Next Article in Journal
A Study on Development of a Cost Optimal and Energy Saving Building Model: Focused on Industrial Building
Next Article in Special Issue
On Scalability and Replicability of Smart Grid Projects—A Case Study
Previous Article in Journal
Measuring the Actual Energy Cost Performance of Green Buildings: A Test of the Earned Value Management Approach
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

An Improved Current Control Strategy for a Grid-Connected Inverter under Distorted Grid Conditions

Department of Electrical and Information Engineering, Seoul National University of Science and Technology, 232 Gongneung-ro, Nowon-gu, Seoul 139-743, Korea
*
Author to whom correspondence should be addressed.
Energies 2016, 9(3), 190; https://doi.org/10.3390/en9030190
Submission received: 13 November 2015 / Revised: 4 December 2015 / Accepted: 7 March 2016 / Published: 12 March 2016

Abstract

:
This paper presents an improved current control strategy for a three-phase grid-connected inverter under distorted grid conditions. The main challenge associated with the grid-connected inverter in distributed generation (DG) systems is to maintain the harmonic contents in output current below the specified values even when the grid is subject to uncertain disturbances such as harmonic distortion. To overcome such a challenge, an improved current control scheme is proposed for a grid-connected inverter, in which the fundamental and harmonic currents are independently controlled by a proportional-integral (PI) decoupling controller and a predictive basis controller, respectively. The controller design approach is based on the model decomposition method, where the measured inverter currents and grid voltages are divided into the fundamental and harmonic components by means of moving average filters (MAFs). Moreover, to detect the angular displacement and angular frequency with better accuracy, even in the presence of the grid disturbance, the MAF is also introduced to implement an enhanced phase-lock loop (PLL) structure. Theoretical analyses as well as comparative simulation results demonstrate that the proposed control scheme can effectively compensate the uncertainties caused by the grid voltages with fast transient response. To validate the feasibility of the proposed scheme, the whole control algorithms are implemented on 2 kVA three-phase grid-connected inverter system using 32-bit floating-point DSP TMS320F28335. As a result, the proposed scheme is an attractive way to control a grid-connected inverter under adverse grid conditions.

Graphical Abstract

1. Introduction

Three-phase grid-connected inverters have been widely employed in various applications, including renewable power generation and regenerative energy systems. This is due to the recent development trend constructing the electrical grid in terms of distributed generation (DG) systems, in which grid-connected inverters are connected in parallel with each other to form a microgrid [1,2]. The essential functionality of microgrids is to have the ability to operate either in grid-connected or autonomous mode in case of the absence of the main grid. Another requirement is to handle effectively the exchange of active and reactive power between the microgrid and main grid [3,4]. In order to fulfill the aforementioned criteria, the control strategy of a microgrid is generally designed based on three levels of hierarchical structure to provide smartness and flexibility to microgrid, which includes the primary control, the secondary control, and the tertiary control [5]. To follow the development trend of the microgrid, the grid-connected inverter should be able to not only provide stable operation but also improve the system performance even during the presence of abnormal grid conditions. In general, the current control loop, which belongs to the primary control, is responsible for the quality of the exchanging power. According to the recently published utility interface standard regarding DG systems [6,7], the harmonic contents in the injected current need to meet certain current-distortion levels in order to guarantee the power quality as well as fulfill interconnection requirements. Consequently, the current control loop should be designed to ensure the effective operation of the grid-connected inverter under any operating conditions of grid.
The PI controller has been widely used as current controller in variety of inverter applications because of its simplicity and stability. The design and implementation of this controller are quite straightforward in continuous as well as in discrete-time domain [8]. Furthermore, low computational burden of this control algorithm makes it easier to implement the whole control system with only one digital signal controller. However, despite these advantages, the PI controllers have the limitations that they are unable to cope with sinusoidal reference signals and periodic disturbances [9]. Although the sinusoidal tracking problem can be completely solved by implementing the controller in the synchronously rotating reference frame, poor disturbance rejection capability makes the PI type controller unsuitable for current control strategy of a grid-connected inverter in the presence of the distorted grid voltages.
For the purpose of eradicating the harmonics from inverter currents, several control approaches have been proposed, which is categorized as selective and non-selective methods [10]. Proportional resonant (PR) controller is widely used as selective harmonic compensation scheme [11]. This controller is often implemented in the stationary reference frame and the resonant term is added to the main controller to suppress the harmonic component in the specific order. However, since this method requires separate resonant terms to compensate each harmonic component, this approach is usually considered to alleviate only a few harmful low order harmonics. When the numbers of resonant terms increase, the control structure becomes complicated or even impractical.
Other approaches to eliminate the harmonics from inverter current use nonlinear control techniques such as the sliding mode control (SMC) [12], predictive control [13], or repetitive control [14]. These control strategies are often referred as non-selective method since the controllers work in wide range of frequency, in contrast to the selective method that only regulates the harmonics in some specified orders. By using such nonlinear controllers, the distorted level of inverter current can be mitigated even under the distorted grid voltages. However, the design task of a robust controller based on above techniques usually makes the system structure complicated because of the remaining problems related to those techniques such as the chattering problem in SMC, parameter sensitive in predictive control, slow dynamic response in repetitive control and so on. Furthermore, the practical complexity of nonlinear controller may degrade the performance of the controlled system. As another approach, a neural-network-based waveform processing and filtering scheme has been reported to reshape voltage or current waveforms [15]. However, this algorithm generally requires lots of computations to be processed in real time, which increases the computational burden of main controller. Moreover, offline training is often required in this method.
Recently, a sliding mode harmonic compensation strategy based on the system model decomposition has been reported to reduce the harmful effects caused by the nonlinear controller [16]. In this work, the system model is first divided into two using the fundamental and harmonic components. Using two decomposed models, the controllers are separately designed, that is, the controller for the fundamental term by the conventional decoupling controller and the harmonic suppression controller by SMC. To decompose the grid voltages and inverter currents into the fundamental and harmonic components, the fourth-order band pass filters (BPFs) have been employed in the harmonic extractors. As reported in [16], even though the steady-state current responses can be quite improved with reduced chattering by adopting the decomposed model, the inverter system exhibits a slow transient response due to the sluggish dynamic characteristics of the BPF. Moreover, the slow response of the BPF may even cause the instability problem during transient duration.
In addition to current controller, the phase lock loop (PLL) also influences on the inverter currents under the distorted grid voltages. Indeed, the conventional synchronous reference frame phase lock loop (SRF-PLL) algorithm integrated with a PI controller to determine the angular displacement of grid voltage is unable to cope with high frequency disturbances due to the limitation of the PI controller. Consequently, the high frequency uncertainty caused by the distorted grid voltages has a profound effect on the determination of the angular displacement of grid voltages. The effects of distorted grid on PLL can be alleviated by reducing the PLL bandwidth. However, this results in slow dynamic response in PLL, which means that the PLL cannot track the angular displacement of grid voltages rapidly. Recent studies have proved the effectiveness of the moving average filter basis PLL (MAF-PLL) under the distorted grid voltages [17,18]. The main concept of the MAF-PLL is to use the MAF as an ideal low pass filter (LPF) to remove the sinusoidal components in the synchronous reference frame before the measured grid voltages are processed in PLL algorithm.
The main objective of this paper is to present a robust current control scheme for a three-phase grid-connected inverter under abnormal grid conditions like the distorted grid. The proposed control strategy is based on the system model decomposition, in which the fundamental and harmonic current controllers are designed separately. Whereas the synchronous PI decoupling controller is employed to control the fundamental current component, a predictive basis compensator is introduced to suppress the harmonic components in inverter currents. For this purpose, the harmonic contents are extracted by means of the MAFs. Furthermore, an MAF-PLL is employed to improve the detecting performance of the conventional SRF-PLL. Also, a simple modification method to improve the transient current response is presented by changing the q-axis and d-axis harmonic currents only during the transient period of the MAF. As a result, the proposed control scheme can effectively control a grid-connected inverter during steady-state as well as transient periods even under the distorted grid voltages.
This paper is organized as follows: Section 2 presents the mathematical system model as well as the decomposition method. Section 3 describes the proposed control scheme composed of the PI decoupling controller, MAF-based harmonic extractor, MAF-PLL, and the predictive basis harmonic compensator. Simulation results are presented in Section 4. Afterwards, the experimental results are provided in Section 5. Finally, the conclusions are given in Section 6.

2. Modeling of a Grid-Connected Inverter

Figure 1 shows a whole configuration of three-phase grid-connected inverter with an L filter. The analyses for current controller in inverter with an L filter are still valid for the case with LCL filter as long as the control bandwidth is kept below resonant frequency of LCL filter [19]. Considering the filter inductance of L and the filter resistance of R, the voltage equations of a grid-connected inverter are expressed in the synchronous reference frame as follows:
v q = R i q + L d i q d t + ω L i d + e q
v d = R i d + L d i d d t ω L i q + e d
where i q and i d are the q-axis and d-axis inverter currents, respectively; e q and e d are the q-axis and d-axis grid voltages, respectively; v q and v d are the q-axis and d-axis inverter output voltages, respectively; and ω is the grid angular frequency.
When phase voltages and currents include harmonic components, the transformed variables into the synchronous reference frame are not in pure direct current (DC)-quantity. Instead, they contain the harmonic components as well as DC-quantity. To apply the decomposition method, the voltage and current variables can be expressed with DC-quantity and sinusoidal harmonic terms as follows:
v q d = V q d + v q d h
i q d = I q d + i q d h
e q d = E q d + e q d h
where the capital letter V, I, and E denote the inverter voltages, inverter currents, and grid voltages having DC-quantity, respectively, the subscript “qd” denotes the variables on the q-axis and d-axis in the synchronous reference frame, the subscripts “h” denotes harmonic quantities.
The decomposed models for the voltage equations of a grid-connected inverter are derived by substituting Equations (3), (4), and (5) into Equations (1) and (2) as follows:
V q + v q h = R ( I q + i q h ) + L d ( I q + i q h ) d t + ω L ( I d + i d h ) + ( E q + e q h )
V d + v d h = R ( I d + i d h ) + L d ( I d + i d h ) d t ω L ( I q + i q h ) + ( E d + e d h )
Voltage equations in Equations (6) and (7) can be rewritten with respect to the DC-quantities and harmonic components as follows:
V q = R I q + L d I q s d t + ω L I d + E q
V d = R I d + L d I d d t ω L I q + E d
v q h = R i q h + L d i q h d t + ω L i d h + e q h
v d h = R i d h + L d i d h d t ω L i q h + e d h
For convenience, Equations (8) and (9) are referred to the fundamental voltage equations because they are obtained through the Park’s transformation of phase variables in the fundamental components. Similarly, Equations (10) and (11) are referred to the harmonic voltage equations.

3. Proposed Control Scheme

The issue on power quality of DG systems is one of most common interconnection requirements for grid-connected inverter basis generation systems, which is being presented in all standards. According to the published standards [6,7], the grid injected current should not have the total harmonic distortion (THD) greater than 5% in most of operating conditions. Although recently developed current controllers for grid-connected inverters including linear and non-linear schemes can fulfill the THD requirement in normal grid condition, the THD of inverter output current may exceed the limit during distorted grid voltages. The main purpose of the proposed control scheme is not only to fulfill the grid interface requirements but also to minimize the harmonic contents in grid injected currents.
Figure 2 shows the control block diagram of the proposed control scheme in which the three-phase inverter is connected to the grid through L filter. The overall system mainly consists of a three-phase inverter, a current controller, a predictive basis harmonic compensator, and MAFs, which are used for system model decomposition as well as performance improvement in PLL. The grid voltages and inverter currents are measured and then transferred into the variables on the synchronous reference frame using the Park’s transformation. The transformed grid voltages into the synchronous frame are first processed with the MAF to obtain pure DC-quantity without the harmonic distortion, and then, used in PLL algorithm to determine the angular displacement in grid voltage accurately. Similarly, the transformed currents into the synchronous frame are processed with the MAF to obtain DC-quantity. These voltages and currents in DC-quantity are subtracted from e q d and i q d to extract the harmonic components of e q d h and i q d h . The current controller is formed by combining a synchronous PI decoupling controller and a predictive controller, where the PI decoupling controller is employed to regulate the inverter currents to follow their references and referred as a main controller.
From the inverter voltage equations in Equations (1) and (2), the reference voltages are obtained from the PI decoupling controller as follows:
V q * = ( k p + k i s ) · ( i q * i q ) + ω L I d + E q
V d * = ( k p + k i s ) · ( i d * i d ) ω L I q + E d
where the symbol “*” denotes the reference quantity and, k p and k i are the proportional and integral gains of the PI controller, respectively.
In the discrete-time domain, the reference voltages in Equations (12) and (13) can be expressed at each sampling instant k as follows:
V q * ( k ) = k p · i q , e r r ( k ) + k i · i = 0 k i q , e r r ( i ) · T s + ω L I d ( k ) + E q ( k )
V d * ( k ) = k p · i d , e r r ( k ) + k i · i = 0 k i d , e r r ( i ) · T s ω L I q ( k ) + E d ( k )
where i q , e r r = i q * i q , i d , e r r = i d * i d , and Ts is the sampling period.

3.1. MAF and MAF-PLL

An MAF is employed as ideal LPF in the proposed control scheme, where the window length is chosen as one period of the fundamental grid voltage to retain the generality. However, the window length can be set to half of fundamental period in the case of the filtered variables are in the synchronous reference frame since the majority of the uncertainties in three-phase voltages are odd harmonics that become even harmonics in the synchronous reference frame.
The input–output relationship of the MAF can be described in continuous-time domain by
x o u t ( t ) = 1 T w t T w t x i n ( τ ) d τ
where Tw is the window length, x o u t ( t ) is the output signal, and x i n ( τ ) is the input signal. The continuous-time transfer function of the MAF can be obtained from Equation (16) as
G M A F ( s ) = x o u t ( s ) x i n ( s ) = 1 e T w s T w s
The transfer function in Equation (17) shows that the MAF only requires a time equal to its window length to reach the steady state. For a digital implementation, the transfer function of the MAF can be discretized from Equation (17) as
G M A F ( z ) = 1 N · 1 z N 1 z 1
where Tw = NTs with N equal to the number of samples in one window length (N must be an integer). From Equation (18), it can be observed that the MAF provides an effective solution in view of the computational burden as compared with the BPF. Moreover, since the MAF only requires one period of fundamental grid voltage for the filter output to converge, the dynamic response of the MAF-based harmonic extractor is much faster than that of the BPF-based harmonic extractor, which requires almost six periods of fundamental grid voltage to reach steady-state condition [16].
In practical implementation, the mismatch between the designed window length Tw and the value of NTs makes errors in amplitude and phase angle. This problem can be solved by using several proved techniques such as rounding of Tw/Ts to the nearest integer, weighted mean value approach [20], and linear interpolation [21]. In order to secure the calculating capability of main controller while retaining the errors within an acceptable value [17], the rounding scheme that adjusts Tw/Ts to the nearest integer is used in this paper. Thus, the number of samples in one window length N can be obtained as follows:
N = r o u n d ( T w T s )
where “ r o u n d ” denotes the round function which returns the nearest integral value.
In the grid-connected inverter system, the inverter needs to monitor the angular displacement of the grid voltage in order to synchronize the inverter currents with the grid. Generally, the SRF-PLL, which is based on the Park’s transformation and a low bandwidth PI controller, is commonly employed in three-phase grid-tied inverter systems. Under the distorted grid voltages, however, the angular displacement of grid voltage cannot be tracked exactly due to the inability of the PI controller to reject sinusoidal disturbances. As a result, the detected angular frequency of grid contains high order harmonics, which cause an increase of harmonic contents in inverter currents. As is illustrated in Figure 2, the filtered d-axis voltage is fed directly to the conventional SRF-PLL instead of the measured d-axis voltage.
The open loop transfer function of MAF-PLL can be obtained from Equation (17) and the conventional SRF-PLL as
G o l ( s ) = G M A F ( s ) * k p , p l l s + k i , p l l s 2
where k p , p l l and k i , p l l are the proportional and integral gains of the PI controller in the conventional SRF-PLL, respectively. By using the first-order Padé approximation [17], Equation (17) may be approximated as
G M A F ¯ ( s ) 1 T w 2 s + 1
Replacing G M A F ( s ) in Equation (20) by approximated term G M A F ¯ ( s ) in Equation (21), the transfer function in Equation (20) becomes
G M A F ¯ ( s ) 2 ( k p , p l l s + k i , p l l ) ( T w s + 2 ) s 2
From Equation (22), the approximated closed-loop transfer function of MAF-PLL can be described as
G c l ( s ) 2 k p , p l l T w s + 2 k i , p l l T w s 3 + 2 T w s 2 + 2 k p , p l l T w s + 2 k i , p l l T w
By using the MAF, which acts as an ideal LPF, to obtain DC-quantity of the d-axis grid voltage, the grid angular displacement can be detected accurately even when the grid voltages are highly distorted. In addition to mathematical analyses, the simulation and experimental results of MAF-PLL will be given in the following sections to demonstrate the performance of the designed filter as well as its effect on inverter currents.

3.2. Predictive Harmonic Compensator

The harmonic compensator, which is based on the predictive control, is also illustrated in Figure 2. The high frequency sinusoidal currents and voltages are extracted by means of the MAFs, and then, these values are used to form a predictive basis harmonic compensator. In the discrete-time domain, the harmonic voltage equations in Equations (10) and (11) can be described as
v q h ( k ) = R i q h ( k ) + L T s ( i q h ( k + 1 ) i q h ( k ) ) + ω L i d h ( k ) + e q h ( k )
v d h ( k ) = R i d h ( k ) + L T s ( i d h ( k + 1 ) i d h ( k ) ) ω L i q h ( k ) + e d h ( k )
In Equations (24) and (25), by replacing the currents at sampling instant ( k + 1 ) by the reference currents, the predictive control law to suppress the harmonic currents can be expressed as
v q h * ( k ) = R i q h ( k ) + L T s ( i q h * ( k ) i q h ( k ) ) + ω L i d h ( k ) + e q h ( k )
v d h * ( k ) = R i d h ( k ) + L T s ( i d h * ( k ) i d h ( k ) ) ω L i q h ( k ) + e d h ( k )
where i q h * ( k ) and i d h * ( k ) denote the q-axis and d-axis harmonic reference currents, respectively. These values should be set to zeros in order to eliminate the harmonic components in inverter output current.
From Equations (14), (15), (26), and (27) with i q h * ( k ) = i d h * ( k ) = 0 , the q-axis and d-axis inverter reference voltages of the proposed control scheme are represented as
v q * ( k ) = V q * ( k ) + v q h * ( k )
v d * ( k ) = V d * ( k ) + v d h * ( k )
As a result of using the decomposition model, the predictive basis harmonic compensator only has to deal with the harmonics model. Therefore, the problems associated with the parameters mismatch and time delay in the predictive control are highly reduced.

4. Simulation Results

To evaluate the performance of the proposed control scheme, the simulations have been done for three-phase grid-connected inverter using the PSIM software. Figure 3 shows the whole system configuration where the main controller is implemented with the PSIM dynamic link library (DLL) block. The system parameters are summarized in Table 1.
In addition to ideal grid voltages, the distorted grid voltages are used in order to evaluate the control performance in adverse operating conditions of the grid. For a distorted condition of grid voltage, the 5th and 7th harmonics with 20% of the fundamental component and the 11th and 13th harmonics with 10% of the fundamental component are added to the ideal grid voltages. The resultant three-phase grid voltages are shown in Figure 4, where the THD is 31.7%. In this figure, e a , e b , and e c denote three-phase grid voltages.
Figure 5 shows the performance comparison of dynamic responses between the BPF and MAF under the distorted grid voltages. As a result of harmonic distortion in grid voltages as shown in Figure 4, the q-axis and d-axis grid voltages e q and e d at the synchronous reference frame contain the harmonic components as well as DC-quantity. In Figure 5, e q , B P F and e d , B P F denote the filtered outputs processed with the BPF, respectively. On the other hand, e q , M A F and e d , M A F denote the filtered outputs processed with the MAF, respectively. It is easy to notice that the transient responses of the MAF are nearly five times faster than those of the BPF in extraction of DC-quantity, since the MAF only requires one window length to reach its steady state. Furthermore, by selecting the number of samples N to the nearest integer, the steady-state errors of the MAF can be lower than those of the fourth-order BPF (See the d-axis values).
Similarly, Figure 6 shows the comparison of dynamic responses to extracts DC-quantity between the BPF and MAF when the input signals are inverter currents. It is obvious that the transient response and steady-state error are much more improved by adopting the MAF, which results in the improvement of harmonic extraction.
As stated earlier, the obtained angular displacement and angular frequency from the conventional SRF-PLL are severely distorted under the distorted grid voltages because of the inability of the PI controller to reject high frequency disturbances. Figure 7 shows the waveforms for the angular frequency ω PLL and angular displacement θ determined by the conventional SRF-PLL. It is easy to notice that the angular frequency fluctuates around the fundamental value ω g r i d . Also, this fluctuation makes the obtained angular displacement θ distorted as is shown in Figure 7b. On the contrary, Figure 8 shows the simulation results for the MAF-PLL scheme under the distorted grid voltages. It can be clearly observed that the dynamic response of the MAF-PLL is comparable to that achieved by the SRF-PLL. The MAF-PLL, however, provides attractive steady-state response as a result of an excellent filtering capability of the MAF.
To highlight the effectiveness of the proposed control scheme, the comparative simulation results with the conventional control scheme for a grid-connected inverter are also presented. The conventional control scheme comprises a synchronous PI decoupling current controller and a SRF-PLL. In order to point out the weakness of the conventional control scheme, the simulation results both under the ideal and distorted grid voltages are shown in Figure 9 and Figure 10, in which i a , i b , and i c denote three-phase inverter currents. As can be observed from the output current waveforms in Figure 9, the conventional control scheme shows a good steady-state performance under the ideal grid voltages. In the abnormal grid conditions, however, the output current waveforms, illustrated in Figure 10, are highly distorted due to the poor sinusoidal disturbance rejection capability of the PI controller both in current controller and in PLL.
In addition to the results obtained using the conventional PI control scheme, the simulations have been carried out for another harmonic compensation approaches for comparison. Figure 11 shows the steady-state responses of the inverter currents using PR controller with different distorted grid conditions. To eliminate harmonic contents in inverter currents, only the resonant terms to compensate the 5th and 7th harmonics are added together with the fundamental controller. As shown in Figure 11a, the compensation works well when the grid disturbance only contains 5th and 7th harmonics. However, when the grid has the harmonic disturbance in other frequencies, the control performance of this scheme is degraded dramatically.
Another widely used compensation approach that employs nonlinear controller is the sliding mode control. As an illustration, Figure 12 shows the control performance under distorted grid conditions when the sliding mode control is employed for harmonic compensation. As stated earlier, this control scheme can guarantee a good steady-state performance of target system, as shown in Figure 12a. However, the chattering in control input signals is unavoidable as is observed in the waveforms of inverter reference voltages v q * and v d * in Figure 12b. Moreover, it is not easy to meet the trade-off between the transient responses and steady-state performance in designing the sliding mode controller.
Figure 13 shows the simulation results of the proposed control scheme under the same distorted grid voltages as Figure 10. In contrast to those in Figure 10, the phase current waveforms in Figure 13a still remain sinusoidal. Also, as can be observed in the q-axis and d-axis current waveforms in Figure 13b, the proposed control scheme gives nearly constant currents, which imply that phase currents have relatively low harmonic contents.
Despite the fact that the harmful disturbances in three-phase grid are mainly sinusoidal harmonics, any type of disturbance may occur in gird in extreme cases. Figure 14 shows the comparative current responses in the presence of random disturbances in three-phase grid voltages. Random values are generated as shown in Figure 14c and these values are added with grid voltages to generate random disturbances in three-phase. From the comparative simulation results between the proposed control scheme in Figure 14a and the conventional PI control scheme in Figure 14b, it is verified that the proposed control scheme is robust against even random disturbance in grid voltage.
Although low harmonic contents in inverter currents at steady state can be achieved even under the distorted grid voltages by using the proposed control scheme, the transient response of the proposed control scheme becomes worse than that of the conventional control scheme. The degradation in transient response is mainly caused by the phase delay of filters used for the harmonic extractor. Figure 15 shows the transient responses of the conventional control scheme, in which Figure 15a shows the waveforms of phase currents and Figure 15b shows the waveforms of the q-axis and d-axis currents with the q-aixs current reference i q * . As can be observed form Figure 15b, the conventional scheme responds rapidly to the change of reference currents. However, as is seen in Figure 16, the transient response of the proposed control scheme is relatively slow due to the delay introduced by the harmonic extractors. The transient response in Figure 16b is almost ten times slower than that of the conventional control scheme. This result is unacceptable to be used for a current control loop in DG systems because they are supposed to provide very fast response.
Even though the major advantage of using the MAF in the harmonic extractor over BPF or LPF is that the transient period introduced by filter is well reduced and predictable, this delay by the MAF should be compensated further in order to improve the transient performance of current controller. A compensation method for phase delay has been proposed in [18]. Although this method reduces the transient response of the MAF, the steady-state error is noticeably increased. By considering that the reference currents are generally obtained from the voltage control loop or droop control loop in grid-connected inverter systems, it is always possible to detect the change in reference currents. Based on this information, to improve the transient response of current control loop, the q-axis and d-axis harmonic currents i q h and i d h are temporally replaced during the transient period of the MAF with
i q h , t = i q I q *
i d h , t = i d I d *
where i q h , t and i d h , t are the approximated q-axis and d-axis harmonic currents based on the assumption that the fundamental currents can reach theirs reference values instantly.
Figure 17 shows the simulation results of the proposed control scheme with temporary replacement of the harmonic currents during the transient period of the MAF, which is one window length. In order to show the transient response of the proposed control scheme, the q-axis reference current is increased from 5 A to 10 A at t = 0.2 s, and then, decreased to 7 A at t = 0.3 s. As is clearly observed in Figure 17b, the q-axis current can reach its reference value immediately, while retaining good harmonic suppression characteristics in phase currents. Although the replacement of the harmonic currents during transient period of the MAF may increase harmonic contents in inverter current, the transient performance can be considerably improved. Moreover, the increase of the harmonic components in inverter currents can be negligible because it lasts during only one window length of the MAF.
Figure 18 shows the fast Fourier transform (FFT) result of a-phase current using the proposed control scheme under the distorted grid voltages, in which the harmonic limits according to the IEEE 1547 interconnection of distributed generation regulations are also indicated for comparison. As can be seen, the 5th and 7th harmonics are significantly reduced and all the harmonic components are within the limits.

5. Experimental Results

The proposed control scheme has been implemented in a 2 kVA three-phase grid-connected inverter system as shown in Figure 19. The whole control algorithms are implemented using 32-bit floating-point DSP TMS320F28335 with clock frequency of 150 MHz [22]. The sampling period is set to 100 µs in the experiments, which yields the switching frequency of 10 kHz. The intelligent power module (IPM) is employed for three-phase grid-connected inverter. The inverter phase currents are detected by the Hall-effect devices and are converted through internal 12-bit A/D converters. The inverter reference voltages are applied using the symmetrical space vector PWM method. The parameters of the experimental system are summarized in Table 1. For distorted condition of the grid voltages, 10% of the fifth and the seventh harmonics, respectively, and 1% of the eleventh and the thirteenth harmonics, respectively, are injected to the grid voltage, which results in the THD of 14.2%.
Figure 20 shows the experimental results for the SRF-PLL and MAF-PLL algorithms under the distorted grid voltages for comparison. As can been seen, the angular frequency waveform obtained by the SRF-PLL algorithm is highly distorted due to the existence of high frequency disturbances in three-phase grid voltages. In contrast, the angular frequency obtained from the MAF-PLL algorithm remains nearly constant in the steady-state even when the grid voltages are highly distorted. As a result, the angular displacement is not influenced by the distorted grid voltages, which proves the effectiveness and robustness of the MAF-PLL.
Figure 21 shows the experimental results for inverter output currents when the conventional synchronous PI decoupling controller and SRF-PLL algorithm are employed under the distorted grid voltages. It is clearly observed in this figure that phase current waveforms are quite non-sinusoidal. This indicates that the conventional control scheme fails to meet the high power quality in a real system where there exist sinusoidal disturbances.
Figure 22 shows the experimental results for inverter output currents using the proposed control scheme under the same conditions as Figure 21. Due to an effective compensating capability of the proposed control scheme, the inverter phase currents shows considerably sinusoidal waveforms regardless of the high distortion level in the grid voltages.
As mentioned previously in Figure 16, the delay of the MAF might slow down the dynamic response in inverter currents. In order to get rid of this problem, a modification technique that replaces the harmonic current with temporary values has been used. The transient current response of the proposed control scheme under the step change in the current reference is demonstrated in Figure 23. As is shown, the q-axis inverter current instantly reaches its new reference value, which validates the fast dynamic response of the proposed control scheme.
Figure 24 shows the experimental FFT result of a-phase inverter current using the proposed control scheme under the distorted grid voltages. It is clearly observed that the low-order harmonic components in the fifth, seventh, eleventh, and thirteenth order are considerably reduced. Furthermore, all the harmonic components well satisfy the harmonic limits of IEEE std. 1547 [6].
As a result, the proposed control scheme has a good disturbance rejection capability in steady state as well as fast dynamic response.

6. Conclusions

In this paper, an improved current control strategy for a grid-connected inverter even in the presence of distorted grid conditions has been proposed for DG systems. The proposed control scheme is designed to overcome the limitation of the conventional PI type control schemes under adverse operation conditions of grid. Two significant enhancements in the proposed control scheme are the implementation of a robust PLL algorithm and the additional harmonic suppression scheme. This is achieved by introducing the model decomposition method and MAF, by which the inverter model can be decomposed into the fundamental and harmonic components. Based on the derived models, the fundamental and harmonic currents are independently controlled by a decoupling PI controller and a predictive basis controller, respectively. The principle and mathematical description of the proposed control scheme have been analyzed to emphasize the simplicity of the control structure. To verify the feasibility and effectiveness of the proposed control scheme, the whole control systems are constructed using 32-bit floating-point DSP TMS320F28335. It has been demonstrated through the comparative simulations and experimental results that the proposed control scheme is an effective way to improve the performance of a grid-connected inverter under the distorted grid voltages.

Acknowledgments

This research was supported by Basic Science Research Program through the National Research Foundation of Korea (NRF) funded by the Ministry of Education (NRF-2014R1A1A2056436). This work was supported by the Human Resources Development of the Korea Institute of Energy Technology Evaluation and Planning (KETEP) grant funded by the Korea government Ministry of Trade, Industry & Energy. (NO. 20154030200720).

Author Contributions

Ngoc Bao Lai and Kyeong-Hwa Kim conceived the main concept of the control structure and developed the entire system. Ngoc Bao Lai carried out the research and analyzed the numerical data with the guidance from Kyeong-Hwa Kim. Ngoc Bao Lai and Kyeong-Hwa Kim collaborated to prepare the manuscript.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Chicco, G.; Mancarella, P. Distributed multi-generation: A comprehensive view. Renew. Sustain. Energy Rev. 2009, 13, 535–551. [Google Scholar] [CrossRef]
  2. Llaria, A.; Curea, O.; Jiménez, J.; Camblong, H. Survey on microgrids: Unplanned islanding and related inverter control techniques. Renew. Energy 2011, 36, 2052–2061. [Google Scholar] [CrossRef]
  3. Zamora, R.; Srivastava, A.K. Controls for microgrids with storage: Review, challenges, and research needs. Renew. Sustain. Energy Rev. 2010, 14, 2009–2018. [Google Scholar] [CrossRef]
  4. Lasseter, R.; Akhil, A.; Marnay, C.; Stephens, J.; Dagle, J.; Guttromson, R.; Meliopoulous, A.S.; Yinger, R.; Eto, J. The CERTS microgrid concept, white paper on integration of distributed energy resources. U.S. Department of Energy 2002. Available online: http://bnrg.eecs.berkeley.edu/~randy/Courses/CS294.F09/MicroGrid.pdf (accessed on 15 January 2016).
  5. Guerrero, J.M.; Vasquez, J.C.; Matas, J.; de Vicuña, L.G.; Castilla, M. Hierarchical control of droop—Controlled AC and DC microgrids—A general approach toward standardization. IEEE Trans. Ind. Electr. 2011, 58, 158–172. [Google Scholar] [CrossRef]
  6. IEEE Std. 1547-2003. Standard for interconnecting distributed resources with electric power systems. IEEE 2003. Available online: http://ieeexplore.ieee.org/xpl/articleDetails.jsp?arnumber=1225051&filter=AND(p_Publication_Number:8676) (accessed on 15 January 2016).
  7. IEC 61727 Ed.2. Photovoltaic (PV) systems—Characteristic of the utility interface. IEC 2004. Available online: https://webstore.iec.ch/publication/5736 (accessed on 15 January 2016).
  8. Bouzid, A.M.; Guerrero, J.M.; Cheriti, A.; Bouhamida, M.; Sicard, P.; Benghanem, M. A survey on control of electric power distributed generation systems for microgrid applications. Renew. Sustain. Energy Rev. 2015, 44, 751–766. [Google Scholar] [CrossRef]
  9. Teodorescu, R.; Liserre, M.; Rodríguez, P. Grid Converters for Photovoltaic and Wind Power Systems, 1st ed.; John Wiley and Sons: West Sussex, UK, 2011; pp. 313–321. [Google Scholar]
  10. Blaabjerg, F.; Teodorescu, R.; Liserre, M.; Timbus, A.V. Overview of control and grid synchronization for distributed power generation systems. IEEE Trans. Indus. Electr. 2006, 53, 1398–1409. [Google Scholar] [CrossRef]
  11. Teodorescu, R.; Blaabjerg, F.; Liserre, M.; Loh, P.C. Proportional-resonant controllers and filters for grid-connected voltage-source converters. IEE Proc. Electr. Power Appl. 2006, 153, 750–762. [Google Scholar] [CrossRef]
  12. Hu, J.; Shang, L.; He, Y.; Zhu, Z.Q. Direct active and reactive power regulation of grid-connected dc/ac converters using sliding mode control approach. IEEE Trans. Power Electr. 2011, 26, 210–222. [Google Scholar] [CrossRef]
  13. Fischer, R.J.; González, S.A.; Carugati, I.; Herrán, M.A.; Judewicz, M.G.; Carrica, D.O. Robust predictive control of grid-tied converters based on direct power control. IEEE Trans. Power Electr. 2013, 29, 5634–5643. [Google Scholar] [CrossRef]
  14. Chen, D.; Zhang, J.; Zhang, Z. An improved repetitive control scheme for grid-connected inverter with frequency-adaptive capability. IEEE Trans. Ind. Electr. 2013, 60, 814–823. [Google Scholar] [CrossRef]
  15. Zhao, J.; Bose, B.K. Neural-network-based waveform processing and delayless filtering in power electronics and AC drives. IEEE Trans. Ind. Electr. 2004, 51, 981–991. [Google Scholar] [CrossRef]
  16. Kang, S.W.; Kim, K.H. Sliding mode harmonic compensation strategy for power quality improvement of a grid-connected inverter under the distorted grid condition. IET Power Electr. 2015, 8, 1461–1472. [Google Scholar] [CrossRef]
  17. Golestan, S.; Ramezani, M.; Guerrero, J.M.; Freijedo, F.D.; Monfared, M. Moving average filter based phase-locked loops: Performance analysis and design guidelines. IEEE Trans. Power Electr. 2014, 29, 2750–2763. [Google Scholar] [CrossRef]
  18. Golestan, S.; Guerrero, J.M.; Abusorrah, A.M. MAF-PLL with phase-lead compensator. IEEE Trans. Ind. Electr. 2015, 62, 3691–3695. [Google Scholar] [CrossRef]
  19. Espi, J.M.; Castello, J.; García-Gil, R.; Garcera, G.; Figueres, E. An adaptive robust predictive current control for three-phase grid-connected inverters. IEEE Trans. Ind. Electr. 2011, 58, 3537–3546. [Google Scholar] [CrossRef]
  20. Svensson, J.; Bongiorno, M.; Sannino, A. Practical implementation of delayed signal cancellation method for phase-sequence separation. IEEE Trans. Power Del. 2007, 22, 18–26. [Google Scholar] [CrossRef]
  21. Wang, L.; Jiang, Q.; Hong, L.; Zhang, C.; Wei, Y. A novel phase-locked loop based on frequency detector and initial phase angle detector. IEEE Trans. Power Electr. 2013, 28, 4538–4549. [Google Scholar] [CrossRef]
  22. TMS320F28335 Digital Signal Controller (DSC)—Data Manual, Texas Instrument, 2008. Available online: http://www.ti.com/lit/ds/sprs581d/sprs581d.pdf (accessed on 15 January 2016).
Figure 1. Block diagram of three-phase grid-connected inverter.
Figure 1. Block diagram of three-phase grid-connected inverter.
Energies 09 00190 g001
Figure 2. Block diagram of the proposed control scheme.
Figure 2. Block diagram of the proposed control scheme.
Energies 09 00190 g002
Figure 3. The whole system configuration for simulation.
Figure 3. The whole system configuration for simulation.
Energies 09 00190 g003
Figure 4. Distorted three-phase grid voltages.
Figure 4. Distorted three-phase grid voltages.
Energies 09 00190 g004
Figure 5. Performance comparison of dynamic responses between the band pass filter (BPF) and moving average filter (MAF) when direct current (DC)-quantity of grid voltages is extracted at the synchronous frame under the distorted grid voltages: (a) with BPF; and (b) with MAF.
Figure 5. Performance comparison of dynamic responses between the band pass filter (BPF) and moving average filter (MAF) when direct current (DC)-quantity of grid voltages is extracted at the synchronous frame under the distorted grid voltages: (a) with BPF; and (b) with MAF.
Energies 09 00190 g005
Figure 6. Performance comparison of dynamic responses between the BPF and MAF when DC-quantity of inverter currents is extracted at the synchronous frame under the distorted grid voltages: (a) using BPF; and (b) using MAF.
Figure 6. Performance comparison of dynamic responses between the BPF and MAF when DC-quantity of inverter currents is extracted at the synchronous frame under the distorted grid voltages: (a) using BPF; and (b) using MAF.
Energies 09 00190 g006
Figure 7. Dynamic response of the conventional synchronous reference frame phase lock loop (SRF-PLL) under the distorted grid voltages: (a) angular frequency; and (b) angular displacement.
Figure 7. Dynamic response of the conventional synchronous reference frame phase lock loop (SRF-PLL) under the distorted grid voltages: (a) angular frequency; and (b) angular displacement.
Energies 09 00190 g007
Figure 8. Dynamic response of the moving average filter phase lock loop (MAF-PLL) under the distorted grid voltages: (a) angular frequency; and (b) angular displacement.
Figure 8. Dynamic response of the moving average filter phase lock loop (MAF-PLL) under the distorted grid voltages: (a) angular frequency; and (b) angular displacement.
Energies 09 00190 g008
Figure 9. Inverter currents of the conventional proportional-integral (PI) decoupling controller under the ideal grid voltages: (a) phase-currents; and (b) q-axis and d-axis currents.
Figure 9. Inverter currents of the conventional proportional-integral (PI) decoupling controller under the ideal grid voltages: (a) phase-currents; and (b) q-axis and d-axis currents.
Energies 09 00190 g009
Figure 10. Inverter currents of the conventional PI decoupling controller under the distorted grid voltages: (a) phase-currents; and (b) q-axis and d-axis currents.
Figure 10. Inverter currents of the conventional PI decoupling controller under the distorted grid voltages: (a) phase-currents; and (b) q-axis and d-axis currents.
Energies 09 00190 g010
Figure 11. Inverter currents using PR controller with different distorted grid conditions: (a) The case when the grid disturbance only contains 5th and 7th harmonics. (b) The case when the grid disturbance contains 5th, 7th, 11th and 13th harmonics.
Figure 11. Inverter currents using PR controller with different distorted grid conditions: (a) The case when the grid disturbance only contains 5th and 7th harmonics. (b) The case when the grid disturbance contains 5th, 7th, 11th and 13th harmonics.
Energies 09 00190 g011
Figure 12. Control performance with harmonic compensation using the sliding mode control under distorted grid conditions: (a) inverter phase currents; and (b) inverter reference voltages.
Figure 12. Control performance with harmonic compensation using the sliding mode control under distorted grid conditions: (a) inverter phase currents; and (b) inverter reference voltages.
Energies 09 00190 g012
Figure 13. Inverter currents of the proposed control scheme under the distorted grid voltages: (a) phase-currents; and (b) q-axis and d-axis currents.
Figure 13. Inverter currents of the proposed control scheme under the distorted grid voltages: (a) phase-currents; and (b) q-axis and d-axis currents.
Energies 09 00190 g013
Figure 14. Steady-state current responses with random limited-band disturbances: (a) using the proposed control scheme; (b) using the conventional PI controller; and (c) waveform of random disturbances in three-phase grid voltages.
Figure 14. Steady-state current responses with random limited-band disturbances: (a) using the proposed control scheme; (b) using the conventional PI controller; and (c) waveform of random disturbances in three-phase grid voltages.
Energies 09 00190 g014
Figure 15. Transient responses of the conventional PI decoupling current controller under the distorted grid voltages: (a) phase-currents; and (b) q-axis and d-axis currents.
Figure 15. Transient responses of the conventional PI decoupling current controller under the distorted grid voltages: (a) phase-currents; and (b) q-axis and d-axis currents.
Energies 09 00190 g015
Figure 16. Transient responses of the proposed current control scheme under the distorted grid voltages: (a) phase-currents; and (b) q-axis and d-axis currents.
Figure 16. Transient responses of the proposed current control scheme under the distorted grid voltages: (a) phase-currents; and (b) q-axis and d-axis currents.
Energies 09 00190 g016
Figure 17. Transient responses of the proposed current control scheme under the distorted grid voltages with temporary replacement of the harmonic currents during transient period: (a) phase-currents; and (b) q-axis and d-axis currents.
Figure 17. Transient responses of the proposed current control scheme under the distorted grid voltages with temporary replacement of the harmonic currents during transient period: (a) phase-currents; and (b) q-axis and d-axis currents.
Energies 09 00190 g017
Figure 18. Fast Fourier transform (FFT) result of a-phase current using the proposed scheme under the distorted grid voltages with harmonic limits according to the IEEE std. 1547.
Figure 18. Fast Fourier transform (FFT) result of a-phase current using the proposed scheme under the distorted grid voltages with harmonic limits according to the IEEE std. 1547.
Energies 09 00190 g018
Figure 19. Experimental test setup.
Figure 19. Experimental test setup.
Energies 09 00190 g019
Figure 20. Experimental results for the SRF-PLL and MAF-PLL under the distorted grid voltages.
Figure 20. Experimental results for the SRF-PLL and MAF-PLL under the distorted grid voltages.
Energies 09 00190 g020
Figure 21. Experimental results for inverter output currents using the conventional PI decoupling controller and SRF-PLL under the distorted grid voltages.
Figure 21. Experimental results for inverter output currents using the conventional PI decoupling controller and SRF-PLL under the distorted grid voltages.
Energies 09 00190 g021
Figure 22. Experimental results for inverter output currents using the proposed control scheme under the distorted grid voltages.
Figure 22. Experimental results for inverter output currents using the proposed control scheme under the distorted grid voltages.
Energies 09 00190 g022
Figure 23. Step response of the inverter currents using the proposed control scheme under the distorted grid voltages.
Figure 23. Step response of the inverter currents using the proposed control scheme under the distorted grid voltages.
Energies 09 00190 g023
Figure 24. FFT result of a-phase current using the proposed control scheme under the distorted grid voltages.
Figure 24. FFT result of a-phase current using the proposed control scheme under the distorted grid voltages.
Energies 09 00190 g024
Table 1. System parameters of grid-connected inverter.
Table 1. System parameters of grid-connected inverter.
ParametersSymbolValueUnits
Rated powerPR2kW
Grid voltageeg180V
Grid frequencyf60Hz
DC-link voltageVDC420V
Filter inductanceL7mH
Filter resistanceR0.5
Switching frequencyfs10kHz

Share and Cite

MDPI and ACS Style

Lai, N.B.; Kim, K.-H. An Improved Current Control Strategy for a Grid-Connected Inverter under Distorted Grid Conditions. Energies 2016, 9, 190. https://doi.org/10.3390/en9030190

AMA Style

Lai NB, Kim K-H. An Improved Current Control Strategy for a Grid-Connected Inverter under Distorted Grid Conditions. Energies. 2016; 9(3):190. https://doi.org/10.3390/en9030190

Chicago/Turabian Style

Lai, Ngoc Bao, and Kyeong-Hwa Kim. 2016. "An Improved Current Control Strategy for a Grid-Connected Inverter under Distorted Grid Conditions" Energies 9, no. 3: 190. https://doi.org/10.3390/en9030190

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop