Next Article in Journal
Alternative Ways of Cooling a Passive School Building in Order to Maintain Thermal Comfort in Summer
Next Article in Special Issue
Effect of the Foresight Horizon on Computation Time and Results Using a Regional Energy Systems Optimization Model
Previous Article in Journal
Numerical Modeling and Optimization of an Air Handling Unit
Previous Article in Special Issue
New Low-Temperature Central Heating System Integrated with Industrial Exhausted Heat Using Distributed Electric Compression Heat Pumps for Higher Energy Efficiency
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Design and Operation Optimization of Distributed Solar Energy System Based on Dynamic Operation Strategy

State Key Laboratory of Green Building in Western China, Xi’an University of Architecture and Technology, Xi’an 710055, China
*
Author to whom correspondence should be addressed.
Energies 2021, 14(1), 69; https://doi.org/10.3390/en14010069
Submission received: 13 November 2020 / Revised: 18 December 2020 / Accepted: 20 December 2020 / Published: 25 December 2020

Abstract

:
The rapid urbanization in Northwest China highlights the mismatch of increasing energy demand and limited local energy supply. Nevertheless, the remote areas in Northwest China are abundant with rich solar energy resources and land space resource. Therefore, establishing a distributed solar energy system (DSES) is a feasible solution to the energy supply problem in remote Northwest China. Due to the strong fluctuations in the availability of solar energy, operation strategies based on fixed parameters may not ensure optimal operation of DSESs. In this study, dynamic operation strategies that allocate surplus power from photovoltaic panels according to variable ratios were developed in both grid-connected and off-grid scenarios, a joint optimization model for optimizing the design and operation of a DSES was established based on the dynamic operation strategies, and a DSES of a residential building in Shaanxi Province was used as a case study. The analysis results indicate that: (1) The dynamic operation strategy can effectively reduce the operating cost of the DSES in both the grid-connected and off-grid scenarios, and the efficiency of the proposed strategy can be further enhanced by increasing the difference between peak and valley time-of-use electricity prices in the grid-connected scenario; (2) the difference between peak and valley time-of-use electricity prices has a significant impact on the optimal capacity of the batteries in the grid-connected scenario when the dynamic operation strategy is implemented. The greater the difference between peak and valley time-of-use electricity prices, the greater the configured capacity of the batteries; (3) in terms of abandoned photovoltaic power in the off-grid scenario, the three operation strategies considered in this study can be arranged in an ascending order (i.e., strategy B, strategy A, and the dynamic operation strategy). The dynamic operation strategy achieves a reduction of 12.4% in abandoned photovoltaic power compared with strategy A and a reduction of 45.4% compared with strategy B.

1. Introduction

The rapid urbanization in Northwest China highlights the mismatch of increasing energy demand and limited local energy supply. As to the remote areas in Northwest China, the problems are even worse due to the poor energy infrastructure [1]. Nevertheless, the remote areas in Northwest China are abundant in rich solar energy resources and land space resources. According to [2], the annual total solar radiation range in Northwest China is 5850~8400 MJ/m2, and the daily radiation range is 4.5~6.4 kWh/m2. In comparison with other regions, the climate in Northwest China is colder and drier, resulting in great heating demands in winter [3]. As the most widely used renewable energy, solar energy is safe, clean, and convenient to exploit. Thus, developing distributed solar energy systems (DSESs) [4] could be a feasible solution to the local energy supply problem in remote Northwest China. However, solar energy also has some prominent shortcomings such as randomness, intermittency, and volatility [5]. By building a distributed energy system that integrates solar energy and other energy sources, it is possible to overcome the instability of solar energy and increase the flexibility and reliability of energy systems through complementation between different forms of energy sources [6]. This opens a promising path to use local abundant solar energy to achieve energy self-sufficiency in Northwest China.
The design and operation of DSESs play important roles in determining whether the DSES can achieve the expected economic, environmental, and efficiency goals [7,8,9]. For multi-energy complementary systems, the design and operation optimization methods can be divided into two types. The methods of the first type optimize the system design by performing full-cycle timing simulation according to predefined operation strategies. For example, Kneiske et al. [10] proposed a new optimization control algorithm which included five system control strategies for a thermo-electric storage system. Compared with the traditional control algorithms, this algorithm has the advantage of being able to achieve optimal control of the system in case of any inaccurate weather forecast and load forecast. Wang et al. [11] established a combined cooling, heating, and power (CCHP) system which integrated multiple energy sources including photovoltaic, solar thermal, and natural gas; used the particle swarm optimization (PSO) algorithm to optimize equipment capacities and operation under different operation strategies; and analyzed the impact of the operation strategy on the overall performance of the system. Nouri et al. [12] proposed a mode in which wind power participated in the energy supply of a gas turbine CCHP system in two ways (i.e., heating and power supply), and optimized the operation strategy of the integrated wind power cogeneration system. Taking minimizing the annual total cost as the optimization goal, Jayasekara et al. [13] used a two-stage PSO algorithm to optimize the capacity of the equipment. Gao et al. [14] established a model of a distributed energy system incorporating solar energy and fuel panels and analyzed the system operation strategy using the example of a typical building in Fukuoka, Japan. Zhang et al. [15] proposed a decentralized optimization strategy for distributed generators power allocation. The authors improved the strategy through replacing information of load demand by predicted power output. Meanwhile, the uncertainty and forecasting errors of renewable generation were taken into account. Aimed at optimizing the design of a stand-alone micro-grid (PV/wind/battery/diesel) system, Yoshida et al. [16] took into account the variation of the weather parameters and used the least-cost perspective approach to optimize the configuration of the proposed system. Berardi et al. [17] presented a smart hybrid energy system, aiming towards reducing the amount of fuel needed and minimizing the transportation logistics. The system combines the existing diesel generators with solar power generation, energy storage, and waste heat recovery technologies. All components are controlled by an energy management system that prioritizes output and switches between different power generators, ensuring operation at optimum efficiencies.
The above studies mainly deal with the optimization of multi-energy complementary systems under certain operation strategies. In the absence of operation strategy, some researchers adopted the approach of combining the optimization of system design with the optimization of system operation. For example, Luo et al. [18] proposed a bi-level optimization methodology to optimize a combined desalination and standalone CCHP system, which is assumed as installed on a remote South China Sea island. The traversing method and branch-and-bound method are used for solving the mixed-integer linear programming (MILP) optimization problem at the design and operation stages, respectively. From the perspectives of energy saving, environment protection, and investment payback period, Jing et al. [19] used the life cycle method to optimize the capacity design and operation strategy of a distributed multi-energy system incorporating photovoltaic power generation. Weeratunge et al. [20] proposed a mixed-integer linear programming (MILP) method to optimize the configuration of solar-assisted ground source heat pump systems which combined solar and geothermal energy. The results show that the integrated heat storage system can improve the peak shaving effect, reduce the peak power demand of the grid, and reduce the operating cost. Ren et al. [21] proposed a distributed energy system incorporating photovoltaic arrays, gas internal combustion engines, and fuel panels. They analyzed the multi-goal operation optimization of the system using the example of an ecological campus in Japan. In order to quantify the influence of the uncertainty in the energy demand and supply on the optimization of a distributed energy supply system, Zhou et al. [22] proposed a two-level stochastic programming model to convert the influence of this uncertainty into a two-level stochastic programming problem, which can be solved using a genetic algorithm (GA) in conjunction with the Monte Carlo method. They applied this model to optimize the design of a distributed energy system which supplied energy to a hotel. Mariaud et al. [23] proposed a comprehensive optimization model of the equipment selection and operation for distributed energy systems in commercial buildings. Using the example of a distribution center in London, UK, they used the steady-state MILP method to optimize the equipment selection, capacity configuration, and operation of a photovoltaic system with batteries as back-up. Ren et al. [24] applied the mathematical programming theory to construct a configuration optimization model that can be used to facilitate simultaneous optimization of the system structure, the number and capacities of devices, and the operation strategy for distributed multi-energy complementary systems. Luo et al. [25] proposed a bi–level optimization model to obtain optimal design, operation, and subsidies for a standalone multi-generation energy system situated on a remote island; the system incorporates solar energy, fossil energy, and storage. Herein, the social cost to the society is set as the upper-level objective, and the private cost to the residents is set as the lower-level objective. Production-based incentives of solar electrical energy and solar thermal energy jointly impact the design and operation of the energy system to minimize the social and private costs simultaneously.
Although joint optimization using the linearization method to approximate a nonlinear model can significantly improve the performance of the system, and it is the most appropriate from the viewpoint of accuracy, on-line operation optimization problems involving a large number of variables result in significantly increased requirements on the optimization algorithms and calculation tools. As a result, design optimization under predefined operation strategies is still a common practice. A compromise approach is to use flexible operation strategies. In the studies on the system optimization under flexible operation strategies, the operation strategies that follow the electric load (FEL) and the thermal load (FTL) strategies are more commonly seen. For example, Liu et al. [26] established a comprehensive evaluation index for a CCHP system combined with solar energy. The system was set to operate in FTL and FEL operating modes. Mago et al. [27] used the life cycle method to analyze the optimization of the FEL and FTL strategies of the distributed energy systems in high-rise buildings. Jing et al. [28] proposed an optimized operation strategy that responded to the changes in electricity–heating mixed load for improving the performance of the CHP system. Liu et al. [29] optimized the running strategy of a residential cogeneration system by introducing and discussing the effect of a hypothetical CHP system for a detached house. Based on the seasonally electricity and thermal load characteristics, several annual running strategies were established, considering the cogeneration equipment efficiency (electricity generation and thermal recover efficiencies). Then, the effect of the running strategy was evaluated from the perspective of energy saving, energy cost, and environmental effects. Considering the regular change trend of renewable energy output and user energy demand during the simulation cycle, it is also common to research on improving the overall performance of the system by switching operating strategies under different conditions. For example, Qiu et al. [30] designed day-time and night-time operation strategies for the distributed CCHP incorporating renewable energy. Hamdullahpur et al. [31] analyzed and evaluated three operating modes (solar energy direct heating mode, solar energy heating and storage mode, and solar energy heat storage mode) of a new type of distributed CCHP system incorporating a parabolic trough solar energy heat collector and an organic Rankine cycle system. The analysis results show that the maximum overall efficiency of the CCHP system is 94%, 47%, and 42% when the system operates in the above three modes, respectively. Moghadam et al. [32] studied the performance of three operation strategies of the micro CHP system (satisfying the minimum annual power consumption, satisfying the maximum annual power consumption, and maintaining constant power output) incorporating solar energy and dish Stirling engine in five cities in Iran with different climatic conditions, and evaluated the performance of each operation strategy in the context of energy, environment, and economy. Under the condition of varying load and energy price, Facci et al. [33] used the dynamic programming method to solve the daily optimal operating conditions of gas turbines, which effectively reduced the operating cost of the system compared with the basic operating modes of FTL and TEL. Zhao et al. [34] proposed a micro-grid optimization strategy that considered demand response. The strategy took into account the uncertainty of distributed renewable energy generation, power load, and daytime market prices. Liu et al. [35] proposed a structural configuration of the CCHP system with hybrid chillers, consisting of a combined electric and absorption chiller. A new operation strategy based on the ratio of the variational electric cooling to cool load was investigated. In addition, a case study was conducted to verify the feasibility of the proposed CCHP system structure and the corresponding optimal operation strategy.
The comparison between the above energy system design optimization methods is shown in Table 1. In real applications, the operation of most multi-energy complementary systems is still based on relatively fixed operation strategies in which the control logic remains unchanged during a long operation period, resulting in a large gap between the actual system design and the optimal system design. Although the switching of operation strategies can improve the operating accuracy of the system to a certain extent, there is still a large scope for improvement in the switching mechanism. For economically underdeveloped areas (e.g., the remote areas in Northwest China), the economics of the energy system is of great importance to the local government and residents. Thus, the reasonable and precise design is vital to the promotion and application of DSES, and the gap between the actual system design and optimal design cannot be ignored. In order to solve this problem, a joint optimization method for the design and operation of a DSES based on dynamic operation strategies is proposed in this study. The choice of dynamic operation strategies is based on the strong fluctuations of power output and complex energy coupling in such energy systems. A simulation is conducted to verify the effectiveness of the proposed method. This method can automatically adjust the operation strategy parameters in real-time according to the supply-demand situation of the system, thereby realizing the joint optimization of the design and operation of the system.

2. System Overview

2.1. System Configurations

The DSES in this study can be either grid-connected or off-grid. The grid-connected system consists of solar heat collectors, solar photovoltaic panels, air source heat pumps, water tank, and batteries. The off-grid system consists of solar heat collectors, solar photovoltaic panels, air source heat pumps, diesel generator, water tank (with electric heater inside), and batteries. The solar photovoltaic panels and auxiliary power systems work together to meet the electricity demand; the solar collectors, air source heat pumps, and electric heater meet the heating demand; and the water tank and batteries serve as energy storage devices. The grid-connected system (Figure 1a) is connected to the power grid. When the system’s power output is greater than the power demand, the surplus power is sold to the grid; when the system’s power output is less than the power demand, the gap is filled by the power grid. The off-grid system is separated from the power grid (Figure 1b). When the system’s power output is greater than the power demand, the surplus power is stored in the batteries; when the system’s power output is less than the power demand, the gap is filled by the batteries and diesel generator.

2.2. Operation Strategies

This study assumed that the system’s water supply temperature is 43 °C [39]. The control methods of solar thermal system include constant temperature control, temperature difference control, photoelectric control, timer control, etc. The most common are constant temperature control and temperature difference control, in which temperature and temperature difference are, respectively, used as driving signals to control the system valve ports and circulating pumps. Compared with constant temperature control, which is usually used in direct current systems, temperature difference control is more widely used in forced circulation systems [40,41]. The proposed system in this paper assumed that the circulating pump is a forced circulation system; thus, temperature difference control is adopted. The on and off of the circulating pump are controlled by the temperature difference between the outlet water temperature of the solar collector and the water temperature in the water tank. This study set this control strategy: when the temperature difference is greater than 5 °C, the solar circulating pump is turned on; when the temperature difference is less than 2 °C, the solar circulating pump will automatically shut down [42,43,44]. The air source heat pump adopted fixed temperature control. When the water temperature of the water tank is lower than the lower limit of 43 °C, the heat pump is turned on; when the water temperature is higher than the upper limit of 53 °C, the heat pump is turned off. According to the above operation strategy, there may exist surplus photovoltaic power, DetaP, after a part of the power generated by the photovoltaic panels is used to meet the power demand, Pload. In this study, DetaP will be allocated via different paths under grid-connected and off-grid scenarios:

2.2.1. Grid-Connected Scenario

In the grid-connected scenario, DetaP can be distributed in two ways: The first is to be sold to the power grid, and the second is to be stored in batteries. Figure 2 shows the flowchart of the operation strategy of a grid-connected DSES. In the dynamic operation strategy, γ was defined as the proportion of the surplus photovoltaic power, Pba, being stored to the batteries in the total surplus photovoltaic power, DetaP, at a certain time. The mathematical expression to calculate γ is shown as follows:
γ ( t ) = P b a ( t ) D e t a P ( t )
As the photovoltaic power output, user energy demand, and cost of electricity of the system vary with time, dynamic allocation of surplus photovoltaic power can be achieved by optimizing the parameter γ in real-time; thus, improving the economic performance of the system. For comparison, this study chose two other operation strategies, namely strategy A and strategy B. Affected by the characteristics of photovoltaic power generation, photovoltaic output varies greatly and voltage control is difficult, which will cause a certain degree of harmonic pollution to the grid. Under the premise of large-scale photovoltaic grid-connected, the grid’s capacity to absorb large-scale photovoltaic power is seriously insufficient. Considering the grid stability limit, the interaction between photovoltaics and the grid should be lower than the upper limit to maintain grid stability [45]. In strategy A, when the electricity sold to the grid exceeds the upper limit of system–grid interaction, the remaining DetaP will be stored into the batteries. In strategy B, DetaP will be stored to the batteries at first. When the batteries are fully charged, the remaining DetaP will be sold to the grid. When the photovoltaic power output in the system is insufficient, and the SOC of the batteries reaches the lower limit, the gap will be filled by the power purchased from the grid. Since the interaction power between the system and the grid is much smaller than the upper limit of the system–grid interaction, there is no power shortage in the system.

