Next Article in Journal
Collection of Thermal Energy Available from a Biogas Plant for Leachate Treatment in an Urban Landfill: A Sicilian Case Study
Previous Article in Journal
Effects of a Green Space Layout on the Outdoor Thermal Environment at the Neighborhood Level
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Transient Analysis of Large Scale PV Systems with Floating DC Section

1
Politecnico di Milano, Via La Masa 34, 20156 Milan, Italy
2
University Politehnica of Bucharest, Splaiul Independentei 313, 060042 Bucharest, Romania
*
Author to whom correspondence should be addressed.
Energies 2012, 5(10), 3736-3752; https://doi.org/10.3390/en5103736
Submission received: 27 July 2012 / Accepted: 13 September 2012 / Published: 26 September 2012

Abstract

:
The increasing penetration of renewable sources with power-electronic interfaces in power systems is raising technical problems and the overall efficiency of photovoltaic systems can decrease dramatically. In this context, the optimal layout for the photovoltaic system is required. The most adequate strategy to connect the renewable system to the electrical power grid or to supply the end users must be adopted. The present paper proposes a design layout of a PV plant using a DC bus system to improve the overall energy conversion efficiency. An analysis of steady-state system stability, voltage drop and DC cable conduction losses is conducted. The leakage currents to the ground are investigated through simulations. Experimental results are shown focused on the analysis of optimal layout of photovoltaic systems under particular operating conditions.

1. Introduction

Renewable energy sources are increasingly present in electrical grids. The economic opportunities, the energy sector liberalization and the potential benefits for the electrical utilities (peak shaving, support for distribution and transmission networks) are contributing to the already existing trend, leading to a more decentralized energy market. In parallel to these aspects, energy and environmental considerations encourage the widespread use of renewable energy sources. The renewable sources can be used in small and decentralized power plants or in large generation systems. They are modular and can be built in small size modules to be used in different locations.
Renewable energy sources require reliable operating interfaces with the main grid, which are mostly based on power electronics converters. The natural variability of environmental conditions and nonlinear behavior of photovoltaic generators make the utilization of photovoltaic energy a challenging task [1,2,3,4]. The increasing penetration of renewable sources with power-electronic interface in the power systems is raising technical problems in various areas such as power quality control [5,6,7], voltage regulation [8], grid protection coordination [9,10], loss of mains detection [11,12], and generator operation following disturbances on the distribution grid [13,14,15].
The overall efficiency of photovoltaic systems dramatically decreases due to panel mismatching [16,17], switching losses in the PV inverter [18,19], maximum power extraction losses [20], and cable conduction losses [21,22]. The power losses become important in complex photovoltaic configurations, like those integrated in roofs and facades, or in large PV systems. The high number of modules, the different radiation level over the panel area and the long distance between PV panels and converters are contributing to the overall system power losses. The complexity represents also an additional factor in maintenance and control operations, since a failure in one PV module, in most of the cases, is difficult to detect [23].
In this context, an optimal layout of the photovoltaic system is required and the most adequate strategy to connect the renewable system to the electrical power grid or to supply the end users must be adopted.
New architectures divided into a modular PV system and a distributed conversion system for power loss reduction were proposed in [2,4]. The first architecture, appropriate for building integrated PV systems and small PV systems, incorporates a DC/AC converter or a DC/DC converter, equipped with MPPT algorithm and placed close to each PV module with the aim to reduce losses due to panel mismatching. The second architecture, appropriate for large PV plants, uses PV strings sub-fields with their own small size DC/DC converter (equipped with maximum power point tracking algorithms) placed close to the PV panels, and afterwards one or two large size common grid-connected inverters [13,14,15].
The present paper proposes a design layout of the PV plant using a DC bus system to improve the overall energy conversion efficiency. An analysis of steady-state system stability, voltage drop and DC cable conduction losses is conducted. The leakage currents to the ground are investigated using the EMTP-ATP simulation tool. Experimental results are shown focused on the analysis of optimal layout of photovoltaic systems under particular operating conditions.
In particular, in Section 2, the PV layout configurations are examined. Section 3 is devoted to the proposed layout of the PV plant: steady state analysis and investigation of voltage drop and cable losses are carried out. In Section 4, the investigation of the leakage currents to the ground and protection systems required is conducted and the transient analysis of the PV configuration is examined and discussed. Experimental results on a small scale prototype are presented in Section 5. Finally, conclusions are given in Section 6.

2. PV Solar Array Configurations

The architectures for PV plant are mainly classified on the basis of conversion stage [2,16]. The power electronic converter must track the MPP of the PV cell [24,25,26] without modifying the mains voltage and frequency [13,14,15]. The conversion stage can be subdivided on the basis of the number of conversion stages (single or double) and on the basis of topology (e.g., centralized, string, modular, distributed). Table 1 reports the different architectures, summarizing their most important characteristics.
Table 1. Architectures of PV systems.
Table 1. Architectures of PV systems.
Config DescriptionAdvantages/disadvantages
Single stage conversionCentralized topology (A) Energies 05 03736 i001Several strings associated to a common grid-connected inverter.
-
High mismatch losses, since the operation is limited to one MPP for the entire array;
-
High sensitivity of the inverter to the voltage on DC side;
-
Use of string diodes and high cable losses.
String topology (B) Energies 05 03736 i002The photovoltaic field is divided into several sub‑fields, each one connected to an inverter for the interconnection to the low voltage electrical grid.
-
Reduced mismatching losses;
-
High sensitivity of inverters;
-
String diodes are not necessary;
-
High cable voltage drop and losses;
-
More expensive: large size power inverter is generally cheaper than few small inverters.
Modular topology (AC Modular) (C) Energies 05 03736 i003The DC/AC converter, with MPPT algorithm, is integrated into each PV module.
-
Significant reduction of mismatching losses;
-
String diodes are not necessary;
-
Very high voltage drop and cable power losses;
-
Very expensive;
-
Design with long lifetime under ambient condition;
-
Fast detection of faults in PV systems.
Double stages conversionString topology (D) Energies 05 03736 i004Each string is connected to a DC/DC boost converters and then to a common grid-connected inverter. All the converters are usually packaged in a single element and localized in the same place.
-
Mismatching losses are reduced;
-
String diodes are not necessary;
-
High cable voltage drop and losses;
-
Cost effective solution because it uses only one inverter with constant input DC voltage.
Modular topology (DC Modular) (E) Energies 05 03736 i005DC/DC converters with MPPT algorithm are incorporated in each PV module. The DC/AC inverter is placed at the point of coupling with the electrical grid.
-
Significant reduction of mismatching losses;
-
String diodes are not necessary;
-
The voltage drop and cable power losses are reduced;
-
Lower cost solution than the AC modular configuration.
String distributed conversion architecture (F) Energies 05 03736 i006The PV sub‑fields are connected to the dc bus through small size DC/DC converters, equipped with MPPT algorithm, placed closed to the PV panels. The DC/AC inverter is placed at the point of coupling with the electrical grid.
-
Reduction of mismatching losses;
-
String diodes are not necessary;
-
The voltage drop and power losses in the cables are reduced due to high values used for the DC bus voltage;
-
The DC/DC boost converters can operate in a wider PV voltage range with respect to inverters;
-
Higher efficiency of the overall system.

3. Proposed Layout of the PV Plant

In this paper, a large size PV plant with three strings in parallel has been considered in two different grid configurations. The first configuration, shown in Figure 1, represents the proposed distributed layout (F) where the DC/DC converters are placed close to each PV string and upstream of the DC cable. The second configuration, shown in Figure 2, is the concentrated layout (D) where the DC/DC converters are installed near the DC/AC inverter and downstream the DC distribution grid. The major difference between the two configurations is the location of the DC/DC boost converters, while the control logic of the various converters remains the same.
Figure 1. Layout of PV plant with double-stage separated conversion [(F) configuration].
Figure 1. Layout of PV plant with double-stage separated conversion [(F) configuration].
Energies 05 03736 g001
Figure 2. Layout of PV plant with double-stage concentrated conversion ((D) configuration).
Figure 2. Layout of PV plant with double-stage concentrated conversion ((D) configuration).
Energies 05 03736 g002
Table 2 reports the main parameters of the considered system. The conducted simulations investigate the voltage drop in the DC grid to evaluate the efficiency of DC distribution system. For a DC cable, characterized by the resistance r, the p.u. power losses are equal to the p.u. voltage drop and can be expressed as:
P p . u . = P P n = r · I n 2 V n · I n = r · I n V n = V V n = V p . u .
For each configuration, the voltage drop along the DC cable lines is evaluated as a function of cable length, i.e., the distance between the PV panels and the grid-connected inverter. The power generated by the PV array is considered constant. The simulation results are illustrated in Figure 3. From the simulation results shown in Figure 3, it can be seen that the voltage drop, and hence the power losses, are always lower in the proposed distributed configuration (F) than in the concentrated configuration (D). The results reveal that, in concentrated configuration (D), the power losses in the DC grid increase linearly with the cable length, because the absorbed current by the DC/DC boost converters is constant.
Table 2. Main parameters for the PV system used in the simulation.
Table 2. Main parameters for the PV system used in the simulation.
ParametersValue
Rated power (kW)80
DC distribution voltage (V)700
PV string voltage (V)500
Cable cross section (mm2)16
Cable resistance (Ω/km)1.21
Figure 3. Voltage drop along the DC cable for the proposed distributed layout (F) and for the concentrated architecture layout (D), function of cable length.
Figure 3. Voltage drop along the DC cable for the proposed distributed layout (F) and for the concentrated architecture layout (D), function of cable length.
Energies 05 03736 g003
In the distributed configuration (F), the DC/DC boost converter output voltage increases with the cable length due to the DC voltage drop and because the inverter input voltage is kept constant by its control logic. Hence, the injected current in the DC grid decreases because the output power is constant. Therefore, the power losses and voltage drop are less then linearly dependent on the cable length.
The efficiency of the analyzed configurations is affected by the different locations of the measurements delivering the inputs for the MPPT algorithm. In the concentrated configuration (D), the measurements are undertaken downstream of the DC line. The algorithm does not optimize the energy produced by the PV, but considers the set composed by the PV and DC line. In this case, the optimization of each objective (maximum PV energy and minimum cable losses) cannot be achieved. In the proposed distributed configuration (F), each objective can be optimized separately. The energy produced by the PV is maximized by the MPPT algorithm, while the cable power losses are minimized through a suitable cable design [16] and keeping the DC voltage as high as possible.
In the distributed configuration, the higher DC voltage allowed by the DC/DC converters, and consequently the lower current, decreases the power losses and the voltage drop. In the concentrated architecture the distribution voltage is smaller and variable as a function of the temperature, solar radiation and the available power.
Another important conclusion of the steady state analysis is that the advantages of a distributed configuration are greater for large and extended power plants (>100 kW) than smaller ones. This is also intuitive because many small concentrated plants tend to a large distributed one. It is possible to conclude that the distributed architecture allows a better exploitation of the solar energy especially in large power plant characterized by different irradiation of the PV panels.

4. Leakage Currents to the Ground and Protection Systems

The PV system was modeled using the EMTP‑ATP software. The model considers two or more DC/DC boost converters, a DC distribution grid, and one grid-connected DC/AC inverter. The DC cable is modeled using the series and shunt parameters to evaluate the current drawn to the ground due to the converter switching. The model has been improved step by step to reach a more realistic configuration. A first model considers the DC cable downstream the DC/DC boost converter and upstream the inverter characterized by its resistance Rline = rlineLline. To size the cable cross-section, the line current as a function of the characteristics and number of DC/DC boost converters for the settled DC voltage of 700 V must be determined.
The total power of the considered DC/DC boost converters is 80 kW and the line current is 114.3 A. The cable cross-section is 35 mm2 and the resistance is rline = 0.55 Ω/km. In case of a cable with a length of 500 m (Rline = 0.275 Ω) and a 80 kW DC/DC boost converter connected at the beginning of the cable, the waveform of DC line voltage at the converter output is shown in Figure 4.
Figure 4. Variation of DC voltage for a cable with a length of 500 m, in proximity of the steady-state condition.
Figure 4. Variation of DC voltage for a cable with a length of 500 m, in proximity of the steady-state condition.
Energies 05 03736 g004
Voltage waveform has trapezoidal shape with amplitude between 700 V and 703 V. These oscillations appear due to the influence of DC cable. The DC cable is not affecting the inverter’s voltage as its value is constant and fixed by the inverter itself. Changing the line length (lline = 2 km and hence Rline = 1.1 Ω), the variation of DC line voltage is illustrated in Figure 5. As it can be observed, the voltage variations have higher amplitude due to the larger voltage drops. The voltage and current harmonics drawn to ground through the capacitances are evaluated. Two DC/DC boost converters operating at different switching frequencies are considered. The case studied is shown in Figure 6. Every DC/DC boost converter realizes the DC/DC conversion in order to adapt the PV voltage to the DC voltage, exploiting the maximum power available from the PV system.
Figure 5. Variation of DC voltage for a cable with a length of 2 km, in proximity of the steady-state condition.
Figure 5. Variation of DC voltage for a cable with a length of 2 km, in proximity of the steady-state condition.
Energies 05 03736 g005
Figure 6. EMTP/ATP implementation of the case studied, with line models based on π circuit.
Figure 6. EMTP/ATP implementation of the case studied, with line models based on π circuit.
Energies 05 03736 g006

4.1. Two DC/DC Boost Converters of 40 kWp Each, Interfaced to the 500 m DC Line Through 150 m Long Cables

The simulations consider a DC bus main connection represented through the π model, in which the longitudinal parameter is the resistance and the transversal one is the capacitance with the relative resistance in series. The adopted values are reported in Table 3.
Table 3. Main parameters for each DC/DC boost converter and for the DC bus.
Table 3. Main parameters for each DC/DC boost converter and for the DC bus.
ParameterValue
PI controller proportional gain kp0.09
PI controller integral gain ki1.7
Switching frequency fsw2000
Switching inductance L (mH)60
DC/DC boost converter’s cable length lcable_converter (m)150
DC Bus parameters
Resistance Rcable_DC/DC boost converter (Ω)0.1815
Line length lline (m)500
Resistance Rline (Ω)0.275
Line capacitance cline (pF/m)277
Capacitance Cline (μF)0.138
The variation of DC line voltage is shown in Figure 7, while Figure 8 illustrates the variation of the current drawn to ground through the capacitance C1. This represents the worst case, as IC1 is the capacitive current that is the most influenced by the vicinity of the DC/DC boost converter.
The voltage oscillations are 7 V, while the currents drawn to ground do not exceed 50 mA. The high frequency currents can generate malfunctions of the system differential relays. The DC line voltage is composed of the DC component and harmonics which can interfere with the telecommunication systems. The most relevant harmonics are the tenth (20,000 Hz), the twentieth (40,000 Hz) for the considered converter with 2 kHz switching frequency. Performing the same analysis on the capacitive currents, the highest value founded, considering the current IC1, is 1.4 mA.
Figure 7. Variation of DC voltage.
Figure 7. Variation of DC voltage.
Energies 05 03736 g007
Figure 8. Variation of the current drawn to ground through the capacitance C1.
Figure 8. Variation of the current drawn to ground through the capacitance C1.
Energies 05 03736 g008
A possible solution to reduce the voltage and current harmonics amplitude is to install an RC filter after the DC/DC boost converter, but before the DC line. For example, simulating the filter insertion, the harmonic at 2000 Hz, that was equal to 2.8 V (without filter), is now equal to 0.30 V. Therefore the voltage behavior will be less rugged (performing the differential protections functioning) but it will have a slower dynamic due to the capacitance introduced that affects the time constant of the system. In Figure 9, a comparison between the C1 current spectrum without (Figure 9a) and with (Figure 9b) filter is reported. Considering the high frequency currents drawn to ground through the line capacitors, it is possible to conclude that the RC filters use after the DC/DC boost converters improves the situation with less problems for the differential protections.
Figure 9. (a) The C1 current spectrum without filter; (b) The C1 current spectrum with filter.
Figure 9. (a) The C1 current spectrum without filter; (b) The C1 current spectrum with filter.
Energies 05 03736 g009

4.2. Two DC/DC Boost Converters of 40 kWp Each, Interfaced to the 2 km DC Line through 150 m Long Cables

The following simulations consider the values reported in Table 4. It is easy to note in Figure 10 that the peak value of the DC line voltage is higher than the previous case (706 V for l = 500 m; 718 V for l = 2000 m) but the oscillation are minor thank to the filters introduction. Consequently, the currents drawn to ground through the capacitances are less.
Table 4. Main parameters for each DC/DC boost converter and for the DC bus.
Table 4. Main parameters for each DC/DC boost converter and for the DC bus.
ParameterValue
PI controller proportional gain kp0.09
PI controller integral gain ki1.7
Switching frequency fsw2000
Switching inductance L (mH)60
DC/DC boost converter's cable length lcable_converter (m)150
Resistance Rcable­DC/DC boost converter (Ω)0.1815
DC Bus parameters
Line length lline (m)2000
Resistance Rline (Ω)1.1
Line capacitance cline (pF/m)277
Capacitance Cline (μF)0.554
Figure 10. DC line voltage (two parallel DC/DC boost converters).
Figure 10. DC line voltage (two parallel DC/DC boost converters).
Energies 05 03736 g010
Performing the same frequency analysis of the previous case, the harmonics in the voltage waveform are at the switching frequency of the two converters and at their multiples. The amplitude values are increased due to the longest line that means higher values of the DC/DC boost converter voltage and, therefore, higher harmonics amplitude. The same is for the currents drawn to ground through the capacitances. The value of the tenth harmonic is now 0.66 mA (respect to the 0.21 mA of the previous case). In conclusion, it is possible to deduce that the most the voltage oscillates (closest to the DC/DC boost converter), the highest is the value of the current drawn to ground and therefore its harmonics.

4.3. Two DC/DC Boost Converters of 40 kWp Each, with Different Switching Frequencies, Interfaced to the 2 km DC Line through 150 m Long Cables

The following simulations consider the values reported in Table 5. It is interesting to observe what happens if the switching frequencies of the two DC/DC boost converters is not the same. In order to consider the most general case, two not multiple frequencies are chosen. Always for synthesis reason, only the case with filters is here reported. The adopted values are reported in the following.
Table 5. Main parameters for each DC/DC boost converter and for the DC bus.
Table 5. Main parameters for each DC/DC boost converter and for the DC bus.
ParameterValue
PI controller proportional gain kp0.09
PI controller integral gain ki1.7
Switching frequency DC/DC boost converter #1 fsw2300
Switching frequency DC/DC boost converter #2 fsw2700
Switching inductance L (mH)60
DC/DC boost converter's cable length lcable_converter (m)150
Resistance Rcable_DC/DC boost converter (Ω)0.1815
DC Bus parameters
Line length lline (m)500
Resistance Rline (Ω)0.275
Line capacitance cline (pF/m)277
Capacitance Cline (μF)0.138
The DC line voltage and the capacitive currents to ground behaviors have strong deformations in their waveforms (Figure 11 and Figure 12). This is due to the different switching frequency of the converters that leads to beating frequencies that distorter the signal.
Figure 11. DC line voltage (two parallel DC/DC boost converters).
Figure 11. DC line voltage (two parallel DC/DC boost converters).
Energies 05 03736 g011
Figure 12. Current drawn to ground through the capacitance C1.
Figure 12. Current drawn to ground through the capacitance C1.
Energies 05 03736 g012
The voltage is constituted by a DC component equal to 704 V and a harmonics series. The frequency considered for the frequency analysis is 100 Hz (Figure 13).
Figure 13. DC line voltage spectrum (two parallel DC/DC boost converters).
Figure 13. DC line voltage spectrum (two parallel DC/DC boost converters).
Energies 05 03736 g013
The highest harmonics are the 23th and the 27th that are the switching frequencies and their influence decreases with the growth of the harmonic order. Regarding the capacitive currents, their harmonic values are very low due to the filter insertion.

5. Experimental Results

The theoretical analysis above described has been tested on a small-scale prototype available in the Solar Tech laboratory of the Politecnico di Milano equipped with different PV module typologies. A picture of the employed system is reported in Figure 14a, while Figure 14b represents the weather station. The DC/AC converter employed in this study is constituted by an input DC/DC stage that performs the MPPT, a middle stage with high frequency transformer for network insulation, a bulk capacitor and an output DC/AC stage. The PV prototype system has been tested in a clear sunny day with an oscilloscope and a voltage and current probes (Figure 15). The PV arrays generate DC current equal to 5.75 A and it has been interfaced to the AC distribution system in pure sinusoidal voltage condition (Figure 16). In particular the DC voltage respect to the ground has been measured (Figure 17a). The carried out measurements confirm the above simulations in which repetitive spikes are overlapped to the DC ripple due to the inverter switching. In particular, a zoom of the spikes is depicted in Figure 17b.
Figure 14. (a) Solar Tech Lab of the Politecnico di Milano, Italy; (b) Weather station of the Solar Tech Lab.
Figure 14. (a) Solar Tech Lab of the Politecnico di Milano, Italy; (b) Weather station of the Solar Tech Lab.
Energies 05 03736 g014
Figure 15. Measurement setup of the DC current generated by the PV arrays.
Figure 15. Measurement setup of the DC current generated by the PV arrays.
Energies 05 03736 g015
Figure 16. Input AC sinusoidal voltage.
Figure 16. Input AC sinusoidal voltage.
Energies 05 03736 g016
Figure 17. (a) Positive pole to ground voltage; (b) Particular of the DC voltage spikes.
Figure 17. (a) Positive pole to ground voltage; (b) Particular of the DC voltage spikes.
Energies 05 03736 g017
The experimental measurements confirm that transient phenomena can occur in the floating DC section and in more powerful PV plant they can cause untimely trip protection or other disturbances in the main system.
Other measurements have been performed in order to evaluate all the system conditions. Firstly, the DC to ground voltage has been zoomed and compared with the DC current (Figure 18). As it can be seen, this voltage contains a sinusoidal ripple at 200 kHz mainly due to the natural oscillation frequency between the connection DC cables and the input EMI filter. This oscillation is maintained by the high switching frequency of the DC/DC converter. In this range of frequencies the DC current appears constant.
Subsequently, the DC current variations have been analyzed. In Figure 19a it is possible to observe a current ripple similar to those one previously simulated and reported in Figure 12 due to the switching of the input DC/DC stage. Instead, Figure 19b shows the current oscillation caused by the MPPT algorithm that continues to vary the DC power in order to maintain the maximum power operating point with changing atmospheric conditions.
Figure 18. (a) DC to ground voltage oscillation (cyan trace) and DC current (yellow trace); (b) Particular of the DC voltage ripple.
Figure 18. (a) DC to ground voltage oscillation (cyan trace) and DC current (yellow trace); (b) Particular of the DC voltage ripple.
Energies 05 03736 g018
Figure 19. (a) DC to ground voltage (cyan trace) and DC current (yellow trace); (b) Particular of the DC current oscillation due to MPPT.
Figure 19. (a) DC to ground voltage (cyan trace) and DC current (yellow trace); (b) Particular of the DC current oscillation due to MPPT.
Energies 05 03736 g019

6. Conclusions

The paper presents a new distributed architecture for DC/DC converters to interface the PV panels with the DC system. This architecture has been compared with other layouts, including concentrated ones. The main idea is to create a DC distribution grid to which the PV arrays in big power plants are connected through DC/DC converters located near them. The interface with the public grid is provided by one or more DC/AC inverters that keep constant the DC voltage at their input. The main advantages of this configuration, related to the greater efficiency due to the higher voltage DC distribution, to the better exploitation of the solar source and to the modularity of the system together with the analysis of voltage drops and power losses in the DC cables are discussed. This paper, thanks to a dedicated model, has analyzed the problem of the currents drawn to ground for the effect of the switching of the various converters in order to prevent untimely trip of the differential protection. The simulations carried out have shown that the problem of the currents drawn to ground depends from the topology of the plant, particularly from the plant extension and from the connected converter type. Experimental results on a small scale prototype confirm the developed theoretical analysis. From the results obtained it is possible to conclude that the proposed configuration is interesting also for the decrease of the effect of the switching of the various converters that can lead untimely trip of the differential protection.

References

  1. Suntio, T.; Leppaaho, J.; Huusari, J.; Nousiainen, L. Issues on solar generator interfacing with current-fed MPP-tracking converters. IEEE Trans. Power Electron. 2010, 25, 2409–2419. [Google Scholar] [CrossRef]
  2. Blaabjerg, F.; Chen, Z.; Kjaer, S.B. Power electronics as efficient interface in dispersed power generation systems. IEEE Trans. Power Electron. 2004, 19, 1184–1194. [Google Scholar] [CrossRef]
  3. Kjaer, S.B.; Pedersen, J.K.; Blaabjerg, F. A review of single-phase grid-connected inverters for photovoltaic modules. IEEE Trans. Ind. Appl. 2005, 41, 1292–1306. [Google Scholar] [CrossRef]
  4. Carrasco, J.M.; Franquelo, L.G.; Bialasiewicz, J.T.; Galvan, E.; Portillo Guisado, R.C.; Prats, M.A.M.; Leon, J.I.; Moreno-Alfonso, N. Power-electronic systems for the grid integration of renewable energy sources: A survey. IEEE Trans. Ind. Electron. 2006, 53, 1002–1016. [Google Scholar] [CrossRef]
  5. Blaabjerg, F.; Teodorescu, R.; Liserre, M.; Timbus, A.V. Overview of control and grid synchronization for distributed power generation systems. IEEE Trans. Ind. Electron. 2006, 53, 1398–1409. [Google Scholar] [CrossRef]
  6. Escobar, G.; Mattavelli, P.; Stankovic, A.M.; Valdez, A.A.; Leyva-Ramos, J. An adaptive control for UPS to compensate unbalance and harmonic distortion using a combined capacitor/load current sensing. IEEE Trans. Ind. Electron. 2007, 54, 839–847. [Google Scholar] [CrossRef]
  7. Mastromauro, R.A.; Liserre, M.; Kerekes, T.; Dell’Aquila, A. A single-phase voltage controlled grid connected photovoltaic system with power quality conditioner functionality. IEEE Trans. Ind. Electron. 2009, 56, 4436–4444. [Google Scholar] [CrossRef]
  8. Ueda, Y.; Kurokawa, K.; Tanabe, T.; Kitamura, K.; Sugihara, H. Analysis results of output power loss due to the grid voltage rise in grid-connected photovoltaic power generation systems. IEEE Trans. Ind. Electron. 2008, 55, 2744–2751. [Google Scholar] [CrossRef]
  9. Carpenter, R.B.; Auer, R.L. Lightning and surge protection of substations. IEEE Trans. Ind. Appl. 1995, 31, 162–170. [Google Scholar] [CrossRef]
  10. Yinger, R.J.; Venkata, S.S.; Centeno, V.A. Southern California Edison’s advanced distribution protection demonstrations. IEEE Trans. Smart Grid 2012, 3, 1012–1019. [Google Scholar] [CrossRef]
  11. Ciobotaru, M.; Agelidis, V.G.; Teodorescu, R.; Blaabjerg, F. Accurate and less-disturbing active anti islanding method based on PLL for grid connected converters. IEEE Trans. Power Electron. 2010, 25, 1576–1584. [Google Scholar] [CrossRef]
  12. Petrone, G.; Spagnuolo, G.; Teodorescu, R.; Veerachary, M.; Vitelli, M. Reliability issues in photovoltaic power processing systems. IEEE Trans. Ind. Electron. 2008, 55, 2569–2580. [Google Scholar] [CrossRef]
  13. Freijedo, F.D.; Doval-Gandoy, J.; Lopez, O.; Acha, E. A generic open-loop algorithm for three-phase grid voltage/current synchronization with particular reference to phase, frequency, and amplitude estimation. IEEE Trans. Power Electron. 2009, 24, 94–107. [Google Scholar] [CrossRef]
  14. Brenna, M.; Lazaroiu, G.C.; Superti-Furga, G.; Tironi, E. Premium power quality with DG integrated DC systems. In Proceedings of IEEE Bucharest PowerTech: Innovative Ideas Toward the Electrical Grid of the Future, Bucharest, Romania, 28 June–2 July 2009; pp. 1–6.
  15. Serban, E.; Serban, H. A control strategy for a distributed power generation microgrid application with voltage and current-controlled source converter. IEEE Trans. Power Electron. 2010, 25, 2981–2992. [Google Scholar] [CrossRef]
  16. Maki, A.; Valkealahti, S. Power losses in long string and parallel-connected short strings of series-connected silicon-based photovoltaic modules due to partial shading conditions. IEEE Trans. Energy Convers. 2012, 27, 173–183. [Google Scholar] [CrossRef]
  17. Petrone, G.; Spagnuolo, G.; Vitelli, M. Analytical model of mismatched photovoltaic fields by means of Lambert W-function. Sol. Energy Mater. Sol. Cells 2007, 91, 1652–1657. [Google Scholar] [CrossRef]
  18. Sahan, B.; Araujo, S.V.; Kirstein, T.; Menezes, L.; Zacharias, P. Photovoltaic converter topologies suitable for SiC-JFETs. In Proceedings of European Conference Power Conversion and Intelligent Motion (PCIM 2009), Nuremberg, Germany, 12–14 May 2009; pp. 431–437.
  19. Mao, X.; Ayyanar, R.; Krishnamurthy, H.K. Optimal variable switching frequency scheme for reducing switching loss in single-phase inverters based on time-domain analysis. IEEE Trans. Power Electron. 2009, 24, 991–1001. [Google Scholar] [CrossRef]
  20. Simonov, M.; Mussetta, M.; Grimaccia, F.; Leva, S.; Zich, R.E. Artificial intelligence forecast of PV plant production for integration in smart energy systems. Int. Rev. Electr. Eng. 2012, 7, 3454–3460. [Google Scholar]
  21. Lu, D.D.-C.; Agelidis, V.G. Photovoltaic-battery-powered DC bus system for common portable electronic devices. IEEE Trans. Power Electron. 2009, 24, 849–855. [Google Scholar] [CrossRef]
  22. Faranda, R.; Leva, S.; Maugeri, V. MPPT Techniques for PV Systems: Energetic and Cost Comparison. In Proceedings of IEEE Power and Energy Society General Meeting—Conversion and Delivery of Electrical Energy in the 21st Century, Pittsburgh, PA, USA, 20–24 July 2008; pp. 1–6.
  23. Dolara, A.; Grimaccia, F.; Leva, S.; Mussetta, M.; Faranda, R.; Gualdoni, M. Performance analysis of a single-axis tracking PV system. IEEE J. Photovolt. 2012, 2, 524–531. [Google Scholar] [CrossRef]
  24. Locment, F.; Sechilariu, M.; Houssamo, I. DC load and batteries control limitations for photovoltaic systems. Experimental validation. IEEE Trans. Power Electron. 2012, 27, 4030–4038. [Google Scholar] [CrossRef]
  25. Miyatake, M.; Veerachary, M.; Toriumi, F.; Fujii, N.; Ko, H. Maximum power point tracking of multiple photovoltaic arrays: A PSO approach. IEEE Trans. Aerosp. Electron. Syst. 2011, 47, 367–380. [Google Scholar] [CrossRef]
  26. Mastromauro, R.A.; Liserre, M.; Dell’Aquila, A. Control issues in single-stage photovoltaic systems: MPPT, current and voltage control. IEEE Trans. Ind. Inform. 2012, 8, 241–254. [Google Scholar] [CrossRef]

Share and Cite

MDPI and ACS Style

Brenna, M.; Dolara, A.; Foiadelli, F.; Lazaroiu, G.C.; Leva, S. Transient Analysis of Large Scale PV Systems with Floating DC Section. Energies 2012, 5, 3736-3752. https://doi.org/10.3390/en5103736

AMA Style

Brenna M, Dolara A, Foiadelli F, Lazaroiu GC, Leva S. Transient Analysis of Large Scale PV Systems with Floating DC Section. Energies. 2012; 5(10):3736-3752. https://doi.org/10.3390/en5103736

Chicago/Turabian Style

Brenna, Morris, Alberto Dolara, Federica Foiadelli, George C. Lazaroiu, and Sonia Leva. 2012. "Transient Analysis of Large Scale PV Systems with Floating DC Section" Energies 5, no. 10: 3736-3752. https://doi.org/10.3390/en5103736

Article Metrics

Back to TopTop