1. Introduction
In recent years, more and more attention has been paid to the energy conversion issue. As a matter of fact, the effects of greenhouse gas (GHG) emissions on the climate are more alarming than ever [
1]. As the demand for energy is ever increasing, the optimization of energy system is mandatory to address the climate change issue. Optimization of energy systems does not only mean replacing fossil sources with renewable ones, such as solar, wind, or geothermal. It also means improving the distribution and the storage of the energy to improve the renewable energy well [
2]. Furthermore, solar and wind sources are extremely fluctuating, also determining a corresponding variation of their electricity production [
3]. Thus, the use of suitable energy storage systems is mandatory to mitigate these fluctuations. Moreover, the use of suitable energy storage systems also allows one to avoid local grid overloading during the most irradiated or windy hours [
4].
In this framework, hydrogen is becoming increasingly attractive as energy vector owing to the variety of processes it can be part of [
5]. Since hydrogen does not exist in nature in its pure form, it is commonly produced by converting hydrocarbons or water. Currently, two main techniques are available. The first one is hydrogen production from electricity by means of the electrolysis process [
6]. In this case, electricity must come from a renewable source, and the final product is called “green hydrogen” [
7]. The second one, which is fairly disputed, is hydrogen production from hydrocarbons (mainly natural gas), also known as “blue hydrogen” [
8].
Recently, interesting economic assessments about hydrogen production from steam methane reforming (SMR) were proposed [
9]. Solutions that are intermediate between “blue” and “green” hydrogen production also are studied [
10].
“Green hydrogen” shows better environmental performance since no CO
2 is produced but it suffers from higher costs [
11]. Thapa et al. [
12] studied the potentials of hydrogen production from hydropower plants in Nepal aiming to replace fossil fuels in road transport sector. An estimation of the surplus energy in the years to come was made relying on current data from the national authority. For the analysis, the surplus electricity produced by hydropower plants was assumed to be exploited. Results showed that by only considering 80% of the total surplus electricity for the year 2027, more than 1.2 million kL of gasoline could be replaced by hydrogen. In a recent work, Rabiee et al. [
13] assessed the technical barriers for the “green hydrogen” harnessing. To quantify the impact of voltage security constraints, they developed a non-linear model validated on the Institute of Electrical and Electronics Engineers (IEEE) 39 bus system. Through the analysis of the most influential technical factors, it resulted that the power to hydrogen (P2H) system location, the loadability constraints, and the renewable energy source (RES) penetration strongly affect the “green hydrogen” exploitability. In addition, the results showed that the location of the P2H plants strongly depends on the RES penetration in a given area. Wind turbine technology in particular was analyzed for P2H demand. It resulted that, for a value of wind penetration of 30% or lower, the H
2 demand is critically influenced by the load margin factor.
The most-quoted technique for hydrogen production is electrolysis due to the too-low efficiency/cost ratio of thermochemical and photocatalytic processes [
14]. Moreover, under dynamic operating conditions, SOCs are preferable to proton exchange membrane (PEM) or alkaline electrolyzer cell (AEC) [
15].
Studies on the dynamic operation of PV systems with reversible SOCs are still lacking in the literature. Indeed, the majority of the papers is still focused on the use of PEM or AEC. Wang et al. [
16] proposed an energy and exergy analysis of a hybrid system including PV, an alkaline fuel cell (AFC) and a Stirling engine for electricity and heat production, and an absorption chiller for cooling energy production. Results showed that a 6.76 kW PV field, a 1 kW AFC, and a 0.73 kW Stirling engine produce, in nominal conditions, 3.42 kW of electricity and 0.91 kW of cooling power. The electricity provided by the PV field accounts for almost 50% of the total electricity produced by the studied plant. In fact, AFC and the Stirling cycle are mainly used for cooling purposes. The electric and overall efficiency of the proposed system are 64.34% and 77.57%, respectively. Finally, an exergy analysis is also carried out, assessing that the studied power plant is featured by 77.44 kW of exergy destruction. Holmes-Gentle et al. [
17] developed a nonlinear model to investigate the functioning of a hybrid system including concentrated PV (CPV) panels with PEM fuel cells and other auxiliary components. The size of the cell is 2 kW. The system is modeled by means of mass and energy balances and the dynamic simulation is carried out in gPROMS. The proposed system is exploited for fuel and thermal energy production. CPV water flowrate and solar irradiance were selected as the parameters to be ranged during the simulation of the nonlinear response of the system. Results from the simulation showed that the operating temperature of the components had a linear response. In contrast, electric components of the CPV and PEM showed a nonlinear behavior.
Cao et al. [
18] developed a multi-objective parametric analysis of a PV-integrated SOEC/SOFC system for “green hydrogen” production. In the case study, the plant is sized considering the SOFC electricity demand, and the surplus hydrogen is sold. The parametric analysis was carried out by varying some of the main parameters such as the current density of the cells or the surplus hydrogen produced. A comprehensive energy, exergy, and economic model was also developed. Results showed an H
2 overproduction four times higher than the demand. In this case, the simple pay back (
SPB) drops below 7 years. Furthermore, the higher the density current of the cell, the lower the efficiency of the cell. Martin-Garcia et al. [
19] proposed a techno-economic feasibility study of a fuel cell coupled with PV for “green hydrogen” production. The system satisfies the electricity demand of a dwelling, and the surplus hydrogen is stored inside a tank. The analysis is carried out by means of Homer Energy Pro tool, which is useful for the components design. Results showed that a 55 kg capacity storage is suitable for the exploitation of 2 PV field of 8 kW of rated power, coupled with a 7.2 kW SOEC. As expected, the double conversion from electricity to hydrogen and vice versa determines a low overall efficiency since 4 kWh of PV electric energy are required to satisfy 1 kWh of load demand. Al-Khori et al. [
20] recently proposed an economic analysis comparing a PV system with electric storage and a PV system coupled with SOFC. The PV size was selected equal to 33.5 MW. Both systems were compared in order to meet the electricity demand of a gas processing plant. Results from the economic analysis showed that the PV-SOFC system has a levelized cost of energy (
LCOE), on a 25 year basis, of 0.11 US
$/kWh. The PV with electric storage system has a LCOE equal to 0.16 US
$/kWh, so the SOFC integrated system is more convenient. Moreover, the PV-SOFC system showed a net present value (
NPV) of 5 million US
$.
A large research effort has been performed for the investigation of the hydrogen as energy vector. A similar effort is also performed to analyze hydrogen as an energy storage system [
21]. Recently, Okundamiya [
22] proposed a parametric analysis of the optimal size of a hybrid system including PV/SOC and hydrogen storage. The system must satisfy the electricity demand of a university laboratory. Hourly simulation performed with HOMER showed that the optimal configuration includes a 54.7 kW PV field, 3 kW electrolyzer, 7 kW fuel cell, and 8 kg hydrogen storage. The renewable fraction of the total load is 96.7%, and the cost of energy (
COE) is 0.0418
$/kWh.
Hydrogen production and storage are also considered for nuclear power hybrid systems. This is due to the high temperature steam released as a consequence of reactor cooling [
23]. Ho et al. [
24] proposed an innovative nuclear hybrid energy system (NHES) with a steam Rankine cycle, an electrolyzer, a hydrogen storage in a salt cavern, and a Brayton cycle for an additional electricity production. All the mentioned components are described by means of a dynamic mathematical model. In particular, the modeling of the salt cavern is interesting since this is an innovative and effective solution for hydrogen storage [
25]. Results showed that the proposed system satisfies the annual grid demand by 93%. The hydrogen production and storage system led to a decrease of the plant loads and improved its flexibility.
Aim and Novelty of the Study
The aim of the paper is to present a dynamic analysis of a hybrid renewable plant that exploits the electricity provided by a PV field to match the power demand of a dwelling. The surplus electricity is supplied to a SOEC system to convert it into hydrogen and store it inside a carbonium-fiber tank. The energy storage allows one to avoid overloads of the electric grid at the local level during the most irradiated hours. Furthermore, the energy stored can be exploited when a deficit of PV production occurs. In that case, hydrogen is withdrawn from the tank and sent to a SOFC system to furnish the needed energy.
As above noted, there is a lack of studies in the literature dealing with the dynamic simulation of PV systems coupled with solid-oxide fuel cells. Several studies handle the hydrogen storage issue for the mitigation of energy fluctuations. However, only a few of these works focus on the dynamic analysis of hydrogen hybrid renewable systems [
26]. Thus, to the best of the authors’ knowledge, there is still a lack of works dealing with the dynamic analysis of green hydrogen production systems. The novelty of this work can be summarized by the following points:
The dynamic analysis of a hybrid renewable system for hydrogen production and storage is carried out by means of a reversible SOC model validated in MATLAB®;
Several control strategies are implemented and discussed both for the operation of the fuel cell and hydrogen storage; furthermore, temperature operating conditions of the cell are managed;
A well-developed thermoeconomic analysis is proposed to evaluate the energy and environmental savings along with the economic feasibility;
A thermoeconomic analysis focused on the hydrogen storage is made to select the optimal size of the H2 storage for the proposed system;
The analysis of the power exchanged with the grid is carried out to investigate how the local grid overloading conditions are avoided by means of the proposed technology.
2. Solid-Oxide Cell Model
The SOC mathematical model proposed in this work is a lumped-parameter model, presented by Wang et al. [
27]. Although several SOC models are available in the open literature, only a few of them are suitable for being integrated in a dynamic simulation. The need to develop an in-house simulation model of the reversible solid-oxide cell comes from the lack of models available in the TRNSYS built-in library. On the other hand, other components are suitably modeled in TRNSYS, as will be shown in the next section, but no model is available for the SOC. The mathematical modeling of the SOC is an interdisciplinary task because it involves different research areas. In fact, a well-structured model must include an electrochemical model, a thermodynamic model, and a chemical reaction model [
28]. Several phenomena have to be considered, such as transport and diffusion, heat and mass transfer, and chemical kinetics [
29]. Obviously, the wider the model, the more accurate the simulation. The models available in the literature range from 0D to 3D analysis; the latter are mainly developed in ANSYS or COMSOL [
30].
The accuracy of the SOC model is not the main concern for the aim of the proposed work. The developed model of the SOC must be integrated in a more general dynamic system that undergoes a one-year simulation. To avoid excessive computational efforts, a 0D quasi-steady state model was selected because a more complex one would determine unacceptable computational times. The model considered in this work was validated by experimental studies, and it allows one to calculate the efficiency, voltage, and operating temperature of the cell starting from the input current. These parameters affect the polarization curve of the cell, which correlates the voltage to the current density. The polarization curve also depends on several design parameters such as geometry, pressure, fuel utilization factor, etc.
In SOFC mode, the cell operating voltage can be calculated starting from the reversible potential of the cell and subtracting the activation, ohmic, and concentration losses, as shown by the Nernst’ law [
31]
Conversely, in SOEC mode, the mentioned losses represent an overvoltage that must be overcome to start the electrolysis process. Thus, terms must be added to the reversible potential
Since more cells are electrically arranged in series to form a stack, the total voltage of the stack is the sum of all the cells’ voltages. Considering that all the cells are equal
The reversible voltage,
Vrev, is calculated starting from the Gibbs free energy of the reaction at standard conditions, which is a known parameter, according to the Nernst’ equation [
32]
where Δ
G0 is the Gibbs free energy at standard conditions (
T = 25°C,
p = 1 bar) and
F is the Faraday constant. Moreover, to calculate
Vrev at the cell operating conditions, the operating temperature and the partial pressures of the gases must be also considered.
The activation losses are due to the charge transfer between electronic and ionic conductors and represent an energy barrier that must be overcome to activate the electrolysis process. This term is calculated by means of the semiempirical Butler–Volmer equation
where
i is the density current,
α is the symmetry factor, and
i0 is the exchange current, calculated as
where
Eact is the activation energy. The ohmic losses depend on the ohmic resistance of the electrons and ions flows through the components and the connectors. It can be calculated as
where
ASRohm is the area-specific ohmic resistance, which is function of the materials adopted and the operating temperature, empirically correlated.
The concentration losses depend on the concentration gradient between the bulk flow and the reaction sites. In fact, because the electrochemical reactions occur at the “three phases boundary”, a mass transport phenomenon within the electrodes takes place. To model the diffusion losses that are caused by this phenomenon, the Fick’s law was selected, which implies less computational effort. According to this law, the concentration losses are calculated as follows:
where
il is the limiting current density, given from the cell datasheet.
The operating current
I is instead obtained by means of the fuel utilization factor
UfBecause the current is an input of the model, the hydrogen produced, or required, by the cell is the result of the equation. The oxygen flow rate is calculated by means of the air utilization factor
UaOnce the cell voltage and the molar fluxes are calculated, the operating temperature is obtained as a function of the equilibrium constant
The overall efficiency of the process is defined as the ratio between the electric energy provided by the SOFC,
Eel,SOFC, and the electric energy supplied to the SOEC,
Eel,SOEC 4. Case Study
The system is designed to meet the electricity demand of a dwelling located in Fuorigrotta (Naples, south of Italy). The electric load of the selected building is evaluated according to the approach described in detail in [
40].
Figure 1 shows the building model developed with the Sketchup plug-in of the TRNSYS software.
The result is a daily load profile that shows three peaks between 8:00 and 10:00, between 11:00 and 12:00, and between 16:00 and 18:00. The first and the second peak are about 40 kW, whereas the last peak reaches 60 kW, which is the maximum value of the load.
Figure 2 shows the considered electric load.
The reference system (RS) is the above-described dwelling, whose power load is met by the grid.
The layout of the proposed hybrid renewable plant is shown in
Figure 3.
The layout mainly consists of two power circuits, the first on the end user side (UPC) and the second one on the SOC side (SPC), and a hydrogen circuit (HC). HC connects a 50 kW SOC with a 1 m3 Hydrogen tank (TK), operating at a maximum pressure of 200 bar. The core of the whole system is the control unit (CU), which manages all the power fluxes among the load, PV system, SOC, and tank. Several control strategies are implemented in the CU to achieve a reliable and efficient operation of the system.
Firstly, the electricity provided by the PV is used to match the power load of the dwelling.
The available surplus power (Pel,surplus), evaluated as the difference between Pel,PV and Pel,LOAD, is delivered to the electrolyzer only if Pel,surplus is greater than or equal to the minimum activation power for the electrolyzer (Pel,EC,min). Note that CU changes the current intensity and voltage of the incoming power according to SOEC polarization curve. Conversely, for values of Pel,surplus lower than the minimum activation power, the electricity is directly supplied to the grid. Similarly, if the value of the Pel,surplus is beyond the upper limit, the maximum suitable power is supplied to the SOEC, and the excess is exported to the grid. This operating strategy is used if the tank is full up to 95% (in terms of maximum pressure), otherwise the power is directly delivered to the grid.
On the other hand, when
Pel,PV is low or PV power production is null, the SOFC is activated, with the aim of matching
Pel,LOAD. The SOFC only operates when the output power required falls within the optimal range of operation for the cell. When the power required is below the lower limit (
Pel,FC,min), the power is directly withdrawn from the grid. On the contrary, when the power required is beyond the cell upper limit (
Pel,FC,max), the maximum power is met by the SOFC, and the residual
Pel,deficit is matched by the grid. No hydrogen is supplied by the tank if this is not at least 16% full. In
Figure 4, the flow charts of the control system are shown.
Further design parameters of the model proposed are reported in
Table 2.
5. Results and Discussion
In this section, the results of both the SOC model validation against experimental data and the dynamic simulation of the hybrid system are presented and discussed. Subsequently, a parametric analysis of the H2 tank is proposed, and the optimal configuration is also discussed.
5.1. SOC Model Validation
The developed model was successfully validated by means of experimental data provided by the same authors [
27]. In particular, the model proposes the simulation of a 50-stack planar cell designed and produced by Topsøe in 2014 made of Nickel/Yttria stabilized Zirconia (Ni/YSZ). Boundary operating conditions are reported in
Table 3.
As reported in this table, the anode is fed by a 50/50 mixture of hydrogen and steam whereas the cathode is fed by pure O2, when the cell operates in SOFC mode.
Figure 5 shows the comparison between the simulated
I–
V curve of the cell and the experimental operating data, both for the electrolyzer and the fuel cell.
There is a very good agreement between the experimental data and the polarization curves obtained by the model, for both configurations of the cell. The deviation between simulations and experiments is always below 2%. The reported curves are also consistent with the previously described model. In fact, for the fuel cell, the voltage decreases in the case of higher current densities, whereas the opposite trend is detected for the electrolyzer.
Figure 6 shows the cell temperature as a function of the cell current density,
icell, for different values of the fuel utilization factor. When the cell operates as a fuel cell, the higher the fuel utilization factor, the higher the temperature of the cell, whatever operating density current is considered. The result can be justified analyzing the energy balance. As a matter of fact, the higher the fuel utilization factor, the higher the amount of H
2 reacting. As a consequence, in this case, a higher amount of heat is also released by the exothermic process.
On the other hand, when the cell operates as an electrolyzer, the opposite trend is detected as far as the density current is below a value of 854 mA/cm2. In fact, as expected, the greater the reacting H2O, the lower the cell temperature. This trend is due to the fact that these electrochemical reactions are endothermic. The temperature difference in this case is lower than the previous case, and it decreases to 0 when a value of current density of about 854 mA/cm2 is reached. For higher values of the current density, the opposite trend occurs. The reason is that, in this case, the efficiency of the cell rapidly decreases due to the high operating temperature. Once the threshold value of current density is exceeded, the increasing of H2 production can no longer compensate for the increasing of absorbed power.
As a consequence, the cell should always operate in a specific range of current density to achieve an optimal operation. For values of this parameter out of the linear field of the polarization curve, the conversion efficiency is very low. Moreover, when the temperature of the cell is too high, the degradation of the cell occurs much faster. The selected current density range for the SOFC is between 400 and 1400 mA/cm2, whereas for the SOEC, it is 300–1100 mA/cm2. By means of the design parameters of the cell, it is possible to determine the range of electric power that can be supplied by the PV field or demanded by the load.
5.2. TRNSYS Model Validation
To evaluate the economic and transient energy performance of the proposed system, a dynamic simulation performed in TRNSYS environment is performed. Results are shown here and discussed on daily, monthly, and yearly basis. The tool returns the time-dependent behavior of the system for a 1-year operation. For sake of brevity, the following sections will analyze only one representative day. Furthermore, a parametric analysis on the hydrogen storage is performed to evaluate the optimal configuration of the proposed system.
5.2.1. Daily Results
Figure 7 shows the dynamic result of the transient simulation for the 31st of July, selected as a representative day to discuss the dynamic trends.
Here, the plot clearly shows the remarkable misalignment between the PV production, Pel,PV, and the electric demand, Pel,LOAD. This is justified by the fact that a residential electric load is considered. In fact, on the one hand, the peaks of the demand mainly occur in the first hours of the morning, between 8:00 and 10:00, and the evening, between 16:00 and 18:00. On the other hand, the solar radiation is maximum during the central hours of the day. Thus, this misalignment promotes the H2 production in the central hours of the day, between 10:00 and 16:00. The compression work, Pel,comp, is not zero when the electricity is supplied to the SOEC, which means that the H2 is correctly supplied to the storage.
Before 8:00, the solar irradiation is almost null, and the PV power is equal to zero. Thus, the PV power is not used to match the load, and the electricity is directly supplied to the grid. The same behavior can be noticed after 18:00. These trends, beyond the climate conditions, are due to the feedback control included in the system, which does not allow the electricity to be supplied to the cell when its value is below the selected threshold value, as seen in
Table 2. Since the selected day for the analysis is one of the most irradiated of the year, the PV field widely covers the load demand, and the H
2 production is remarkably high. Despite this remarkable production of renewable power and renewable H
2, the electricity withdrawn from the grid,
Pel,fromGRID, is definitely not negligible. This trend is consistent with the selected control strategy; in fact, no H
2 is withdrawn from the tank until its state of charge is at least 16%. As a consequence, the SOFC is discharged for meeting the dwelling demand (
Pel,fromSOFC) after 16:00 when the H
2 tank is recharged. This means that, despite the remarkable production of hydrogen, the tank is only able to meet the load for a few hours.
5.2.2. Monthly Results
Figure 8 shows the average results for each month of operation.
The results from the monthly analysis clearly show the advantage of using the SOC storage system with such a system. The previously described misalignment leads to a large use of the SOEC for H
2 production and storage. As a matter of fact, during the summer season, the electric energy supplied by the grid,
Eel,fromGRID, decreases below 1 MWh/month. In fact, the electricity withdrawn from the grid matches 10% of user electric energy demand during the month of July, as seen in
RfromGRID in
Figure 9.
In the summer season, the energy provided by the SOFC, Eel,fromSOFC, is high, and the self-consumption of the system shows the maximum values. During the summer season (April–September), matches up to 70%. This result is justified by the fact that the electric energy demand is almost constant during the year, but it highlights the profitability of the proposed system. The electric energy needed for the compression work, Eel,comp, is always negligible compared to the electric load. By comparing the electricity supplied to the SOEC, Eel,toSOEC, and the electricity supplied to the PV system, Eel,PV, a dual trend can be detected. During the winter season, when the solar irradiation is lower, Eel,toSOEC follows the same trend shown for Eel,PV. During the summer season, when the solar radiation is higher, according to the designed control strategy, the surplus energy is not supplied to the SOEC, and Eel,toSOEC is almost constant. In this case, the electricity is directly supplied to the grid and Eel,toGRID is higher.
Figure 9 shows that the electricity fraction from the PV, which is supplied to the grid, increases in the summer period, as expected from
Figure 8. More specifically, since the PV energy dramatically decreases in the winter period, the electricity fraction supplied to the grid increases. The majority of the load is met by the coupled PV + SOC + storage system in summer period, when the coverage rises up to 90% of the total energy demand.
5.2.3. Yearly Results
In
Table 4 reports the results obtained by the dynamic simulation considering one year of operation. According to the presented data, the overall efficiency of the SOC is 0.47, which is fairly high with respect to values available in literature. This result is due to the adopted control managing the cell, which allows the cell to always work in the optimal field of operating conditions.
The energy supplied to the grid is about 6.3% of the total energy provided by the PV field, whereas the energy withdrawn from the grid is 37.2% of the energy demand. These results confirm that the goal of the proposed system is reached since the energy exchanged with the national grid is strongly reduced. The total self-consumption of the system reaches 62.8%, which means that the proposed system is fairly energy-independent. In
Table 5, the main results from the thermoeconomic analysis are reported.
The results of the proposed system (PS) are compared to the reference system (RS), in which the overall energy demand of the dwelling is supposed to be met by the grid. The high profitability of the PS is shown by the relevant energy savings, with a PES of 69%. The coupling of the PV with the SOC and H2 storage system determines a decrease of the PE consumption from 203.05 to 75.50 MWh/year. As a consequence, the CO2 equivalent emissions also undergo a strong reduction. Furthermore, the operating costs are strongly decreased since, in the PS, the energy withdrawn by the grid is by far lower than in the RS. Moreover, the surplus electricity is sold to the grid, and a further saving is obtained.
The proposed shows interesting results with a total investment cost of 110.13 k€, and SPB of 10.1 years. The NPV, calculated on the basis of 25 years of life, is equal to 42.70 k€. In conclusion, the economic profitability of the investment is 39%.
5.2.4. Parametric Analysis
The results shown in the previous section demonstrate the relevant SPB of the proposed system. The thermoeconomic analysis shows that the economic profitability of the system is not encouraging. This is also due to an unoptimized selection of components capacities, mainly for the case of the storage tank. As a matter of fact, a tank of 1 m3 volume and 200 bar of maximum pressure can store the energy produced by the SOEC for 13 h of nominal operating conditions.
Figure 10 shows the results from the parametric analysis of the tank size, ranging from 25 bar to 200 bar of maximum pressure. The curves are referred to three different volumes of the storage, that are 0.50, 0.75, and 1 m
3.
The capital cost of the system is the sum of two terms. The constant term is represented by the plant capital costs, in particular PV and SOC systems. The linearly increasing term is the storage cost, which is proportional to the maximum capacity. The storage cost is per unit of kg of hydrogen stored.
The higher the tank capacity and pressure, the higher the amount of energy that can be stored and the greater the energy self-consumed by the plant. At the same time, the increase of the tank capacity causes a reduction of the surplus electricity exported to the grid. Note that 1 kWh produced by the PV field and delivered to the grid corresponds to 0.96 kWh exported to the grid, due to the regulator/inverter efficiency. Conversely, 1 kWh produced by the PV field and delivered to the SOEC and stored into the tank corresponds to about 0.80 kWh self-consumed by the plant, because of the efficiency of the electrolyzer, fuel cell, and compressor.
These figures justify the reduction of the PES as the tank capacity increases.
From the economic point of view, the self-consumed electricity plays a significant role, much more than the one played by the electricity exported to the grid: jel,fromGRID = 0.20 €/kWh vs. jel,toGRID = 0.05 €/kWh. As mentioned before, the higher the tank capacity and maximum pressure, the higher the amount of energy stored in the tank.
However,
SPB curves in
Figure 10 exhibit a minimum that represents a threshold value. A further increase in tank capacity would not increase the self-consumed energy since the system is not able to fill the tank beyond that value. For example, for a 1 m
3 tank, the system achieves the best profitability for a tank maximum pressure equal to 75 bar. A further increase of the maximum tank pressure only determines an increase of the storage capital cost, without increasing the exploitation of the storage charge/discharge capacity.
The same trend can be detected for the PI graph. Once a value of 1 m3 of capacity and 75 bar of maximum pressure are selected, wider energy storage leads to a lower profitability of the system. In this case, the difference is significant since the optimal solution shows a PI by 46%, and it can only decrease, even below 40%.