2.2.2. Off-Grid Scenario

In the off-grid scenario, DetaP can be distributed in two ways (i.e., storage directly in the batteries or conversion into heat energy before being stored in the water tank). When there is surplus power in the DSES, the air source heat pump will convert the electric energy into heat energy and store it into the water tank, if the water tank temperature Tst is lower than 53 °C and the surplus power meets the rated power Php of the heat pump. If the surplus power is less than the rated power, Php, of the heat pump, the electric heating device will convert electric energy into heat energy and transfer it to the water tank for storage. Here, γ was defined as the proportion of the surplus photovoltaic power Pp being converted into heat energy which is stored in the water tank at a certain time in the total surplus photovoltaic power DetaP. The mathematical expression is as follows:
γ ( t ) = P p ( t ) D e t a P ( t )
This study chose the fixed-parameter strategies C and D to serve as comparison control strategies. In strategy C, the surplus power will be stored in the batteries first. When the batteries are fully charged, the surplus power will be disposed of in different ways depending on the water tank temperature. If the Tst is higher than 53 °C, the surplus photovoltaic power will be abandoned. If the Tst is lower than 53 °C, the surplus power will be converted into heat by either heat pump or electric heater and stored in the water tank. In strategy D, the surplus power is converted into heat by either a heat pump or electric heater and stored in the water tank first. When the Tst is higher than 53 °C, the surplus power will be stored in the batteries. When the batteries are fully charged, the photovoltaic power will be abandoned. In this study, the Tst is not allowed to be higher than 80 °C. The control flowcharts of the three operation strategies are shown in Figure 3.

3. System Equipment Model

3.1. Solar Collector

The energy balance equation representing the amount of effective heat collection of the solar collector is as follows [46]:
Q C o , h ( t ) = A Co [ F R ( τ α ) e I h ( t ) F R U L ( T Ci , h ( t ) T a , h ( t ) ) ]
Q C o , h ( t ) = c f m JR ( T C o , h ( t ) T C i , h ( t ) )
where QCo,h is the amount of effective heat collection of the solar collector, ACo is the solar heat collection area, FR(τα)e is the product of the heat transfer factor of the solar heat collector and the effective projected absorption product (set to 0.7843), Ih is the solar irradiance, FRUL is the total heat loss coefficient of the solar heat collector (set to 5.5024 W/(m2·°C)), TCi,h is the inlet temperature of the heat transfer medium, Ta,h is the ambient temperature of the solar heat collector, TCo,h is the outlet temperature of the heat transfer medium, Cf is the specific heat of the heat transfer medium, and mJR is the mass flow rate of solar collector. (The solar collector used in this study is the P-Y/0.6-T/L/YH−1.86 reference flat plate collector of Siji Muge.)

3.2. Water Tank

In this study, it was assumed that the water temperature in the water tank is uniformly distributed. The energy balance equation is shown in Equation (5), where the heat loss of the water tank is determined by the tank’s loss coefficient and the heat storage temperature difference [46,47]:
T s t ( t + Δ t ) T s t ( t ) = Δ t ( ρ V s t c ) ( Q h x ( t ) + Q h p ( t ) + Q d j r ( t ) Q L ( t ) Q E ( t ) )
Q E ( t ) U s t V s t ( T s t ( t ) T b ) = 0
where Tst is the water temperature of the water tank, Vst is the capacity of the water tank, Qhx is the amount of effective heat exchange between the heat collection system and the water tank, Qhp is the amount of heat supplied by the air source heat pump, QL is the heat required by the building, QE is the heat loss of the water tank, Ust is the loss coefficient of the water tank, and Tb is the ambient temperature of the water tank. In the study, Δt is the time step and set to 0.5 h.

3.3. Solar Photovoltaic Panels

The power output of a solar photovoltaic panel is [48]:
P p v ( t ) = P S T C G ( t ) [ 1 + k ( T ( t ) T r   ) ] G STC
T ( t ) = T a , h ( t ) + 30 G ( t ) 1000
where Ppv is the power output of the photovoltaic module (kW), PSTC is the rated photovoltaic power under the standard test conditions, G is the solar irradiance, T is the working temperature of the photovoltaic module, Tr is the ambient temperature under the standard test conditions (set to 25 °C), and k is the temperature coefficient of power (set to −0.47%/h) [47], GSTC is the solar irradiance under standard test conditions (set to 1 kW/m2).

3.4. Batteries

The SOC of the batteries is determined by the remaining battery power at the previous moment and the charging and discharging power at the adjacent moment [49,50].
S O C ( t + Δ t ) = ( 1   δ × Δ t ) × S O C ( t ) + P c × Δ t × η c E c
S O C ( t + Δ t ) = ( 1   δ × Δ t ) × S O C ( t ) P d × Δ t E c × η d
where SOC is the state of charge of the batteries, δ is the self-discharge rate of the batteries (set to 0.01%/h), Pc is the charging power of the batteries, Pd is the discharge power of the batteries, ηc and ηd are the charging and discharging efficiencies of the batteries (set to 0.9) [49], Ec is the rated capacity of the batteries, Δt is the time step and equal to 0.5 h.

3.5. Air Source Heat Pump

The performance curve of a certain type of air source heat pump is fitted according to its dynamic parameters [51]. The heating capacity of the air source heat pump is determined by the ambient temperature and the power of the heat pump. The mathematical model is as follows:
  C O P ( t ) = 4.593 × 10 4 T a l ( t ) 2 + 0.04489 T a l ( t ) + 3.18
Q h p ( t ) = C O P ( t ) P h p β
where COP is the coefficient of performance of the air source heat pump, Php is the input power of the air source heat pump, β is the loss coefficient of frosting-defrosting [52].

3.6. Diesel Generator

The fuel consumption of a diesel generator is determined by the generator’s rated power and actual operating power, which can be estimated using the following formula [53]:
f c ( t ) = c P d i e ( t ) + d P r d i e
where fc is the fuel consumption of diesel generator, Prdie is the rated capacity of the diesel generator, and Pdie is the actual output power of the diesel generator, c and d are the coefficients of fuel consumption curve (c= 0.2461 L/(kWh)), d = 0.081451 L/(kWh)) [53].

3.7. Electric Heater

The relationship of electric heater’s input power and output heat power can be simply described as the following formula [54]:
Q d i r = m P d j r
where Qdjr is output heat power of the electric heater, Pdjr is the actual input power of the electric heater, m is the denotes the electric-thermal conversion efficiency of the electric heater efficiency.

4. System Optimization Model

4.1. Objective Function

In the system optimization model, the optimization goal is minimizing the annualized total cost (ATC) of the DSES, and its function is expressed as the sum of the capital expenditure (CAPEX) cost and operating expenditure (OPEX) [55]:
min   C = C r + C o | i ( 1 + i ) n ( 1 + i ) n - 1 |
where i is the real interest rate (set to 4.35%, China’s current real interest rate), and n is the service life of the equipment (set to 20 years).
CAPEX is calculated as follows:
C o = C c o A co + C s t V s t + C h p P h p + C r fj + C p v P p v + C b a E c + C d i e P r d i e
where Cco is the equipment cost per unit area of the collector; Cst is the equipment cost per unit capacity of the water tank; Chp is the equipment cost per unit heating capacity of the air source heat pump; Crfj is the cost of system piping accessories, water pumps, etc.; Cpv is the equipment cost of photovoltaic panels per unit power; and Cdie is the equipment cost of diesel generator per unit power.
OPEX includes the annual maintenance cost, annualized equipment replacement cost, grid interaction cost, photovoltaic subsidies, fuel cost, and annual environmental governance cost. The calculation formula is as follows:
C r = C w + C c + C g C b + C f + C e
where Cw is the system maintenance cost, Cc is the equipment replacement cost of the system, Cg is the annual cost of interaction between the system and grid, Cb is the photovoltaic subsidy, Cf is the fuel cost of the diesel generator, and Ce is the environmental governance cost.
The annual maintenance cost of the system includes the daily maintenance costs of solar photovoltaic panels, batteries, power distribution equipment, and diesel generator. The calculation formula is as follows:
C w = C y x p v 0 τ P p v ( t ) d t + C y x b w 0 τ P b w ( t ) d t + C y x b a E C + C y x d i e 0 τ P d i e ( t ) d t
where Cyxpv is the maintenance cost coefficient of photovoltaic panels, Cyxbw is the daily maintenance cost coefficient of power distribution equipment, Pbw is the interaction amount between the system and the grid, Cyxba is the maintenance cost coefficient of the batteries, and Cyxdie is the maintenance cost coefficient of the diesel generator. τ is the upper limit of the annual operating time, the value is 8760.
The annual equipment replacement cost of the system is the average annual replacement cost of the batteries [56]. The calculation formula is as follows:
C c = i ( 1 + i ) n 1 C b a P r b a L
where Prba is the rated power of the batteries, L is the number of replacements of the energy storage device during the service life of the system (set to four times), and Cba is the battery capacity cost coefficient.
In China, the power generated by solar panels is subsided by the government. The formula to calculate the annual grid interaction cost are as follows:
C g = C d j 0 τ P b w 1 ( t ) d t + C s t 0 τ P b w 2 ( t ) d t
C b = C d t 0 τ P p v ( t ) d t
where Cdj is the purchase cost per unit electricity, Pbw1 is the input power of the system from the grid, Cts is the benchmark price of on-grid electricity that is generated by burning desulfurized coal and sold to the grid, Pbw2 is the output power to the grid from the system, and Cdt is the state subsidy per unit electricity generated by photovoltaic panels.
By introducing the terms of emission governance, the environmental polluting effects of the carbon dioxide, sulfur dioxide, nitric oxide, and other gases emitted during the operation of a diesel generator can be converted into economic costs [57], as shown in Table 2. The corresponding formula is shown as follows:
C e = 0 τ j = 1 3 k j e k j p P d i e ( t ) d t
where kp represents the treatment cost coefficients of different pollutants, ke corresponds to the discharge coefficients of different pollutants, and j indicates the pollutant type (corresponding to CO2, SO2, and NO).
The formula for calculating the annual fuel cost [57] incurred by the operation of a diesel generator is shown as follows:
C f = C f u l 0 τ f c ( t ) d t
where Cful is the fuel cost per unit electricity generated by diesel generator.

4.2. Optimization Variables

The system optimization model contained two types of optimization variables: design optimization variables and the operation optimization variable. The design optimization variables included the solar heat collection area (Aco), rated input power of air source heat pump (Php), water tank capacity (Vst), rated power of solar photovoltaic panels (PSTC), rated capacity of batteries (Ec), and rate power of diesel generator (Prdie) in the off-grid scenario. The operation optimization variable was the real-time distribution coefficient (γ) of surplus photovoltaic power. The real-time dynamic optimization of this coefficient enables real-time and reasonable distribution of surplus photovoltaic power of the system.

4.3. Constraints

The rated power of the air source heat pump and the capacity of the water tank should be within a certain reasonable range. The interaction power between the system and the grid should not exceed the upper limit of the interaction. The maximum available land area should be considered when determining the parameter value ranges of the grid-connected systems. The area limitation is not applicable to the off-grid systems because more land can be used. The batteries have the constraint of maximum charge (discharge) power Pc.max (Pd.max). In addition, the SOC of batteries should be subject to a certain constraint so as to guarantee service life (in this study, the upper limit and lower limit were set to 0.9 and 0.1, respectively). The output power of a diesel generator should be less than their rated powers. The capacities and operation constraints of related equipment are as follows:
0 P h p Q L . max C O P β ; 0 V s t V max ; 0 P b w P b w . max ; 0 A c o A max ; S O C min S O C ( t ) S O C max ; 0 P d i e P r d i e
At the initial moment, the water temperature of the water tank was 45 °C, the temperature of the heat transfer medium inside the solar heat collector was 10 °C, and the battery SOC was 0.5.
T s t ( t = 1 ) = 45 ; S O C ( t = 1 ) = 0 . 5 ; T c o , h ( t = 1 ) = T c i , h ( t = 1 ) = 10 ;

4.4. Optimization Algorithm

The optimization algorithm in this paper uses the genetic algorithm (GA), which is a random search algorithm that draws on the natural selection and natural genetic mechanism of the biological world. It does not rely on gradient information and searches for the optimal solution by simulating the natural evolution process [58]. First, a binary code is used to randomly generate an initial population, which contains several individuals, and each individual is represented by a set optimization variable (Aco, Php, Vst, PSTC, Ec, Prdie, γ). The genetic optimization algorithm substitutes each individual into the fitness function to calculate its fitness value, and judges whether it meets the optimization criteria. If it meets the criteria, the best individual and the corresponding optimal solution are output, and the optimization process is ended; otherwise, it performs according to the fitness value selection that weeds out individuals with low adaptability, selects excellent individuals with high adaptability, and obtains a new generation of individuals through crossover and mutation operations. Then use the fitness function to calculate the fitness of the new individual until it meets the optimization criterion [59]. The flow chart of genetic algorithm is shown in Figure 4.

5. Results and Discussion

5.1. Case Study

In this study, a DSES of a two-story residential building in Shaanxi Province was used as a case study. As shown in Figure 5, the total building area is 178.2 m2, and the total heating area of the building is 136.8 m2. The main building has a length of 10.8 m, a width of 7.6 m, and a height of 7.4 m. The roof area is 82.1 m2. The building faces south. The calculation temperature of indoor heating is 18 °C. The Cts is 0.35 ¥/kWh, the subsidy per kWh of solar electricity is ¥ 0.08, and the maintenance cost is 0.009 ¥/kWh. The hourly heating load during the heating season was calculated using the Energy Plus software, and the daily electricity load of the residential building was obtained through a site survey. For the convenience of calculation, three typical weeks in the heating season (15 November to 15 March of the following year), transition season (16 March to 20 June; 22 September to 14 November), and summer season (21 June to 21 September) are chosen. Figure 6 shows the hourly heating and electrical load of the building in the three typical weeks.
In this study, the GA was used to optimize the DSES through the MATLAB software. The optimization variables and their value ranges are shown in Table 3, and the equipment costs are shown in Table 4. The photovoltaic and solar collectors in this study are arranged directly south. The azimuth angle of photovoltaic and heat collector is 0°, and the tilt angle is 34.1°.

5.2. Optimization Results in the Grid-Connected Scenario

5.2.1. System Equipment Capacities and Economic Analysis

When the system is connected to the grid, it is assumed that there are three time-based electricity pricing schemes (see Table 5). Table 5 shows the results of optimal system equipment capacities under different time-based pricing schemes and operation strategies.
It can be seen from Table 6 that, under different operation strategies, the differences between the system equipment capacities in scenario 1 and those in scenario 2 are not significantly different. Compared with scenario 1 and scenario 2, the three strategies of heat pump rated power in scenario 3 have slightly increased. Compared with the control operation strategies, the implementation of the dynamic operation strategy in scenario 3 introduces the following differences: the system uses more solar energy to meet the heating demand of the building, it needs larger solar heat collection area and water tank capacity. In addition, the rated power of photovoltaic panels reaches the maximum value of the allowable range in all scenarios, which means the system can generate as much revenue from electricity sales as possible while meeting the electricity demand of the building and the system equipment.
It can also be seen from Table 6 that the difference between peak and valley time-of-use electricity prices has a significant impact on the configuration of the battery capacity in the system. In scenarios 1 and 2, the battery capacity is zero under all operation strategies. In scenario 3, the battery capacity is not zero under the dynamic operation strategy. This can be attributed to the fact that the difference between peak and valley time-of-use electricity prices is larger in scenario 3 than in scenarios 1 and 2. When the electricity price is at a valley, the system purchases electricity from the grid, and the surplus energy is used to charge the batteries; when the electricity price is at a peak, the batteries discharge if the power supply in the system is insufficient, reducing the power purchase from the grid. When the difference between peak and valley time-of-use electricity prices increases, the utilization of batteries in the system also increases, which necessitates larger battery capacity.
Since the equipment capacities and operation strategy of the DSES in scenario 1 are roughly consistent with those in scenario 2, this study mainly analyzes the different effects of the three operation strategies on the system operation in scenario 3. Figure 7 shows the results of ATC after system optimization in scenario 3. It can be seen that in scenario 3, in which the difference between peak and valley time-of-use electricity prices is biggest, the dynamic operation strategy achieves a cost saving of 5.61% compared with strategy A and a saving of 3.94% compared with strategy B.
A detailed analysis was conducted on the optimal system operation in the heating season, transition season, and summer season in scenario 3. Analysis results show that, due to the battery discharge, the system’s power purchase under the dynamic operation strategy is less than those under the comparison strategies. Compared with the comparison strategy, due to the larger area of the collector and the smaller rated power of the heat pump under the dynamic operation strategy, the system consumes less electricity and can sell more electricity to the grid. Therefore, increase the economic benefits of the system and improve the economic performance of the system. In addition, the depth of discharge of the batteries under the dynamic operation strategy is smaller, which helps reduce the loss of the batteries and prolong the service life of the batteries. In Figure 8, the quantity of electricity is negative, which means the energy storage battery is discharged, and the system purchases electricity from the grid. Ebba is the amount of remaining photovoltaic energy allocated to the battery. Ebw is the amount of remaining photovoltaic energy allocated to the grad.

5.2.2. Sensitivity Analysis

The fact that the subsidy (Cdt) for photovoltaic electricity has been decreasing gradually in recent years has a greater impact on the economics of DSESs. Under the assumption that other factors remain unchanged, this study used Cdt as a variable to conduct a single-factor sensitivity analysis of the system. Since the equipment capacities and operation strategy of DSES in scenario 1 are roughly consistent with those in scenario 2, under all three operation strategies, this study conducted a sensitivity analysis based on scenario 3. The analysis results, shown in Figure 9, indicate that when Cdt fluctuates in the range of 0~0.16 ¥/kWh, the ATC under the dynamic operation strategy has the largest variation range, while the strategy A yields the smallest variation range. In terms of the impact of Cdt on the ATC, the three operation strategies can be arranged in the descending order as dynamic operation strategy, strategy B, and strategy A. Taking Cdt = 0.08 ¥/kWh as a reference, the sensitivity analysis shows that when Cdt fluctuates 25% upwards (downwards), the ATC of the system fluctuates 7.5%, 6.7%, and 5.3% downwards (upwards) under dynamic strategy, strategy B, and strategy A, respectively. When Cdt is less than or equal to 0.04 ¥/kWh, the ATC yielded by the dynamic operation strategy is relatively high. Under such circumstances, the most suitable operation strategy is strategy A rather than the dynamic operation strategy. When Cdt is greater than 0.04 ¥/kWh, the dynamic operation strategy yields an ATC much lower than that yielded by the other operation strategies, which means better economic performance. Under such circumstances, the dynamic operation strategy is the optimal strategy.

5.3. Optimization Results in the Off-Grid Scenario

5.3.1. System Equipment Capacities and Economics

The goal of system design and operation optimization is minimizing the ATC regardless of whether the system is operating under the dynamic operation strategy, strategy C, or strategy D. In terms of economic performance, dynamic operation strategy yields the lowest ATC of ¥20,027, strategy D yields a slightly higher ATC of ¥20,246, and strategy C yields the highest ATC of ¥21,824. The dynamic operation strategy achieves a cost saving of 8.97% compared with strategy C and 1.10% compared with strategy D. Table 7 shows that the OPEX of the system under the dynamic operation strategy is much lower than those under the control strategies, indicating that the dynamic operation strategy delivers better economic performance.

5.3.2. Analysis of Optimal System Operations

Since the system only needs to meet both the electricity and heating demand in the heating season, this study chose to analyze the optimization results of the system operation in the heating season. The water tank temperature (Tst), the distribution of the remaining photovoltaic power (Ep indicates the power allocated to electric conversion equipment, and Ebba is allocated to batteries), charging/discharging state of batteries (SOC) within a week of operation (from 22 January to 28 January in heating season), and amount of abandoned photovoltaic power (Edump) are shown in Figure 10.
Strategy C dictates that the surplus photovoltaic power is to be stored in the batteries at first and then be converted to heat energy and stored in the water tank. The storage of surplus photovoltaic power cannot proceed when the SOC of the batteries reaches the upper limit, and the water temperature of the water tank exceeds 53 °C, resulting in a large amount of abandoned photovoltaic power (see Figure 10a). Strategy D dictates that the surplus photovoltaic power is to be converted into heat energy and stored in the water tank until its temperature reaches 53 °C and then be stored in the batteries. After the system is optimized under strategy D, the surplus photovoltaic power is to be converted to heat energy and stored in water tank at first and then be stored in the batteries. Some photovoltaic power may be abandoned after the battery is fully charged. The dynamic operation strategy enables a reasonable distribution of the surplus photovoltaic power. When the temperature of the water tank is higher than 53 °C, and the SOC of the batteries reaches the upper limit, some photovoltaic power will be abandoned after system optimization, but the amount of abandoned photovoltaic power is significantly lower than that under the fixed strategies C and D (see Figure 10c).
In this case study, the variation patterns of the water temperature of the water tank under the three strategies are consistent. Under the limitations of the SOC of the batteries and the temperature of the water tank, some photovoltaic power will be abandoned no matter which operation strategy is implemented. During the one week operation period, the amounts of abandoned photovoltaic power in heating season, summer season, and transition season are shown in Table 8. During the heating season operation, strategy D has the largest amount of abandoned photovoltaic power and strategy C has the smallest amount of discarded photovoltaic power, the amount of abandoned photovoltaic power under the dynamic operation strategy is between the two. In the summer operation, the amount of photovoltaic power discarded by the system under strategy C is the largest, and the amount of photovoltaic power discarded under the dynamic operation strategy is the smallest. In the transition season, the smallest amount of photovoltaic power discarded is under the dynamic operation strategy, and strategy D has the largest amount of photovoltaic power discarded. In this study, it is assumed that there are 17 weeks in the heating season, 13 weeks in the summer season, and 22 weeks in the transition season in the whole year. Therefore, the three operation strategies can be arranged in the following descending order in terms of the annual amount of abandoned photovoltaic power (i.e., strategy D, strategy C, and dynamic operation strategy). The dynamic operation strategy achieves a reduction of 12.4% in the amount of abandoned photovoltaic power compared with strategy C, and a reduction of 45.4% compared with strategy D.

6. Conclusions

In this study, this study constructed an optimization model of the DSES and developed a dynamic operation strategy, based on surplus photovoltaic power distribution, to facilitate joint optimization of the system design and operation. The proposed operation strategy was applied to the energy system of a typical two-story residential building in Shaanxi Province and was compared with comparison operation strategies with fixed operating parameters. The main conclusions are as follows:
(1) The difference between peak and valley time-of-use electricity prices has a great impact on the selection of the optimal operation strategy for the grid-connected system. When the difference between peak and valley time-of-use electricity prices is large, the economic performance of the system under the dynamic operation strategy is significantly improved: In scenario 3, in which the difference between peak and valley time-of-use electricity prices is 0.75 ¥/kWh, the dynamic operation strategy achieves a saving of 5.61% in ATC compared with strategy A and a saving of 3.94% compared with strategy B.
(2) The difference between peak and valley time-of-use electricity prices has a great impact on the battery capacity configuration of the grid-connected system under the dynamic operation strategy. When the difference between peak and valley time-of-use electricity prices is large, as in scenario 3, batteries should be included in the system optimal capacity configuration so as to achieve the best economic performance of the system.
(3) In terms of the influence of the subsidy on the on-grid system cost under different operation strategies, the ATC of the system decreases with the increase of Cdt. Taking Cdt = 0.08 ¥/kWh as a reference, the sensitivity analysis shows that when Cdt fluctuates 25% upwards (downwards), the ATC of the system fluctuates 7.5%, 6.7%, and 5.3% downwards (upwards) under dynamic strategy, strategy B, and strategy A, respectively. The three operation strategies of the grid-connected system can be arranged in descending order as dynamic operation strategy, strategy B, and strategy A. When Cdt ≤ 0.04 ¥/kWh, strategy A is the most suitable for the system; when Cdt > 0.04 ¥/kWh, the dynamic operation strategy yields an ATC much lower than those yielded by the control operation strategies, which means it is the best operation strategy.
(4) In terms of the economic performance of the off-grid system, the annual net cost of the three operating strategies, in increasing order, are dynamic operating strategy, strategy B, and strategy A. Compared with strategy A and strategy B, the ATC under the dynamic operating strategy saves 8.97% and 1.10%, respectively.
(5) In terms of the amount of photovoltaic power abandoned in the off-grid scenario, the three operation strategies can be arranged in descending order as strategy D, strategy C, and dynamic operation strategy. The dynamic operation strategy achieves a reduction of 12.4% in the amount of photovoltaic power abandoned compared with strategy C, and a reduction of 45.4% compared with strategy D.

Author Contributions

Methodology, Y.L. and X.L.; software, Y.W.; formal analysis, Y.W.; investigation, Y.W.; data curation, Y.W.; writing—original draft preparation, Y.W.; writing—review and editing, X.L. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by the National Natural Science Foundation of China (51878532 and 52008328), National Key Research and Development Project (2018YFD1100202), Science and Technology Department of Shaanxi Province (2018ZDCXL-SF-03-01 and 2020SF-393), and Education Department of Shaanxi Province (19JS041).

Conflicts of Interest

The authors declare no conflict of interest.

Nomenclature

Abbreviations
ATCannualized total costCAPEXcapital expenditure cost
CCHPcombined cooling, heating, and powerDESdistributed energy system
DSESdistributed solar energy systemFTLfollow the thermal load
FELfollow the electric loadGAgenetic algorithm
MILPmixed-integer linear programmingOPEXoperating expenditure
PSOparticle swarm optimizationSOCstate of charge
Parameters
Acosolar collector area, m2COPperformance coefficient of air source heat pump
Cbphotovoltaic subsidy, ¥Cbabattery initial cost, ¥/kWh
Ccbattery replacement cost, ¥Ccounit cost of collector equipment, ¥/m2
Cdjunit electricity purchase cost, ¥/kWhCdtphotovoltaic power subsidy, ¥/kWh
Cdiediesel generator initial cost, ¥/kWCeenvironmental management fees, ¥
Cfcost of diesel generator fuel, ¥Cfulannual fuel cost diesel generator, ¥/kWh
Cgannualized interaction cost between the system and the grid, ¥Chpunit cost of air source heat pump, ¥/kW
Cpvsolar photovoltaic cell initial cost, ¥/kWCstunit cost of heat storage tank, ¥/m3
Cwsystem operation and maintenance costs, ¥Cyxbwannual maintenance costs of distribution equipment, ¥/kW
Cyxdieannual maintenance costs of diesel generator, ¥/kWhCyxbaannual maintenance costs of battery, ¥/kWh
Cyxpvannual maintenance costs of photovoltaic cell, ¥/kWEcrated capacity of energy storage battery, kWh
FRULtotal heat loss coefficient of collector, W/(m2·°C)fcthe fuel consumption of diesel generator, L
GSTClight intensity under standard test conditions, kW/m2Gillumination intensity, kW/m2
ireal interest rateIhsolar radiation intensity, W/m2
jpollutant typektemperature coefficient of power
kpthe treatment cost coefficients of different pollutantskedischarge coefficients of different pollutants
mJRheat collection flow, kg/m3nlifetime of system, years
Pc(d)charging and discharging power of energy storage battery, kWPbwpower interaction between the system and the grid, kW
Pdumpdumped electricity, kWPdiepower output of the diesel generator, kW
Ppvphotovoltaic power output, kWPhpinput power of air source heat pump, kW
PSTCrated photovoltaic power under standard test conditions, kWPrbarated power of battery, kW
QEheat loss in the heat storage tank, WQCo,hheat effectively collected by solar collectors, kW
Qhpoutput heat power of air source heat pump, kWQhxeffective heat exchange between the collecting system and the heat storage, kW
QLheating load of the building, Wttime step
Tphotovoltaic module operating temperature, °CTa,henvironment temperature, °C
TCi,hinlet temperature of collector working medium, °CTbambient temperature of the heat storage tank, °C
Trambient temperature under standard test conditions, °C TCo,houtlet temperature of collector working medium, °C
Tstwater temperature of the regenerator tank, °CUstloss coefficient of heat storage tank, W/(°C·m3)
Vstvolume of heat storage tank, m3ηc(d)charging and discharging efficiency of energy storage battery
δself-discharge rate of energy storage battery, %

References

  1. Guo, H.; Liu, Y.; Guo, H.; Zhang, M.; Liang, J. Research on the Adaptability of Solar Heating Mode in Northwest Rural Areas. Chin. Sci. Technol. Pap. 2015, 10, 31–34. [Google Scholar]
  2. Zhou, G. Discussion on the Energy-saving Problem of Rural Houses in Northwest my country. Sci. Technol. Inf. 2009, 21, 291–292. [Google Scholar]
  3. Zhu, Y.; Liu, J. Research on indoor thermal environment of rural buildings in Northwest China in winter. China Civil Eng. J. 2010, S2, 400–403. [Google Scholar]
  4. Luo, X.; Liu, Y.; Liu, J.; Liu, X. Optimal design and cost allocation of a distributed energy resource (DER) system with district energy networks: A case study of an isolated island in the South China Sea. Sustain. Cities Soc. 2019, 51, 101726. [Google Scholar] [CrossRef]
  5. Luo, X.; Liu, Y.; Liu, J.; Liu, X. Energy scheduling for a three-level integrated energy system based on energy hub models: A hierarchical Stackelberg game approach. Sustain. Cities Soc. 2020, 52, 101814. [Google Scholar] [CrossRef]
  6. Luo, X.; Liu, Y. A multiple-coalition-based energy trading scheme of hierarchical integrated energy systems. Sustain. Cities Soc. 2021, 64, 102518. [Google Scholar] [CrossRef]
  7. Olia, H.; Torabi, M.; Bahiraei, M.; Ahmadi, M.H.; Goodarzi, M.; Safaei, M.R. Application of Nanofluids in Thermal Performance Enhancement of Parabolic Trough Solar Collector: State-of-the-Art. Appl. Sci. 2019, 9, 463. [Google Scholar] [CrossRef] [Green Version]
  8. Ghalandari, M.; Maleki, A.; Haghighi, A.; Shadloo, M.S.; Nazari, M.A.; Tlili, I. Applications of nanofluids containing carbon nanotubes in solar energy systems: A review. J. Mol. Liq. 2020, 313, 113476. [Google Scholar] [CrossRef]
  9. Sarafraz, M.M.; Tlili, I.; Tian, Z.; Bakouri, M.; Safaei, M.R. Smart optimization of a thermosyphon heat pipe for an evacuated tube solar collector using response surface methodology (RSM). Phys. A Stat. Mech. Appl. 2019, 534, 122146. [Google Scholar] [CrossRef]
  10. Tanja, M.K.; Martin, B. Flexibility potentials of a combined use of heat storages and batteries in PV-CHP hybrid systems. Energy Procedia 2018, 135, 482–495. [Google Scholar]
  11. Wang, Z.; Yang, X.; Wang, Y.; Weng, S. Strategic analysis and optimal design of a multi-energy coupling combined cooling, heating and power system. Therm. Energy Power Eng. 2019, 34, 9–14. [Google Scholar]
  12. Nouri, G.; Noorollahi, Y.; Yousefi, H. Designing and optimization of solar assisted ground source heat pump system to supply heating, cooling and hot water demands. Geothermics 2019, 82, 212–231. [Google Scholar] [CrossRef]
  13. Jayasekara, S.; Halgamuge, S.K.; Attalage, R.A.; Rajarathne, R. Optimum sizing and tracking of combined cooling heating and power systems for bulk energy consumers. Appl. Energy 2014, 118, 124–134. [Google Scholar] [CrossRef]
  14. Gao, X.; Akashi, Y.; Sumiyoshi, D. Installed capacity optimization of distributed energy resource systems for residential buildings. Energy Build. 2014, 69, 307–317. [Google Scholar] [CrossRef]
  15. Zhang, S.; Yu, Z.; Zhou, B.; Yang, Z.; Yang, D. A Decentralized Optimization Strategy for Distributed Generators Power Allocation in Microgrids Based on Load Demand-Power Generation Equivalent Forecasting. Energies 2020, 13, 648. [Google Scholar] [CrossRef] [Green Version]
  16. Yoshida, Y.; Farzaneh, H. Optimal Design of a Stand-Alone Residential Hybrid Microgrid System for Enhancing Renewable Energy Deployment in Japan. Energies 2020, 13, 1737. [Google Scholar] [CrossRef] [Green Version]
  17. Berardi, U.; Tomassoni, E.; Khaled, K. A Smart Hybrid Energy System Grid for Energy Efficiency in Remote Areas for the Army. Energies 2020, 13, 2279. [Google Scholar] [CrossRef]
  18. Luo, X.; Zhu, Y.; Liu, J.; Liu, Y. Design and analysis of a combined desalination and standalone CCHP (combined cooling heating and power) system integrating solar energy based on a bi-level optimization model. Sustain. Cities Soc. 2018, 43, 166–175. [Google Scholar] [CrossRef]
  19. Jing, Y.; Bai, H.; Zhang, J. Multi-objective optimization design and operation strategy analysis of solar energy combined cooling, heating and power system. Proc. Chin. Soc. Electr. Eng. 2012, 32, 82–87. [Google Scholar]
  20. Weeratunge, H.; Narsilio, G.; Hoog, J.; Dunstall, S.; Halgamuge, S. Model predictive control for a solar assisted ground source heat pump system. Energies 2018, 152, 974–984. [Google Scholar] [CrossRef]
  21. Ren, H.; Zhou, W.; Nakagami, K.; Gao, W.; Wu, Q. Multi-objective optimization for the operation of distributed energy systems considering economic and environmental aspects. Appl. Energy 2010, 87, 3642–3651. [Google Scholar] [CrossRef]
  22. Zhou, Z.; Zhang, J.; Liu, P.; Li, Z.; Georgiadis, M.C.; Pistikopoulos, E.N. A two-stage stochastic programming model for the optimal design of distributed energy systems. Appl. Energy 2013, 103, 135–144. [Google Scholar] [CrossRef]
  23. Mariaud, A.; Acha, S.; Ekins-Daukes, N.; Shah, N.; Markides, C.N. Integrated optimisation of photovoltaic and battery storage systems for UK commercial buildings. Appl. Energy 2017, 199, 466–478. [Google Scholar] [CrossRef]
  24. Ren, H.; Gao, W. A MILP model for integrated plan and evaluation of distributed energy systems. Appl. Energy 2010, 87, 1001–1014. [Google Scholar] [CrossRef]
  25. Luo, X.; Liu, J.; Liu, Y.; Liu, X. Bi-level optimization of design, operation, and subsidies for standalone solar/diesel multi-generation energy systems. Sustain. Cities Soc. 2019, 48, 101592. [Google Scholar] [CrossRef]
  26. Liu, X.; Wu, H. Control Strategy and Operation Optimization of Combined Cooling, Heating and Power System for Comprehensive Utilization of Solar Energy. Electr. Power Syst. Autom. 2015, 12, 1–6. [Google Scholar]
  27. Mago, P.J.; Chamra, L.M. Analysis and optimization of CCHP systems based on energy, economical, and environmental considerations. Energy Build. 2009, 41, 1099–1106. [Google Scholar] [CrossRef]
  28. Bai, H.; Jing, Y.; Wang, J. Multi-objective optimization design and operation strategy analysis of BCHP system based on life cycle assessment. Energy 2012, 37, 405–416. [Google Scholar]
  29. Liu, Q.; Ruan, Y.; Ren, J. Running Strategy Optimization of Micro-Cogeneration System in Residential Building. Adv. Mater. Res. 2012, 1477, 774–780. [Google Scholar] [CrossRef]
  30. Qiu, Y.; Zheng, X.; Zhan, X.; Zhu, X.; Meng, C.; Zhao, Y. Design and operation strategy optimization of distributed cogeneration system coupled with renewable energy. J. Xiamen Univ. (Nat. Sci. Ed.) 2019, 58, 110–117. [Google Scholar]
  31. Al-Sulaiman, F.A.; Hamdullahpur, F.; Dincer, I. Performance assessment of a novel system using parabolic trough solar collectors for combined cooling, heating, and power production. Renew. Energy 2012, 48, 161–172. [Google Scholar] [CrossRef]
  32. Moghadam, R.S.; Sayyaadi, H.; Hosseinzade, H. Sizing a solar dish Stirling micro-CHP system for residential application in diverse climatic conditions based on 3E analysis. Energy Convers. Manag. 2013, 75, 348–365. [Google Scholar] [CrossRef]
  33. Facci, A.L.; Andreassi, L.; Ubertini, S. Optimization of CHCP (combined heat power and cooling) systems operation strategy using dynamic programming. Energy 2014, 66, 387–400. [Google Scholar] [CrossRef]
  34. Zhao, H.; Lu, H.; Li, B.; Wang, X.; Zhang, S.; Wang, Y. Stochastic Optimization of Microgrid Participating Day-Ahead Market Operation Strategy with Consideration of Energy Storage System and Demand Response. Energies 2020, 13, 1255. [Google Scholar] [CrossRef] [Green Version]
  35. Liu, M.; Shi, Y.; Fang, F. A new operation strategy for CCHP systems with hybrid chillers. Appl. Energy 2012, 95, 164–173. [Google Scholar] [CrossRef]
  36. Franco, A.; Versace, M. Multi-objective optimization for the maximization of the operating share of cogeneration system in District Heating Network. Energy Convers. Manag. 2017, 139, 33–44. [Google Scholar] [CrossRef]
  37. Jin, R.; Song, J.; Liu, J.; Li, W.; Lu, C. Location and Capacity Optimization of Distributed Energy Storage System in Peak-Shaving. Energies 2020, 13, 513. [Google Scholar] [CrossRef] [Green Version]
  38. Wang, X.; Tian, H.; Yan, F.; Feng, W.; Wang, R.; Pan, J. Optimization of a distributed energy system with multiple waste heat sources and heat storage of different temperatures based on the energy quality. Appl. Therm. Eng. 2020, 181, 115975. [Google Scholar] [CrossRef]
  39. Design Code for Heating, Ventilation and Air Conditioning of Civil Buildings (with Instructions): GB 50736-2012. 2012. Available online: http://www.jianbiaoku.com/webarbs/book/16582/1663593.shtml (accessed on 13 November 2020).
  40. Liu, Y. Operational Simulation and Application Research of Air-Source Heat Pump-Assisted Solar Water Heating System in Hot Summer and Cold Winter Area. Master’s Thesis, Chongqing University, Chongqing, China, 2011. [Google Scholar]
  41. Zheng, R. Engineering Manual of Solar Water Heating System for Civil Buildings; Chemical Industry Press: Beijing, China, 2011. [Google Scholar]
  42. Calise, F.; d’Accadia, M.D.; Figaj, R.D.; Vanoli, L. A novel solar-assisted heat pump driven by photovoltaic/thermal collectors: Dynamic simulation and thermoeconomic optimization. Energy 2016, 95, 346–366. [Google Scholar] [CrossRef]
  43. Figaj, R.; Zoladek, M.; Goryl, W. Dynamic Simulation and Energy Economic Analysis of a Household Hybrid Ground-Solar-Wind System Using TRNSYS Software. Energies 2020, 13, 3523. [Google Scholar] [CrossRef]
  44. Figaj, R.; Szubel, M.; Przenzak, E.; Filipowicz, M. Feasibility of a small-scale hybrid dish/flat-plate solar collector system as a heat source for an absorption cooling unit. Appl. Therm. Eng. 2019, 163, 114399. [Google Scholar] [CrossRef]
  45. Qin, R.; Dong, K.; Wang, H.; Yang, P.; Liu, H. Analysis and countermeasures of the impact of large-scale photovoltaic power stations on the power grid. Electr. Autom. 2014, 03, 57–59. [Google Scholar]
  46. Liu, Y. Design Principles and Technology of Solar Heating; China Building Industry Press: Beijing, China, 2016. [Google Scholar]
  47. Zhu, C.; Liu, Y.; Sun, T.; Zhou, Y. Operation Optimization of Solar Energy and Air Source Heat Pump Combined Heating System. Build. Energy Environ. 2020, 39, 53–57. [Google Scholar]
  48. Ding, M.; Wang, B.; Zhao, B.; Chen, Z. Optimization of the capacity of the independent wind and diesel storage microgrid system. Power Grid Technol. 2013, 037, 575–581. [Google Scholar]
  49. Liu, B. Optimal Design of Typical Applications of Multi-Source Microgrid. Master’s Thesis, Southeast University, Nanjing, China, 2015. [Google Scholar]
  50. Hatata, A.Y.; Osman, G.; Aladl, M.M. An optimization method for sizing a solar/wind/battery hybrid power system based on the artificial immune system. Sustain. Energy Technol. Assess. 2018, 27, 83–93. [Google Scholar] [CrossRef]
  51. Zhang, H.; Wang, Z.; Chen, X.; Chen, W. Experimental Research on Variable Operating Conditions of Air Source Heat Pump Water Heater. Refrig. Air Cond. Electr. Mach. 2009, 30, 1–4. [Google Scholar]
  52. Jiang, Y.; Yao, Y.; Ma, Z. Calculation of frosting and defrosting loss coefficient for air source heat pumps. HVAC 2000, 5, 24–26. [Google Scholar]
  53. Sharafi, M.; Elmekkawy, T.Y. Multi-objective optimal design of hybrid renewable energy systems using PSO-simulation based approach. Renew. Energy 2014, 68, 67–79. [Google Scholar] [CrossRef]
  54. Li, R.; Guo, S.; Yang, Y.; Liu, D. Optimal sizing of wind/concentrated solar plant/electric heater hybrid renewable energy system based on two-stage stochastic programming. Energy 2020, 209, 118472. [Google Scholar] [CrossRef]
  55. Feng, W. Engineering Economics; Peking University Press: Beijing, China, 2012. [Google Scholar]
  56. Zhang, J. Research on Capacity Optimization Configuration of Micro Wind Power Grid for Independent Wind and Diesel Storage. Master’s thesis, North China Electric Power University, Baoding, China, 2018. [Google Scholar]
  57. Dufo-Lopez, R.; Bernal-Agustin, J.L. Multi-objective design of PV-wind-diesel-hydrogen-battery systems. Renew. Energy 2008, 33, 2559–2572. [Google Scholar] [CrossRef]
  58. Lei, Y. MATLAB Genetic Algorithm Toolbox and Application; Xi’an University of Electronic Science and Technology Press: Xi’an, China, 2014. [Google Scholar]
  59. Yang, W.; Shi, M. Optimization of solar geothermal composite source heat pump system based on Genetic Algorithm. Heat. Vent. Air Cond. 2007, 2, 12–17. [Google Scholar]
Figure 1. Two types of distributed solar energy systems. (a) Grid-connected system; (b) off-grid system.
Figure 1. Two types of distributed solar energy systems. (a) Grid-connected system; (b) off-grid system.
Energies 14 00069 g001aEnergies 14 00069 g001b
Figure 2. System operation strategy in the grid-connected scenario. Ppv is photovoltaic power generation; SOC is the state of charge of the batteries.
Figure 2. System operation strategy in the grid-connected scenario. Ppv is photovoltaic power generation; SOC is the state of charge of the batteries.
Energies 14 00069 g002
Figure 3. System operation strategy in the off-grid scenario.
Figure 3. System operation strategy in the off-grid scenario.
Energies 14 00069 g003
Figure 4. Flow chart of genetic algorithm.
Figure 4. Flow chart of genetic algorithm.
Energies 14 00069 g004
Figure 5. The typical building and the Energy Plus model diagram.
Figure 5. The typical building and the Energy Plus model diagram.
Energies 14 00069 g005
Figure 6. Electricity and heating demands during typical weeks.
Figure 6. Electricity and heating demands during typical weeks.
Energies 14 00069 g006
Figure 7. The net annual value of system costs in scenario 3.
Figure 7. The net annual value of system costs in scenario 3.
Energies 14 00069 g007
Figure 8. Operational optimization results of the heating season. (a) Strategy A; (b) strategy B; (c) dynamic operation strategy.
Figure 8. Operational optimization results of the heating season. (a) Strategy A; (b) strategy B; (c) dynamic operation strategy.
Energies 14 00069 g008aEnergies 14 00069 g008b
Figure 9. The impact of Cdt on ACT under different operating strategies.
Figure 9. The impact of Cdt on ACT under different operating strategies.
Energies 14 00069 g009
Figure 10. System operation optimization results under different operating strategies. (a) Strategy C; (b) strategy D; (c) dynamic operation strategy.
Figure 10. System operation optimization results under different operating strategies. (a) Strategy C; (b) strategy D; (c) dynamic operation strategy.
Energies 14 00069 g010aEnergies 14 00069 g010b
Table 1. Comparison between design optimization methods for hybrid energy systems.
Table 1. Comparison between design optimization methods for hybrid energy systems.
NumberOptimization MethodPros and ConsLiterature
1Design optimization under predefined operation strategyMost widely used in actual engineering due to reliability and economy, but the operating strategy is not optimized [36].[12,13,14,15,16,26,27,28,29]
2Design optimization under combined operation strategiesSet a variety of conditions to optimize the design, but the capacity allocation methods under other uncertain conditions are lacking [37][11,17,30,31,32,33,34,35]
3Design and operation joint optimizationMost appropriate from the viewpoint of accuracy, but need more computing time [38][18,19,20,21,22,23,24,25]
Table 2. Pollutant emissions and charges of diesel generators [57].
Table 2. Pollutant emissions and charges of diesel generators [57].
SpeciesEmission Coefficient (g·kWh−1)Governance Cost Coefficient (¥·kg−1)
CO26790.21
SO20.20614.842
NO9.8962.946
Table 3. Ranges of optimization variables.
Table 3. Ranges of optimization variables.
Optimization VariableGrid-Connected ScenarioOff-Grid Scenario
Aco/m20~500~167
Vst/m30.5~140.5~14
Php/kW0~150~15
PSTC/kW0~120~20
Ec/(kW·h)0~120~20
Prdie/kW/0~10
γ0~10~1
Table 4. Cost of each device.
Table 4. Cost of each device.
System ComponentsUnit CostMaintenance Cost (¥·kWh−1)
Solar collector800 ¥·m−2/
Air source heat pump5400 ¥·kW−1/
Water tank500 ¥·m−3/
Batteries2000 ¥·kWh−10.008
Diesel generators3000 ¥·kW−10.088
Solar photovoltaic panels5000 ¥·kW−10.0096
Water pump and other accessories2000 ¥/
Table 5. Time-of-use rate.
Table 5. Time-of-use rate.
ScenarioTime PeriodElectricity Price/¥·(kWh)−1
17:00~11:00; 19:00~24:000.77
11:00~19:000.58
1:00~7:000.40
27:00~11:00; 19:00~24:000.87
11:00~19:000.58
1:00~7:000.30
37:00~11:00; 19:00~24:000.97
11:00~19:000.58
1:00~7:000.20
Table 6. Optimal equipment capacity.
Table 6. Optimal equipment capacity.
ScenarioCapacityDynamic StrategyStrategy AStrategy B
1Aco/m2444341
Php/kW2.52.72.8
Vst/m310.610.510.5
PSTC/kW12.012.011.9
Ec/kWh000
2Aco/m2424441
Php/kW2.62.72.8
Vst/m310.510.410.7
PSTC/kW12.012.012.0
Ec/kWh000
3Aco/m243 3837
Php/kW2.93.13.0
Vst/m311.210.410.1
PSTC/kW12.012.012.0
Ec/kWh1.3600
Table 7. Optimized equipment capacities and system costs.
Table 7. Optimized equipment capacities and system costs.
Equipment CapacityDynamic StrategyStrategy CStrategy D
Aco/m2817682
Php/kW1.82.51.9
Vst/m3141314
PSTC/kW3.34.53.9
Ec/kWh57.53.1
Prdie/kW1.92.92.3
CAPEX/¥16,67218,02116,386
OPEX/¥335538033860
ATC/¥20,02721,82420,246
Table 8. Abandoned photovoltaic energy during typical weeks.
Table 8. Abandoned photovoltaic energy during typical weeks.
Abandoned Photovoltaic Energy/kWhDynamic StrategyStrategy CStrategy D
Heating season35.0225.3344.10
Summer season29.1342.5334.75
Transition season24.9232.8945.98
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Liu, Y.; Wang, Y.; Luo, X. Design and Operation Optimization of Distributed Solar Energy System Based on Dynamic Operation Strategy. Energies 2021, 14, 69. https://doi.org/10.3390/en14010069

AMA Style

Liu Y, Wang Y, Luo X. Design and Operation Optimization of Distributed Solar Energy System Based on Dynamic Operation Strategy. Energies. 2021; 14(1):69. https://doi.org/10.3390/en14010069

Chicago/Turabian Style

Liu, Yanfeng, Yaxing Wang, and Xi Luo. 2021. "Design and Operation Optimization of Distributed Solar Energy System Based on Dynamic Operation Strategy" Energies 14, no. 1: 69. https://doi.org/10.3390/en14010069

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop