Next Article in Journal
Water Is a Viable Data Storage Medium: A Security and Privacy Viewpoint
Next Article in Special Issue
Energy Harvesting and Energy Storage Systems
Previous Article in Journal
High-Frequency Vacuum Electron Devices
Previous Article in Special Issue
Parameter Extraction of Solar Module Using the Sooty Tern Optimization Algorithm
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Renewable Energy Micro-Grid Interfacing: Economic and Environmental Issues

1
Electrical Engineering Department, Faculty of Engineering, Menoufiya University, Shebin el Kom 32512, Egypt
2
Department of Electrical Engineering, Faculty of Engineering, Kafrelsheikh University, Kafrelsheikh 33516, Egypt
3
Department of Electrical Engineering, Faculty of Engineering, Suez University, Suez 43533, Egypt
4
Sharaf Energy Systems Inc., Fredeticton, NB E3C 2P2, Canada
*
Author to whom correspondence should be addressed.
Electronics 2022, 11(5), 815; https://doi.org/10.3390/electronics11050815
Submission received: 6 February 2022 / Revised: 3 March 2022 / Accepted: 3 March 2022 / Published: 5 March 2022
(This article belongs to the Special Issue Energy Harvesting and Energy Storage Systems)

Abstract

:
This paper presents a study on the technical, economic, and environmental aspects of renewable energy resources-based distributed generation units (DGs). These units are connected to the medium-voltage network to create a new structure called a microgrid (MG). Renewable energies, especially wind and solar, are the most important generation units among DGs. The stochastic behavior of renewable resources increases the need to find the optimum operation of the MG. The optimal operation of a typical MG aims to simultaneously minimize the operational costs and the accompanied emission pollutants over a daily scheduling horizon. Several renewable DGs are investigated in the MG, consisting of biomass generators (BGs), wind turbines (WTs), and photovoltaics (PV). For the proposed operating strategy of the MG, a recent equilibrium optimization (EO) technique is developed and is inspired by the mass balance models for a control volume that are used to estimate their dynamic and equilibrium states. The uncertainties of wind speed and solar irradiation are considered via the Weibull and Beta-probability density functions (PDF) with different states of mean and standard deviation for each hour, respectively. Based on the developed EO, the hourly output powers of the PV, WT, and BGs are optimized, as are the associated power factors of the BGs. The proposed MG operating strategy based on the developed EO is tested on the IEEE 33-bus system and the practical large-scale 141-bus system of AES-Venezuela in the metropolitan area of Caracas. The simulation results demonstrate the significant benefits of the optimal operation of a typical MG using the developed EO by minimizing the operational costs and emissions while preserving the penetration level of the DGs by 60%. Additionally, the voltage profile of the MG operation for each hour is highly enhanced where the minimum voltage at each hour is corrected within the permissible limit of [0.95–1.05] Pu. Moreover, the active power losses per hour are greatly reduced.

1. Introduction

Due to the continuous increase in power demand and rapid depletion of fossil fuels, researchers all over the world have no other option but to look for alternative energy sources by utilizing small-scale distributed power generation (DG) and energy storage systems (ESS) [1]. However, due to the inherent intermittency and volatility of renewable energy sources (RESs), its large-scale integration into the power system will increase the regulation burden and affect the security operation of the main grid. The microgrid is defined as small-scale controllable electrical distribution systems, which have the important advantage of operating either islanded or interconnected to the main grid. Microgrids (MGs) are usually composed of Distributed Energy Resources (DERs), ESSs, and controllable loads [2]. The DERs are based on conventional resources, such as diesel generators and RESs such as photovoltaics (PV) and wind turbines (WT) [3,4,5,6]. There are two modes of operation for MGs. In a grid-connected operation, the MGs draw/supply power from/to the grid based on load and generation conditions with regard to the market prices. On the other hand, it will be disconnected from the grid to provide electricity to associated critical loads in the event of faults [7].
In the first mode of operation, the MGs should be operated economically and reliably, where a supervisory control and data acquisition (SCADA) system is activated to monitor, control, and dispatch all DERs to guarantee the economic and secure operation of the MGs. For this targeted operation of the MGs, various conventional and artificial intelligent programming techniques were applied for dispatching the DERs [8]. In [9,10,11,12], the operation of distribution systems was optimally controlled via DERs commitment, Capacitor Banks (CBs) switching, SVC, and reconfiguration using the jellyfish search algorithm and manta ray foraging optimization algorithm, respectively. In both studies, the wasted energy of power losses was minimized considering the daily load variations, but the uncertainties of the DERs were not taken into account. In [13], the optimal operation and energy management method for a hybrid MG including photovoltaics, wind turbines, a pump as a turbine system, and a diesel generator was introduced, with a study on day-ahead scheduling. The optimal energy management minimizes the fuel cost of diesel generators, the daily operating cost, as well as the balance between the generation and load for both warm and cold days using an imperialist competitive algorithm. In [14], a hybrid ant lion optimization with a bat algorithm was utilized for the power management of the MG considering a droop controller strategy. The main target of this droop controller was stabilized by the MG by minimizing the errors of real and reactive power under a power shortage and power maximum. In [15], an optimal energy scheduling mechanism was presented in multi-MGs in order to minimize the total operational costs of their committed DERs. This study provided different DERs types and their associated uncertainties in a multi-MG system, but the linked lines and their losses were completely ignored. In [16], a Tabu search algorithm was applied for the design of the MG system components with minimum investment, operation, and emission costs. This study utilized the Monte Carlo simulation to deal with the uncertainties due to load forecasting and the random outages of the units. However, the uncertainties due to the intermittent sources of WTs and PVs were not taken into consideration where their outputs were directly evaluated from the daily wind velocity and solar irradiance, respectively. In [17], particle swarm optimization (PSO) was dedicated to minimize the MG operational costs considering the variations in loadings, DGs, and requirements of stable grid operational constraints.
Despite that, only the fuel costs of the committed DGs were handled where the quadratic cost models were utilized for the fuel cells and the micro turbines. In [18], a manta ray foraging optimizer was developed to optimally solve the economic dispatch problem with wind power inclusion considering the valve point effects of the generators, while the wind power effects were ignored in [19,20]. However, the environmental impacts of this operation were not considered. In [21], an artificial ecosystem-based optimizer was applied considering the demand side management for minimizing the techno-economic evaluations of hybrid energy systems. In [22], an optimal operational strategy was presented for MGs including hydrogen storage to integrate RESs and decrease the emissions. In [23], in off-grid MG simulation and tests, an adaptable energy management strategy relying on a mixed energy systems has been provided to preserve the stable operating condition of the off-grid MG and lengthen the lifetime of batteries.
In [24], a harmony search algorithm was combined with differential evolution for the optimal operation of MGs. Added to that, an optimal operation of MGs was considered with WTs, PVs, battery energy storage (BES) systems, electric vehicles (EVs), and demand response for minimizing the total operating costs [25]. In this study, Sparse Nonlinear OPTimizer (SNOPT) solver was utilized using Generalized Algebraic Modeling Systems (GAMS) software. In both studies [24,25], the outputs of WTs and PVs were directly evaluated from the hourly wind velocity and solar irradiance, respectively. Therefore, the uncertainties due to the intermittent sources require an effective handling procedure. In [26,27] a moth flame optimization algorithm was employed for the optimal operation of a hybrid energy system including WTs, PVs, gas turbines, and energy storage.
In [28], an optimal MG operation strategy was presented to minimize the fuel costs and the produced emissions. In this study, the DER uncertainties were considered via the probability distributions and confidence. However, the application was limited to a very small number of sources where linear programming and quadratic programming (QP) were utilized as solvers. In [29], RES was allocated and optimized in a distribution system using Mixed Integer-Linear Programming (MILP) and was solved by FICO® XPRESS optimization software. In [30], the Energy Storage (ES) and RES were integrated using MILPmethod.
Recently, a new effective optimization algorithm of Equilibrium optimizer (EO) was presented [31]. EO provides strong exploratory and exploitative search mechanisms to adjust solutions at random, assisting in local minima avoidance in the optimization process, which is a common drawback of many optimization algorithms [31]. EO was efficiently used for solving the optimal power flow (OPF) problem in the AC power systems [32] and hybrid AC/DC power grids [33]. In [34,35], EO was utilized for handling the economic and the combined economic environmental dispatch problems, respectively, considering the power constraints, effects of the valve point, transmission losses, and ramp rate limits. In [36], an adaptive EO was developed for an optimal allocation procedure of biomass DGs to enhance the performance of the distribution systems and to reduce the related environmental emissions. In [37], EO was used to deal with the energy management optimization (EMO) in the MG considering the variations of WTs, PVs, and load demand for cost minimization and voltage magnitude improvements. In [38], an improved EO integrated for with optimal allocation of multiple PV units with batteries has been described. In [39], EO was utilized for the EMO considering the energy storage devices and the emissions from the associated DERs. In [40], EO was employed for estimating the undefined parameters for the lithium-ion batteries. In [41], EO was employed for identifying the prediction of oil breakdown voltage considering the barrier impact.
In this paper, an optimal operating strategy based on EO is developed for the techno-economic and environmental optimization scheme for MGs with multiple RESs. For this target, two objective functions are represented for minimizing the generation costs and minimizing the emissions of environmental pollution caused by them. The proposed algorithm is tested on two systems in order to verify its effectiveness and efficiency. The two systems are IEEE 33-bus and a practical large-scale 141-bus system of AES-Venezuela in the metropolitan area of Caracas. Added to that, EO is compared with other recent algorithms of DE and RAO algorithms. The main contributions of this paper can be summarized as follows:
  • Proposing an operational optimization problem of MG incorporating PV, WT, and BG with consideration of the uncertainties of PV and wind as RESs.
  • Simultaneously minimizing the operational costs and the accompanied pollutants.
  • Hourly load variations over a 24-h scheduling horizon are handled.
  • EO technique is employed with higher performance compared to DE and RAO.
  • The validity of the proposed methodology is validated on a large-scale 141-bus real distribution system.
Four additional rest sections of the current paper are organized thusly: Section 2 shows the mathematical formulation of the MG operation. The EO algorithm is developed in Section 3. Section 4 reveals the simulation results on the two small and large scale tested distribution systems. Section 5 concludes the paper findings.

2. Problem Formulation

DGs based on renewable energies are the main technologies that greatly affect the operation of the MG units. Because of their stochastic nature, optimal MG operation has to effectively handle their types and associated uncertainties in hourly basis. In this section, an optimization scheme is presented for the techno-economic and environmental operation of MGs that are established with several DGs based on renewable energies, including PV/WT/BG considering hourly variable load demand.

2.1. Types of DGs

Four types of the DG resources are classified based on their ability to deliver active and reactive powers [42,43,44]. In the first type, the DG units supply active power only. In Type-2, the DG units provide reactive power only. The DG units in Type 3 inject real and reactive power. The 4th type of DG units injects the active power and consumes reactive power. In this work, the WT model is considered Type-4. The related reactive power to be consumed by these units is obtained by [45].
Q D G , i = ( 0.05 + 0.04 P D G , i 2 )
where PDG,i and QDG,i are the active and reactive powers of the DG unit i, respectively.

2.2. Modeling of Renewable Energy Sources

2.2.1. Photovoltaic DGs

The small-scale PV DGs are the most common renewable sources in the MGs. PV modules are usually modeled using single, double, and triple diode-equivalent circuits [46,47]. Unfortunately, the produced power is intermittent and varied in each hour with high uncertainty levels due to their dependency on the solar irradiances. Therefore, they should be treated with an effective way for each hour where the uncertainty of solar irradiance is modeled by the Beta Probability Density Function (PDF). Consequently, in each hour, different states of the solar irradiance are considered to generate its Beta-PDF. For each state of solar irradiance s, the output power from the PV module, Ppv0(s), can be expressed as follows [48,49]:
F F = V M P P × I M P P V O C × I S C
where
P p v 0 ( s ) = N × F F × V y × I y
V y = V O C K v × T c y
I y = s   I s c + K i × ( T c y 25 )
T c y = T A + s   ( N O T 20 0.8 )
f b ( s ) = Γ ( α + β ) Γ ( α )   Γ ( β )   s ( α 1 )   ( 1 s ) ( β 1 )   0   s 1 ,   α ,   β   0 0                 o t h e r w i s e
β =   ( 1 μ )   μ   ( 1 + μ ) σ 2   1
α = μ × β 1 μ
ρ ( s ) = s 1 s 2 f b ( s )   d s
P p v ( t ) = 0 1 P p v 0   ( s ) ρ ( s ) d s
where N is the module number; s is the solar irradiance kW/m2; Ki and Kv are current and voltage temperature coefficients (A/°C and V/°C), respectively; Tcy and TA are cell and ambient temperatures (°C), respectively; NOT is the nominal operating temperature of the cell in °C; FF is the fill factor; Voc and Isc are the open circuit voltage (V) and short circuit current (A), respectively; VMPP and IMPP are the voltage and current at the maximum power point, respectively; fb(s) is the Beta-PDF of s; α and β are the parameters of the Beta-PDF; µ and σ are the mean and standard deviation of the random variable s, respectively; s1 and s2 are the solar irradiance limits of state (s); and ρ(s) is the probability of the solar irradiance state (s) during any specific hour.
Figure 1 describes in detail the calculation of the total average power at each hour including the uncertainties of solar irradiance. As shown, the related uncertainties are modeled using Beta-PDF where the day is split into 24-h periods, each of which is 1 hr. From the collected historical data, the mean and standard deviation of the hourly solar irradiance of the day is estimated. For each hour, different states of the solar irradiance among the Beta-PDF with equal steps are taken. In this study, each hour has 20 states for solar irradiance with a step of 0.05 kW/m2. Accordingly, the PV output power is obtained for each state using Equation (3). Besides, the probability of the solar irradiance state (s) is estimated using Equation (10). Thus, the average output power of the PV module at any specific hour can be obtained using Equation (11) [48]. This study considers that a PV unit is associated with the type of converter that can deliver active power only (i.e., unity power factor) as the standard IEEE 1547 [50].

2.2.2. Wind Turbine DGs

The WT-DGs are renewable sources, as well, where their produced powers are intermittent and varied in each hour with high uncertainty levels due to the dependency on wind speed. Generally, the power output from WT is calculated as Equation (12) [51]:
P W ( v ) = 0 0 v v c i P r × v v c i v r v c i v c i v v r P r v r v v c o 0 v v c o
where vco and vci are the cut-out and cut-in wind speeds of Wind Turbines (WT), respectively; v is the average wind speed of the hour; vr is nominal operating wind speed of WT; and Pr is the maximum power generated by the WT.
For the WT-DGs, the uncertainty of wind speed is modeled by the Weibull-PDF. The Weibull-PDF f(v) is formulated as in Equations (13)–(15) [52,53]:
f ( v ) = K C   v C K 1 e x p   v C K
K = σ v m 1.086
C = v m Γ 1 + 1 k
where K and C are the shape and scale indexes of the Weibull-PDF; vm is the mean wind speed; and σ is the standard deviation.
Based on that, in each hour, different states of the wind speeds are generated. Accordingly, the output power of the WT-DG is obtained for each state using Equation (12). Besides, the probability of the wind speed for each state is estimated using Equation (16).
ρ ( v ) = v w 1 v w 2 f ( v ) d v
where ρ(v) is the probability of wind speed in each state whereas vw1 and vw2 are the regarding limits of the wind speed.
Thus, the average output power of the WT-DG for each hour is calculated using Equation (17) [48].
P w ( t ) = 1 25 P w ( v ) ρ ( v ) d v
Figure 2 describes in detail the calculation of the total average power at each hour including the uncertainties of wind speed, where each hour has 20 states for wind speed with a step of 5% of the maximum wind speed.

2.2.3. Biomass DGs

The biomass generators (BGs) are firm generation DGs. The resulted BGs power is constant with no associated uncertainties in its rated value. The BG active and reactive powers at bus i can be expressed as in [36]:
Q B G , i = a i × P B G , i
a i = ± t a n   ( c o s 1 ( P F B G , i ) )
where QBG,i and PBG,i are the reactive and active powers associated with BG unit i, respectively. PFBG,i refers to the lag/lead operating biomass power factor, and ai takes positive or negative signs for the BG when supplying and consuming reactive powers, respectively.

2.3. Techno-Economic and Environmental Optimization Scheme of MGs

The optimal operation of a typical MG is investigated to reduce the economical operational costs and the accompanied pollutants simultaneously over a 24-h scheduling horizon.

2.3.1. Objective Function

Nowadays, the environmental emission reduction comes with great importance in order to reduce emission levels [54]. In this work, the goal is to optimize two conflicting cost functions simultaneously, which are the operating cost and the emissions of the WT, PV, BG, and grid. The objective function is modeled as follows:
M i n   O C t ( P B D G ,   P w ,   P p v ,   P g r i d ) +   H .   E t   ( P B D G ,   P w ,   P p v ,   P g r i d )
where OCt and Et are the total operational and emission costs in the MG for each hour (t), which are functions of the output powers of the renewable sources and grid; PBG is the output of BGs; Pw is the scheduled output of WT units; Ppv is the scheduled output of PV units; Pgrid is the grid output power; and H is the price penalty factor ($/Ton Co2). The price penalty factor was used [55], which is the ratio between the maximum fuel cost and the maximum emission of the associated generator
The total operational cost function is expressed in Equation (21) as
O C t = i = 1 N w C p w , i , t + i = 1 N p v C p v , i , t + C B G i = 1 N B G P B G , i , t + C g r i d P g r i d , t
The total emission cost function can be expressed in Equation (22) as follows:
E t = E w i = 1 N w P w , i , t + E p v i = 1 N p v P p v , i , t + E B G i = 1 N B G P B G , i , t + E g r i d P g r i d , t
where Nw is the number of WT units; Npv is the number of PV units; NBG is the number of BG units; Cpw is the operational costs of WT ($); Cpv is the operational costs of PV units ($); CBG is the cost coefficients of the operation and maintenance of BG; Cgrid is the cost coefficients related to grid; and Ew, Epv, EBG, and Egrid are the emission coefficients related to WT, PV, BG, and the grid, respectively.

2.3.2. Operational Costs

First, for the WT-DGs, the operational cost is the summation of two parts. The first part refers to the cost of the actual output power of the WT. The second part is the penalty cost of unavailable wind output power that refers to the deviation between the available and scheduled wind powers. At time t, the total operational costs of each WT (i) can be represented, as in [56], as
C p w , i , t = c w P w , i , t + c p w ( P w a v , i , t P w , i , t ) ,   i f   P w , i , t   < P w a v , i , t c w P w , i , t + c r w ( P w , i , t P w a v , i , t ) ,   i f   P w , i , t   > P w a v , i , t
where Cpw,i,t is the total operating cost of the wind, cw is the operational cost of the wind output ($/kW), cpw is the penalty costs for under-estimation power of the WT ($/kW), Pwav,i,t is the available ith WT power at time t (kW), and crw is the reserve cost for over-estimation wind turbine power ($/kW).
Second, for the PV units, the operational costs for each unit (i) at each time (t) are described as in [56]:
C p v , i , t = c p v P v , i , t + c p p v ( P p v _ a v , i , t P p v , i , t ) ,   i f   P p v , i , t   < P p v _ a v , i , t c p v P v , i , t + c r p v ( P p v , i , t P p v _ a v , i , t ) ,   i f   P p v , i , t   > P p v _ a v , i , t
where Cpv,i,t is the total operating cost of the PV, cpv is the operational cost of the PV units ($/kW), cppv and crpv are, respectively, the penalty costs for under-estimation and over-estimated powers ($/kW), and Ppv_av,i,t is the available power that can be produced (kW).
The first parts of Equations (23) and (24) represent the cost based on the actual PV and WT generation power, while the second part represents the costs due to under-estimation or over-estimation. The under-estimation costs are related to penalties due to the generated PV, and WT output power is less than the scheduled one, whereas the over-estimation costs are related to the reserve costs in case the scheduled output power is greater than the available generated power for both PV and WT.

2.4. Constraints

For the optimal operating strategy in MGs, different equality and inequality constraints have to be maintained as presented in Equations (25)–(31). Equations (25) and (26) represent the active and reactive power balance constraints mentioned as Ps and Qs that are the supplied active and reactive power by the main feeder and the active and reactive power losses denoted by PTloss and QTloss in the MG, respectively [57,58]. Equations (27)–(29) present the allowable limits of the output powers of different RERs. Equation (30) represents the output power for BG; PV and WT units must follow their operating limits. The power factor (PF) limits for each BG are maintained as in [59]. The bus voltage (V) limits should be in the range of [0.95–1.05] for each bus j [59], as presented in Equation (31). Equation (32) preserves the thermal capacity of the branches below their maximum thermal capacity for each branch [60,61]. Equation (33) gives the penetration bounds of the total renewable sources capacity in the system (KP) as [62,63]:
P s + n = 1 N B G P B G , n + n = 1 N w P w , n + n = 1 N p v P p v , n t = P T l o s s + P l o a d t     t = 1 , 2 , …… 24
Q s + n = 1 N B G Q B G , n + n = 1 N w Q w , n t = Q T l o s s + Q l o a d t     t = 1 , 2 , …… 24
0 P B G , i , t P B G , m a x     i = 1 , 2 , …… N B G , t = 1 , 2 , …… 24
0   P p v , i , t P p v , m a x     i = 1 , 2 , …… N p v ,   t = 1 , 2 , …… 24
0   P w , i , t P w , m a x    i = 1 , 2 , …… N w ,   t = 1 , 2 , …… 24
P F B G , m i n P F B G , i , t P F B G , m a x    i = 1 , 2 , …… N B G ,   t = 1 , 2 , …… 24
V j , m i n V j , t V j , m a x j = 1 , 2 , …… n b u s ,   t = 1 , 2 , …… 24
I b r , t I b r , m a x     b r = 1 , 2 , …… n b r ,   t = 1 , 2 , …… 24
i = 1 N B G P B G , i + i = 1 N w P w , i + i = 1 N p v P p v , i t K P n = 1 n b u s P l o a d , n t   ,   t = 1 , 2 , …… 24

3. Equilibrium Optimization for Optimal Operation Strategy in MGs

EO Algorithm

The dynamic balance of mass on the control volume is a key source of inspiration for the EO technique. The following three steps can be used to explain its mathematical model:
Step 1: Initialization: In the starting of the optimization process, the EO randomly generates the population. The initial concentrations are calculated using uniform random initialization based on the particle number, population, and dimensions, as in Equation (34) [64]:
C i , i n i t i a l = C i , m i n + r a n d i ( C i , m a x C i , m i n ) ,   i = 1 , 2 , …… N i
where Ci,initial refers to the initial vector for each particle (i), Ci,min and Ci,max are the lower and upper bounds of the control variables, randi refers to a random distributed vector in [0,1], and Ni is the number of particles.
In this step, the fitness of the initialized particles is estimated, and the best scores are used to find the nominee solutions.
Step 2: Equilibrium pool and candidates: In this step, the EO finds the particle’s equilibrium state. The algorithm reaches a near-optimal solution at its equilibrium state. It assigns the best four particles in the population at equilibrium candidates and the fifth one containing the average of the previous best four particles. The pool of equilibrium (Ceq, pool) that helps the EO features in their exploitation and exploration operations is expressed by these five equilibrium candidates.
Step 3: Updating the concentration: The evaluation process for updating each concentration vector (C) is carried out as
C = C e q + ( C   C e q ) F + G λ V ( 1 F )
where Ceq is a randomly generated vector (Ceq, pool) from the pool of equilibrium; λ is a random vector [0,1]; G is the generation rate; V stands for the volume unit, which is equal to one [31]; and F is an exponential term that helps the EO algorithm in achieving a balance between the exploration and extraction phases. It can be determined as follows:
F = e λ ( t t o )
where t0 is the initial start time, and the time (t) depends on the number of iterations (Iter) as follows:
t = 1 I t e r M a x _ i t e r a 2 I t e r M a x _ i t e r
where Iter and Max_iter are the initial and maximum iteration numbers, respectively; and a2 is a constant value equal to 1 that is used to monitor exploitation potential [31]. The following formula can be considered to boost the developed technique’s exploration and exploitation abilities.
t o = 1 λ ln a 1 s i g n ( r 0.5 ) ( 1 e λ t ) + t
where a1 is a constant value of 2 that is used to control exploration ability [31], r is a random vector in the range of 0 to 1, and the term (sign (r − 0.5)) affects exploration and exploitation directions. The generation rate (G) is calculated as follows:
G = G c p C e q λ C F
G c p = 0.5 r 1     r 2 G p 0        r 2 G p
where Gcp is the control parameter of the generation rate that is used to update the EO technique, GP is the generation probability that equals 0.5 [31], and r1 and r2 are random numbers in the range [0,1]. Figure 3 shows the EO based optimal operation procedure of MG in the tested distribution systems.

4. Simulation Results

The EO is applied to determine the optimal operation of MG to achieve technical and economic benefits with respecting the associated operational and emission costs for two distribution systems. For the optimal operation, the control variables are the active power resulted from different RERs, including BGs, wind, and PV, and the power factor of BGs.

4.1. Test Systems

Two test systems are considered to apply the proposed operation strategy. The 1st test system is the 12.66 kV IEEE 33-bus distribution system. It contains 33-node and 32 branches whilst its total active and reactive demand is 3715 kW + 2300 kVAr [65]. Figure 4 displays the first MG configuration where this system includes 1.1 MW-WT connected at bus 3, and five PV generators with ratings of 20, 25, 30, 40, and 50 kW are connected at buses 13, 17, 20, 27, and 33, respectively. In addition to that, four BGs with ratings of 400, 500, 700, and 1000 kVA are installed at buses 15, 25, 9, and 31, respectively [36].
The 12.47 kV AES-Venezuela in the metropolitan area of Caracas that is modeled by 141-node is considered the large-scale test system. The total peak load is 12.19 MW + 6.2894 MVAR [66,67]. Figure 5 displays the second MG configuration where the 141-bus system is modified to include one WT with a capacity of 3 MW connected at bus 50, and five PV generators with ratings of 40, 50, 60, 80, and 100 kW are connected at buses 60, 70, 80, 90, and 100, respectively. Added to that, four BGs with ratings of 650, 2500, 3500, and 2000 kVA are installed at buses 109, 16, 78, and 63, respectively [36]. For both studied systems, the load profile is taken into consideration where Figure 6 describes this hourly loading as a percentage of the peak load [68].
Also, the maximum iterations number equals 400 for the tested systems. The particles number is considered to be 50 for IEEE 33-bus and 100 for the large scale 141-bus system. The numbers of iterations and particles are considered the same for all competitive algorithms for a fair assessment of their performance. Additionally, the allowable number of the RERs units, BGs, wind, and PV are assumed as 4, 1, and 5, respectively. The maximum penetration level is limited by 60% of the load demand [69].Table 1 shows the data of operational costs and the emission for the shared energy sources in the microgrid.

4.2. Cases Studied

In this paper, three different cases studied are performed for each system, and these cases are described as follows:
Case 1: this is considered the basic system condition without adding DGs units.
Case 2: in this case, the MG is operated without considering the optimal control settings of BGs, WT, and PV with daily load variations.
Case 3: this case develops the optimal operation of the MG with optimal control settings by using the EO algorithm for BGs, WT, and PV, simultaneously with considering the daily load variations.

4.3. Simulation Results of 33-Bus Test System

4.3.1. Case 1: Without DGs

In the first case, the hourly load flow is carried out at each loading hour of the 33-bus system without DGs installations. At the peak loading (hour 12) and without DGs units, the initial power losses equal 211.2 kW. Bus 18 has a minimum voltage that equals 0.9038 p.u. as in [65].

4.3.2. Case 2: MG without Optimal Control on BGs, Wind, and PV with Daily Load Variation

In the second case, MG is operated without optimal control on DGs whereas the WTs and PVs generate its available power, and the BGs generate its full capacity at a unity power factor. For the small-scale PV DGs, the Beta-PDF is used to model the uncertainty of the solar irradiance and the evaluation of PV output power is performed as described in Figure 1 considering the uncertainties in solar irradiance. From the collected historical data, the mean and standard deviations of the hourly solar irradiance of the day are estimated. Based on that, the Beta-PDF is generated for each hour. Consequently, 20 different states of solar irradiance among the Beta-PDF are taken with equal step sizes of 0.05 kW/m2 for each hour. Figure 7 displays their produced powers from each PV source at each hour. There is no power output to be generated from the PV sources in the first and last five hours in the morning and evening since there are no solar irradiances at these hours. Additionally, the highest output of each PV source occurred at 12 pm, with 55.2, 55.3%, 55.4%, 55.2% and 55.3% from their installed capacities for the PV sources at buses 13, 17, 20, 27, and 33, respectively.
For the WT-DGs, the Weibull-PDF is used to model the uncertainty of the wind speed and the evaluation of WT output power, considering that the uncertainties in wind speed is performed as described in Figure 2. For each hour, the mean and standard deviations of the hourly wind speed of the day are estimated, and the associated Weibull-PDF is generated. Similarly, 20 states of the wind speed, for each hour, are considered where the step is 1.25 m/s. Figure 8 displays the hourly active and reactive powers that are produced from the WT source at bus 3. The type 4 distributed generation, WT-DG, is used in this study to deliver the active power and to consume reactive power using the induction generators at a fixed speed. At hour 18, the WT-DG produces the highest active power with 692.1 kW and consumes the highest reactive power with 69.16 kVAr. Thus, it is operated with 62.92% from its full capacity. At hour 7, the WT-DG is operated with 36.53% from its full capacity, where it produces the least active power with 401.8 kW and consumes the least reactive power with 56.45 kVAr.
On the other side, the BGs are operated at full capacity without optimal control. By running the load flow algorithm for these hourly circumstances, Figure 9 shows the total active power of each type of DG and the summation of loads and the hourly power losses. Then, Figure 9 concludes the following findings:
  • During nine hours (1–8 and 24), the sign of the grid power is negative. At these hours, the DGs generated power in the MG is greater than the loads and the MG power losses so that the excess power is back to the grid bus. Consequently, there is surplus active power to be generated from the DGs in the MG and injected to the grid bus. The maximum extra power is reached at hour 4 with 913.438 kW, whilst the minimum surplus power is reached at hour 8 with 191.873 kW.
  • During the other 15 h, the MG absorbs active power from the grid bus. The maximum absorbed power is reached at hour 14 with 655.4086 kW, whilst the minimum absorbed power is reached at hour 23 with 160.7345 kW.

4.3.3. Case 3: MG with Optimal Control on BGs, WT, and PV Simultaneously with Daily Load Variation

In the third case, the EO algorithm is applied to operate the economical solution of MG considering the emission concerns by simultaneously minimizing the hourly operational costs and the accompanied pollutants. Added to that, the assessment of EO performance is carried out compared with other optimization algorithms such as DE [74] and RAO [75] techniques at different hours. The convergence comparisons between the developed EO, DE, and RAO algorithms at hours 6 and 12 are described in Figure 10 where the associated outcomes of them are tabulated in Table 2 and Table 3 at hours 6 and 12, respectively. At hour 6 (Table 2), the developed EO achieves the minimum objective function of $124.4644, whereas DE and RAO algorithms acquire objective functions of $127.5425 and $124.6005, respectively. Similarly, at hour 12 (Table 3), the developed EO achieves the minimum objective function of $224.2039, whereas the DE and RAO algorithms acquire objective functions of $234.7754 and $224.2165, respectively.
Based on the developed EO, the output powers of the PV, WT, and BGs are optimized besides the associated power factors of the BGs. Figure 11a shows the percentage apparent power of the BGs at buses 15, 25, 9, and 31 for each hour, whereas Figure 11b displays the hourly optimized value of the power factor. From Figure 11a,b:
  • The first BG at bus 31 is operating within range [40:100] % of its capacity to inject apparent power demand to the MG during the day. Similarly, the second BG at bus 15 is operating within range [60:100] % of its capacity during the day excluding hour 6.
  • Both BG1 and BG2 at buses 31 and 15 are approximately operating at a power factor of 0.85, which has the minimum power factor to be considered, and so their injected reactive power is directly proportional to their scheduled output power.
  • Both BG3 and BG4 at buses 25 and 9 produce very small apparent power at the first five hours, respectively, which has the smallest loadings. Then, their output powers increase through the loading increases, whereas BG3 at bus 25 is operating with 100% of its capacity at hour 6. Added to that, BG4 at bus 9 is operating with 100% of its capacity at hours 12, 14, 17, and 18.
  • BG3 at bus 25 is operating at a varied power factor through the day. BG4 at bus 9 is operating at a varied power factor at the first nine hours with low loading values, whilst its power factor is nearly fixed at 0.85 for the next hours.
To study the hourly power balance operation of the MG, Figure 12 illustrates the total active power for each type of DG and the summation of loads and hourly power losses. This figure leads to the following findings:
  • The total generation equals to the loads and power losses at each hour, where the summations of the output powers from the BGs are varied, which is optimally controlled by the developed EO algorithm at each hour.
  • The developed EO algorithm optimizes the output powers from WT and PV sources at their available outputs to make use of their environmentally friendly characteristics.
  • During the day, there are no excess powers in the MG back to the grid bus. The MG was supplied with the active power from the grid bus. The maximum supplied power is achieved at hour 12 with 1520 kW, whilst the minimum supplied power is reached at hour 5 with 843.97 kW.
  • As a result, the supplied power represents 40.58% and 40.34% referred to the loading and power losses at hours 12 and 5, respectively. Therefore, the total produces power from the DGs with 59.42% and 59.66% referred to the loading and power losses at hours 12 and 5, respectively.
  • Nevertheless, the penetration of the total DGs power production in the MG does not exceed the penetration limit of 60%.
To assess the voltage quality of the MG operation for each hour, Figure 13 displays the minimum voltage at each hour for the three cases studied. It is shown that the minimum voltage is corrected in cases 2 and 3 where, when the voltages at all hours are below the permissible limit of 0.95 Pu in the case (case 1), the highest minimum voltage occurs at bus 18 at hour 5, whereas the least minimum voltage occurs at the same bus at hour 15. At both hours, the voltage profiles at all MG buses are described in Figure 14. The voltage profile at each bus is improved at light loading at hour 5. At this loading hour, the minimum voltage at bus 18 is corrected from 0.9495 to 0.9877 Pu, which exceeds the minimum limit of 0.95 Pu in case 3; consequently, this improvement represents 4.02%. Additionally, the voltage profile at each bus is improved at peak loading at hour 15, where the minimum voltage at bus 18 is improved with 7.822% and corrects the voltage from 0.9038 to 0.9745 Pu, which exceeds the minimum limit of 0.95 Pu in case 3.
In addition, Figure 15 shows the hourly active power losses for the three cases that are greatly reduced from case 1 to cases 2 and 3, whereas the optimal operating strategy based on the developed EO algorithm in case 3 provides the minimum power losses at each hour through the day. Compared to case 1, the percentages of the reduction in power losses that are achieved by case 3 reach 81.9, 79.6, 73.7, 80.6, 80.9, 74.2, 71.8, 75.5, 84.9, 83.7, 85.3, 85.2, 85.5, 85.2, 84.2, 84.8, 82.1, 81.1, 82.4, 83.1, 83.7, 84.5, 84.3, and 79.8% for hours 1–24, respectively. Compared to case 2, the percentages of the reduction in power losses that are achieved by case 3 reach 41.9, 48.5, 48.6, 61.7, 61.8, 48.6, 31.6, 19.5, 22.3, 18.7, 19.7, 19.4, 19.9, 19.4, 18.3, 19.4, 16.7, 15.7, 17.6, 20.3, 19.1, 19.7, 21.3, and 27.6% for hours 1–24, respectively.
Additionally, the hourly operational costs and the associated emissions of the distributed energy sources in the MG for the cases studied are depicted in Figure 16. As shown, the operational costs and the associated emissions in the MG at each hour are greatly reduced from case 1 to cases 2 and 3. Despite that case 2 provides the least operational costs and the emissions in the MG in comparison to case 3, the penetration limit of the total output of the DGs in the MG exceeds the limits of the 60% penetration ratio, as detailed in Figure 9. In Figure 9, the penetration level in case 2 exceeds 100% at nine hours, where it reaches 129.96, 136.83, 143.25, 146.15, 145.67, 140.93, 126.89, 108.86, and 117.60% at hours 1–8 and 24, respectively.

4.4. Simulation Results of a Large-Scale 141-Bus Test System

In this subsection, the proposed solution methodology is applied on a large-scale 141-bus system. Three cases studied are investigated. The system’s initial power loss (without DGs) was 603.821 kW, where bus 87 has the minimum voltage that is 0.9294 Pu. In the 2nd case, the resulted uncertainties of the solar irradiance and wind speed are modeled by Beta-PDF and Weibull-PDF for the PV and WT sources, respectively. Therefore, the PV output power is evaluated at buses 60, 70, 80, 90, and 100. The active and reactive powers are hourly produced from the WT source at bus 50, as displayed in Figure 17.
On the other side, the BGs are operated at their full capacity without optimal control. By running the load flow algorithm for these hourly circumstances, Figure 18 shows the total active power of each type of DG and the summation of loads and losses at each hour. During 9 h (1–8 and 24), there is surplus active power to be generated from the DGs in the MG and injected to the grid bus, where the generated power from the DGs in the MG is greater than the loads and the power losses so that the excess power is back to the grid bus. In the other 15 h, the MG absorbs active power from the grid bus.
In the third case, the developed EO algorithm is applied to optimally operate the MG in order to minimize the operational costs and the accompanied pollutants simultaneously over a 24-h scheduling horizon. Based on the developed EO, the output powers of the PV, WT, and BGs are optimized besides the associated power factors of the BGs. Figure 19a shows the percentage apparent power of the BGs at buses 109, 16, 78, and 63 for each hour, whereas Figure 19b displays the hourly optimized value of the power factor.
To describe the power balance operation of the MG for each hour, Figure 20 illustrates the total active power of each type of DG and the summation of loads and power losses at each hour. At each hour, the generated grid power is always higher than 40% of summation loads and power losses whereas the penetration level of 60% is preserved by means of the developed EO algorithm.
For each hour, Figure 21 displays the minimum voltage for the three-cases studied. For hours 8–23, the minimum voltages are corrected in cases 2 and 3. In addition, in cases 2 and 3, the minimum voltages at all hours are above the permissible limit of 0.95 Pu. In the initial case (case 1), the highest minimum voltage occurs at bus 87 at hour 5, whereas the least minimum voltage occurs at the same bus at hour 15. At both hours, the voltage profile at all MG buses is described in Figure 22. However, the voltage profile at each bus is improved at light loading at hour 5. At this loading hour, bus 87 has the minimum voltage level in case 3. It is declined from 0.9616 to 0.9914 Pu. Additionally, the voltage profile at each bus is corrected at peak loading at hour 15, where the bus 87 has the minimum voltage level in case 3 that is declined from 0.9294 to 0.9772 Pu which exceeds the minimum limit of 0.95 Pu; consequently, this improvement represents 5.14%.
Moreover, the active power losses at each hour for the three cases studied are depicted in Figure 23. The power losses at each hour are greatly reduced from case 1 to cases 2 and 3, whereas the optimal operating strategy based on the developed EO algorithm in case 3 provides the minimum power losses at each hour through the day. Compared to case 1, the percentages of the reduction in power losses that are achieved by case 3 reached 78.9, 67.3, 58.0, 70.0, 77.1, 64.8, 49.5, 72.5, 79.9, 84.1, 80.2, 79.3, 80.6, 80.4, 73.8, 80.7, 79.9, 75.6, 73.4, 77.7, 80.4, 80.9, 77.2, and 71.3% for hours 1–24, respectively. Compared to case 2, the percentages of the reduction in power losses that are achieved by case 3 reached 66.7, 54.9, 48.3, 65.3, 73.2, 54.2, 13.3, 32.4, 38.9, 46.7, 32.0, 28.0, 32.8, 32.2, 11.9, 37.7, 38.5, 27.0, 23.7, 34.9, 41.9, 41.5, 34.1, and 42.6% for hours 1–24, respectively.
Additionally, the operational costs and the associated emissions of the distributed energy sources in the MG at each hour for the three cases studied are depicted in Figure 24. However, the operational costs and the associated emissions in the MG at each hour are greatly reduced from case 1 to cases 3 and 2. Despite case 2 providing the least operational costs and the emissions in the MG in comparison to case 3, the penetration limit of the total output of the DGs in the MG exceeds the limits of the 60% penetration ratio, as described by Figure 18.

5. Conclusions

  • The optimal operating strategy based on the developed equilibrium optimization (EO) technique has been presented and is proposed in order to minimize the operational costs and the accompanied pollutants simultaneously over a 24-h scheduling horizon.
  • Several renewable DGs have been investigated in the understudy MG, consisting of biomass generators (BG), wind turbines (WTs), and photovoltaics (PV).
  • The uncertainties of wind speed and solar irradiation have been considered via Weibull and Beta-PDF with different states of mean and standard deviation at each hour, respectively.
  • The developed EO methodology has been tested on the IEEE 33-bus system and the practical large-scale 141-bus system of AES-Venezuela in the metropolitan area of Caracas to verify its effectiveness and efficiency.
  • Added to that, the optimal operation of MG using the developed EO has been compared with other recent algorithms of DE and RAO algorithms.
  • Based on the developed EO, the hourly output powers of the PV, WTs, and BGs are optimized, as are the associated power factors of the BGs.
  • Significant benefits of the optimal operation of a typical MG using the developed EO have been demonstrated by minimizing the operational costs and emissions while preserving the penetration level of the DGs by 60%.
  • The voltage profiles of the MG operation for every hour have been greatly improved, with the minimum voltage adjusted within the permitted limit of [0.95–1.05] p.u.
  • The active power losses per hour have been significantly decreased.

Author Contributions

Data curation, N.A.N.; Formal analysis, S.M.A., N.A.N. and A.M.S. (Abdullah M. Shaheen); Funding acquisition, A.M.S. (Adel M Sharaf); Investigation, N.A.N.; Methodology, R.A.E.-S., N.A.N. and A.M.S. (Abdullah M. Shaheen); Project administration, S.M.A.; Resources, R.A.E.-S. and S.M.A.; Software, N.A.N. and A.M.S. (Abdullah M. Shaheen); Supervision, A.A.A.E.-E. and S.M.A.; Validation, A.A.A.E.-E. and R.A.E.-S.; Writing—review and editing, A.A.A.E.-E., R.A.E.-S. and A.M.S. (Adel M Sharaf). All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Institutional Review Board Statement

The study did not require ethical approval.

Informed Consent Statement

Not applicable.

Data Availability Statement

Data is contained within the article.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Shahooei, Z.; Martin, L.; Nehrir, H.; Bahramipanah, M. A Novel Agent-Based Power Management Scheme for Smart Multiple-Microgrid Distribution Systems. Energies 2022, 15, 1774. [Google Scholar] [CrossRef]
  2. Konneh, K.V.; Adewuyi, O.B.; Lotfy, M.E.; Sun, Y.; Senjyu, T. Application Strategies of Model Predictive Control for the Design and Operations of Renewable Energy-Based Microgrid: A Survey. Electronics 2022, 11, 554. [Google Scholar] [CrossRef]
  3. Guoping, Z.; Weijun, W.; Longbo, M. An Overview of Microgrid Planning and Design Method. In Proceedings of the 2018 IEEE 3rd Advanced Information Technology, Electronic and Automation Control Conference (IAEAC), Chongqing, China, 12–14 October 2018; pp. 326–329. [Google Scholar] [CrossRef]
  4. Su, W.; Wang, J. Energy Management Systems in Microgrid Operations. Electr. J. 2012, 25, 8. [Google Scholar] [CrossRef]
  5. Shaheen, A.M.; Elattar, E.E.; El-Sehiemy, R.A.; Elsayed, A.M. An Improved Sunflower Optimization Algorithm-Based Monte Carlo Simulation for Efficiency Improvement of Radial Distribution Systems Considering Wind Power Uncertainty. IEEE Access 2020, 9, 2332–2344. [Google Scholar] [CrossRef]
  6. Bayoumi, A.S.; El-Sehiemy, R.A.; Mahmoud, K.; Lehtonen, M.; Darwish, M.M.F. Assessment of an Improved Three-Diode against Modified Two-Diode Patterns of MCS Solar Cells Associated with Soft Parameter Estimation Paradigms. Appl. Sci. 2021, 11, 1055. [Google Scholar] [CrossRef]
  7. Sood, V.K.; Ali, M.Y.; Khan, F. Energy Management System of a Microgrid Using Particle Swarm Optimization (PSO) and Communication System. In Lecture Notes in Electrical Engineering; Springer: Berlin/Heidelberg, Germany, 2020; p. 625. [Google Scholar]
  8. Vera, Y.E.G.; Dufo-López, R.; Bernal-Agustín, J.L. Energy Management in Microgrids with Renewable Energy Sources: A Literature Review. Appl. Sci. 2019, 9, 3854. [Google Scholar] [CrossRef] [Green Version]
  9. Shaheen, A.M.; Elsayed, A.M.; Ginidi, A.R.; Elattar, E.E.; El-Sehiemy, R.A. Effective Automation of Distribution Systems with Joint Integration of DGs/ SVCs Considering Reconfiguration Capability by Jellyfish Search Algorithm. IEEE Access 2021, 9, 92053–92069. [Google Scholar] [CrossRef]
  10. Shaheen, A.M.; Elsayed, A.M.; El-Sehiemy, R.A.; Ginidi, A.R.; Elattar, E. Optimal management of static volt-ampere-reactive devices and distributed generations with reconfiguration capability in active distribution networks. Int. Trans. Electr. Energy Syst. 2021, 31, e13126. [Google Scholar] [CrossRef]
  11. Elattar, E.E.; Shaheen, A.M.; El-Sayed, A.M.; El-Sehiemy, R.A.; Ginidi, A.R. Optimal Operation of Automated Distribution Networks Based-MRFO Algorithm. IEEE Access 2021, 9, 19586–19601. [Google Scholar] [CrossRef]
  12. Shaheen, A.M.; El-Sehiemy, R.A. Optimal allocation of capacitor devices on MV distribution networks using crow search algorithm. CIRED Open Access Proc. J. 2017, 2017, 2453–2457. [Google Scholar] [CrossRef] [Green Version]
  13. Bidgoli, M.A.; Payravi, A.R.; Ahmadian, A.; Yang, W. Optimal day-ahead scheduling of autonomous operation for the hybrid micro-grid including PV, WT, diesel generator, and pump as turbine system. J. Ambient Intell. Humaniz. Comput. 2021, 12, 961–977. [Google Scholar] [CrossRef]
  14. Sridhar, N.; Kowsalya, M. Enhancement of power management in micro grid system using adaptive ALO technique. J. Ambient Intell. Humaniz. Comput. 2021, 12, 2163–2182. [Google Scholar] [CrossRef]
  15. Funde, N.; Dhabu, M.; Deshpande, P. CLOES: Cross-layer optimal energy scheduling mechanism in a smart distributed multi-microgrid system. J. Ambient Intell. Humaniz. Comput. 2020, 11, 4765–4783. [Google Scholar] [CrossRef]
  16. Hosseinnia, H.; Nazarpour, D.; Talavat, V. Multi-objective optimization framework for optimal planning of the microgrid (MG) under employing demand response program (DRP). J. Ambient Intell. Humaniz. Comput. 2018, 10, 2709–2730. [Google Scholar] [CrossRef]
  17. Maulik, A.; Das, D. Optimal operation of microgrid using four different optimization techniques. Sustain. Energy Technol. Assess. 2017, 21, 100–120. [Google Scholar] [CrossRef]
  18. Shaheen, A.M.; Ginidi, A.R.; El-Sehiemy, R.A.; Elattar, E.E. Optimal economic power and heat dispatch in Cogeneration Systems including wind power. Energy 2021, 225, 120263. [Google Scholar] [CrossRef]
  19. Ginidi, A.; Elsayed, A.; Shaheen, A.; Elattar, E.; El-Sehiemy, R. An Innovative Hybrid Heap-Based and Jellyfish Search Algorithm for Combined Heat and Power Economic Dispatch in Electrical Grids. Mathematics 2021, 9, 2053. [Google Scholar] [CrossRef]
  20. El-Sehiemy, R.; Elsayed, A.; Shaheen, A.; Elattar, E.; Ginidi, A. Scheduling of Generation Stations, OLTC Substation Transformers and VAR Sources for Sustainable Power System Operation Using SNS Optimizer. Sustainability 2021, 13, 11947. [Google Scholar] [CrossRef]
  21. Omotoso, H.O.; Al-Shaalan, A.M.; Farh, H.M.H.; Al-Shamma’a, A.A. Techno-Economic Evaluation of Hybrid Energy Systems Using Artificial Ecosystem-Based Optimization with Demand Side Management. Electronics 2022, 11, 204. [Google Scholar] [CrossRef]
  22. Zhu, Z.; Weng, Z.; Zheng, H. Optimal Operation of a Microgrid with Hydrogen Storage Based on Deep Reinforcement Learning. Electronics 2022, 11, 196. [Google Scholar] [CrossRef]
  23. Wu, X.; Li, S.; Gan, S.; Hou, C. An Adaptive Energy Optimization Method of Hybrid Battery-Supercapacitor Storage System for Uncertain Demand. Energies 2022, 15, 1765. [Google Scholar] [CrossRef]
  24. Reddy, S.S.; Park, J.Y.; Jung, C.M. Optimal operation of microgrid using hybrid differential evolution and harmony search algorithm. Front. Energy 2016, 10, 355–362. [Google Scholar] [CrossRef]
  25. Reddy, S.S. Optimal Operation of Microgrid considering Renewable Energy Sources, Electric Vehicles and Demand Response. In Proceedings of the 1st International Conference on Sustainable Energy and Future Electric Transportation (SeFet 2019), Hyderabad, India, 14–16 February 2019; EDP Sciences: Les Ulis, France, 2019; Volume 7, p. 01007. [Google Scholar]
  26. Wang, Y.; Li, F.; Yu, H.; Wang, Y.; Qi, C.; Yang, J.; Song, F. Optimal operation of microgrid with multi-energy complementary based on moth flame optimization algorithm. Energy Sources Part A Recover. Util. Environ. Eff. 2020, 42, 785–806. [Google Scholar] [CrossRef]
  27. Elsakaan, A.A.; El-Sehiemy, R.A.; Kaddah, S.S.; Elsaid, M.I. Optimal economic–emission power scheduling of RERs in MGs with uncertainty. IET Gener. Transm. Distrib. 2020, 14, 37–52. [Google Scholar] [CrossRef]
  28. Balasubramaniam, K.; Hadidi, R.; Makram, E. Optimal operation of microgrids under conditions of uncertainty. In Proceedings of the 2015 IEEE Power & Energy Society General Meeting, Denver, CO, USA, 26–30 July 2015; pp. 1–5. [Google Scholar] [CrossRef]
  29. Andrychowicz, M. Optimization of distribution systems by using RES allocation and grid development. In Proceedings of the 15th International Conference of European Energy Market, Łodź, Poland, 27–29 June 2018. [Google Scholar]
  30. Andrychowicz, M. RES and ES Integration in Combination with Distribution Grid Development Using MILP. Energies 2021, 14, 383. [Google Scholar] [CrossRef]
  31. Faramarzi, A.; Heidarinejad, M.; Stephens, B.; Mirjalili, S. Equilibrium optimizer: A novel optimization algorithm. Knowl.-Based Syst. 2020, 191, 105190. [Google Scholar] [CrossRef]
  32. Nusair, K.; Alhmoud, L. Application of Equilibrium Optimizer Algorithm for Optimal Power Flow with High Penetration of Renewable Energy. Energies 2020, 13, 6066. [Google Scholar] [CrossRef]
  33. Abdul-Hamied, D.T.; Shaheen, A.M.; Salem, W.A.; Gabr, W.I.; El-Sehiemy, R.A. Equilibrium optimizer based multi dimensions operation of hybrid AC/DC grids. Alex. Eng. J. 2020, 59, 4787–4803. [Google Scholar] [CrossRef]
  34. Agnihotri, S.; Atre, A.; Verma, H.K. Equilibrium optimizer for solving economic dispatch problem. In Proceedings of the PIICON 2020—9th IEEE Power India International Conference, Sonepat, India, 28 February–1 March 2020. [Google Scholar]
  35. El-Shorbagy, M.A.; Mousa, A.A. Constrained Multiobjective Equilibrium Optimizer Algorithm for Solving Combined Economic Emission Dispatch Problem. Complexity 2021, 2021, 6672131. [Google Scholar] [CrossRef]
  36. El-Ela, A.A.A.; Allam, S.M.; Shaheen, A.M.; Nagem, N.A. Optimal allocation of biomass distributed generation in distribution systems using equilibrium algorithm. Int. Trans. Electr. Energy Syst. 2020, 31, e12727. [Google Scholar] [CrossRef]
  37. Ahmed, D.; Ebeed, M.; Ali, A.; Alghamdi, A.; Kamel, S. Multi-Objective Energy Management of a Micro-Grid Considering Stochastic Nature of Load and Renewable Energy Resources. Electronics 2021, 10, 403. [Google Scholar] [CrossRef]
  38. El-Ela, A.A.A.; El-Seheimy, R.A.; Shaheen, A.M.; Wahbi, W.A.; Mouwafi, M.T. PV and battery energy storage integration in distribution networks using equilibrium algorithm. J. Energy Storage 2021, 42, 103041. [Google Scholar] [CrossRef]
  39. El Sayed, S.; Al Otaibi, S.; Ahmed, Y.; Hendawi, E.; Elkalashy, N.; Hoballah, A. Probabilistic Modeling and Equilibrium Optimizer Solving for Energy Management of Renewable Micro-Grids Incorporating Storage Devices. Energies 2021, 14, 1373. [Google Scholar] [CrossRef]
  40. Shaheen, A.M.; Hamida, M.A.; El-Sehiemy, R.A.; Elattar, E.E. Optimal parameter identification of linear and non-linear models for Li-Ion Battery Cells. Energy Rep. 2021, 7, 7170–7185. [Google Scholar] [CrossRef]
  41. Ghoneim, S.S.M.; Alharthi, M.M.; El-Sehiemy, R.A.; Shaheen, A.M. Prediction of Transformer Oil Breakdown Voltage with Barriers Using Optimization Techniques. Intell. Autom. Soft Comput. 2022, 31, 1593–1610. [Google Scholar] [CrossRef]
  42. El-Fergany, A. Optimal allocation of multi-type distributed generators using backtracking search optimization algorithm. Int. J. Electr. Power Energy Syst. 2015, 64, 1197–1205. [Google Scholar] [CrossRef]
  43. Hien, N.C.; Mithulananthan, N.; Bansal, R. Location and Sizing of Distributed Generation Units for Loadabilty Enhancement in Primary Feeder. IEEE Syst. J. 2013, 7, 797–806. [Google Scholar] [CrossRef]
  44. Gözel, T.; Hocaoglu, M.H. An analytical method for the sizing and siting of distributed generators in radial systems. Electr. Power Syst. Res. 2009, 79, 912–918. [Google Scholar] [CrossRef]
  45. El-Fergany, A. Multi-objective Allocation of Multi-type Distributed Generators along Distribution Networks Using Backtracking Search Algorithm and Fuzzy Expert Rules. Electr. Power Compon. Syst. 2015, 44, 252–267. [Google Scholar] [CrossRef]
  46. Ginidi, A.; Ghoneim, S.M.; Elsayed, A.; El-Sehiemy, R.; Shaheen, A.; El-Fergany, A. Gorilla Troops Optimizer for Electrically Based Single and Double-Diode Models of Solar Photovoltaic Systems. Sustainability 2021, 13, 9459. [Google Scholar] [CrossRef]
  47. Said, M.; Shaheen, A.M.; Ginidi, A.R.; El-Sehiemy, R.A.; Mahmoud, K.; Lehtonen, M.; Darwish, M.M.F. Estimating Parameters of Photovoltaic Models Using Accurate Turbulent Flow of Water Optimizer. Processes 2021, 9, 627. [Google Scholar] [CrossRef]
  48. Atwa, Y.M.; El-Saadany, E.F.; Salama, M.M.A.; Seethapathy, R. Optimal Renewable Resources Mix for Distribution System Energy Loss Minimization. IEEE Trans. Power Syst. 2009, 25, 360–370. [Google Scholar] [CrossRef]
  49. Soroudi, A.; Aien, M.; Ehsan, M. A Probabilistic Modeling of Photo Voltaic Modules and Wind Power Generation Impact on Distribution Networks. IEEE Syst. J. 2011, 6, 254–259. [Google Scholar] [CrossRef] [Green Version]
  50. IEEE. IEEE application guide for IEEE std 1547TM, IEEE standard for interconnecting distributed resources with electric power systems. IEEE 2009, 1–217. [Google Scholar] [CrossRef]
  51. Ahmed, A.; Nadeem, M.F.; Sajjad, I.A.; Bo, R.; Khan, I. Optimal Allocation of Wind DG with Time Varying Voltage Dependent Loads Using Bio-Inspired: Salp Swarm Algorithm. In Proceedings of the 2020 3rd International Conference on Computing, Mathematics and Engineering Technologies (iCoMET), Sukkur, Pakistan, 3–4 March 2020; pp. 1–7. [Google Scholar] [CrossRef]
  52. Murty, V.V.V.S.N.; Kumar, A. Optimal Energy Management and Techno-economic Analysis in Microgrid with Hybrid Renewable Energy Sources. J. Mod. Power Syst. Clean Energy 2020, 8, 929–940. [Google Scholar] [CrossRef]
  53. Rehman, W.U.; Khan, M.F.N.; Sajjad, I.A.; Afzaal, M.U. Probabilistic generation model for grid connected wind DG. J. Renew. Sustain. Energy 2019, 11, 045301. [Google Scholar] [CrossRef]
  54. Bentouati, B.; Khelifi, A.; Shaheen, A.M.; El-Sehiemy, R.A. An enhanced moth-swarm algorithm for efficient energy management based multi dimensions OPF problem. J. Ambient Intell. Humaniz. Comput. 2021, 12, 9499–9519. [Google Scholar] [CrossRef]
  55. Raglend, I.J.; Veeravalli, S.; Sailaja, K.; Sudheera, B.; Kothari, D. Comparison of AI techniques to solve combined economic emission dispatch problem with line flow constraints. Int. J. Electr. Power Energy Syst. 2010, 32, 592–598. [Google Scholar] [CrossRef]
  56. Eladl, A.A.; El Desouky, A.A. Optimal economic dispatch for multi heat-electric energy source power system. Int. J. Electr. Power Energy Syst. 2019, 110, 21–35. [Google Scholar] [CrossRef]
  57. Shaheen, A.; Elsayed, A.; Ginidi, A.; El-Sehiemy, R.; Elattar, E. Reconfiguration of electrical distribution network-based DG and capacitors allocations using artificial ecosystem optimizer: Practical case study. Alex. Eng. J. 2021, 61, 6105–6118. [Google Scholar] [CrossRef]
  58. El-Ela, A.A.A.; El-Sehiemy, R.A.; Shaheen, A.M.; Elllien, A.R. Multiobjective coyote optimization algorithm for techno-economic simultaneous placement of DGs and FCLs in distribution networks. Int. Trans. Electr. Energy Syst. 2021, 31, e13050. [Google Scholar] [CrossRef]
  59. Talaat, H.E.; Al-Ammar, E. Optimal allocation and sizing of Distributed Generation in distribution networks using Genetic Algorithms. In Proceedings of the 11th International Conference on Electrical Power Quality and Utilisation, Lisbon, Portugal, 17–19 October 2011; pp. 1–6. [Google Scholar]
  60. Shaheen, A.; Elsayed, A.; Ginidi, A.; El-Sehiemy, R.; Elattar, E. A heap-based algorithm with deeper exploitative feature for optimal allocations of distributed generations with feeder reconfiguration in power distribution networks. Knowl.-Based Syst. 2022, 241, 108269. [Google Scholar] [CrossRef]
  61. Shaheen, A.M.; Elsayed, A.M.; Ginidi, A.R.; El-Sehiemy, R.A.; Elattar, E.E. Improved Heap-Based Optimizer for DG Allocation in Reconfigured Radial Feeder Distribution Systems. IEEE Syst. J. 2022, 1–10. [Google Scholar] [CrossRef]
  62. Shaheen, A.M.; Elsayed, A.M.; El-Sehiemy, R.A.; Kamel, S.; Ghoneim, S.S.M. A modified marine predators optimization algorithm for simultaneous network reconfiguration and distributed generator allocation in distribution systems under different loading conditions. Eng. Optim. 2021, 1–22. [Google Scholar] [CrossRef]
  63. Shaheen, A.M.; El-Sehiemy, R.A.; Kamel, S.; Elattar, E.E.; Elsayed, A.M. Improving Distribution Networks’ Consistency by Optimal Distribution System Reconfiguration and Distributed Generations. IEEE Access 2021, 9, 67186–67200. [Google Scholar] [CrossRef]
  64. Abdel-Basset, M.; Chang, V.; Mohamed, R. A novel equilibrium optimization algorithm for multi-thresholding image segmentation problems. Neural Comput. Appl. 2020, 1–34. [Google Scholar] [CrossRef]
  65. Kefayat, M.; Ara, A.L.; Niaki, S.N. A hybrid of ant colony optimization and artificial bee colony algorithm for probabilistic optimal placement and sizing of distributed energy resources. Energy Convers. Manag. 2015, 92, 149–161. [Google Scholar] [CrossRef]
  66. Khodr, H.; Olsina, F.; Jesus, P.D.O.-D.; Yusta, J. Maximum savings approach for location and sizing of capacitors in distribution systems. Electr. Power Syst. Res. 2008, 78, 1192–1203. [Google Scholar] [CrossRef] [Green Version]
  67. Nasef, A.; Shaheen, A.; Khattab, H. Local and remote control of automatic voltage regulators in distribution networks with different variations and uncertainties: Practical cases study. Electr. Power Syst. Res. 2022, 205, 107773. [Google Scholar] [CrossRef]
  68. Grigg, C.; Wong, P.; Albrecht, P.; Allan, R.; Bhavaraju, M.; Billinton, R.; Chen, Q.; Fong, C.; Haddad, S.; Kuruganty, S.; et al. The IEEE Reliability Test System-A report prepared by the Reliability Test System Task Force of the Application of Probability Methods Subcommittee. IEEE Trans. Power Syst. 1999, 14, 1010–1020. [Google Scholar] [CrossRef]
  69. Shaheen, A.M.; El-Sehiemy, R.A. Optimal Coordinated Allocation of Distributed Generation Units/ Capacitor Banks/ Voltage Regulators by EGWA. IEEE Syst. J. 2021, 15, 257–264. [Google Scholar] [CrossRef]
  70. Shafei, M.A.R.; Anwar, Y.A.; Ibrahim, D.K. Sharm El-Sheikh 5 MW PV Plant Performance, Environmental Impact and Grid Connection Parameters. In Proceedings of the 2019 21st International Middle East Power Systems Conference (MEPCON), Cairo, Egypt, 17–19 December 2019; pp. 790–795. [Google Scholar]
  71. Basu, M. Combined heat and power dynamic economic dispatch with demand side management incorporating renewable energy sources and pumped hydro energy storage. IET Gener. Transm. Distrib. 2019, 13, 3771–3781. [Google Scholar] [CrossRef]
  72. Owens, E.; Chapman, S. Valuing the Greenhouse Gas Emissions from Wind Power. Int. J. Energy Eng. 2013, 3, 41–54. [Google Scholar] [CrossRef]
  73. Soroudi, A.; Ehsana, M.; Zareipour, H. A practical eco-environmental distribution network planning model including fuel cells and non-renewable distributed energy resources. Renew. Energy 2011, 36, 179–188. [Google Scholar] [CrossRef] [Green Version]
  74. Shaheen, A.M.; El-Sehiemy, R.A.; Farrag, S.M. A reactive power planning procedure considering iterative identification of VAR candidate buses. Neural Comput. Appl. 2017, 31, 653–674. [Google Scholar] [CrossRef]
  75. Rao, R.V. Rao algorithms: Three metaphor-less simple algorithms for solving optimization problems. Int. J. Ind. Eng. Comput. 2020, 11, 107–130. [Google Scholar] [CrossRef]
Figure 1. Evaluation of PV output power considering the uncertainties in solar irradiance.
Figure 1. Evaluation of PV output power considering the uncertainties in solar irradiance.
Electronics 11 00815 g001
Figure 2. Evaluation of WT output power considering the uncertainties in wind speed.
Figure 2. Evaluation of WT output power considering the uncertainties in wind speed.
Electronics 11 00815 g002
Figure 3. Flowchart of the optimal proposed operation procedure of MG.
Figure 3. Flowchart of the optimal proposed operation procedure of MG.
Electronics 11 00815 g003
Figure 4. First MG configuration.
Figure 4. First MG configuration.
Electronics 11 00815 g004
Figure 5. Second MG configuration.
Figure 5. Second MG configuration.
Electronics 11 00815 g005
Figure 6. Daily load demand profile.
Figure 6. Daily load demand profile.
Electronics 11 00815 g006
Figure 7. Scheduled output power from each PV at each hour for the first MG.
Figure 7. Scheduled output power from each PV at each hour for the first MG.
Electronics 11 00815 g007
Figure 8. Scheduled active and reactive power from wind at each hour for the first MG system.
Figure 8. Scheduled active and reactive power from wind at each hour for the first MG system.
Electronics 11 00815 g008
Figure 9. Results of the first MG operation without optimal control.
Figure 9. Results of the first MG operation without optimal control.
Electronics 11 00815 g009
Figure 10. Convergence curves of EO, DE and RAO for the first MG at hours 6 and 12, respectively.
Figure 10. Convergence curves of EO, DE and RAO for the first MG at hours 6 and 12, respectively.
Electronics 11 00815 g010
Figure 11. Hourly Percentage apparent power and power factor for each BG for the first MG system.
Figure 11. Hourly Percentage apparent power and power factor for each BG for the first MG system.
Electronics 11 00815 g011
Figure 12. Results of the optimal operation of the first MG.
Figure 12. Results of the optimal operation of the first MG.
Electronics 11 00815 g012
Figure 13. Minimum voltage at each hour for different cases studied of the first MG.
Figure 13. Minimum voltage at each hour for different cases studied of the first MG.
Electronics 11 00815 g013
Figure 14. Voltage profile for the first MG at light and peak loading at hours 5 and 15, respectively.
Figure 14. Voltage profile for the first MG at light and peak loading at hours 5 and 15, respectively.
Electronics 11 00815 g014
Figure 15. Active power losses at each hour for different cases for the first MG.
Figure 15. Active power losses at each hour for different cases for the first MG.
Electronics 11 00815 g015
Figure 16. Hourly optimal operational costs and the associated emissions in the MG for the first MG.
Figure 16. Hourly optimal operational costs and the associated emissions in the MG for the first MG.
Electronics 11 00815 g016
Figure 17. Hourly produced active and reactive power from PV and WT sources for the second MG.
Figure 17. Hourly produced active and reactive power from PV and WT sources for the second MG.
Electronics 11 00815 g017
Figure 18. Results of the second MG operation without optimal control.
Figure 18. Results of the second MG operation without optimal control.
Electronics 11 00815 g018
Figure 19. Hourly apparent power and power factor of each BG for case 3 for the second MG.
Figure 19. Hourly apparent power and power factor of each BG for case 3 for the second MG.
Electronics 11 00815 g019
Figure 20. Results of the optimal operation for the second MG.
Figure 20. Results of the optimal operation for the second MG.
Electronics 11 00815 g020
Figure 21. Minimum voltage profiles for different cases studied at each hour for the second MG.
Figure 21. Minimum voltage profiles for different cases studied at each hour for the second MG.
Electronics 11 00815 g021
Figure 22. Bus voltage profiles for different cases studied at hours 5 and 15 for the second MG.
Figure 22. Bus voltage profiles for different cases studied at hours 5 and 15 for the second MG.
Electronics 11 00815 g022
Figure 23. Active power losses for different cases studied at each hour for the second MG.
Figure 23. Active power losses for different cases studied at each hour for the second MG.
Electronics 11 00815 g023
Figure 24. Hourly optimal operational costs and the associated emissions in the second MG.
Figure 24. Hourly optimal operational costs and the associated emissions in the second MG.
Electronics 11 00815 g024
Table 1. Operational costs as well as emissions of the renewable sources and the grid.
Table 1. Operational costs as well as emissions of the renewable sources and the grid.
Energy SourceCO2 Emission (Ton Co2/MWh)Operational Costs ($/MWh)
BGEBG = 0.733 [36] cBG = 46 [36]
GridEgrid = 0.91 [36]cgrid = 76 [36]
PVEpv = 0.045 [70]cpv = 6 [71]
WTEw = 0.016 [72]cw = 7 [71]
Price penalty factorH = 10 $/Ton Co2 [73]
Table 2. Optimal operations of MG at hour 6 using EO, DE, and RAO algorithms.
Table 2. Optimal operations of MG at hour 6 using EO, DE, and RAO algorithms.
EODERAO
Pw (kW)423.1423.1423.1
Qw (kVAR)−57.1605 *−57.1605 *−57.1605 *
Ppv (kW)0.2696, 0.3378, 0.4059, 0.5392, 0.67550.2697, 0.3379, 0.4058, 0.5392, 0.67550.2696, 0.3378, 0.4059, 0.5392, 0.6755
kW PBG (Power factor)304.0531 (0.8508), 0.043 (0.8514), 70.7528 (0.9895), 492.6431 (0.925)391.616 (0.9878), 330.0176 (0.8794), 83.1291 (0.85), 55.6774 (0.9869)315.214 (0.9889), 213.145 (0.8535), 1.449 (0.8521), 337.6556 (0.8501)
Pgrid (kW)879.0094888.9166879.1928
Pu Vmin (bus)0.9761(18)0.9795(33)0.9796(33)
PTloss (kW)17.129419.984717.2843
CBG ($)39.904639.580239.9033
Cw ($)2.96193.26743.0122
CPV ($)0.01972.32820.0915
Cgrid ($)66.804767.557766.8187
EBG ($)6.70576.65126.7055
Egrid ($)7.9998.08918.0007
Epv ($)0.0010.0010.001
Ew ($)0.06770.06770.0677
OCt ($)109.691112.7335110
Et ($)14.773414.80914.7748
Objective function ($)124.4644127.5425124.6005
* negative sign means that wind consumes reactive power.
Table 3. Optimal operation of MG at hour 12 using EO, DE, and RAO algorithms.
Table 3. Optimal operation of MG at hour 12 using EO, DE, and RAO algorithms.
EODERAO
Pw (kW)437.4437.4002437.4
Qw (kVAR)−57.6528 *−57.6528 *−57.6528 *
Ppv (kW)11.0451, 13.8367, 16.6283, 22.0901, 27.673311.0452, 13.8367, 16.6281, 22.09, 27.673311.0451, 13.8367, 16.6283, 22.0901, 27.6733
kW PBG (Power factor)853.2986 (0.8537), 243.3503 (0.8663), 17.8781 (0.8866), 585.7994 (0.85)853.9887(0.9),
400.0 (1),
347.2767 (0.85),
848.6954 (0.8505), 312.6636 (0.8506), 126.229 (0.85), 410.301 (0.85)
Pgrid (kW)152016401517.6
Pu Vmin (bus)0.9787 (18)0.9533 (18)0.9774 (18)
PTloss (kW)31.331157.749429.1443
CBG ($)78.21573.658278.1029
CW ($)3.06184.79793.143
CPV ($)0.54774.02740.5887
Cgrid ($)115.3172124.8536115.3362
EBG ($)13.143512.377813.1247
Egrid ($)13.807714.949613.81
Epv ($)0.04110.04110.0411
Ew ($)0.070.070.07
OCt ($)197.1416207.337197.1708
Et ($)27.062327.438427.0457
Objective function ($)224.2039234.7754224.2165
* negative sign means that wind consumes reactive power.
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Abou El-Ela, A.A.; El-Sehiemy, R.A.; Allam, S.M.; Shaheen, A.M.; Nagem, N.A.; Sharaf, A.M. Renewable Energy Micro-Grid Interfacing: Economic and Environmental Issues. Electronics 2022, 11, 815. https://doi.org/10.3390/electronics11050815

AMA Style

Abou El-Ela AA, El-Sehiemy RA, Allam SM, Shaheen AM, Nagem NA, Sharaf AM. Renewable Energy Micro-Grid Interfacing: Economic and Environmental Issues. Electronics. 2022; 11(5):815. https://doi.org/10.3390/electronics11050815

Chicago/Turabian Style

Abou El-Ela, Adel A., Ragab A. El-Sehiemy, Sohir M. Allam, Abdullah M. Shaheen, Nadia A. Nagem, and Adel M. Sharaf. 2022. "Renewable Energy Micro-Grid Interfacing: Economic and Environmental Issues" Electronics 11, no. 5: 815. https://doi.org/10.3390/electronics11050815

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop