Article

Four-Quadrant Operations of Bidirectional Chargers for Electric Vehicles in Smart Car Parks: G2V, V2G, and V4G

1
School of Electrical Engineering, Beijing Jiaotong University, Beijing 100044, China
2
Faculty of Engineering and Information Technology, University of Technology Sydney, Sydney, NSW 2007, Australia
*
Author to whom correspondence should be addressed.
Energies 2021, 14(1), 181; https://doi.org/10.3390/en14010181
Submission received: 20 November 2020 / Revised: 22 December 2020 / Accepted: 24 December 2020 / Published: 31 December 2020
(This article belongs to the Special Issue Power Quality in Electrified Transportation Systems)

Abstract

:
This paper presents the four-quadrant operation modes of bidirectional chargers for electric vehicles (EVs) framed in smart car parks. A cascaded model predictive control (MPC) scheme for the bidirectional two-stage off-board chargers is proposed. The controller is constructed in two stages. The model predictive direct power control for the grid side is applied to track the active/reactive power references. The model predictive direct current control is proposed to achieve constant current charging/discharging for the EV load side. With this MPC strategy, EV chargers are able to transmit the active and reactive powers between the EV batteries and the power grid. Apart from exchanging the active power, the vehicle-for-grid (V4G) mode is proposed, where the chargers are used to deliver the reactive power to support the grid, simultaneously combined with grid-to-vehicle or vehicle-to-grid operation modes. In the V4G mode, the EV battery functions as the static var compensator. According to the simulation results, the system can operate effectively in the full control regions of the active and reactive power (PQ) plane under the aforementioned operation modes. Fast dynamic response and great steady-state system performances can be verified through various simulation and experimental results.

Graphical Abstract

1. Introduction

Electric vehicles (EVs), including railway, public service, and personal vehicles, play an important role in building a clean and efficient environment in the transportation market [1,2,3,4,5]. They reduces the pollution, gas emissions, and the reliability of fuel oil. With the permeation of EVs in recent decades, they are considered a new major load in the main grid and distributed systems [6]. When connected to the grid, EV batteries can deliver power to the grid as energy storage devices. When the EVs consume power, it is denoted as a grid-to-vehicle (G2V) operation. On the other hand, it is known as a vehicle-to-grid (V2G) operation when the energy is provided from the EVs to the grid [7,8]. Therefore, the installation of bidirectional EV charging stations is needed to fulfill the demands mentioned above.
As a new paradigm of transport devices, EV batteries have the ability to compensate the grid with active power via the bidirectional chargers. The current chargers can be classified into several types in terms of the location (on-/off-board) and function (unidirectional/bidirectional) [9]. In a recent work, Kwon et al. proposed an electrolytic capacitor bidirectional EV charger to exchange the active power between the grid, EVs, and smart homes [10]. In [11], Zahid designed a bidirectional DC/DC resonant converter to reduce the cost and size of the chargers for V2G operation. As control methods for converters have developed in recent years, it is now possible for the EVs to exchange the reactive power with the main grid, in addition to the active power. A system in which EVs can participate in the microgrids as the reactive power provider was presented in [12]. The economic efficiency from different aspects, including the energy market, reactive market, and lost opportunities, was analyzed to show the effectiveness of EV participation. The reactive power compensation capabilities of EVs in two different bidirectional battery converter topologies were investigated in [13]. EV batteries were used as static var compensators to support the main grid; this was named the vehicle-for-grid (V4G) mode in this paper. Under this working condition, the reactive power is transmitted between the EVs and the power grid. In [14], the EV batteries could operate only in the V2G mode or with reactive power operation. It is impossible for the controller to meet the active and reactive power requirements at the same time. In [15,16], reactive power could be controlled to be provided from/to the EVs. According to the types of the operation modes, the current references of the EV and grid sides were generated and sent to be used according to the pulse width modulation (PWM) strategy. Then, the bidirectional chargers were able to operate in the V2G/G2V/V4G modes in smart grids or homes.
Compared with the PWM strategies for current-tracking targets used in [14,15,16], an advanced model predictive control (MPC) algorithm was proposed with no need for modulation. Due to its easy implementation and its combination of multiple objectives, the MPC scheme has recently attracted researchers [17,18]. The adoption of the MPC method strongly depends on the calculation speed of the components and system. With the application of microprocessors, it is now possible to apply it in the MPC method to control powered electronic devices [19]. A cost function was designed to select an optimal switching state for the next sampling period [20]. The model predictive direct power control with duty cycle optimization was proposed to control the PWM rectifier [21]. A nonzero vector and a zero vector operating with optimal control times were selected to achieve better system performance. In [22], the model predictive current control was applied on the grid side to track the grid current reference. Currently, the predictive control strategy is used for unidirectional power flow in general. The active power is delivered from the grid side to the load side.
To achieve bidirectional active/reactive power flow (four-quadrant operation), a cascaded model predictive control is proposed in this paper. The controller is divided into two parts. One is for the active and reactive power control used in the grid side, denoted as the model predictive direct power control (MPDPC). The combination of the active and reactive powers’ errors is designed as the cost function. It is used to track the active/reactive power demands for the power grid. Another is the current control for the EV side to achieve a constant current charging target, which is named the model predictive direct current control (MPDCC). The key novelties of the paper can be summarized as follows: (1) The active and reactive powers can be controlled independently with the cascaded predictive control; (2) EV batteries regarded as the reactive power generator (V4G mode) are proposed to support the main grid; (3) the initial constant current control for charging/discharging operation is available on the load side.
In this paper, a three-phase laboratory converter and a DC/DC half-bridge converter were developed as the bidirectional EV charger. Simulation and experimental tests were implemented to verify the proposed method in the four-quadrant operation. The detailed working scenarios were: (1) the pure G2V operation mode; (2) the pure V2G operation mode; (3) the pure inductive V4G operation mode; (4) the pure capacitive V4G operation mode; (5) the G2V along with the inductive V4G operation mode; (6) the V2G along with the inductive V4G operation mode; (7) the V2G along with the capacitive V4G operation mode; (8) the G2V along with the capacitive V4G operation mode. It should be noted that the inductive/capacitive operation refers to positive/negative reactive power during the transmission.
The rest of this paper is presented as follows. Section 2 discusses the topologies, application fields, and pros and cons of the unidirectional and bidirectional chargers. In Section 3, the selected off-board EV battery charger prototype is introduced and the proposed MPC methods for both the first stage and second stage are explained in detail. Section 4 and Section 5 present the simulation and experimental results of the bidirectional charger under the G2V, V2G, and V4G operation modes. Finally, the conclusions are shown in Section 6.

2. Electric Vehicle Battery Chargers for Smart Car Park Integration

According to the power flow direction, the types of EV chargers can be summarized as: unidirectional/bidirectional with on-/off-board chargers [23]. The active and reactive power (PQ) coordinate in Figure 1 shows the full control region for EV battery chargers. The positive directions of P and Q represent the power being delivered from the grid to the EVs. According to the direction of active and reactive power transmission, the PQ plane can be divided into eight operation modes. The xy axes of the PQ frame, defined as Modes I–IV, represent the pure G2V, inductive V4G, V2G, and capacitive V4G operations, respectively. The other four quadrants show the V2G or G2V operation along with the capacitive or inductive V4G operation.

2.1. Unidirectional Chargers

Unidirectional chargers can only operate on the positive x-axis (i.e., P ≥ 0) of the P-Q coordinates (Modes I, V, and VIII), as shown in Figure 1. EVs can only be charged. On the other hand, reactive power is able to be transmitted during the battery charging process. However, low-frequency current harmonics will be introduced in the utility, which is inadvisable [24]. Therefore, these chargers are used to achieve a unity power factor operation, as presented in Mode I.
Various topologies have been studied for both single- and three-phase unidirectional chargers with half-bridge, full-bridge, or multilevel topologies. Considering the cost, size, and component stresses of the chargers, different topology circuits are applied in diverse application fields. The power factor correction boost converter, a conventional topology, is used in the low-power-level application [24]. To increase the application power level, some advanced topologies were proposed and discussed, such as the interleaved AC/DC boost converter, inverting or positive buck/boost PFC converter, and the multilevel converter [23,25].

2.2. Bidirectional Chargers

To make full use of EV batteries, smart chargers with V2G technology have been proposed and extensively studied. With the G2V and V2G technologies, the active power can be transferred to the EV batteries and returned back to the grid. They are controlled for operation in all regions of the PQ plane. This kind of bidirectional charger takes into account the grid’s and EV drivers’ energy demands. Along with optimal charging/discharging schemes, potential commercial benefits stemming from EV chargers can be achieved, as discussed in our previous work [26]. Apart from transmitting the active power in V2G/G2V operations, reactive power (inductive or capacitive) can be provided by the batteries to improve the power quality. During the reactive power operation process, the EV batteries can be regarded as capacitor banks, static compensators, etc. Note that it is impossible for the state of charge (SOC) and lifetime of the batteries to be affected when operating as a reactive power provider [16]. However, due to the increasing charge–discharge cycles, the DC-link filter capacitor is affected under this reactive power support condition.
Figure 2 shows the typical single-/three-phase bidirectional battery chargers, respectively. There are three power level types for EV chargers, namely, Level 1, Level 2, and Level 3. Most EV chargers are able to be plugged into a home or office outlet for Level 1 (slow charging) or Level 2 [23]. They are usually designed for on-board chargers for private or public facilities with a single-phase topology. For commercial applications, such as shopping malls and official car parking spots, three-phase structures are normally applied with Level 2 or 3 (fast-charging) chargers installed for off-board charging. The EVs can be controlled to fully charge within two or three hours. Therefore, the three-phase circuits are selected and studied for the smart car park in this paper.

3. Proposed System and Control Scheme for Bidirectional Power Flow

With the integration of EVs, car parks located in workplaces or shopping malls show enormous potential for getting EVs involved in the grid. To exploit this commercial potential, a smart car park where large populations of EVs would be parked was proposed in a previous work [26]. The proposed smart car park system consists of bidirectional charging stations, a control center, and energy storage devices, as presented in Figure 3. The active/reactive power management system can be regarded as a central controller. The power demands from the EVs and storage system (such as a supercapacitor/flywheel) are sent to this central controller. Optimal control strategies are applied to generate the control signals. The switching states are transferred to drive the relevant converters or devices.
The bidirectional chargers should be controlled to track the active/reactive power and charging/discharging current references provided from the grid and EVs, respectively. Due to the easy implementation and ability to fulfill multiple objectives, the proposed MPC method is designed to track these targets. The classical topology in Figure 2b is used for energy storage systems with the bidirectional power flow [27]. However, as a boost converter, the range of the battery voltage is limited, varying from the grid peak voltage to the battery maximum voltage [28], which will be proved later in this section.
Considering that the common nominal battery voltage is between 300 and 400 V, an AC/DC boost converter, the typical topology, is preferred in the rectification stage with a 120/240 V grid connection [25]. A DC/DC half-bridge bidirectional converter is used to interface with the EV batteries. With this DC/DC converter, the low boundary of the charging/discharging range can be enlarged from the peak value of the grid voltage to 0 V.
Based on the above analysis, a three-phase two-stage converter is used as the off-board bidirectional charger, as depicted in Figure 4. The two-level AC/DC converter is connected with the power grid via a line resistance (R) and a filter inductor (L). A filter capacitor (C) is connected on the DC bus to smooth the DC voltage. The half-bridge DC/DC converter is applied as the second stage. An output inductor ( L d c ) connecting the battery is used on the DC side.
The switching signals of the three-phase AC/DC converter are defined as
S k = 1 S 1 or S 3 , or S 5 is on 0 S 2 or S 4 , or S 6 is on ,
where k = a, b, c phase.
The switching state is transformed into the stationary α β coordinate system, written as
S α β = 2 3 1 1 2 1 2 0 3 2 3 2 S abc ,
where
S α β = S α S β , S abc = S a S b S c .
Similarly, the input voltage of the AC/DC converter in the α β coordinates can be expressed as:
V α β = V α V β = S α β V d c = S α S β V d c .
The eight possible switching states and the corresponding input voltage vectors are summarized in Table 1.

3.1. The Charging Rate Analysis

Assuming that the reference voltage V r e f is located in sector 1 of the vector diagram presented in Figure 5, based on the parallelogram law, it can be obtained from the two closest voltage vectors ( V 1 and V 2 ), expressed as
T 1 T s V 1 + T 2 T s V 2 = V r e f T 1 + T 2 + T 0 = T s ,
where T 1 , T 2 , and T 0 are the action periods for the three basic voltage vectors, V 1 , V 2 , and V 0 , 7 , respectively.
In the α β coordinate system, the included angle between the reference value ( V r e f ) and the voltage vector ( V 1 ) is denoted as θ . Based on the law of sines, the relationship among V 1 , V 2 , and V r e f can be recorded as
| V r e f | s i n ( 2 π 3 ) = | T 1 T s V 1 | s i n ( π 3 θ ) = | T 2 T s V 2 | s i n θ .
Because V 1 and V 2 have the same amplitude, which is equal to 2 V d c 3 , (4) and (5) can be rewritten as
T 1 = m T s s i n ( π 3 θ ) T 2 = m T s s i n θ T 0 = T s T 1 + T 2 ,
where m is the modulation in index, which can be calculated by
m = 3 | V r e f | V d c .
In the space vector modulation, a system constraint condition should be met:
T 1 + T 2 T s .
Substituting (6)–(8), the system constraint can be represented as
| V r e f | V d c 3 s i n ( π 3 + θ ) .
In order to satisfy (9) for any included angle θ , it can be deduced that
V m = | V r e f | V d c 3 ,
which can be rewritten as
V d c 3 V m = V p h p h ,
where V m is amplitude of the phase voltage and V p h p h is the phase-to-phase voltage, known as the line voltage.
Therefore, the output DC-link voltage V d c of the three-phase AC/DC converter has a minimum value. With the topology in Figure 2b, the DC-side output voltage is limited to between the voltage-line voltage and the fully charged voltage of the battery. In order to achieve the full range of charging/discharging from the minimum to the maximum battery voltage, a DC/DC bidirectional half-bridge converter is connected with the battery, as described in Figure 4.

3.2. Model Predictive Direct Power Control for the Grid Side

The MPC strategy for tracking the grid active/reactive power—named MPDPC—is proposed in this section. A cost function is designed as the combination of the error between the predicted and expected values of the active and reactive powers. The appropriate switching state that minimizes the cost function is chosen for the next sampling period.
A balanced source power is considered on the AC side. The system model in the standard α β frame transformation can be written as
L d i g , α β d t = V g , α β R i g , α β V α β ,
where V g , α β and i g , α β represent the grid voltage and phase current vectors, respectively, and are expressed by
V g , α β = V g , α V g , β = 2 3 1 1 2 1 2 0 3 2 3 2 V g , a V g , b V g , c ,
i g , α β = i g , α i g , β = 2 3 1 1 2 1 2 0 3 2 3 2 i g , a i g , b i g , c .
Based on the forward Euler approximation, the derivative of the grid current can be assumed as
d i g , α β d t = i g ( k + 1 ) i g ( k ) T s .
The grid current (12) in the discrete time domain can be written as
i g ( k + 1 ) = T s L ( V g , α β ( k ) R i g , α β ( k ) V α β ( k ) ) + i g , α β ( k ) .
Then, the active/reactive powers for the next time instant ( k + 1 ) are predicted as
P ( k + 1 ) = 3 2 R e V g i g * = 3 2 ( V g , α ( k + 1 ) i g , α ( k + 1 ) + V g , β ( k + 1 ) i g , β ( k + 1 ) )
Q ( k + 1 ) = 3 2 I m V g i g * = 3 2 ( V g , β ( k + 1 ) i g , α ( k + 1 ) V g , α ( k + 1 ) i g , β ( k + 1 ) ) ,
where V g , α ( k + 1 ) , V g , β ( k + 1 ) , i g , α ( k + 1 ) , and i g , β ( k + 1 ) are the predicted values. i g , α ( k + 1 ) and i g , β ( k + 1 ) are obtained from (14). Due to the large value of the rate between the grid frequency and sampling frequency, V g , α ( k + 1 ) and V g , β ( k + 1 ) can be assumed to be same as the measured values, V g , α ( k ) and V g , β ( k ) , respectively.
The cost function is designed as
g = ( P r e f P ( k + 1 ) ) 2 + ( Q r e f Q ( k + 1 ) ) 2 .
The commands of the active/reactive powers ( P r e f and Q r e f ) are determined by the center controller to satisfy the requirements of the grid and the EV customers.

3.3. Model Predictive Direct Current Control for the EV Side

For the half-bridge DC/DC converter, the switching state G is defined as
G = 1 upper   switch G 1 is   on 0 lower   switch G 2 is   on .
This means that the switching state G is set to 1 when the upper switch is on and the lower one is off, or vice versa.
Based on Kirchhoff’s voltage law (KVL), when G is controlled to be 1, the DC-link voltage can be obtained as
V d c = L d i b a t d t + V b a t ,
where V d c is the voltage on the DC bus, V b a t is the battery voltage, and i b a t is the battery charging/discharging current.
Similarly, when the switching state G is 0, the KVL value of the DC/DC converter can be expressed as
0 = L d i b a t d t + V b a t .
Based on (19) and (20), the mathematical model of the bidirectional DC/DC converter can be written as
G V d c = L d i b a t d t + V b a t .
Then, the predicted battery current at the k + 1 time instant is obtained as
i b a t ( k + 1 ) = i b a t + T s L ( G V d c V b a t ) .
For constant current charging, the cost function g c c is defined as
g c c = ( i b a t i b a t * ) 2 ,
where i b a t * is the reference value of the battery current.
Neglecting the power loss in the transmission, the grid active power reference ( P r e f ) can be calculated as
P r e f = n = 1 N P b a t # n * + P s t o r = n = 1 N V b a t # n i b a t # n * + P s t o r ,
where P b a t # n * , V b a t # n and i b a t # n * are the charging power reference, voltage, and expected charging current of the nth EV battery, respectively, N is the total number of the parked EVs, and P s t o r is the power delivered to the storage system. In this paper, as an example, N is set to 1 without the storage system, which leads to P r e f = P b a t * = V b a t i b a t * . The proposed control algorithm is shown in Figure 6.

4. Simulation Results

In [14], Metin et al. used a proportional-integral controller (PI) controller for V2G reactive power operation with an off-board charger. With the proposed system controller, the reactive power reference can be tracked effectively while charging the EV battery. However, it took around three grid cycles (60 ms) to respond to a new command.
By using the proposed MPC method for the system in [14] under the same transient simulation operation, the response time can be reduced dramatically. From the zoomed version of the active and reactive power in Figure 7a, it can be seen that the response time for the system changing from a unity power factor operation to a 0.4 pf (leading) operation is less than 2 ms. Compared with the three-cycle (60 ms) response time in [14,15], the response speed is improved significantly. The grid current in Figure 7b can also reach the new command operation within 2 ms.
This section provides the simulation results of the proposed control method for the four-quadrant P-Q operation in Matlab/Simulink. The parameters of the bidirectional charger were chosen as shown in Table 2. The simulation scenarios are designed as follows:
(1)
The charging current i b a t * declines from 6.67 to −6.67 A at t = 1.04 s, which leads to the active power reference P r e f dropping from 2 to −2 kW. It steps up to 0 A at t = 1.08 s and stays constant for the next four cycles. Meanwhile, the reactive power reference stays at 0 kvar during the first four-cycle period. Then, it rises to 1 kvar at t = 1.08 s and drops to −1 kvar at t = 1.12 s.
(2)
The charging current is decreased from 6.67 to 3.33 A at t = 1.04 s, which means that the active power reference P r e f is reduced from 2 to −1 kW, and after two cycles, it is restored to 6.67 A. At t = 1.12 s, it steps down to −3.33 A with P r e f equal to −1 kW. During this period, the reactive power reference is reduced from 1 to −1 kvar at t = 1.08 s.
Figure 8 presents the results of the first operation condition, which was used to describe the system performance in the independent operation of G2V, V2G, and (capacitive/inductive) V4G. The active/reactive power demands can be tracked effectively by using the proposed MPC strategy. In Modes I and II, no reactive power is transferred in this operation. Based on the active power reference, the bidirectional charger works effectively in the G2V and V2G modes. The grid current is controlled to be in phase with the grid voltage, as in the operation in the G2V mode. The EV batteries charge the energy from the source. The total harmonic distortion (THD) of the grid current is around 4.23%. Conversely, the active power is delivered from the EV to the grid in the V2G mode. It can be seen that the current is in phase opposition with the grid voltage. In Modes III and IV, the converter supports the grid with the reactive power compensation (V4G operation). With the reactive power being delivered from the grid to the load side, the grid current is 90 and leading the grid voltage; otherwise, it is 90 and lagging behind, as shown in Figure 8c.
The second simulation was performed to show the system dynamic and steady-state performance in the four-quadrant regions of the PQ plane, as described in Figure 9. The bidirectional charger works in G2V or V2G with the capacitive or inductive V4G operation modes. Similarly, it can be observed clearly in Figure 9a that the system can track the references of the active and reactive powers at the same time. Figure 9b,c shows the battery operation details and the grid-side performance in the a-phase, respectively. In Mode V, where the charger operates in G2V with inductive V4G operation, the main power grid provides the positive active/reactive power to the load. The grid current leads its voltage, as depicted inFigure 9c. The system operates as V2G with the inductive V4G mode in Mode VI, delivering the active power from the EV battery to the power grid. The system serves as a static var generator to compensate the reactive power in V2G or G2V with capacitive V4G operation (Modes VII and VIII). The grid current lags behind the same-phase voltage in both operation modes. The battery is charged and discharged according to the transmission direction of the active power.

5. Experimental Results

The proposed control strategy was further verified by a scaled-down experiment that used a laboratory setup, as shown in Figure 10. The setup was composed of the following devices: an insulated-gate bipolar transistor-based three-phase two-stage bidirectional converter, three AC filter inductors, and DC power sources. Twelve 12 V 24 Ah sealed lead-acid batteries connected in series were used to simulate an EV battery. Therefore, the nominal voltage and the capacity of this sealed battery were 144 V and 24 Ah, respectively. The experimental parameters are listed in Table 3. The control algorithm was implemented on a dSPACE DS1104 processor board. The operations were performed with a sampling frequency equal to 10 kHz. All of the measured parameters were viewed through the dSPACE control desk. Note that during the experimental test, the battery contactor should be closed prior to turning on the main power on the AC side. Otherwise, a current spike occurs due to the voltage change between the DC bus ( V d c ) and the battery ( V b a t ). Since there is a direct connection between the converter output capacitor and the battery, this current spike cannot be controlled. It might even destroy the converter output contactor and the battery contactors, as well as other semiconductor devices.
In the experimental test, the charging and discharging current references were set to be 2 and −2 A, respectively. The battery voltage was about 154 V. The active power demand delivered from the grid was around 308 and −308 W for the charging and discharging processes, separately. For inductive and capacitive operations, the reactive power references were 200 and −200 var, respectively.
Figure 11 shows that the system operates properly in Quadrants I, II, III, and IV. The battery can be charged and discharged with the proposed MPDPC and MPDCC strategies. The grid active and reactive power is well maintained according to the reference values presented in Figure 11a. The battery current can track the reference value (2 and −2 A) effectively, as shown in Figure 11b. Figure 11c depicts the experimental current and voltage waveforms in the a-phase. The input current has a nearly sinusoidal waveform. When the reactive power is 0 var, it is in or out of phase with the grid voltage depending on the direction of the active power.
In Figure 12, the reactive power is varied from 200 to −200 var, and the active power is controlled to change between 308 and −308 W. It can be seen clearly that during this process, not only can the active power be delivered between the EVs and the grid, but the reactive power can also be provided or absorbed by the EV battery. Figure 12c presents the grid voltage and current waveforms. The response time is only approximately 2 ms for the system to reach the next demand condition.

6. Conclusions

This paper proposed a model predictive control composed of model predictive direct power control and a model predictive direct current control schemes for three-phase two-stage off-board bidirectional EV chargers. The MPDPC method was designed to track the grid active/reactive power references for the AC/DC converter. The MPDCC scheme was applied in a second-stage DC/DC converter for constant current charging. The proposed system controller receives the discharging and charging currents from the EV charging stations. With the proposed method, the bidirectional charger can operate in G2V or V2G with/without the capacitive/inductive V4G modes. The EV battery can not only exchange active power with the grid, but can also function as a static var compensator to improve the power quality based on the grid requirements. It can be seen from the simulation and experimental results that the designed MPC scheme has a fast dynamic response and good steady-state performance. The demands from both the grid and the EV batteries can be met effectively. However, there are some gaps between the laboratory and real-life off-board EV chargers, including the power level, charging conditions, and battery types. (a) In the real-life EV chargers, the power level is much higher than in the laboratory ones. In the US Society of Automotive Engineers (SAE) J1772 standard, DC Level 1 and DC Level 2 are the two levels of fast DC charging, with a rated power equal to 80 and 400 kW, respectively. (b) Only the initial constant current charging operation is considered in this paper. Generally, the constant voltage charging mode in the final process is required in most real cases. (3) In the current EV market, due to their long lifetime and high energy density, lithium batteries are used in the real vehicles, rather than sealed lead-acid batteries. (4) An isolated DC/DC converter is used in real-life chargers to protect EV batteries and the grid. To narrow the gap between the scaled-down laboratory setup and the real-life deployment, a high-power-level topology with an isolated DC/DC converter interfaced with lithium batteries will be considered in future work.

Author Contributions

All authors contributed to the research in the paper. Conceptualization, T.H.; formal analysis, T.H. and D.D.-C.L.; methodology, M.W. and T.H.; project administration, M.W.; supervision, D.D.-C.L.; validation, T.H. and Q.L.; writing-original draft, T.H.; writing-review and editing, T.L. and Q.Y.; all the authors have read and approved the final manuscript. All authors have read and agreed to the published version of the manuscript.

Funding

This work was supported in part by Fundamental Research Funds for the Major Projects: KEJB0220001536.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

Not applicable.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Anamika, D.; Santoso, S. Electric Vehicle Charging on Residential Distribution Systems: Impacts and Mitigations. IEEE Access 2015, 3, 1871–1893. [Google Scholar]
  2. Choi, S.Y.; Gu, B.W.; Jeong, S.Y. Advances in wireless power transfer systems for roadway-powered electric vehicles. IEEE J. Emerg. Sel. Top. Power Electron. 2015, 3, 18–36. [Google Scholar] [CrossRef]
  3. Mi, C.C.; Buja, G.; Choi, S.Y. Modern Advances in Wireless Power Transfer Systems for Roadway Powered Electric Vehicles. IEEE Trans. Ind. Electron. 2016, 63, 6533–6546. [Google Scholar] [CrossRef]
  4. Tian, Z.; Wang, Y.; Zhang, F. Real-time charging station recommendation system for electric-vehicle taxis. IEEE Trans. Intell. Transp. Syst. 2016, 17, 3098–3109. [Google Scholar] [CrossRef]
  5. Sjafie-khah, M.; Heydarian-Forushani, E.; Oso´rio, G.J. Optimal Behavior of Electric Vehicle Parking Lots as Demand Response Aggregation Agents. IEEE Trans. Smart Grid 2016, 7, 2654–2665. [Google Scholar] [CrossRef]
  6. Farzin, H.; Aghtaie, M.M.; Firuzabad, M.F. Reliability studies of distribution systems integrated with electric vehicles under battery-exchange mode. IEEE Trans. Power Deliv. 2016, 31, 2473–2482. [Google Scholar] [CrossRef]
  7. Karfopoulos, E.L.; Panourgias, K.A.; Hatziargyriou, N.D. Distributed Coordination of Electric Vehicles providing V2G Regulation Services. IEEE Trans. Power Syst. 2016, 31, 2834–2846. [Google Scholar] [CrossRef]
  8. Alam, M.J.E.; Muttaqi, M.; Sutanto, D. Effective utilization of available pev battery capacity for mitigation of solar PV impact and grid support with integrated V2G functionality. IEEE Trans. Smart Grid 2016, 7, 1562–1571. [Google Scholar] [CrossRef] [Green Version]
  9. Yilmaz, M.; Krein, P.T. Review of the impact of vehicle-to-grid technologies on distribution systems and utility interfaces. IEEE Trans. Power Electron. 2013, 28, 5673–5689. [Google Scholar] [CrossRef]
  10. Kwon, M.; Choi, S. An Electrolytic Capacitorless Bidirectional EV Charger for V2G and V2H Applications. IEEE Trans. Power Electron. 2017, 32, 6792–6799. [Google Scholar] [CrossRef]
  11. Zahid, Z.U.; Dalala, Z.M.; Chen, R. Design of Bidirectional DC–DC Resonant Converter for Vehicle-to-Grid (V2G) Applications. IEEE Trans. Transport. Electrific. 2015, 1, 232–244. [Google Scholar] [CrossRef]
  12. Rabiee, A.; Farahani, H.F.; Khalili, M.; Muttaqi, J.A.K.M. Integration of plug-in electric vehicles into microgrids as energy and reactive power providers in market environment. IEEE Trans. Ind. Inform. 2016, 12, 1312–1320. [Google Scholar] [CrossRef] [Green Version]
  13. Buja, G.; Bertoluzzo, M.; Fontana, C. Reactive power compensation capabilities of V2G-enabled electric vehicles. IEEE Trans. Power Electron. 2017, 32, 9447–9459. [Google Scholar] [CrossRef]
  14. Kesler, M.; Kisacikoglu, M.C.; Tolbert, L.M. Vehicle-to-grid reactive power operation using plug-in electric vehicle bidirectional off-board charger. IEEE Trans. Ind. Electron. 2014, 61, 6778–6784. [Google Scholar] [CrossRef]
  15. Monteiro, V.; Pinto, J.G.; Afonso, J.L. Operation modes for electric vehicle in smart grids and smart homes: Present and proposed modes. IEEE Trans. Veh. Technol. 2016, 65, 1007–1020. [Google Scholar] [CrossRef] [Green Version]
  16. Kisacikoglu, M.C. Single-phase on-board bidirectional PEV charger for V2G reactive power operation. IEEE Trans. Smart Grid 2015, 6, 767–775. [Google Scholar] [CrossRef]
  17. Khan, S.A.; Guo, Y.; Zhu, J. Model predictive observer based control for single-phase asymmetrical T-type AC/DC power converter. IEEE Trans. Ind. Appl. 2015, 55, 2033–2044. [Google Scholar] [CrossRef]
  18. Kouro, S.; Cortes, P.; Vargas, R.; Ammann, U.; Rodriguez, J. Model predictive control—A simple and powerful method to control power converters. IEEE Trans. Ind. Electron. 2009, 56, 1826–1838. [Google Scholar] [CrossRef]
  19. Rodriguez, P.; Cortes., J. (Eds.) Predictive control of power converters and electrical drives. In Predictive Control of Power Converters and Electrical Drives.; John Wiley & Sons, Ltd.: West Sussex, UK, 2012. [Google Scholar]
  20. Lezana, P.; Aguilera, R.; Quevedo, D.E. Model predictive control of an asymmetric flying capacitor converter. IEEE Trans. Ind. Electron. 2009, 56, 1839–1846. [Google Scholar] [CrossRef]
  21. Zhang, Y.; Xie, W.; Li, Z.; Zhang, Y. Model predictive direct power control of a PWM rectifier with duty cycle optimization. IEEE Trans. Power Electron. 2013, 28, 5343–5350. [Google Scholar] [CrossRef]
  22. Calle-Prado, A.; Alepuz, S.; Bordonau, J.; Nicolas-Apruzzese, J.; Cortés, P.; Rodriguez, J. Model predictive current control of grid-connected neutral-point-clamped converters to meet low-voltage ride-through requirements. IEEE Trans. Ind. Electron. 2015, 628, 1503–1514. [Google Scholar] [CrossRef] [Green Version]
  23. Yilmaz, M.; Krein, P.T. Review of battery charger topologies, charging power levels, and infrastructure for plug-in electric and hybrid vehicles. IEEE Trans. Power Electron. 2013, 28, 2151–2169. [Google Scholar] [CrossRef]
  24. Kisacikoglu, M.C. EV/PHEV bidirectional charger assessment for V2G reactive power operation. IEEE Trans. Power Electron. 2013, 28, 5717–5727. [Google Scholar] [CrossRef]
  25. Dusmez, S.; Khaligh, A. A compact and integrated multifunctional power electronic interface for plug-in electric vehicles. IEEE Trans. Power Electron. 2013, 28, 5690–5701. [Google Scholar] [CrossRef]
  26. He, T.; Bai, Y.; Zhu, J. Optimal charging strategy of electric vehicles customers in a smart electrical car park. In Proceedings of the 8th IET International Conference on Power Electronics, Machines and Drives (PEMD 2016), Glasgow, UK, 19–21 April 2016. [Google Scholar]
  27. Akter, M.P.; Mekhilef, S.; Tan, N.M.L. Modified model predictive control bidirectional AC/DC converter based on lyapunov function for energy storage systems. IEEE Trans. Ind. Electron. 2013, 63, 704–715. [Google Scholar] [CrossRef]
  28. Singh, B.; Singh, B.N.; Chandra, A. A review of three-phase improved power quality AC/DC converters. IEEE Trans. Ind. Electron. 2004, 51, 641–660. [Google Scholar] [CrossRef]
Figure 1. Four-quadrant operation for chargers.
Figure 1. Four-quadrant operation for chargers.
Energies 14 00181 g001
Figure 2. Bidirectional charger structures.
Figure 2. Bidirectional charger structures.
Energies 14 00181 g002
Figure 3. Framework of the smart car park system.
Figure 3. Framework of the smart car park system.
Energies 14 00181 g003
Figure 4. Three-phase off-board charger.
Figure 4. Three-phase off-board charger.
Energies 14 00181 g004
Figure 5. Eight possible input voltage vectors.
Figure 5. Eight possible input voltage vectors.
Energies 14 00181 g005
Figure 6. Proposed control algorithm.
Figure 6. Proposed control algorithm.
Energies 14 00181 g006
Figure 7. Performance by using the model predictive control (MPC) for the system in Ref. [14].
Figure 7. Performance by using the model predictive control (MPC) for the system in Ref. [14].
Energies 14 00181 g007
Figure 8. Simulation results in Quadrants I, II, III, and IV.
Figure 8. Simulation results in Quadrants I, II, III, and IV.
Energies 14 00181 g008
Figure 9. Simulation results in Quadrants V, VI, VII, and VIII.
Figure 9. Simulation results in Quadrants V, VI, VII, and VIII.
Energies 14 00181 g009
Figure 10. Experimental setup.
Figure 10. Experimental setup.
Energies 14 00181 g010
Figure 11. Experimental results in Quadrants I, II, III, and IV.
Figure 11. Experimental results in Quadrants I, II, III, and IV.
Energies 14 00181 g011
Figure 12. Experimental results in Quadrants V, VI, VII, and VIII.
Figure 12. Experimental results in Quadrants V, VI, VII, and VIII.
Energies 14 00181 g012
Table 1. Input voltage vectors of the AC/DC converter in the α β coordinates.
Table 1. Input voltage vectors of the AC/DC converter in the α β coordinates.
No. S a S b S c S α S β V α V β V α +j V β
000000000
1100 2 3 0 2 V d c 3 0 2 V d c 3
2110 1 3 1 3 V d c 3 V d c 3 2 V d c 3
3010 1 3 1 3 V d c 3 V d c 3 2 V d c 3
4011 2 3 0 2 V d c 3 0 2 V d c 3
5001 1 3 1 3 V d c 3 V d c 3 2 V d c 3
6101 1 3 1 3 V d c 3 V d c 3 2 V d c 3
711100000
Table 2. System parameters for the simulation test.
Table 2. System parameters for the simulation test.
ParameterValue
Line resistance per phase, R0.25 Ω
Filter inductor per phase, L10 mH
DC capacitor, C470 μ F
DC inductor, L d c 100 mH
Output capacitor, C d c 470 μ F
Grid r.m.s voltage, V L L 100 V/50 Hz
Sampling frequency, f s 20 kHz
Battery voltage, V b a t 300 V
Table 3. System parameters for the experimental test.
Table 3. System parameters for the experimental test.
ParameterValue
Filter inductor per phase, L20 mH
DC capacitor, C680 μ F
DC inductor, L d c 35 mH
Output capacitor, C d c 68 μ F
Grid r.m.s. voltage, V L L 100 V/50 Hz
Sampling frequency, f s 20 kHz
Battery voltage, V b a t 144 V
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

He, T.; Lu, D.D.-C.; Wu, M.; Yang, Q.; Li, T.; Liu, Q. Four-Quadrant Operations of Bidirectional Chargers for Electric Vehicles in Smart Car Parks: G2V, V2G, and V4G. Energies 2021, 14, 181. https://doi.org/10.3390/en14010181

AMA Style

He T, Lu DD-C, Wu M, Yang Q, Li T, Liu Q. Four-Quadrant Operations of Bidirectional Chargers for Electric Vehicles in Smart Car Parks: G2V, V2G, and V4G. Energies. 2021; 14(1):181. https://doi.org/10.3390/en14010181

Chicago/Turabian Style

He, Tingting, Dylan Dah-Chuan Lu, Mingli Wu, Qinyao Yang, Teng Li, and Qiujiang Liu. 2021. "Four-Quadrant Operations of Bidirectional Chargers for Electric Vehicles in Smart Car Parks: G2V, V2G, and V4G" Energies 14, no. 1: 181. https://doi.org/10.3390/en14010181

APA Style

He, T., Lu, D. D. -C., Wu, M., Yang, Q., Li, T., & Liu, Q. (2021). Four-Quadrant Operations of Bidirectional Chargers for Electric Vehicles in Smart Car Parks: G2V, V2G, and V4G. Energies, 14(1), 181. https://doi.org/10.3390/en14010181

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop