4.1. Preliminary Analysis of the PVC Behaviour and Pressure Fluctuations in Part-Load Conditions
In this section, the results in terms of pressure fluctuations obtained in the case of two draft tube geometries (DT3 and DT4) in part-load conditions (GVO 40%) are analysed to highlight the different phenomena involved and the possible influence of the draft tube geometry on the PVC dynamics.
For all draft tube geometries, the pressure fluctuations at the wall are monitored in two different sections of the draft tube cone during unsteady CFD simulations at GVO 40%, see
Figure 8. In each section, the pressure is monitored at four different locations regularly spaced by an angle of
. Section 1 is located
downstream of the runner outlet in all draft tube geometries, whereas the
z-coordinate of Section 2 changes from one draft tube to another due to the variation of the draft tube cone length. Section 2 is, however, placed
upstream of the elbow inlet in all draft tube geometries.
A cross-spectral analysis between the pressure signals simulated at the monitoring points
and
is performed in the case of DT3 and DT4. The results for DT3 and DT4 are given in
Figure 9a (left figures) and
Figure 9b (right figures). It includes the raw pressure signals made dimensionless by the head
H (top figure), the amplitude (middle figure) and the phase (bottom figure) of the cross-spectral density function between
and
.
In both cases, a clear frequency peak is observed at and for DT3 and DT4, respectively. This frequency corresponds to the vortex precession frequency that locally induces pressure fluctuations on the draft tube wall. The amplitude of these pressure fluctuations in the case of DT3 is slightly higher than that in DT4. The phase shift at between and (bottom figures) reveals the nature of the pressure fluctuations in the corresponding cross-section: in the case of DT3, the phase shift is almost equal to 0, which corresponds to synchronous (or in-phase) pressure pulsations, whereas it is equal to ≈ in the case of DT4.
The precession of a vortex core in the draft tube of Francis turbine is known to induce two different types of pressure fluctuations, both occurring at the precession frequency
. The convective pressure component, or asynchronous, is locally induced by the rotation of the inhomogeneous pressure field with the vortex core. If the pressure fluctuations measured by two sensors located in the same cross-section and spaced by an angle
are purely convective, the phase shift at
between both pressure signals is equal to
. In the case of an elbowed draft tube, the interaction between the PVC and the elbow dissymmetric geometry induces an additional type of pressure fluctuations at
, the so-called synchronous component [
39]. It has equal phase and amplitude in a given cross-section, and propagates through the complete hydraulic circuit, including the pipe upstream of the machine. Therefore, the pressure fluctuations measured in a Francis turbine elbowed draft tube correspond to the superimposition of both components. The phase shift between two pressure sensors in the same cross-section is not equal to neither 0 (pure synchronous nature) nor the angular difference between both sensors (pure convective nature) but to a value depending on the amplitude and phase of each component. For the present case, it can be assumed that the synchronous component in the case of DT3 is dominant in the corresponding section of interest, leading to a phase shift close to 0.
Several mathematical tools have been developed to decompose the pressure fluctuations induced by a PVC in Francis turbine draft tube into synchronous and convective components [
4,
40,
41]. If
N sensors are equally distributed along the wall in one cross-section, the pressure components can be decomposed by using the following equations [
42]:
where
corresponds to the synchronous pressure component common to all pressure sensors,
is the convective pressure component relative to the pressure sensor
i and
is the individual raw pressure signal
i. In the present case, four monitoring pressure points located in Section 1 (
) are used to calculate the pressure components. A Fast Fourier Transform (FFT) is then applied to each pressure component. The FFT obtained in Section 1 are given in
Figure 10a,b for the cases DT3 and DT4, respectively. As concluded by analysing the phase of the cross-spectral density function, the synchronous component is dominant in Section 1 of DT3, whereas the convective component amplitude is equal to twice the amplitude of the synchronous component in the DT4. However, the amplitude of the convective components in Section 1 is similar in both draft tubes while the synchronous component in DT3 is almost five time higher than the one in DT4.
The results obtained in Section 2 are given in
Figure 11. While the amplitude of the synchronous pressure components is close to the one observed in Section 1 in both draft tubes, the amplitude of the convective components in DT3 remarkably increases compared with the one in Section 1 (see
Figure 10).
The amplitude of the convective component in a given section is directly related to the PVC trajectory radius in this section, as already demonstrated in simplified test cases generating swirling flows [
43]. In addition, the synchronous component results from the interaction between the precession motion of the vortex core and the dissymmetric geometry of the elbow, and it has been assumed that a wider PVC trajectory in the elbow may induce higher synchronous pressure pulsations [
3].
To understand the differences observed between both draft tubes in terms of pressure components amplitude, the instantaneous position of the vortex centre is estimated in 4 cross-sections along the draft tube, including Sections 1 and 2, and 2 additional sections in the elbow. A total of 30 time steps are considered, corresponding to approximately three complete PVC rotations. To determine the PVC center position at each time step, the vortex centre identification algorithm proposed by Graftieaux et al. [
44] is applied. It relies on the computation of the criterion
, which is only based on the flow topology and does not involve any velocity gradients. It has been successfully used for the identification of PVC in hydraulic turbines [
37] and simplified swirling flow applications [
45], and tip vortices in hydrofoil applications [
46].
The instantaneous positions of the PVC centre are given at 30 time steps in
Figure 12 and
Figure 13 for DT3 and DT4, respectively. The black dots indicate the position of the consecutive instantaneous vortex centres while the red line corresponds to a mean PVC trajectory based on the 30 instantaneous vortex centres by considering a pure circular trajectory.
In DT3, the vortex center trajectory is very close to the section center in Section 1 and then strongly widens along the draft tube cone, with a vortex trajectory radius
in Section 2 equal to six times the radius in
Section 1. It should be noted that the dispersion of the instantaneous vortex centre around the mean trajectory is remarkably low, highlighting a high level of periodicity in the precession motion. These features are also observed in the elbow, even if the centre of the vortex trajectory is slightly shifted from the geometrical centre of the section. This strong periodical precession of the vortex in the elbow may be responsible for the high-amplitude synchronous pressure pulsations observed in the draft tube cone. Therefore, the results in
Figure 10 can be explained by a weak vortex precession in Section 1 (low convective pressure fluctuations) combined with a strong, periodical vortex precession in the elbow producing high synchronous pressure fluctuations that propagate upstream.
In DT4, the evolution of the vortex precession trajectory is remarkably different from the one in DT3. First, the instantaneous vortex centres feature a higher dispersion around the mean trajectory compared with the previous case. In addition, the radius of the vortex trajectory remains similar in the draft tube cone and then slightly widens along the elbow, but with a radius much lower than the one in DT3. These features, combined with the weak periodicity of the vortex precession, explain the notable difference observed between the amplitude of the pressure components in DT3 and DT4. In DT4, the precession of the vortex in the elbow only produces low-amplitude synchronous fluctuations, making the convective pressure fluctuations at the runner outlet dominant.
This preliminary analysis, based on the results obtained in only two draft tubes featuring radically different geometries, clearly highlights the influence of the draft tube geometry on the structure of the PVC and the amplitude of the associated pressure fluctuations. Moreover, it also reveals the complexity of the phenomenon: in a given geometry, the structure of the PVC evolves along the draft tube, producing convective pressure fluctuations whose amplitude depends on the local vortex trajectory and changes along the draft tube. The synchronous pressure component is directly related to the precession of the vortex in the elbow, and the study of the impact of the draft tube geometry on the flow stability should ideally consider the vortex structure along the complete draft tube.
However, as this is not feasible from a practical point of view in the case of an analysis by DOE and ANOM, the following will only focus on the pressure fluctuations (including both convective and synchronous components) at the runner outlet in the monitoring Section 1 of the draft tube cone. This simplification is supported by the two following arguments. First, the runner will be impacted by the local convective pressure fluctuations, i.e., the precession of the vortex just at the runner outlet. In addition to that, the synchronous pressure pulsations measured at the runner outlet also propagate upstream, through the runner blade channels, and affect directly the runner dynamic stresses and fatigue. Therefore, minimizing the pressure fluctuations at the runner outlet will result in a reduction of the dynamic stresses on the runner blades and an improvement of the runner lifetime. One should, however, keep in mind that the development of convective pressure fluctuations farther in the draft tube may induce additional vibrations of the stationary components and additional fatigue. This aspect is, however, out of the scope of the present paper.
4.2. Analysis of Means of Pressure Fluctuations in Part-Load Conditions
In this section, the influence of each geometrical parameter on the amplitude of the pressure fluctuations simulated in the monitoring Section 1 is assessed. The pressure fluctuations are first made dimensionless by defining the pressure coefficient
as follows:
where
p is the pressure,
is the time-averaged pressure and
H is the available head of the hydropower unit. Pressure fluctuations in Francis turbines are commonly normalized by the net head
of the machine. However, in the present study, the net head varies from one case to another (see
Figure 7), making the normalization by the net head irrelevant for further comparisons between the nine different cases.
The Root-Mean-Square (RMS) value of the pressure coefficient
, where the index
is the number of the experiment, is the characteristic function of the experiments. The mean value
m of this characteristic function is calculated by considering its value over the nine experiments as follows:
The pressure coefficient RMS value
is given for each DT geometry in
Figure 14, together with the mean value
m. The DT geometry has a great influence on the amplitude of the pressure coefficient
, its value ranging from 0.05% (DT1) to 0.57% (DT8) while the mean value
m is equal to 0.36%.
The effect of each level of the geometrical parameters on the pressure coefficient amplitude is assessed by applying an ANOM approach [
30] to the results given in
Figure 14. Considering a level
j (
j ranging from 1 to 3) of a geometrical parameter
(
k ranging from 1 to 4), the effect of the geometrical parameter
on the characteristic function when equal to its level
j can be estimated by the difference between the average value of the characteristic function over the experiments featuring the same level
j of the parameter
(noted
) and the mean value
m.
For example, the first level of the factor
corresponding to the DT cone angle, i.e.,
(see
Table 1), is used in three different DT geometries among the nine DT geometries (experiments DT1, DT2 and DT3). Therefore, the effect of the level 1 of the factor
on the pressure coefficient amplitude can be estimated as follows [
30]:
For each geometrical parameter, the effect of the three different levels on the pressure coefficient amplitude is estimated by using Equation (
9). The results are reported in
Figure 15. In this figure, the mean characteristic function
m is not subtracted to the mean value of each level
to avoid negative value, but the mean value is indicated by the horizontal dashed line. Therefore, values below/above this line correspond to a mitigating (green zone in
Figure 15)/enhancing (red zone in
Figure 15) effect with respect to the mean value
m, respectively.
Based on the ANOM of the pressure coefficient amplitude presented in
Figure 15, the following conclusions can be drawn. First, the parameters with the most influence on the pressure coefficient amplitude are the DT cone angle and the elbow section ratio. For both parameters, as their value is increased, the amplitude of the pressure coefficient is amplified. This is particularly significant for the elbow section ratio: when this parameter is modified from its lowest value (
) to its maximum value (
), its effect on the pressure coefficient amplitude is multiplied by a factor of about 2.5. At its lowest level, this parameter decreases the amplitude of the pressure coefficient with respect to the mean value
m (mitigating effect of
), while the amplitude is increased with respect to the mean value
m when this parameter is set at its highest level (enhancing effect of
). In the case of the DT cone angle
, its effect on the pressure coefficient amplitude varies from
(mitigating effect) with
to
(enhancing effect) with
.
The influence of these two parameters can be explained by the fact that increasing the diffuser effect in the cone results in a higher adverse pressure gradient, increasing the potential flow recirculation and the PVC trajectory radius. This, in turn, induces local convective pressure fluctuations with a higher amplitude. Concerning the influence of the elbow section ratio, it was shown in
Section 4.1 that an increase in the section area in the elbow may induce a wide PVC trajectory in the cone on one hand, and high synchronous pressure pulsations on another hand. Reducing the diffuser effect in both DT cone and elbow seems therefore crucial to reduce the amplitude of the pressure fluctuations at the runner outlet. The DT cone length has also a slight influence on the amplitude of the pressure pulsations, while the influence of the diffuser angle does not appear clearly: the minimum value of the pressure coefficient amplitude is observed at
, then its value increases and decreases as the value of
is increased.
Based on the ANOM, it can be concluded that the combination of levels that produce the minimum amplitude of pressure fluctuations in the monitoring Section 1 corresponds to the draft tube geometry 1, i.e., the value of each geometrical parameter is set at its first level. This is in agreement with the comparison between the results obtained with the different draft tube geometries, see
Figure 14.
However, using this geometry as a final design is not a reliable solution, since the outlet and inlet sections of the draft tube have equal diameter: there is no pressure recovery in the draft tube, which leads to a drop of the net head
of the turbine and of the output power
P compared with the other geometries, as shown in
Section 3.4. This effect is particularly important at full-load conditions (GVO 100%) with a higher flow rate and remaining kinetic energy in the draft tube. In the following, the energy losses and pressure recovery in the DT are considered.
4.3. Analysis of Means of Draft Tube Energy Losses
The ANOM is applied to the energy losses in the draft tube at both part-load (GVO 40%) and full-load (GVO 100%) conditions. The losses in the draft tube are estimated based on steady-state and unsteady-state CFD simulations at GVO 40% and
GVO 100%, respectively, by considering the difference of total pressure between the inlet and outlet of the draft tube:
The results of the ANOM of the draft tube losses are given in
Figure 16. The elbow section ratio
and the diffuser angle
have a clear influence on the energy losses in the draft tube at both operating points: the effect of both parameters continuously increase as the value of their level is increased. This is particularly significant for the elbow section ratio at full-load conditions: it has a mitigating effect of
with respect to the mean value
m as the parameter is set at its first level, whereas it has an enhancing effect of
with respect to the mean value
m as the parameter is set at its third level.
The influence of the DT cone angle and length on the losses is more ambiguous. At both operating points, the losses decrease and then increase as the value of the cone angle is increased. However, this effect is weak and the minimum losses value is only 9% lower than the maximum value. Concerning the DT cone length, the losses continuously increase as the value of this parameter is increased at GVO 40%, whereas they decrease and then increase in the case of GVO 100%.
The combination of geometrical parameters inducing the minimum energy losses in the draft tube is given in
Table 6. Concerning the level of the DT cone length, the one minimizing the losses at GVO 100% is selected, since its effect at GVO 40% is negligible. The combination minimizing the pressure fluctuations amplitude (previous section) is also included in
Table 6.
The minimization of either the energy losses or the pressure fluctuations amplitude does not lead to the same set of geometrical parameters and are therefore conflictive. In addition, the pressure recovery must be considered to ensure a sufficient effective head for the turbine. In the following section, the geometry featuring the best compromise between sufficient pressure recovery, minimization of both draft tube losses and pressure fluctuations is discussed based on additional analysis. The ANOM approach is finally validated by comparing the results provided by CFD simulation of the final design with the values estimated by ANOM.
4.4. Determination of the Final Draft Tube Geometry
The value of a characteristic function (i.e., the draft tube losses or the pressure coefficient amplitude in the present case) for any combination of level
can be estimated based on the results provided by the ANOM as follows [
30]:
For instance, for the combination of parameters minimizing the draft tube energy losses (combination 1 in
Table 6), the value of the draft tube losses
at GVO 40% can be estimated as follows:
Equation (
11) is applied to estimate the value of the draft tube energy losses at both GVO 40% and GVO 100% and the pressure coefficient amplitude at GVO 40% for both combinations of geometrical parameters given in
Table 6. The results are given in
Table 7.
As shown in
Table 7, the energy losses in the draft tube and the amplitude of the pressure coefficient cannot be minimized at the same time. The amplitude of the pressure coefficient is for instance multiplied by 3.5 if the combination 1 minimizing the losses is used instead of the combination 2. A compromise between mitigation of energy losses and pressure fluctuations amplitude may be reached by setting the geometrical parameters 1 to 3 to their first level, while the diffuser angle (parameter 4) will be set at a value enabling a sufficient pressure recovery, as described in the following.
The pressure recovery in a Francis turbine draft tube corresponds to the increase in the static pressure due to the deceleration of the flow along the draft tube induced by the increase in the cross-section area. This enables the reduction of the losses at the draft tube outlet by minimizing the remaining kinetic energy, thereby increasing the net head of the turbine.
The ideal pressure recovery
in the draft tube is defined as the difference of static pressure between the inlet and outlet of the draft tube without considering the energy losses, i.e.,:
where
and
correspond to the radius of the draft tube section at the inlet and outlet, respectively, as defined in
Figure 4.
The influence of the ratio
on the ideal pressure recovery at both operating conditions is given in
Figure 17. A maximum of 6% and 1% of the total available head
H can be recovered and transformed into pressure by the draft tube at GVO 100% and 40%, respectively. According to
Figure 17, the head recovered by the draft tube does not significantly further increase beyond a ratio
higher than 2 at both operating conditions, i.e., for a diffuser angle
. The difference between the recovered head with
and the maximum value of recovered head does not exceed
and
at full-load and part-load conditions, respectively. However, this analysis does not consider the energy losses in the draft tube: the latter induce a decrease in the recovered head as they increase when the diffuser angle is increased (see results of the ANOM in
Figure 16).
The balance between the ideal recovered head and the head losses in the draft tube as a function of the diffuser angle is, therefore, considered in the following to determine a suitable value of the diffuser angle. To do so, three additional draft tube geometries are investigated (experiments 10 to 12). They feature different values of diffuser angle, ranging from
to
, while the other geometrical parameters are fixed and set at their first level as defined previously. The parameters for each draft tube geometry are summarized in
Table 8.
For each geometry, steady and unsteady CFD simulations are performed at full-load (GVO 100%) and part-load (GVO 40%) conditions, respectively. The results of the simulation with (experiments 11) are also used to validate the methodology and the consistency of the estimation provided by the ANOM in terms of losses and pressure fluctuations amplitude, since the level is included in the experiments 1 to 9.
The influence of the diffuser angle on the draft tube losses
, the ideal recovered head
and the actual recovered head
is presented in
Figure 18. The actual recovered head corresponds to the difference between the ideal recovered head and the draft tube losses. First, it can be noticed that the pressure recovery is not sufficient at part-load conditions and does not compensate for the draft tube losses, leading to a negative value of actual recovered head. However, the pressure recovery plays a crucial role in full-load conditions where maximum 4% of the head
H can be recovered.
At both part-load and full-load conditions, the draft tube losses increase as the diffuser angle is increased, which is in agreement with the results obtained by the ANOM in
Section 4.3. In addition, the ideal pressure recovery does not significantly increase beyond
, as highlighted previously. Since the losses increase in the meantime as
is further increased beyond
, the actual recovered head
remains almost constant from
to
at GVO 100% and even slightly decreases in the case of GVO 40%. It can be expected than increasing further the diffuser angle may lead to a decrease in both the actual recovered head and the net head of the turbine.
The influence of the diffuser angle on the pressure fluctuations amplitude in Section 1 at part-load conditions is provided in
Figure 19. The tendency is similar to the one obtained by the ANOM in
Section 4.3. The amplitude first increases as the diffuser angle is increased and it then decreases beyond
.
Therefore, by considering the results and the analysis of both the energy losses and the pressure fluctuations amplitude, it can be concluded that the diffuser angle can be set at to reach the maximum actual recovered head without enhancing the development of pressure fluctuations at the runner outlet.