1. Introduction
Wind energy is a major renewable energy source. Wind energy plants can be classified with respect to their drivetrain configuration [
1]. For modern variable-speed wind turbines, in many cases, synchronous generators or squirrel cage machines are used to convert mechanical power into electrical power. In these concepts, fully rated power converters are employed to transmit the generated power to the electrical grid. To enable a grid stabilizing behavior comparable to a classical synchronous generator used in conventional power plants, many approaches have been proposed that operate the inverters in a voltage-fed fashion [
2,
3,
4,
5] so that the inverter behaves in many aspects, such as a synchronous generator. One strategy uses droops for frequency and voltage magnitude, reproducing classical ancillary services, such as frequency and voltage support.
However, for wind energy plants equipped with a doubly fed induction generator (DFIG) and a power converter controlling the rotor circuit, no comparable grid forming control has been established. Due to the partial power rating of the inverter supplying the rotor circuit of the generator only, the DFIG concept is still widely employed, especially in the power range below
[
6]. In
Figure 1, the power conversion and grid connection structure of a DFIG-based wind turbine is shown.
While the stator of the induction generator is directly connected to the electrical grid, the rotor side converter (RSC) operates the rotor circuit with only a fraction of the generated power transmitted through the converted depending on the machine slip.
The classical control schemes for the RSC have been derived from the established schemes used for adjustable motor drives. Typically, they are current controlled [
7], where the set-points of the current controllers are derived from the references for active/reactive power, torque or voltage magnitudes [
8,
9]. The current control is usually done in a rotating reference frame. The reference frame is either voltage- or flux-oriented, which means that the d-axis of the reference frame is oriented along the stator voltage or flux (stator or rotor). Current control is also possible in the stationary reference frame using proportional resonant controllers, with a high or infinite gain at grid frequency [
10,
11,
12]. The current control approach has the persuasive advantage of easy inverter protection by limiting the set-point values of the controllers but relies on an existing electrical grid that forms the connection point of the wind energy system.
To enable a stand-alone operation, i.e., autonomously supplying electrical loads, some concepts have been proposed to control the voltage at the generator terminal at a fixed frequency [
13,
14,
15,
16]. These concepts rely on a cascaded structure where an outer voltage control loop supplies the set-point for an inner rotor current control loop using the RSC. Instead of controlling the voltage directly [
17], in [
13,
16], it has been proposed to control the stator flux to achieve the stand-alone operation. Using the stator flux linkages has the advantage that they are directly connected to the power of the machine, so these state variables are much less volatile compared to the stator voltage, for instance. In stationary operation, the stator flux linkages and the voltage magnitude are directly connected by the frequency if the voltage drop across the stator resistance is neglected.
In order to increase the grid support capabilities, in [
18], it was proposed to adopt the rotor current set-points depending on the grid frequency and voltage magnitude after detecting an islanding event by means of corresponding droops. During the islanding events, significant oscillations have been observed. A similar structure has been proposed in [
19] for stand-alone operation. In [
20], the influence of different orientation systems on stability in low-voltage grids have been compared, but no results concerning transients, load changes or islanding events have been presented.
The main contribution of this paper is to extend the stator flux control of the DFIG by the droop control mechanisms known from full-power-rated inverter solutions. The aim is to operate the DFIG in a grid-forming mode, where the same control structure is used for grid-tied, stand-alone or islanded operation. In the case of an islanded grid involving the parallel operation of several generating units, the droop-based approach is inherently capable of performing power sharing according to the implemented droops.
The paper focuses on the grid forming nature of the proposed stator flux control and thereby does not cover any low-voltage ride through scenarios. Since the inner current control loop, however, is based on classical approaches, the well-established solutions [
21,
22] can be integrated into the control scheme, making the DFIG capable of low-voltage ride through. In addition, this paper does not cover the aspects of turbine control.
The paper is structured as follows: First, the stator flux control is described, and the extension using the frequency and voltage magnitude droops is discussed. Second, experimental results obtained from a laboratory setup are presented, which illustrate the operational properties using the proposed control scheme. Simulation results of a more complex three-node system follow. The article ends with a discussion and conclusion.
2. Stator Flux Control
The equivalent space vector circuit diagram in an arbitrary reference frame rotating at the angular frequency
is shown in
Figure 2.
The stator flux
of the machine can be calculated using the stator
and rotor
current [
23]
where
and
are the stator and magnetizing inductances, respectively. This formulation, however, has the disadvantage that the flux depends on the inductances that vary significantly at different operating points due to the iron saturation. To avoid this dependency, the stator flux can be alternatively calculated by the integration of the stator voltage over time
On the other hand, the integration method is sensitive against even minor offset errors in stator voltage and current. Stabilizing the voltage integration by the low-pass filtered flux calculated from the currents will again result in strong dependency on the non-linear inductances. Therefore, we propose approximating the integration itself by a low-pass filter with a low cut-off frequency
compared to the grid frequency
[
24]. For frequencies far beyond the cut off frequency, the low-pass filtering results in a phase shift of the output signal of nearly
. The resulting amplitude and phase error of the low-pass filter approximation with respect to the ideal integrator at grid frequency is compensated by a subsequent vector rotation established by the exponential in Equation (
3). Usually, the voltage drop across the stator resistance can safely be neglected as they are in a range of
. As a result, the transfer function of the implemented open-loop flux estimator is given by
which is independent of any machine parameters. The aim of the proposed DFIG control is to guide the stator flux space vector in the stationary reference frame on a circular trajectory with a given magnitude and rotational frequency, such that in stationary conditions, the generator acts like a three-phase voltage source. As shown in [
16], the stator flux can be controlled by the rotor currents in a cascaded structure with an inner fast rotor current control loop and an outer slower stator flux control loop. The cross-coupling between the d- and q-components in the inner rotor current control loop are reduced by introducing the corresponding feedforward terms for the induced voltages. The resulting control structure is shown in
Figure 3.
During the design of the PI-control parameters of the rotor current controller,
the LCL-filter between the RSC and the rotor has to be taken into account. The reset time,
, of the controller has been set to compensate for the open stator time constant of the plant while neglecting the filter capacitance of the filter. To avoid excitation of the filter resonance, the proportional gain
is set such that the cut-off frequency of the rotor control loop is 10x lower than the resonant frequency of the LCL-filter.
2.1. Control of Frequency and Magnitude
In quasi-stationary operation and neglecting the voltage drop at the stator resistance, the stator flux control results in a fixed stator voltage magnitude,
. The simplified equivalent circuit shown in
Figure 4 applies for the connection of the DFIG to the grid with the appropriate phasor diagram. The resulting impedance seen from the stator side mainly consists of the short circuit impedance of the feeding transformer in addition to the stator resistance and line filter. Other impedances usually have negligible effects on grid stability.
The active and reactive power components flowing to the grid depend mainly on the voltage amplitudes on both sides, the voltage angle
between inverter and grid voltage and the resulting longitudinal impedance. Typically, the voltage angle is small so that the approximations
and cos
can be applied. In addition, the resistive component of the resulting filter impedance is small compared to the inductive component. As a result, using per unit quantities, the power relations are given by
where
p and
q represent the active and reactive power in per unit, respectively;
represents the relative
s/c voltage drop of the filter impedance;
and
denote the magnitude of stator and line voltage in per unit, respectively;
represents the per unit stator flux magnitude;
represent the angle between stator and line voltage phasors. These equations form the basics of grid control on a transmission level with high X/R values, where the active power
p mainly depends on the voltage angle
, and the reactive power
q is mainly determined by the voltage amplitude difference and thus on the magnitude of stator flux. Both equations are well decoupled as long as the resistive component of the resulting impedance can be neglected, which is usually the case for transmission lines with typically high X/R ratios.
The primary control of conventional power plants with synchronous generators apply an active power dependent droop control for frequency and a voltage magnitude droop control depending on the reactive power. Depending on the type of power plant, the slope of the frequency droop is typically in the range of 2...6%, see
Figure 5a.
This droop control of frequency causes good load sharing according to their p-f-curve and ensures inherent synchronism of the generators. Each power plant delivers the amount of active power according to its individual p-f-curve at the stationary condition. Using proper filter elements and tracking the p-f-curve by a secondary control, the dynamic behavior and load sharing can be controlled safely with regard to the specific type of power plant and the overall control objective.
In practice, a change in grid frequency greater than
is only observed in very rare cases in the European grid. Thus, the corresponding power changes are usually less than 4% due to primary control. The aim is to maintain this grid’s stabilizing feature by controlling the DFIG accordingly. The droop control generates set-point values for frequency and stator flux amplitude. Under some conditions, this implementation can be shown to provide a similar dynamic behavior to a virtual synchronous machine [
25]. The goal is not to reproduce the synchronous generator in all details but to extract its essential properties for grid stability.
2.1.1. Frequency Control
In [
5,
26,
27], it has been proposed to extend the basic concept of frequency droop control by an additional phase intervention, which feeds the power error directly onto the voltage phase angle, see
Figure 6. In principle, this corresponds to a differential intervention of the active power error to the frequency. The analytical gains design for this structure has been discussed in [
28]:
where the closed loop transfer function results in
The additional feedforward path onto the voltage phase enables excellent damping, independent of the selected active power filter time constant. Thus, the slope of the frequency droop can be set similarly to those in conventional power plants maintaining a well-damped system response. Using this design, the response time is typically very fast, much less than . By means of an additional set-point filter, the desired overall time constant can be increased to a desired value with respect to the targeted frequency inertia.
2.1.2. Stator Flux Magnitude Control
According to Equation (
5), the difference in voltage magnitudes of the stator and grid is proportional to the reactive power. In order to stabilize the grid voltage to a desired value, the amount of reactive power will be set as a function of the grid voltage, see
Figure 5b. Instead of directly controlling the stator voltage magnitude, the desired stator flux magnitude can be adjusted accordingly. At constant frequency, the stator flux control will also yield a constant voltage magnitude neglecting the typically small voltage drop at the stator resistance. The stator flux amplitude is adjusted depending on the reactive power supplied to the grid, see
Figure 7.
Thus, operating the DFIG like a voltage source or synchronous generator with adjustable frequency, phase and amplitude, the generator inherently gives ancillary grid services, such as frequency and voltage support. On a grid frequency change, the generator will immediately respond with a corresponding change in active power, and on a voltage sag, the generator will immediately increase the reactive power. In addition, it ensures adequate sharing of active and reactive power among multiple feeding power plants. These important properties are to be maintained by modern control strategies for DFIG in order to ensure grid stability with the future increase in renewable energy sources.
3. Experimental Validation of the Control Scheme
The test bench, see
Figure 8, consists of a back-to-back
inverter with corresponding LCL-filters, a grid representation and a fault branch [
29]. The impedances of the grid and the fault branch can be changed in a wide range. With the help of contactors Q1... Q3, an islanding event and dynamic changes of transmission impedances can be realized. The parameters of the test bench have been chosen as to emulate a real
wind power plant with typical pu values for filter and grid impedances, switching frequency and filter resonance frequencies of LCL-filters. Since low-power transformers usually have lower X/R values than high-power transformers, transformers with a low short-circuit impedance have been used, which have been artificially increased by external chokes with low-resistive components.
The controller for the back-to-back inverter uses a
dual core signal controller of the type TMS320F28379D from Texas Instruments. The RSC is controlled by one core, the GSC by the other one, and data exchange is done via on-chip shared memory. The control algorithm of the RSC is set up in accordance to the structures shown in
Figure 3,
Figure 6 and
Figure 7. The software of the main control functions was generated by the code generation tool from the simulation structure. The functions and tasks for inverter protection, pulse width modulation, A/D conversion, communication and state machine were developed separately. The system parameters are summarized in
Table 1.
In grid-tied operation, the excellent behavior of the control scheme could be verified.
Figure 9 shows the voltages and currents at the point of common coupling (PCC) when the active power set-point changes from 50% to 100%. The rise time is about 20 ms, and the response is well damped.
The ability to operate at varying rotor speeds and, thereby, slips is shown in
Figure 10. The mechanical speed has been changed from 10% supersynchronous speed to 10% subsynchronous speed within
. Stator and rotor currents do not show any disruptive transients during these significant speed changes.
The advantage of the proposed stator flux control is evident, especially after an islanding event. In
Figure 11, the DFIG is first connected to the grid with full power. At
, the DFIG is disconnected from the grid and feeds a residual load of only 40%. There are no significant transients, and the voltage at the PCC slightly rises due to the reduced voltage drop across the line filter, see
Figure 11b. The frequency is not constant anymore in islanded operation but varies slightly according to the implemented frequency droop.
The system behavior at load changes in islanded mode is presented in
Figure 12. The load has been changed from 20% to 100% and back within about
. During the full-load period, the voltage drops again slightly, but otherwise, no disruptive transients occurred.
4. Simulation of 3-Node Grid
To evaluate the performance of the proposed control system in a more complex environment, a system consisting of a 3-node grid, see
Figure 13, has been modeled in Simulink
®.
The 3-node grid consists of a grid connection on one node and two DFIGs on the other nodes. Both DFIGs are equally rated and parameterized, but the line impedances between the node are different. The transmission line impedance between the two DFIGs is
, and the transmission line impedances between the DFIG1/DFIG2 and the grid are
and
, respectively. A load with
is connected to the grid and a load of
is connected to the DFIG2, while DFIG1 has no load connected directly. The simulation is carried out as a full EMT simulation, and the result is shown in
Figure 14.
When the simulation commences, both DFIGs are in idle mode, i.e., all the power for both the loads is supplied by the grid. At , the reference power for DFIG1 is ramped up to within . The power drawn from the grid reduces accordingly. The voltage at DFIG1 is increased due to the flux droop. During the rise time of active power, the frequency is increased slightly in order to build up the proper voltage angle and decays back to the grid frequency. At , the power reference of DFIG2 is ramped up to . As a result, the active power drawn from the grid decays to almost zero. At , the grid is disconnected from the node, and the DFIGs supply the residual grid consisting of three transmission lines and two loads alone. From now on, the frequency is no more fixed, and both rise according to their p-f curves. The node voltages decrease after islanding because of missing reactive power from the grid. After islanding, the DFIGs show effective active and reactive power sharing despite significant asymmetries in the network transmission lines. The simulation has proven that the proposed stator flux control is well suited for grid-tied operation as well as for islanding events or island operation.