available in public benchmark datasets such as ASHRAE’s data [23].
Black box models are known for prediction techniques and gained huge consideration over last decade. Commonly, these models are used in prediction of building energy consumption [23,25,55], indoor temperature [54,56], heating/cooling load demand [24], HVAC parameters, occupancy [57,58], and energy generation from RES. Some major algorithms of these models are ANNs [59], SVM [60], GAs [61], decision trees [62], and other statistical machine learning methods.
Indoor comforts are influenced by various parameters, especially weather conditions (e.g., wind speed, air temperature, and humidity) that are volatile in nature. In such conditions, indoor thermal comfort can be rapidly affected and could cause excessive energy consumption to maintain temperature range. To maintain indoor thermal comfort under a given range despite of rapid changes in influential parameters, a prediction model and temperature controller is introduced by Marvuglia et al. [54]. In this framework, outdoor temperature, air relative humidity, wind speed, and indoor temperature data are used to train artificial neural network with external inputs (NNARX) model and predicted values fed to fuzzy logic controller to maintain indoor temperature in a given range. Results show good efficiency of predictions and temperature controller. Mararulla et al. [27] implemented ANN-based predictive controller to a commercial building energy management system for operation of boilers in buildings, shown in Figure 2. This method resulted in around 20% reduction in energy required to heat the building. The ANN implementation is illustrated in Figure 2, where data obtained from the simulation tool are fed to the ANN with 10 neurons in each hidden layer and predicted results are given to BEMS for optimal operation.
In 2016, Ascione et al. [22] used feed-forward multilayer perceptron (MLP) ANN structure to predict building energy and thermal behaviour in retrofit scenarios, which produced significant prediction values. Furthermore, the authors indicated that the number of hidden layers highly influences the ANN performance. Additionally, the importance of training data size is discussed in [30,63], both concluded that larger the training data sample is, the better the performance of ANN model.
Normally, residential buildings have non-constant occupancy and maintenance of thermal comfort for whole day leads energy wastage. Hence prediction of unoccupied hours was performed by [28] by using ANN algorithm and prediction of time required for restoration of indoor temperature to set-point temperature using another ANN model. Multi-Objective Genetic Algorithm (MOGA) controller have been efficient technologies in attaining balance between energy consumption and thermal comfort [64] and with hybrid MOGA author achieved around 31.6% energy management efficiency and 71.8% comfort index efficiency. Triple objective controller using particle swarm optimization (PSO) has been developed by [21], which achieved 19.8–33.3% decrease in annual cooling energy, while increasing in annual heating and lighting: 1.7–4.8% and 0.5–2.6% respectively. Final optimization resulted 1.6–11.3% reduction in annual electricity consumption for four climate regions in Iran. Whereas, O’Neill et al. [65] developed Bayesian networks (BNs) [66] model to predict hourly building energy performance with associated uncertainties. The BNs-based building energy performance prediction system can be applied in various scenarios: (1) Retrofitting buildings; (2) Model-based optimization systems; and (3) Energy diagnostics.
Occupancy’s thermal comfort sensation of hot or cold mainly depends on subjective parameters (metabolic rate and clothing insulation) and physical ones (mean radiant temperature, air temperature, air velocity, and relative humidity) as described by Fanger’s predicted mean vote (PMV) and predicted percentage of dissatisfied (PPD) model-ISO 7730. This method was developed in 1960–1970 and is still used as a baseline model for comfort measurement. Fanger’s base model advancements over the last 40 years are critically reviewed in [67]. An existing HVAC system can optimize PMV index with conventional controller, however, a fuzzy logic-based system is integrated to existing HVAC system to maintain PMV, CO2, and energy consumption for efficient building performance [68]. This fuzzy logic’s member function together with rule selection were then tuned by multi-objective evolutionary algorithms (MOEA-GA) to minimize number of rules and thus maximizing system performance. This proved to be the best combination for FLC’s with reduced number of rules to maintain PMV and optimizing energy consumption. Table 1 gives the standard values for thermal sensation scale of PMV in which +3 being very hot and −3 being very cold. It is always suggested that the PMV value should be maintained within −0.5 to +0.5 to achieve better thermal comfort. The comfort classification based on relationship between PMV and PPD is shown in Table 2 [69]. Chen et al. [70] developed data-driven state-space Weiner model to evaluate the dynamic relation between dry bulb temperature variation and occupant thermal sensation. Later they compared developed model to dynamic thermal sensation (DTS). The DTS model is a reactive thermal comfort system with constantly changing its values based on the dynamic variation of weather conditions and occupant preferred thermal sensation votes delivered by an extended Kalman filer (EKF) with feedback system. Furthermore, predicted mean vote and dynamic thermal sensation models were compared by developing MPC-DTS and MPC-PMV. Results indicated that the MPC-DTS achieved better thermal comfort and energy optimisation than the MPC-PMV model, but both efficiently maintained thermal comfort compared to the baseline model using proportional integral (PI) controller. However, they assumed that there is a feedback system in BEMS, which actually is not the case. Later, Chen et al. [71] conducted the same experiment to investigate the performance difference between MPC-DTS and MPC-PMV with real time actual mean vote feedback values, in addition authors detailed the probable reasons for performance difference.
The above mentioned researches mainly focus on optimization techniques used to achieve comfort measurement. However, the accuracy of subjective and physical parameters measurement taken from sensors has a significant impact ion the PMV index evaluation. These measurement uncertainties can be evaluated using efficient tools such as: monte carlo analysis (MCA) [72], guide to the expression of uncertainty in measurement (GUM) [73], and sensitivity analysis (SA) [69]. These studies show that the proper handling of measurement uncertainties is essential in PMV index model.
Black box models are less complex, does not need complete data of building physical parameters, efficient performance, and easy to build. Nevertheless, they require huge building operational and environmental parameter data for training in order to have efficient prediction values. These data are however difficult to obtain, while low quality data can cause huge prediction error. Even though, these models are accurate and less complex, the lack of knowledge/explanation of the inner processes from the point of view of physics, there is some reluctance towards black box model implementation over physics-based model.

2.3. Gray Box Models

The third category of BEMS is known as gray box models. These are hybrid ones combining simplified physics-based models and data-driven ones. In a gray box model, the process is expressed in mathematical expression that may be based on the physics and/or thermodynamics laws. They consist expressions that have physical explanation (e.g., resistor capacitance network) and a part of the model may be obtained through regression from the available data.
A gray box model is a balanced model between the white box model and black box model. This combination ensures that the non-linearities in white box model can be handled using black box models and lack of laws of physics reasoning in black model can be represented through white box models, but extra effort is required to design and develop these models. However, selection of suitable gray box model structure for developing a good performance system is still a difficult task. Bacher and Madsen, ref. [7] proposed an approach to find appropriate heat dynamics of a building. Indeed, a set of different RC network models have been configured and compared using likelihood ratio tests. The study concludes that significant improvements can be obtained as the model order increases, while no further notable improvements can be expected beyond a model order of 3. Široký et al. [74] proposed an experimental analysis of a heating system using lumped capacitance network in a university building and analysis was carried out for two months. Through this approach they were able to achieve around 15% and 28% energy savings. The experimental analysis not only investigated the performance of MPC but also detailed the issues that can be encountered in its application.
Figure 3 illustrates the basic principle of MPC model structure [74], the inputs of the systems are time varying parameters: energy price can be taken from energy market, comfort conditions set by the occupants, occupancy prediction, and environmental parameters. The MPC system formulates the optimization of an objective function by using building dynamic model, a cost-function and constraints. After each time sample formulation, feedback from occupants and weather conditions are fed back to MPC for the formulation of next time sample, which ensures that unanticipated disturbances are taken in consideration through feedback loop.
A simplified low order gray box modelling has been introduced in [75]. The study considered a whole building as single zone building (Figure 4) neglecting the inter-zone heat exchange. Most of the studies in literature did not take account of inter-zone thermal interactions as it increases the complexity of the model and includes numerous uncertainties. In addition, the model perform-ability declines with the increase of the number of zone. However, Cai and Braun [76] proposed a resistance capacitance thermal network model for multi-zone buildings (Figure 5) with a unique three-step estimation approach to reduce the complexity of the model and thus improving the performance of BEMS system, through:
  • De-grouping weakly linked zones and grouping strongly linked zones.
  • Sensitivity analysis to identify and eliminate non-influential variables.
  • Correlation analysis to eliminate Non-correlated variables.
Performance of BEMS system is significantly increased because of the above-considered three steps, which have simplified the estimation problem by eliminating non-influential parameters.
In general, gray box models can be used for predictions of energy consumption, thermal comfort conditions, occupancy, and heating/cooling load of buildings. These applications leads to use gray box modelling to building in smart Grid context for dynamic load management and energy storage. The reduced order gray box model for buildings connected to smart Grid was investigated in [31], where it is applied on two buildings types (insulated and uninsulated). Furthermore, Sharma et al. [77] presented a study of MPC controller implementation for buildings in centralized energy management system framework (CEMS). In addition, The insulated buildings opens the possibilities of enabling demand-side management (DSM) by exploiting heat capacity flexibility in building thermal wall mass. Harb et al. [78] developed gray-box models for forecasting the building thermal response. The analysis was conducted on four gray box models and data from three building. Building areas varied from 3000 to 30,000 m 2 and data duration from 39 to 110 days. To determine thermal behaviour of the building, three forcing functions were used in this paper:
  • Radiative building environment is expressed as the solar irradiation.
  • Building thermal environment is represented by the outdoor air dry temperature.
  • Various heat sources consists of heating elements.
From the above a three-function input vector is constructed:
U = [ T a Q i r r a d ϕ h ] T
where T a —outdoor dry bulb temperature, Q i r r a d —global solar radiation on horizontal surface, and ϕ h —Building thermal consumption.
Four gray box model structures were developed in this paper: (1) 1R1C—the simplest structure characterizes the whole building into a single parameter (Figure 6); (2) 3R2C—consists of three resistors and two capacitors. Three resistors indicate convective and radiative heat exchange, and heat exchange between interior to environment, two capacitor indicates interior and exterior thermal mass (Figure 6); (3) 4R2C—extension of the 3R2C structure with additional indoor node (Figure 7); and (4) 8R3C-extension of the 4R2C considering all type of heat exchanges between interior, exterior, heating elements, and indoor air (Figure 7).
The achieved results show that the 1R1C model produced more harmonics in the prediction values due to its simple structure, the 3R2C have produced similar disturbances in indoor air temperature prediction, due to the lack of consideration of heat exchange between indoor and outdoor air temperature. The 4R2C produced accurate prediction in daily indoor temperature prediction, due to the consideration of heat exchange between various parameters. The 8R3C produced similar accurate prediction values with no significant improvements in the results despite the detailed model. The 4R2C model can thus be considered as the suitable structure for implementation because of its accuracy and low complexity. From the achieved results it can be concluded that the addition of indoor air temperature node (4R2C and 8R3C) provides stable prediction values compared to model without indoor air temperature node (1R1C and 3R2C).
Meanwhile, application of MPC systems for building energy and comfort management has gained larger attention, Sturzenegger et al. [79] applied MPC strategy on commercial building of 6000 m 2 area for energy and comfort control. The results are later compared with existing rule-based control systems. The analysis of MPC implementation proved that energy savings were around 17% with an improved comfort level.
The above-described studies have shown that gray box models are robust, accurate, and applicable to complex buildings. However, these models posses high computational cost making them only profitable in applications for commercial buildings. Further investigations are needed to ensure adaptability and application for small buildings.

3. Observations and Discussion

This paper mainly focused on review of recent development in intelligent controller systems applied to building energy and comfort management. Several papers have been reviewed in this paper and around 80% of the papers are from the year 2013 onwards. The reviewed papers are arranged in descending chronological order in Table 3, which highlights the carried out review. The listed papers does not consider the total number of reviewed papers. Indeed, these ones have different control strategies, methods, objective parameters, and applications. Some assumptions are made for this literature review’s observations:
  • Buildings in the context of smart-grid are considered as residential ones.
  • Apartments with large commercial space are considered as non-residential buildings.
  • Grid is considered to be a supply source for papers without specific indication on the supply source.
  • Demand side management and load shifting are considered as dynamic pricing.
Based on the above-given assumptions, the following observations have been made. The carried out review shows that research majority is conducted on non-residential buildings, around 66%, and residential ones, being 34% (Figure 8). Non-residential buildings include: institutional, public, office, swimming pool, hospital, and hotel buildings. This lack of research may be due to the unavailability of data or controller systems. Figure 9 illustrates control strategies applied for both building types, where black box models are dominating with 74% and 67% of the overall applied controllers for residential and non-residential buildings, respectively. Significant researches have therefore been conducted on black box models due to their ease of application. Around 21% and 27% gray box models were applied to residential and non-residential building, respectively, while gray box models were less used in residential cases compared to non-residential ones mainly because of their high computational and design costs. Simulation tools combined with other control strategies are used for building energy performance analysis but the standalone use is low because of their complexity and high data acquisition cost.
In the context of comfort parameters, thermal comfort acquired more importance in both non-residential and residential buildings, whereas, other parameters are taken into consideration in few papers (Figure 10). This indicates the significance of thermal comfort in overall indoor comfort sensation and optimization of thermal energy leads great amount of overall energy consumption reduction in comparison to other comfort variables energy consumption optimization. There is a major lack in consideration of indoor air quality and lighting control. However, regulations and standards urge maintenance of CO2 and luminance level in order to keep occupants good health and productivity, hence more research on this topic is necessary. Only 5% of the papers have developed controller for all four comfort parameters control. This shows the difficulties in implementation of controller for overall indoor comfort management.
Towards sustainable development, installation of renewable energies are important. This factor has also been considered in the literature review. The literature review highlights 16% and 23% renewable energies integration into non-residential and residential buildings, respectively (Figure 11). Most of RES integration is observed in smart grid and in big buildings context. The dynamic response in energy consumption by loads is an effective way of maintaining grid balance, grid durability, and cost optimization. Around 22% of non-residential and 25% of residential buildings have adopted DR. In Figure 12, it can be noticed the controller types used for DR application in both building types. Gray box modelling has higher implementation percentage because of the high flexibility for multi-objective optimization. Controllers used for RES integration are shown in Figure 13, where it should be noticed that black box models have higher percentage of implementation in residential buildings and gray box modelling in non-residential ones. This difference can be justified as follows: (1) Gray box models are characterized by high accuracy and higher computational cost that limit their usage only for large buildings; while (2) black box models are characterized by high accuracy and lower flexibility of MIMO that limit their application to multi-objective optimization purpose. In the literature review, it had been found that black box models includes controllers such as fuzzy logic, artificial neural networks, genetic algorithms, decision trees, particle swarm optimization, reinforced learning, etc., while gray box models includes lumped capacitance model, model predictive controller, hybrid systems, etc.

4. Conclusions

This paper has dealt with a state of the art review of recent developments on building energy and comfort management, and the related control. The carried out investigations includes explanation of conventional controllers and their up-gradation to the current challenging applications and new methods viz., black and gray box modelling. These models have been compared and critically reviewed on the basis of comfort conditions, RES integration, DR application, and building type. The proposed critical review will be useful for engineers and researchers in selection of suitable controller methods for BEMS model based on various conditions. In addition, the following observations, comments, and recommendations should be helpful.
  • All the comfort parameters (thermal, visual, air quality, and relative humidity) need to be controlled in the building to ensure occupants’ health and productivity. However, thermal comfort control remains dominant as the other parameters have a minimal impact on energy consumption. In addition, these parameters inclusion may introduce complexity in the controller model and leads to poor performance.
  • White box models have been investigated as preliminary models for building energy performance analysis and were found to be used for low scale application.
    However, the white box application is restricted only for initial analysis and is not efficient to implementation due to its limitations.
  • Black box models have high accuracy, low computational cost, and higher flexibility for building non-linearities. These models have gained significant attention in recent years. Constant developments of new algorithms ensures the improved efficiency and suitable for multi-objective applications. Nevertheless, these applications have restricted implementation due to lack of physics-laws explanation and huge amount of data is required for model training.
  • Gray box models are found out to be more feasible for multi-objective optimization, predictive/adaptive, and cost-optimization applications, where design and computational time are high. This makes them not suitable for low scale applications.
Significant improvements can be noticed in intelligent controller for BEMS applications. The developments of new algorithms, and combination of various intelligent methods have ensured development of buildings towards sustainable environment. However, there is still lack of proper trade-off between energy and comfort parameters, thus further investigations in this area are still needed. The following are few future perspective points:
  • Further research required on air quality and lighting parameters.
  • Research efforts towards gray box models for residential buildings.
  • Integration of RES into buildings still requires research efforts with feasible and uninterrupted energy supply.
  • Dynamic response (dynamic pricing) for energy consumption is yet to be implemented in large scale applications.
  • Development of new methods with IoT technologies will push towards more intelligent building models.
  • Research efforts towards adaptive building controller models.

Author Contributions

All the authors contributed equally for elementary related research, papers selection, literature survey, discussions, and state of the art review of the paper.

Funding

This research received no external funding.

Conflicts of Interest

The authors declare no conflict of interest. The founding sponsors had no role in the design of the study; in the collection, analyses, or interpretation of data; in the writing of the manuscript, and in the decision to publish the results.

Abbreviations

The following abbreviations are used in this manuscript:
ABCArtificial Bee Colony
ABMAgent-Based Modelling
AFLCAdaptable Fuzzy Logic Model
ANFISAdaptive Neuro-Fuzzy Interference System
ANNsArtificial Neural Networks
ASHRAEAmerican Society of Heating, Refrigerating and Air-Conditioning Engineers
BCHPsBuilding Heating Cooling Power Systems
BCVTBBuilding Controls Virtual Test Bed
BEMSBuilding Energy Management System
BMSBuilding Management System
BNsBayesian Networks
BPABack Propagation Algorithm
BRLBatch Reinforcement Learning Model
BTOBuilding TechNologies Office
CEBEMSCyber Physical System Enabled BEMS
CEMSCentralised Energy Management System Framework
CEMSCentralized Energy Management System
CPSCyber Physical Systems
DERDistributed Energy Resources
DOEDepartment of Energy
DRDemand Response
DSMDemand-Side Management
DTSDynamic Thermal Sensation
EEECEuropean Energy Efficiency Commission
EKFExtended Kalman Filter
EMLExtreme Machine Learning
EUEuropean Union
FFNNsFeed Forward Back-propagation Neural Networks
FLCFuzzy Logic Controller
FRSCFuzzy Rough Set Controller
GAsGenetic Algorithms
GMBAGlobal Model Based Anticipative
GMMGaussian Mixture Regression Model
GPMGaussian Process Regression Model
GRNNGeneral Regression Neural Network
GUMGuide to the expression of Uncertainty in Measurement
HMIHuman Machine Interface
HVACHeating, Ventilation and Air-Conditioning
ICAIncremental Conductance Algorithm
IEAInternational Energy Agency
IoTInternet of Things
LMALevenberg-Marquardt Algorithm
LQTLinear Quadratic Tracking
MACMulti-Agent Controller
MASMulti-Agent System
MBPCModel-Based Predictive Control
MBPETMModel Based Periodic Event-Triggered Mechanism
MCAMonte Carlo Analysis
MIMOMulti Input Multi Output
MLPMulti Layer Perceptron
MOEA-GAMulti-Objective Evolutionary Algorithms
MOGAMulti-Objective Genetic Algorithm
MPCModel Predictive Controller
NNARXArtificial Neural Network with External Output
NRELNational Renewable Energy Laboratory
NSGANon-dominated Sorting Genetic Algorithm
NSGA-IINon-dominated Sorting Genetic Algorithm
PABParameter Adaptive Building
PIProportional Controller
PIDProportional Integral Derivative
PMVPredictive Mean Vote
PPDPredicted Percentage of Dissatisfied
PSOParticle Swarm Optimization
RBFNsRadial Basis Function Networks
RBMRule-Based Modelling
RCResistor Capacitor
RESRenewable Energy Sources
RLReinforcement Learning
SASensitivity Analysis
SVMSupport Vector Machine

References

  1. The European Commission. Communication From the Commission to the European Parliament, the Council, the European Economic And Social Committee and the Committee of the Regions; The European Commission: Brussels, Belgium, 2011. [Google Scholar]
  2. The European Energy Efficiency Commission. Available online: https://ec.europa.eu/energy/en/ topics/energy-efficiency/buildings (accessed on 16 July 2018).
  3. IEA Publications. Building Energy Performance Metrics, Supporting Energy Efficiency Progress in Major Economies; International Energy Agency (IEA) and International Partnership for Energy Efficiency Cooperation (IPEEC): Paris, France, 2015. [Google Scholar]
  4. IEA. IEA Energy Technology Perspectives; Technical Report; IEA: Paris, France, 2015. [Google Scholar]
  5. Vieira, F.M.; Moura, P.S.; de Almeida, A.T. Energy storage system for self-consumption of photovoltaic energy in residential zero energy buildings. Renew. Energy 2017, 103, 308–320. [Google Scholar] [CrossRef]
  6. Minoli, D.; Sohraby, K.; Occhiogrosso, B. IoT Considerations, Requirements, and Architectures for Smart Buildings—Energy Optimization and Next Generation Building Management Systems. IEEE Int. Things J. 2017, 4, 269–283. [Google Scholar] [CrossRef]
  7. Bacher, P.; Madsen, H. Identifying suitable models for the heat dynamics of buildings. Energy Build. 2011, 43, 1511–1522. [Google Scholar] [CrossRef] [Green Version]
  8. Yu, Z.; Fung, B.C.; Haghighat, F.; Yoshino, H.; Morofsky, E. A systematic procedure to study the influence of occupant behavior on building energy consumption. Energy Build. 2011, 43, 1409–1417. [Google Scholar] [CrossRef] [Green Version]
  9. Rocha, P.; Siddiqui, A.; Stadler, M. Improving energy efficiency via smart building energy management systems: A comparison with policy measures. Energy Build. 2015, 88, 203–213. [Google Scholar] [CrossRef]
  10. Gul, M.S.; Patidar, S. Understanding the energy consumption and occupancy of a multi-purpose academic building. Energy Build. 2015, 87, 155–165. [Google Scholar] [CrossRef] [Green Version]
  11. Shaikh, P.H.; Nor, N.M.; Nallagownden, P.; Elamvazuthi, I.; Ibrahim, T. Robust stochastic control model for energy and comfort management of buildings. Aust. J. Basic Appl. Sci. 2013, 7, 137–144. [Google Scholar]
  12. Carlucci, S.; Cattarin, G.; Causone, F.; Pagliano, L. Multi-objective optimization of a nearly zero-energy building based on thermal and visual discomfort minimization using a non-dominated sorting genetic algorithm (NSGA-II). Energy Build. 2015, 104, 378–394. [Google Scholar] [CrossRef] [Green Version]
  13. Kwak, Y.; Huh, J.H.; Jang, C. Development of a model predictive control framework through real-time building energy management system data. Appl. Energy 2015, 155, 1–13. [Google Scholar] [CrossRef]
  14. Maasoumy, M.; Rosenberg, C.; Sangiovanni-Vincentelli, A.; Callaway, D.S. Model Predictive Control Approach to Online Computation of Demand-Side Flexibility of Commercial Buildings HVAC Systems for Supply Following; IEEE: Portland, OR, USA, 2014; pp. 1082–1089. [Google Scholar]
  15. National Renewable Energy Laboratory. EnergyPlus Documentation; National Renewable Energy Laboratory (NREL): Washington, DC, USA, 2018.
  16. Klein, S.A. TRNSYS–A Transient System Simulation Program; Engineering Experiment Station Report; University of Wisconsin-Madison: Madison, WI, USA, 1988; pp. 12–38. [Google Scholar]
  17. Hirsch, J.J. eQuest, The QUick Energy Simulation Tool. DOE2 Com, Epub, 2006. Available online: http://www. doe2. com/equest (accessed on 10 August 2018).
  18. Farrokhifar, M.; Momayyezi, F.; Sadoogi, N.; Safari, A. Real-time based approach for intelligent building energy management using dynamic price policies. Sustain. Cities Soc. 2018, 37, 85–92. [Google Scholar] [CrossRef]
  19. Kim, W.; Jeon, Y.; Kim, Y. Simulation-based optimization of an integrated daylighting and HVAC system using the design of experiments method. Appl. Energy 2016, 162, 666–674. [Google Scholar] [CrossRef]
  20. Liu, J.; Zhang, W.; Chu, X.; Liu, Y. Fuzzy logic controller for energy savings in a smart LED lighting system considering lighting comfort and daylight. Energy Build. 2016, 127, 95–104. [Google Scholar] [CrossRef]
  21. Delgarm, N.; Sajadi, B.; Kowsary, F.; Delgarm, S. Multi-objective optimization of the building energy performance: A simulation-based approach by means of particle swarm optimization (PSO). Appl. Energy 2016, 170, 293–303. [Google Scholar] [CrossRef]
  22. Ascione, F.; Bianco, N.; De Stasio, C.; Mauro, G.M.; Vanoli, G.P. Artificial neural networks to predict energy performance and retrofit scenarios for any member of a building category: A novel approach. Energy 2017, 118, 999–1017. [Google Scholar] [CrossRef]
  23. Li, K.; Hu, C.; Liu, G.; Xue, W. Building’s electricity consumption prediction using optimized artificial neural networks and principal component analysis. Energy Build. 2015, 108, 106–113. [Google Scholar] [CrossRef]
  24. Jovanović, R.Ž.; Sretenović, A.A.; Živković, B.D. Ensemble of various neural networks for prediction of heating energy consumption. Energy Build. 2015, 94, 189–199. [Google Scholar] [CrossRef]
  25. Platon, R.; Dehkordi, V.R.; Martel, J. Hourly prediction of a building’s electricity consumption using case-based reasoning, artificial neural networks and principal component analysis. Energy Build. 2015, 92, 10–18. [Google Scholar] [CrossRef]
  26. Von Grabe, J. Potential of artificial neural networks to predict thermal sensation votes. Appl. Energy 2016, 161, 412–424. [Google Scholar] [CrossRef]
  27. Macarulla, M.; Casals, M.; Forcada, N.; Gangolells, M. Implementation of predictive control in a commercial building energy management system using neural networks. Energy Build. 2017, 151, 511–519. [Google Scholar] [CrossRef]
  28. Moon, J.W.; Jung, S.K. Development of a thermal control algorithm using artificial neural network models for improved thermal comfort and energy efficiency in accommodation buildings. Appl. Therm. Eng. 2016, 103, 1135–1144. [Google Scholar] [CrossRef]
  29. Naji, S.; Keivani, A.; Shamshirband, S.; Alengaram, U.J.; Jumaat, M.Z.; Mansor, Z.; Lee, M. Estimating building energy consumption using extreme learning machine method. Energy 2016, 97, 506–516. [Google Scholar] [CrossRef]
  30. Macas, M.; Moretti, F.; Fonti, A.; Giantomassi, A.; Comodi, G.; Annunziato, M.; Pizzuti, S.; Capra, A. The role of data sample size and dimensionality in neural network based forecasting of building heating related variables. Energy Build. 2016, 111, 299–310. [Google Scholar] [CrossRef]
  31. Reynders, G.; Diriken, J.; Saelens, D. Quality of grey-box models and identified parameters as function of the accuracy of input and observation signals. Energy Build. 2014, 82, 263–274. [Google Scholar] [CrossRef]
  32. Li, N.; Cui, H.; Zhu, C.; Zhang, X.; Su, L. Grey preference analysis of indoor environmental factors using sub-indexes based on Weber/Fechner’s law and predicted mean vote. Indoor Built Environ. 2016, 25, 1197–1208. [Google Scholar] [CrossRef]
  33. Paris, B.; Eynard, J.; Grieu, S.; Polit, M. Hybrid PID-fuzzy control scheme for managing energy resources in buildings. Appl. Soft Comput. 2011, 11, 5068–5080. [Google Scholar] [CrossRef] [Green Version]
  34. Dounis, A.; Caraiscos, C. Advanced control systems engineering for energy and comfort management in a building environment—A review. Renew. Sustain. Energy Rev. 2009, 13, 1246–1261. [Google Scholar] [CrossRef]
  35. Pérez-Lombard, L.; Ortiz, J.; Pout, C. A review on buildings energy consumption information. Energy Build. 2008, 40, 394–398. [Google Scholar] [CrossRef]
  36. Zhao, H.X.; Magoulès, F. A review on the prediction of building energy consumption. Renew. Sustain. Energy Rev. 2012, 16, 3586–3592. [Google Scholar] [CrossRef]
  37. Amasyali, K.; El-Gohary, N.M. A review of data-driven building energy consumption prediction studies. Renew. Sustain. Energy Rev. 2018, 81, 1192–1205. [Google Scholar] [CrossRef]
  38. Wei, Y.; Zhang, X.; Shi, Y.; Xia, L.; Pan, S.; Wu, J.; Han, M.; Zhao, X. A review of data-driven approaches for prediction and classification of building energy consumption. Renew. Sustain. Energy Rev. 2018, 82, 1027–1047. [Google Scholar] [CrossRef]
  39. Missaoui, R.; Joumaa, H.; Ploix, S.; Bacha, S. Managing energy Smart Homes according to energy prices: Analysis of a Building Energy Management System. Energy Build. 2014, 71, 155–167. [Google Scholar] [CrossRef]
  40. Farmani, F.; Parvizimosaed, M.; Monsef, H.; Rahimi-Kian, A. A conceptual model of a smart energy management system for a residential building equipped with CCHP system. Int. J. Electr. Power Energy Syst. 2018, 95, 523–536. [Google Scholar] [CrossRef]
  41. Salakij, S.; Yu, N.; Paolucci, S.; Antsaklis, P. Model-Based Predictive Control for building energy management. I: Energy modeling and optimal control. Energy Build. 2016, 133, 345–358. [Google Scholar] [CrossRef]
  42. Building Energy Software Tools, IBPSA-USA. Available online: https://www.buildingenergysoftwaretools.com/ software-listing (accessed on 16 July 2018).
  43. Winkelmann, F.C.; Birdsall, B.E.; Buhl, W.F.; Ellington, K.L.; Erdem, A.E.; Hirsch, J.J.; Gates, S. DOE-2 Supplement: Supplement: Version 2.1 E; Lawrence Berkeley Lab.: Berkeley, CA, USA; Hirsch (James J.) and Associates: Camarillo, CA, USA, 1993.
  44. Zhao, P.; Suryanarayanan, S.; Simoes, M.G. An Energy Management System for Building Structures Using a Multi-Agent Decision-Making Control Methodology. IEEE Trans. Ind. Appl. 2013, 49, 322–330. [Google Scholar] [CrossRef]
  45. Baheti, R.; Gill, H. Cyber-physical systems. Impact Control Technol. 2011, 12, 161–166. [Google Scholar]
  46. Hussain, S.; Gabbar, H.A.; Bondarenko, D.; Musharavati, F.; Pokharel, S. Comfort-based fuzzy control optimization for energy conservation in HVAC systems. Control Eng. Pract. 2014, 32, 172–182. [Google Scholar] [CrossRef]
  47. Fritzson, P.A. Principles of Object-Oriented Modeling and Simulation with Modelica 2.1; IEEE Press: Piscataway, NJ, USA; Wiley-Interscience: New York, NY, USA, 2004; ISBN 9780471471639. [Google Scholar]
  48. Wetter, M. GenOpt (R), Generic Optimization Program, User Manual, Version 2.0. 0; Lawrence Berkeley National Laboratory: Berkeley, CA, USA, 2003.
  49. Kwak, Y.; Huh, J.H. Development of a method of real-time building energy simulation for efficient predictive control. Energy Convers. Manag. 2016, 113, 220–229. [Google Scholar] [CrossRef]
  50. Wetter, M.; Haves, P.; Coffey, B. Building Controls Virtual Test Bed; Lawrence Berkeley National Laboratory: Berkeley, CA, USA, 2008.
  51. Lu, Y.; Wang, S.; Yan, C.; Shan, K. Impacts of renewable energy system design inputs on the performance robustness of net zero energy buildings. Energy 2015, 93, 1595–1606. [Google Scholar] [CrossRef]
  52. Langevin, J.; Wen, J.; Gurian, P.L. Quantifying the human–building interaction: Considering the active, adaptive occupant in building performance simulation. Energy Build. 2016, 117, 372–386. [Google Scholar] [CrossRef] [Green Version]
  53. Afram, A.; Janabi-Sharifi, F. Gray-box modeling and validation of residential HVAC system for control system design. Appl. Energy 2015, 137, 134–150. [Google Scholar] [CrossRef]
  54. Marvuglia, A.; Messineo, A.; Nicolosi, G. Coupling a neural network temperature predictor and a fuzzy logic controller to perform thermal comfort regulation in an office building. Build. Environ. 2014, 72, 287–299. [Google Scholar] [CrossRef]
  55. Yuce, B.; Li, H.; Rezgui, Y.; Petri, I.; Jayan, B.; Yang, C. Utilizing artificial neural network to predict energy consumption and thermal comfort level: An indoor swimming pool case study. Energy Build. 2014, 80, 45–56. [Google Scholar] [CrossRef]
  56. Ferreira, P.; Ruano, A.; Silva, S.; Conceição, E. Neural networks based predictive control for thermal comfort and energy savings in public buildings. Energy Build. 2012, 55, 238–251. [Google Scholar] [CrossRef] [Green Version]
  57. D’Oca, S.; Hong, T. Occupancy schedules learning process through a data mining framework. Energy Build. 2015, 88, 395–408. [Google Scholar] [CrossRef] [Green Version]
  58. Mahdavi, A.; Tahmasebi, F. Predicting people’s presence in buildings: An empirically based model performance analysis. Energy Build. 2015, 86, 349–355. [Google Scholar] [CrossRef]
  59. Schalkoff, R.J. Artificial Neural Networks; McGraw-Hill: New York, NY, USA, 1997; Volume 1. [Google Scholar]
  60. Hearst, M.; Dumais, S.; Osuna, E.; Platt, J.; Scholkopf, B. Support vector machines. IEEE Intell. Syst. Their Appl. 1998, 13, 18–28. [Google Scholar] [CrossRef]
  61. Whitley, D. A genetic algorithm tutorial. Stat. Comput. 1994, 4. [Google Scholar] [CrossRef] [Green Version]
  62. Quinlan, J.R. Induction of decision trees. Mach. Learn. 1986, 1, 81–106. [Google Scholar] [CrossRef] [Green Version]
  63. Benedetti, M.; Cesarotti, V.; Introna, V.; Serranti, J. Energy consumption control automation using Artificial Neural Networks and adaptive algorithms: Proposal of a new methodology and case study. Appl. Energy 2016, 165, 60–71. [Google Scholar] [CrossRef]
  64. Shaikh, P.H.; Nor, N.B.M.; Nallagownden, P.; Elamvazuthi, I.; Ibrahim, T. Intelligent multi-objective control and management for smart energy efficient buildings. Int. J. Electr. Power Energy Syst. 2016, 74, 403–409. [Google Scholar] [CrossRef]
  65. O’Neill, Z.; O’Neill, C. Development of a probabilistic graphical model for predicting building energy performance. Appl. Energy 2016, 164, 650–658. [Google Scholar] [CrossRef]
  66. Friedman, N.; Geiger, D.; Goldszmidt, M. Bayesian network classifiers. Mach. Learn. 1997, 29, 131–163. [Google Scholar] [CrossRef]
  67. van Hoof, J. Forty years of Fanger’s model of thermal comfort: Comfort for all? Indoor Air 2008, 18, 182–201. [Google Scholar] [CrossRef] [PubMed]
  68. Gacto, M.J.; Alcalá, R.; Herrera, F. A multi-objective evolutionary algorithm for an effective tuning of fuzzy logic controllers in heating, ventilating and air conditioning systems. Appl. Intell. 2012, 36, 330–347. [Google Scholar] [CrossRef]
  69. d’Ambrosio Alfano, F.R.; Palella, B.I.; Riccio, G. The role of measurement accuracy on the thermal environment assessment by means of PMV index. Build. Environ. 2011, 46, 1361–1369. [Google Scholar] [CrossRef]
  70. Chen, X.; Wang, Q.; Srebric, J. A data-driven state-space model of indoor thermal sensation using occupant feedback for low-energy buildings. Energy Build. 2015, 91, 187–198. [Google Scholar] [CrossRef]
  71. Chen, X.; Wang, Q.; Srebric, J. Occupant feedback based model predictive control for thermal comfort and energy optimization: A chamber experimental evaluation. Appl. Energy 2016, 164, 341–351. [Google Scholar] [CrossRef] [Green Version]
  72. Ricciu, R.; Galatioto, A.; Desogus, G.; Besalduch, L. Uncertainty in the evaluation of the Predicted Mean Vote index using Monte Carlo analysis. J. Environ. Manag. 2018, 223, 16–22. [Google Scholar] [CrossRef] [PubMed]
  73. Ribeiro, A.S.; Alvese Sousa, J.; Cox, M.G.; Forbes, A.B.; Matias, L.C.; Martins, L.L. Uncertainty Analysis of Thermal Comfort Parameters. Int. J. Thermophys. 2015, 36, 2124–2149. [Google Scholar] [CrossRef]
  74. Široký, J.; Oldewurtel, F.; Cigler, J.; Prívara, S. Experimental analysis of model predictive control for an energy efficient building heating system. Appl. Energy 2011, 88, 3079–3087. [Google Scholar] [CrossRef]
  75. Hazyuk, I.; Ghiaus, C.; Penhouet, D. Optimal temperature control of intermittently heated buildings using Model Predictive Control: Part I—Building modeling. Build. Environ. 2012, 51, 379–387. [Google Scholar] [CrossRef]
  76. Cai, J.; Braun, J.E. A practical and scalable inverse modeling approach for multi-zone buildings. In Proceedings of the 9th International Conference on System Simulation in Buildings, Liège, Belgium, 10–12 December 2014. [Google Scholar]
  77. Sharma, I.; Dong, J.; Malikopoulos, A.A.; Street, M.; Ostrowski, J.; Kuruganti, T.; Jackson, R. A modeling framework for optimal energy management of a residential building. Energy Build. 2016, 130, 55–63. [Google Scholar] [CrossRef]
  78. Harb, H.; Boyanov, N.; Hernandez, L.; Streblow, R.; Müller, D. Development and validation of grey-box models for forecasting the thermal response of occupied buildings. Energy Build. 2016, 117, 199–207. [Google Scholar] [CrossRef]
  79. Sturzenegger, D.; Gyalistras, D.; Morari, M.; Smith, R.S. Model Predictive Climate Control of a Swiss Office Building: Implementation, Results, and Cost—Benefit Analysis. IEEE Trans. Control Syst. Technol. 2016, 24, 1–12. [Google Scholar] [CrossRef]
  80. Doukas, H.; Patlitzianas, K.D.; Iatropoulos, K.; Psarras, J. Intelligent building energy management system using rule sets. Build. Environ. 2007, 42, 3562–3569. [Google Scholar] [CrossRef]
  81. Hall, M.; Frank, E.; Holmes, G.; Pfahringer, B.; Reutemann, P.; Witten, I.H. The WEKA data mining software: an update. ACM SIGKDD Explor. Newslett. 2009, 11, 10. [Google Scholar] [CrossRef]
  82. Shein, W.W.; Tan, Y.; Lim, A.O. PID Controller for Temperature Control with Multiple Actuators in Cyber-Physical Home System; IEEE: Melbourne, Australia, 2012; pp. 423–428. [Google Scholar]
  83. Virote, J.; Neves-Silva, R. Stochastic models for building energy prediction based on occupant behavior assessment. Energy Build. 2012, 53, 183–193. [Google Scholar] [CrossRef]
  84. Hu, J.; Karava, P. Model predictive control strategies for buildings with mixed-mode cooling. Build. Environ. 2014, 71, 233–244. [Google Scholar] [CrossRef]
  85. Yang, R.; Wang, L. Multi-zone building energy management using intelligent control and optimization. Sustain. Cities Soc. 2013, 6, 16–21. [Google Scholar] [CrossRef]
  86. Chen, C.; Wang, J.; Heo, Y.; Kishore, S. MPC-Based Appliance Scheduling for Residential Building Energy Management Controller. IEEE Trans. Smart Grid 2013, 4, 1401–1410. [Google Scholar] [CrossRef]
  87. Papantoniou, S.; Kolokotsa, D.; Kalaitzakis, K. Building optimization and control algorithms implemented in existing BEMS using a web based energy management and control system. Energy Build. 2015, 98, 45–55. [Google Scholar] [CrossRef]
  88. Rodger, J.A. A fuzzy nearest neighbor neural network statistical model for predicting demand for natural gas and energy cost savings in public buildings. Expert Syst. Appl. 2014, 41, 1813–1829. [Google Scholar] [CrossRef]
  89. Maasoumy, M.; Razmara, M.; Shahbakhti, M.; Vincentelli, A.S. Handling model uncertainty in model predictive control for energy efficient buildings. Energy Build. 2014, 77, 377–392. [Google Scholar] [CrossRef]
  90. Yuan, J.; Farnham, C.; Emura, K. Development and application of a simple BEMS to measure energy consumption of buildings. Energy Build. 2015, 109, 1–11. [Google Scholar] [CrossRef]
  91. Kang, C.S.; Hyun, C.H.; Park, M. Fuzzy logic-based advanced on–off control for thermal comfort in residential buildings. Appl. Energy 2015, 155, 270–283. [Google Scholar] [CrossRef]
  92. Huang, H.; Chen, L.; Hu, E. A neural network-based multi-zone modelling approach for predictive control system design in commercial buildings. Energy Build. 2015, 97, 86–97. [Google Scholar] [CrossRef]
  93. Zhang, Y.; O’Neill, Z.; Dong, B.; Augenbroe, G. Comparisons of inverse modeling approaches for predicting building energy performance. Build. Environ. 2015, 86, 177–190. [Google Scholar] [CrossRef]
  94. De Coninck, R.; Helsen, L. Practical implementation and evaluation of model predictive control for an office building in Brussels. Energy Build. 2016, 111, 290–298. [Google Scholar] [CrossRef]
  95. Chen, X.; Wang, Q.; Srebric, J. Model predictive control for indoor thermal comfort and energy optimization using occupant feedback. Energy Build. 2015, 102, 357–369. [Google Scholar] [CrossRef] [Green Version]
  96. Mahendra, S.; Stéphane, P.; Frederic, W. Modeling for Reactive Building Energy Management. Energy Procedia 2015, 83, 207–215. [Google Scholar] [CrossRef]
  97. Korkas, C.D.; Baldi, S.; Michailidis, I.; Kosmatopoulos, E.B. Occupancy-based demand response and thermal comfort optimization in microgrids with renewable energy sources and energy storage. Appl. Energy 2016, 163, 93–104. [Google Scholar] [CrossRef] [Green Version]
  98. Wetter, M.; Bonvini, M.; Nouidui, T.S. Equation-based languages—A new paradigm for building energy modeling, simulation and optimization. Energy Build. 2016, 117, 290–300. [Google Scholar] [CrossRef]
  99. Kaczmarczyk, V.; Fiedler, P.; Bradac, Z.; Franek, L.; Pasek, J. Simulator for optimal scheduling of domestic appliances. IFAC-PapersOnLine 2015, 48, 95–100. [Google Scholar] [CrossRef]
  100. Keshtkar, A.; Arzanpour, S. An adaptive fuzzy logic system for residential energy management in smart grid environments. Appl. Energy 2017, 186, 68–81. [Google Scholar] [CrossRef]
  101. O’Dwyer, E.; De Tommasi, L.; Kouramas, K.; Cychowski, M.; Lightbody, G. Modelling and disturbance estimation for model predictive control in building heating systems. Energy Build. 2016, 130, 532–545. [Google Scholar] [CrossRef]
  102. Delgarm, N.; Sajadi, B.; Delgarm, S.; Kowsary, F. A novel approach for the simulation-based optimization of the buildings energy consumption using NSGA-II: Case study in Iran. Energy Build. 2016, 127, 552–560. [Google Scholar] [CrossRef]
  103. Costanzo, G.; Iacovella, S.; Ruelens, F.; Leurs, T.; Claessens, B. Experimental analysis of data-driven control for a building heating system. Sustain. Energy Grids Netw. 2016, 6, 81–90. [Google Scholar] [CrossRef] [Green Version]
  104. Cai, J.; Kim, D.; Jaramillo, R.; Braun, J.E.; Hu, J. A general multi-agent control approach for building energy system optimization. Energy Build. 2016, 127, 337–351. [Google Scholar] [CrossRef] [Green Version]
  105. Ahn, J.; Cho, S.; Chung, D.H. Analysis of energy and control efficiencies of fuzzy logic and artificial neural network technologies in the heating energy supply system responding to the changes of user demands. Appl. Energy 2017, 190, 222–231. [Google Scholar] [CrossRef]
  106. Ahn, J.; Chung, D.H.; Cho, S. Performance analysis of space heating smart control models for energy and control effectiveness in five different climate zones. Build. Environ. 2017, 115, 316–331. [Google Scholar] [CrossRef]
  107. Faia, R.; Pinto, T.; Abrishambaf, O.; Fernandes, F.; Vale, Z.; Corchado, J.M. Case based reasoning with expert system and swarm intelligence to determine energy reduction in buildings energy management. Energy Build. 2017, 155, 269–281. [Google Scholar] [CrossRef]
  108. Sharma, S.; Singh, M.; Prakash, S. A Novel Energy Management System for Modified Zero Energy Buildings Using Multi-Agent Systems; IEEE: Singapore, 2017; pp. 267–271. [Google Scholar]
  109. Favilla, B.; Fantozzi, F.; Salvadori, G.; Widerin, P. Artificial Lighting in Low Energy Buildings as Unique Backup Heating System: Results of Dynamic Simulations Based on the Climate Surface Method; IEEE: Milan, Italy, 2017; pp. 1–6. [Google Scholar]
  110. Yu, N.; Salakij, S.; Chavez, R.; Paolucci, S.; Sen, M.; Antsaklis, P. Model-based predictive control for building energy management: Part II—Experimental validations. Energy Build. 2017, 146, 19–26. [Google Scholar] [CrossRef]
  111. Sharma, S.; Dua, A.; Singh, M.; Kumar, N.; Prakash, S. Fuzzy rough set based energy management system for self-sustainable smart city. Renew. Sustain. Energy Rev. 2018, 82, 3633–3644. [Google Scholar] [CrossRef]
  112. Xu, Z.; Hu, G.; Spanos, C.J.; Schiavon, S. PMV-based event-triggered mechanism for building energy management under uncertainties. Energy Build. 2017, 152, 73–85. [Google Scholar] [CrossRef] [Green Version]
  113. Ye, H.; Ren, Q.; Hu, X.; Lin, T.; Shi, L.; Zhang, G.; Li, X. Modeling energy-related CO2 emissions from office buildings using general regression neural network. Resour. Conserv. Recycl. 2018, 129, 168–174. [Google Scholar] [CrossRef]
Figure 1. Process of generating a weather data file based on the forecasted weather [49].
Figure 1. Process of generating a weather data file based on the forecasted weather [49].
Energies 11 02604 g001
Figure 2. Artificial neural network implementation [27].
Figure 2. Artificial neural network implementation [27].
Energies 11 02604 g002
Figure 3. Basic principle of model predictive control for buildings [74].
Figure 3. Basic principle of model predictive control for buildings [74].
Energies 11 02604 g003
Figure 4. RC thermal network for single zone building [75].
Figure 4. RC thermal network for single zone building [75].
Energies 11 02604 g004
Figure 5. Resistor capacitance thermal network for multi-zone building [76].
Figure 5. Resistor capacitance thermal network for multi-zone building [76].
Energies 11 02604 g005
Figure 6. Building thermal structures—1R1C and 3R2C [78].
Figure 6. Building thermal structures—1R1C and 3R2C [78].
Energies 11 02604 g006
Figure 7. Building thermal structures—4R2C and 8R3C [78].
Figure 7. Building thermal structures—4R2C and 8R3C [78].
Energies 11 02604 g007
Figure 8. Research conducted on type of building.
Figure 8. Research conducted on type of building.
Energies 11 02604 g008
Figure 9. Controller application on both type of buildings.
Figure 9. Controller application on both type of buildings.
Energies 11 02604 g009
Figure 10. Controller application on comfort parameters.
Figure 10. Controller application on comfort parameters.
Energies 11 02604 g010
Figure 11. Renewable energy sources integration in both type of buildings.
Figure 11. Renewable energy sources integration in both type of buildings.
Energies 11 02604 g011
Figure 12. Controller used for demand response application in non-residential and residential buildings.
Figure 12. Controller used for demand response application in non-residential and residential buildings.
Energies 11 02604 g012
Figure 13. Controller used for renewable energy sources integration in non-residential and residential buildings.
Figure 13. Controller used for renewable energy sources integration in non-residential and residential buildings.
Energies 11 02604 g013
Table 1. Thermal sensation scale of PMV.
Table 1. Thermal sensation scale of PMV.
PMVSensation
+3Hot
+2Warm
+1Slightly warm
0Neutral
−1Slightly cool
−2cool
−3cold
Table 2. Comfort classification based on ISO-7730.
Table 2. Comfort classification based on ISO-7730.
ClassPercentage of Dissatisfied (%)Predicted Mean Vote
A<6−0.20 < PMV < 0.20
B<10−0.50 < PMV < 0.50
C<15−0.70 < PMV < 0.70
->15PMV < −0.70 or PMV > 0.70
Table 3. Literature review survey.
Table 3. Literature review survey.
Ref.Year      Techniques UsedBuilding TypeComfort ConditionsEnergyDynamicSupply SourceSimulation ToolData DurationResult
ThLtAQRHPricing
[80]2007Decision support modelOffice buildingYesYesYesYesYesNoGridCLIPS with visual basics language1 year10% annual energy reduction
[33]2011PID and FLCResidentialYesNoNoNoYesNoGrid and RES-30 daysDeveloped strategy can be implemented on already in use PID controller
[8]2011Cluster analysisResidentialn/an/an/an/an/an/an/aWEKA [81]1 yearInvestigated the relation between occupancy behaviour and energy consumption
[82]2012CPS based PID controllerResidentialYesNoNoNoYesNoGridMatlab8 hDesigned a system which connects PID controller to CPS for real time weather forecasting to enhance performance of installed temperature controller
[56]2012MBPC, ANN, and GAInstitutionalYesNoNoYesYesNo--Training: 15, 8 days, and testing 1 dayEstimation of 50% and above energy savings
[83]2012Stochastic Markov modelsCommercial and DwellingsNoYesNoNoYesNo---Prediction of energy consumption through learning from occupancy behaviour and also indicates the unnecessary energy consumption areas
[68]2012FLC and GAOffice buildingYesNoYesNoYesNo---Comparison of various evolutionary algorithms and conventional controller. Result shows multi-objective evolutionary algorithm can achieve 30.4% and 50.3% higher efficiency in energy and stability optimization, respectively
[44]2013CEBEMSCommercial Building (Food Service Center)YesYesNoNoYesYesPV, CHP and GridEnergyPlus1 dayDeveloped MAS for CEBEMS have shown better electrical and thermal energy consumption optimization in comparison with BCHP model
[54]2013ANN and FLCOffice buildingYesNoNoNoYesNo-Matlab7 monthsPrediction and control of indoor temperature
[84]2013MPCCommercial buildingYesNoNoNoYesNoGridMatlab and GenOpt6 daysReduction in energy consumption for the simulation period 75.7% without and 85.5% with shading is achieved
[85]2013PSOCommercial buildingYesNoNoNoYesYesRES-1 dayApplied PSO shows high comfort level achievement during shortage in energy supply
[86]2013MPC and Gray box modelInstitutional buildingYesNoNoNoYesYesGridMatlab and CPLEX50 daysEnergy cost saving considering customers preferences using developed MPC-based appliance scheduling technique
[39]2013GMBA-BEMSInstitutional buildingYesNoNoNoYesYesGrid and RESMatlab/Simbad1 dayCost saving 1.2 $ per day
[87]2014FLC, GA, and ANNHospital buildingYesNoNo-YesNoGridMatlab and TRNSYSTraining : 2 months and testing : 1 day36% annual energy consumption reduction
[46]2014GA and FLCCommercial buildingYesNoNoNoYesNo-Matlab, BCVTB and EnergyPlus1 month16.8% and 18.1% decrease in cooling and heating load, respectively over the simulation period
[88]2014ANN and FLCCommercial buildingYesNoNoNoYesYes (gas)Grid and gas-111 daysDeveloped model is applied to the complex building to control and optimize gas consumption using real time data from the gas market
[55]2014ANN-BPA and MLPSwimming pool------Co-generation plants and solar thermal panelsMatlab1 yearPrediction of thermal energy consumption, electrical energy consumption, and PMV
[53]2014Gray box modelResidential houses-------LabView and Matlab/Simulink60 daysPrediction of indoor temperature and GSHP in/out temperature for optimization process
[89]2014MPC and PABOffice room-------Matlab14 daysPrediction of indoor temperature and energy consumption considering model uncertainties
[57]2014Decision support modelOffice buildings-------Rapidminer and EnergyPlus2 years90.3% accuracy rate in prediction of occupancy
[14]2014MPCCommercial buildingYesNoNoNoYesYesGrid-1 dayManagement of uncertainties in prediction of indoor temperature and energy consumption
[58]2014Probabilistic and non-probabilistic methodsInstitutional building--------Training: 9 months and testing: 28 daysOccupancy pattern prediction
[31]2014Gray box modelSingle zone buildingYesNoNoNoYes-GridModelica and CTSM in R7 days to 100 daysModel reduction method for buildings in a smart grid context
[9]2014Smart BEMS2 Institutional buildingsYesNoNoNoYesYesGrid and RESMatlab1 dayDifferent outputs for different variables
[10]2014-University building--------5 monthsEnergy consumption and occupancy pattern analysis shows that occupancy has least significance on building energy consumption
[76]2014MPC and Gray box modelCommercial buildingYesNoNoNoYesNoGrid-Training: 7 days and testing: 30 daysModel reduction method for multi-zone models
[90]2015Online BEMSUniversity buildingNoYesNoNoYesNoGrid-2 yearsReduction in energy consumption of 1% per annum
[91]2015FLCResidential buildingYesNoNoNoYesNoGridLabView30 daysThe developed fuzzy-based advanced hydronic radiant floor heating controller produced better control characteristics over conventional controller
[23]2015iPSO-ANNLibrary building--------6 monthsHourly prediction of electrical energy consumption
[63]2015ANNOffice buildingYesYesYesYesYesNo--23 months————
[24]2015FFNN, RBFN, and ANFISUniversity building-------MatlabTraning: 3 years and testing: 1 yearHourly prediction of heating energy
[25]2015CBR and ANNUniversity building--------15 monthsHourly prediction of electricity consumption
[19]2015ANN and GAOffice roomYesYesYesYesYesNo-Matlab and EnergyPlusTraining: 3 months and testing: 8 days13.7% energy savings over the simulation period
[30]2015ANNOffice building-------Matlab612 days—————
[92]2015ANNAirport buildingYesNoNoNoYesNo- 10% energy saving per month
[93]2015GPM, GMM, and ANNOffice building--------Training: 50, 340 days and test: 23, 180 daysPrediction of daily and hourly hot water energy rate
[65]2015BNsOffice building-------GeNieTraining: 55 days and testing: 23 daysPrediction of HVAC hot water consumption with uncertainties
[51]2015GAnZEB buildings------Grid and RESTRNSYS and Matlab-—————
[94]2015MPC and Gray box modelOffice buildingYesNoNoNoYesYesGridModelica2 months30% energy savings with better thermal comfort
[52]2015ABMOffice buildingYesNoNoNoYesNo-HABIT, Matlab, EnergyPlus, and BCVTB2 months28% reduction in HVAC energy per month
[70]2015Weinar modelSingle zone building-------Matlab48 hPrediction of occupancy comfort based on real time feedback data
[95]2015MPCSingle zoneYesNoNoYesYesNo-Matlab6 daysPrediction of indoor temperature and PMV
[13]2015MPCCommercial buildingYesNoNoNoYesNoGridMatlab, EnergyPlus, and BCVTB1 day0.5% energy savings per day
[96]2015MLPInstitutional buildingYes-Yes--Yes--1 hPrediction of thermal comfort parameters and faults (unplanned events)
[64]2015MOGA and HMOGA-Yes---YesDRRES--31.6% energy and 8.1% comfort improvement over the simulation period
[71]2015Weinar modelSingle zoneYesNoNoNoYesNoGridEnergyPlus and Matlab36 h—————
[97]2015RBMResidential, commercial, and industrial buildingsYesNoNoYesYesYesGrid and RESEnergyPlus51 days12–22% improvements in building performance
[12]2015NSGA-II and GAResidential buildingYesNoNoNoYesNo-GenOpt and EnergyPlus25 days—————
[98]2015White box modelnZEB buildingsYesNoNoNoYesNoGrid and RESModelica and EnergyPlus-Developed model can produce solution 2200 times faster than the conventional method
[99]2015RBMDwellingsYesNoNoNoYesYesGridCPLEX-Developed RTP model can lead to better optimization compared to existing models
[64]2016MOGA-YesYesYesYesYesNoDRESMatlab1 daymulti-objective controller presented better trade-off between comfort and energy management
[100]2016AFLCResidence buildingYesNoNoNoYesYesGridMatlab90 days21.3% reduction in energy consumption
[20]2016FLCOffice roomNoYesNoNoYesNoGridDIALux1 day11.22% to 56.56% energy savings based on illumination level 350 lx to 200 lx
[28]2016ANNHotel buildingYesNoNoNoYesNo-Matlab and TRNSYSTraining: 4 months and testing: 13 days18–38% energy savings over the simulation period with the developed algorithms
[21]2016PSOSingle zoneYesYesNoNoYesNo-Matlab, EnergyPlus, and JEPlus-23.8–42.2% reduction in annual energy consumption
[101]2016MPC, PSO, and Gray box modelInstitutional buildingYesNoNoNoYesNo-Matlab/SimulinkTraining: 5 days and testing: 10 days11.3% Energy savings over the 10 days period
[79]2016MPCCommercial buildingYes---YesNoGridMatlab/BRCM-17% energy savings per year compare to the conventional model
[77]2016MPC and CEMSResidential buildingYesNoNoNoYesYesDER and GridCPLEX1 day17% energy cost and 8% energy consumption savings per day
[102]2016NSGASingle zoneYesYesNoNoYesNoGridJEPlus, EnergyPlus, and Matlab-55.8–76.4% reduction in cooling demand compared to baseline scenario
[41]2016MPCResidential buildingsYesNoNoYesYesNo-Matlab and EnergyPlus2 daysNearly 43% energy consumption reduction compared to the conventional control method
[103]2016BRLLaboratory demonstratorYesNoNoNoYesYes--Training: 20 days and testing: 2, 8, 12 and 16 days———————-
[49]2016MPCPublic buildingYesNoNoYesYesLSGrid and PVBCVTB, EnergyPlus, and GenOptTraining: 1 day and testing: 1 day1.7% energy saving per day
[5]2016ICAResidential buildingNoNoNoNoYesYesGrid and RESMatlab/Simulink2 monthsReduction of 87.2% in the annual energy bill
[104]2016MACResidential buildingsYesNoNoNoYesNoGridMatlab-92% of the maximum energy savings compared to the baseline strategy
[21]2016ABCSingle roomYesNoNoNoYesNoGridEnergyPlus and Matlab-49.1–56.8% decrease in PPD compared to the traditional method
[29]2016EMLResidential buildingYesNoNoNoYesNo-EnergyPlus and Matlab1 yearPrediction of energy and thermal comfort based on material thickness and insulation values
[105]2017FIS and ANNData centerYesNoNoNoYesNo-Matlab-————-
[106]2017FIS and ANNAirport buildingYesNoNoNoYesNoGrid-1 day60% perfomance increase compare to conventional on/off controller
[107]2017CBR, k-NNA, and PSOResidence buildingYesYesNoNoYesNoGrid--————-
[40]2017SVMDwellingsYesNoNoNoYesYesGrid and RESCPLEX2 days82.97% performance improvement with respect to baseline strategy on weekend
[108]2017MAS and GAResidential buildingNoNoNoNoYesNoGrid and RESJAVA-The developed model appears as an effective, smart and energy efficient solution to the problem of instantaneous power management in self-sufficient buildings
[109]2017SimulationHostel buildingYesYesNoNoYesNo-The Energy Guide II1 year————-
[27]2017ANN and LMACommercial buildingYesNoNoNoYesNoGas for boilerMatlab6 months20% reduction in gas consumption for given data duration
[110]2017MPC and LQTModel house (Wooden)YesNoNoNo-No-Matlab and LabView12 h48% of energy savings compared to the constant temperature set-point control
[111]2017FRSCSmart cityYesNoNoNoYesNoRES-12 months———–
[18]2017-Residence buildingNoNoNoNo-YesGridGAMS1 day22.40% energy cost savings over the simulation period
[112]2017MBPETMOffice roomYesNoNo-YesYes-Matlab2 daysPMV model is developed for indoor comfort management
[6]2017IoTCommercial buildingYesYesNoYesYes----Investigation of IoT-based building energy management
[113]2017GRNNCommercial building-------Matlab1 yearCO2 emission analysis to predict future CO2 emission in China
Th—Thermal, Lt—Lighting, AQ—Air Quality and RH—Relative Humidity.

Share and Cite

MDPI and ACS Style

Boodi, A.; Beddiar, K.; Benamour, M.; Amirat, Y.; Benbouzid, M. Intelligent Systems for Building Energy and Occupant Comfort Optimization: A State of the Art Review and Recommendations. Energies 2018, 11, 2604. https://doi.org/10.3390/en11102604

AMA Style

Boodi A, Beddiar K, Benamour M, Amirat Y, Benbouzid M. Intelligent Systems for Building Energy and Occupant Comfort Optimization: A State of the Art Review and Recommendations. Energies. 2018; 11(10):2604. https://doi.org/10.3390/en11102604

Chicago/Turabian Style

Boodi, Abhinandana, Karim Beddiar, Malek Benamour, Yassine Amirat, and Mohamed Benbouzid. 2018. "Intelligent Systems for Building Energy and Occupant Comfort Optimization: A State of the Art Review and Recommendations" Energies 11, no. 10: 2604. https://doi.org/10.3390/en11102604

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop