1. Introduction
A clean and low-carbon energy system taking renewable energy as the mainstay are being built in China in order to address the increasingly pressing issues of energy security, environmental degradation, climate warming, etc. However, the instability of the power grid frequency is gradually increasing because of the increase in generating capacity from the renewable energy generator sets. The coal-fired generating units play a key role in the peak modulation and the frequency modulation in the power grid to maintain the stability of the grid frequency. The operating conditions of the power plant boilers vary frequently with the constant adjustment of the boiler load. The changes in the boiler operating conditions have a great effect on the combustion in the furnace and the NOx concentration in the economizer outlet. It has been reported that the fluctuation amplitude of the NOx concentration at the economizer outlet reached ±150 mg/Nm
3 when the boiler load was adjusted for a 600 MW supercritical pressure generating unit. It brings great difficulty to the regulation of the ammonia injection of SCR denitrification facility, which usually results in excessive ammonia injected into the SCR denitrification facility for the environmental protection [
1,
2]. Therefore, the ammonia escape increases sharply because of excessive ammonia injected, which can lead to serious problems such as ash deposition and heavy clogging because of the ammonium bisulfate formed in the air heater. Finally, it seriously affects the economic efficiency and the environmental protection performance of the power generation sets. The main reason for the aforementioned problems is that there is a large hysteresis during the adjustment of the amount of ammonia injected according to the measured value of NOx concentration at the exit of the SCR reactor. In recent years, some researchers have proposed to establish a prediction model of NOx concentration at the economizer outlet according to the operational parameters, and the variation in the NOx concentration at the economizer outlet can be predicted when the operating conditions begin to change, so as to coordinate the adjustment of ammonia injection and make timely operational adjustments. This idea has been generally recognized, and the prediction model about NOx is considered to be an effective means to guide the ammonia injection of the SCR denitrification facility [
3]. It is much too complicated to establish the prediction model of NOx, because its input parameters of the prediction model are directly related to the factors affecting the furnace combustion, such as the coal consumption, the air distribution, the oxygen content, etc. The parameter variation will influence the formation and the reduction in NOx in the furnace and further the NOx concentration at the economizer outlet. Under the background of deep peak shaving, the temperature and the oxygen amount in the furnace have greater influence on NOx formation [
4]. Hence, it is necessary to investigate the influence factors and the laws of NOx formation in the furnace.
Scholars all around the world have performed a lot of research on the formation law of NOx and its prediction models. Generally, the data from the field tests and the distributed control system (DCS) of the power plant are used to establish the prediction models of NOx formation [
5]. However, those data may fluctuate greatly and include many outliers, and as a result the data cleaning becomes a challenge for the modeling process. When the NOx concentration at the furnace outlet is taken as a mean value, without the consideration of the nonuniform NOx distribution on the cross section of the flue, it is unable to control the SCR denitrification facility to implement the partitioned ammonia injection. Fortunately, the numerical simulation based on the computational fluid dynamics (CFD) software can be used not only to analyze the influence law of various parameters on the NOx formation, but also to provide the detailed data for establishing the NOx prediction model [
5].
At present, it is accepted that the NOx formation mechanism in coal combustion includes the thermal NOx, the prompt NOx and the fuel NOx [
6,
7,
8,
9]. The simple chemical model established by Zeldovich is generally used to describe the formation mechanism of thermal NOx [
10]. The chemical reaction model established by De S is used to describe the formation mechanism of the fuel NOx [
5,
11]. The nitrogen component from the fuel is divided into the nitrogen fixed in char and the volatile nitrogen [
12]. The volatile N is first released in the form of HCN and NH
3 during the pyrolysis process, then these substances are competitively oxidized to NO or reduced to N
2 according to the local oxidizing or reducing atmosphere [
11]. However, the fixed N in char can be directly oxidized into NO. This formation model of fuel NOx is widely used in the simulation calculation. The prompt NOx is mainly produced by the hydrocarbons in the volatile matter of pulverized coal reacting with N
2 in air at high temperature. The prompt NOx accounts for a very small proportion of the total NOx [
13], so the thermal NOx and the fuel NOx are usually mainly considered in many studies on the NOx formation in coal combustion [
5,
14,
15,
16,
17,
18].
In recent years, the domestic and foreign scholars have established the calculation models of NOx using CFD software and constantly optimized the models. In 2015, Fortunato et al. performed a numerical investigation into the roles of closure sub-models for the modelling of a flameless furnace and the main NO formation paths using the commercial software of Ansys Fluent 6.3 [
19]. The results show that different combustion/kinetic models used can result in different distributions of temperature/chemical species in the furnace and the N
2O mechanism is the dominant factor influencing NO formation, but the formation mechanism of thermal NO is not as relevant as in traditional combustion regime. In 2016, Li et al. developed a new NOx calculation model for pulverized coal combustion by User-Defined Function (UDF) [
20]. The gasification reaction models of char with CO
2 and H
2O were added to the char combustion model during the developing of the NOx calculation model. Thus, the homogeneous reaction of NOx reduced by the hydrocarbons was quantitatively described through calculating the amount of CO and H
2 produced. In 2017, Tan et al. simulated the NOx formation process in a 660 MW tangentially fired boiler using the post-processing method [
21], where the proportion of nitrogen in volatiles and char was determined by the chemical percolation devolatilization (CPD) model [
22,
23]. Their study results indicated that the NOx calculation results were more reasonable when the gasification reactions of char with CO
2 and H
2O were considered in the char combustion reaction model. Thus, the relative error between the simulated value and the measured value is only 5.9%. Zhang et al. studied a circulating fluid bed boiler using the software of CFD and the chemical reactors(CR), and reasonably made use of the advantages of the total package reaction and the elementary reaction; ultimately, the accurate calculation results were obtained in the case of using less computing resources [
24]. In 2022, Lamioni et al. investigated the effect of H
2 addition on the combustion process and the pollutant emissions in domestic condensing boilers through the coupling research between numerical simulations and the practical operating conditions [
25]. The study results can help design the strategies to restrict pollutant emissions. The above research shows that the numerical simulation can be used to investigate the NOx formation in furnace combustion more effectively.
In recent years, some researchers have applied the intelligence algorithm to predict the generation of NOx. Meanwhile, other scholars are continually optimizing the NOx prediction algorithm and utilizing the NOx prediction model to optimize the boiler operation. The input parameters of the NOx prediction model are usually from the field tests and the DCS of the power plant [
26]. The quality of the data will directly affect the training of the prediction model, and then determine the prediction accuracy of NOx generation. More detailed information on furnaces can be obtained by means of the numerical simulation based on the CFD software. The detailed information is not only used to investigate the influence law of many factors on the NOx formation, but also to be the new data source for the NOx prediction model. In 2019, Shi et al. established an artificial neural network (ANN) model for predicting the boiler operation and the NOx emission characteristics according to the simulated data and the boiler operational data [
27]. The model provided a good prediction of the thermal efficiency and the NOx emission of a 660 MW coal-fired boiler, and the average errors were only 0.04% and 3.56 mg/Nm
3, respectively. The study results indicated that the CFD numerical simulation data contributed to the generalization ability of the neural network models. Ye et al. built the prediction model of NOx generation for a coal-fired power plant based on the historical operating data from the DCS and the numerical simulation data of the NOx [
28]. The study results indicated the simulation data could improve the prediction ability of the model as well as the depth and the completeness of the data set.
Nowadays, the numerical simulation method has been relatively mature enough to obtain the combustion characteristics of the pulverized coal and the laws of NOx generation. However, the range of the previous simulation research is usually only from the burner inlet to the super-heater outlet. There is little system-wide research from the burner inlet to the economizer outlet, and the number of simulated operating conditions is also relatively small. Although the NOx emission can be predicted well via the machine learning method, the previous study is often only focused on describing the nonlinear relationships between the NOx concentration at the furnace outlet and the boiler operating parameters, without taking into consideration of other factors affecting the formation and reduction process of NOx. In addition, the prediction model established is unable to control the SCR denitrification facility to perform the partitioned ammonia injection if there is no consideration of nonuniform NOx distribution on the cross section of flue. Under the background of the deep peak shaving, it is necessary to perform the simulation research on batch variable operating conditions; the detailed information from the numerical simulation can be a new data source of the prediction models of NOx formation, so that the prediction models can be further optimized to accurately guide the SCR denitrification facility achieving the partition ammonia injection.
In this study, taking a 600 MW supercritical opposed firing coal-fired boiler as the research object, the numerical calculation models of pulverized coal combustion and NOx formation are established. The numerical simulation of variable operational conditions is performed. The factors influencing NOx formation and its concentration distribution in the furnace are studied.
3. Results and Discussion
In this section the numerical calculations of the combustion process in the furnace under variable operating conditions are performed, based on the established physical and mathematical models. The effects of the boiler load, the air rate and the air temperature on the parameters, including the NOx concentration and the burnout rate of pulverized coal at the furnace outlet, have been analyzed to provide the data for the prediction of NOx concentration and more accurately guide the ammonia injection of the SCR denitrification facility.
3.1. Operating Condition Setting and Description of Batch Quantity Calculation
According to the range of peak regulation in the historical operation of the boiler, the boiler loads from 250 to 600 MW are selected as the research objects, and the combustion processes in the furnace under 8 different load conditions have been simulated. The specific operating parameters of 8 different conditions are listed in
Table 3.
Based on the study of boiler load change, the influences of the air amount and the air temperature are researched under 4 boiler loads including 600, 500, 400 and 250 MW. The changed air amount conditions include the changed excess air coefficient, the changed OFA ratio, the changed primary air ratio and the changed internal secondary air ratio. The changed supply air temperature conditions include the changed primary air temperature and the changed temperature of the secondary air and the OFA. Each of the above parameters changes 20 working conditions, so there are a total of 120 groups of working conditions, as listed in
Table 4. It should be noted that other parameters remain unchanged when studying the influences of a parameter change on the formation and the distribution of NOx.
During the numerical simulation, the inlet boundary of the furnace model in this study includes the inlet boundary of 36 burners and 12 OFA nozzles. Each burner is equipped with a primary air inlet, an internal secondary air and an external secondary air inlet. When the working condition is changed more than 300 inlet parameters will change, which makes the operating process of setting the inlet parameters very complicated. Consequently, in this study the command statements for modifying the parameters are exported from the Journal file included in Fluent software, and the scripts are written in Python language, so that these statements can be read repeatedly by the solver of Fluent software. Additionally, the values required to be modified are automatically read according to the ID information of the model boundary surface, which greatly reduces human labor. Meanwhile, the command statements in the solver of Fluent software to calculate the sectional temperature, the NOx concentration, etc., are similarly processed.
3.2. Effects of Boiler Loads on NOx Formation
3.2.1. Effects on the Distributions of the Temperature Field and O2 Concentration
When the boiler load is separately 600, 500, 400 and 250 MW, the temperature distribution on the central longitudinal section of the furnace burner is shown in
Figure 5. It can be seen from
Figure 5 that the temperature distribution in the furnace is basically the same under different boiler loads and is well symmetrical. As the boiler load decreases the temperature of the furnace center decreases, and the high temperature zone of the furnace center gradually becomes smaller. When the boiler load is 600 MW, a large amount of pulverized coal is injected into the furnace from the upper burner and is not burnt out in the combustion zone. However, the unburned pulverized coal burns violently in the burning-out zone, which makes the temperature higher in the furnace upper zone and easily causes ash fouling on the superheater. When the boiler load is 500 MW there is no pulverized coal through the F-layer burners, but there is only a small amount of primary air and secondary air injected into the furnace. This ensures that the flame is still in the center of the furnace and prevents the flame deflection. When the boiler load is 250 MW, the temperature of the dry bottom hopper is also significantly reduced.
In the actual operation of the power plant, the air–coal ratio is often larger under the lower boiler load. When the boiler load is separately 600, 500, 400 and 250 MW, the volume concentration of O
2 on the central longitudinal section of the furnace burners is shown in
Figure 6. As shown in
Figure 6, with the declining of the boiler load the overall O
2 concentration in the furnace increases. When the boiler load is 500 MW the O
2 concentration is higher because there is no pulverized coal through the F-layer burners. When the boiler load is 400 MW and below the upper burners are completely shut down, so the O
2 concentration in the area near the OFA is higher.
3.2.2. Effects on the Distribution of NOx Concentration
When the boiler load is separately 600, 500, 400 and 250 MW, the NOx concentration on the central longitudinal section of the furnace burner is shown in
Figure 7. It can be seen that when the boiler load is reduced from 600 to 400 MW, the overall NOx concentration in the furnace is reduced. When the boiler load is 250 W the NOx concentration is the highest among them. When the boiler load is 600 MW the central temperature of the furnace is higher (see
Figure 5a), and a large amount of thermal NOx is generated. When the boiler load declines, the furnace center temperature decreases (see
Figure 5b–d) and the thermal NOx is greatly reduced. When the boiler load is 250 MW, due to the larger ratio of air to coal in the boiler at low boiler load the O
2 concentration in furnace is high, forming a strong oxidizing atmosphere and generating a large amount of fuel NOx, so the NOx concentration is greater.
Based on the above analysis, the NOx concentrations at the outlet plane of the economizer under different boiler loads are quantitatively calculated, and the simulated values of NOx concentration are compared with the measured values. The results are shown in
Figure 8. It can be seen from
Figure 8 that the relative errors between the calculated values and the measured values of the NOx concentration at the economizer outlet do not exceed 3.3% under different loads, which further proves the accuracy and reliability of the models established. It can also be seen from
Figure 8 that the NOx concentration at the economizer outlet decreases first and then increases with the decrease in boiler load. When the boiler load is gradually reduced from 600 to 400 MW, the furnace center temperature will be reduced from 1678 K to 1423 K (see
Figure 5). According to the calculation analysis the amount of thermal NOx formed is reduced by 13.26%, so the overall NOx concentration in the furnace is reduced. However, when the boiler load is reduced from 400 MW to 250 MW due to the increase in air–coal ratio in furnace, the O
2 concentration in the furnace increases, which results in an increase in fuel NOx so the NOx concentration increases to 392 mg/m
3.
As is shown in
Figure 9, the variation trend of NOx concentration with the furnace height is basically the same. In the dry bottom hopper area the NOx concentration rises with the increase in furnace height, but due to the low temperature and the low oxygen content in the dry bottom hopper area, the NOx concentration in this area under different loads is lower than 324 mg/m
3. In the main combustion zone most of the pulverized coal burns here and a large amount of NOx is generated, which results in an overall increase in NOx concentration with the increase in furnace height. The NOx concentration in the main combustion zone increases by 39–51 mg/m
3 at different loads. Since the excess air coefficient in the burner zone is less than 1, some of the generated NOx is reduced by the intermediates (such as CO). The concentration of NOx fluctuates at the height of each burner nozzle, and the fluctuation of NOx concentration is more obvious, especially at low loads.
When operating at the boiler loads of 600 and 550 MW the six-layer burners are all put into operation, so the NOx concentration in the combustion zone increases more evenly when the flue gas flows upwards. When the boiler is operated under 500 and 450 MW loads the F-layer burners are turned off and the amount of pulverized coal injected into the furnace decreases, but there is still a small amount of air injected to the furnace through the burners out of operation and the oxidizing atmosphere is enhanced, which is conducive to the oxidation of intermediate products such as HCN and NH3 from the middle and lower burners to generate NOx. Hence, there is still a large amount of NOx generated at the upper-layer burner position. When the boiler operates at 400 MW and below-400 MW loads the upper burners are all out of operation, so the fuel NOx generation is less in this area. Due to the low temperature in the center of the furnace in this area the thermal NOx is hardly generated, but the NOx concentration increases obviously with the increase in height in the middle and lower layer burner region. In the OFA area, the generated NOx is diluted by a large amount of OFA, so the NOx concentration at the height of OFA layer decreases by 20–41 mg/m3. The amount of oxygen in the furnace is replenished in the area above the OFA nozzles, so the intermediates such as HCN and NH3 from the combustion zone are oxidized to NOx. Therefore, with the increase in furnace height the concentration of NOx increases by 15–60 mg/m3. In the area above the furnace arch the formation and reduction in NOx in the furnace tends to be balanced, and the NOx concentration is basically stable.
3.3. Effects of Air Amount on NOx Formation
In this section, under the boiler loads of 600, 500, 400 and 250 MW, the excess air coefficient, the OFA ratio, the primary air ratio and the internal secondary air ratio in the burner are changed in turn, and the furnace combustion and the NOx generation process are numerically simulated under different air distribution modes.
3.3.1. Effects of Excess Air Coefficient
According to the actual operating conditions, the numerical simulation of changing the excess air coefficient is carried out under the load of 600, 500, 400 and 250 MW, respectively. The excess air coefficient is adjusted to 1.1, 1.2, 1.3, 1.4 and 1.5 when the coal feeding rate, the air distribution mode and the air distribution temperature of the boiler are kept unchanged. There are 20 operational conditions in total.
Effects of Excess Air Coefficient on NOx Concentration at Economizer Outlet
When the boiler is operated under different loads,
Figure 10 shows the variation in NOx concentration at the economizer outlet with the excess air coefficient. It can be seen from
Figure 10 that in the load range of 400–600 MW the NOx concentration at the economizer outlet goes up with the increase in the excess air coefficient. The reason is that a large amount of fuel NOx is generated because the increase in the air amount enhances the oxidizing atmosphere in the furnace. Under the high boiler loads, the variation amplitude of NOx with the excess air coefficient is also larger. Under the boiler load of 400, 500 and 600 MW, the NOx concentration at the economizer outlet increases by 53, 65 and 78 mg/m
3, respectively, when the excess air coefficient increases from 1 to 1.5. In addition, under the same load, when the excess air coefficient is larger the variation in NOx concentration with the excess air coefficient is smaller. This is because the increase in air volume reduces the early combustion temperature of pulverized coal and delays the combustion of pulverized coal, which finally reduces the thermal NOx production. At the boiler load of 250 MW, when the excess air coefficient is in the range of 1.3–1.5, the NOx concentration at the outlet of the economizer rises slightly with the increase in the excess air coefficient. However, when the excess air coefficient is less than 1.3 the NOx concentration increases as the excess air coefficient decreases. The reason is that the secondary air is mixed with the pulverized coal prematurely due to the small amount of primary air at the outlet of a single burner, which results in a large amount of NOx at the outlet of the burner.
Effects of Excess Air Coefficient on NOx Distribution in the Furnace
Under the different excess air coefficient, the variation curves of NOx concentration along the furnace height are shown in
Figure 11.
Figure 11a–d separately corresponds to four different boiler loads. It can be seen from
Figure 11 that the NOx concentration in the furnace increases with the increase in furnace height on the whole, corresponding to each excess air coefficient under four different boiler loads. When the excess air coefficient is larger, the NOx concentration fluctuates greatly in the main combustion zone. At the nozzle height of the burning-out zone, the NOx concentration decreases because NOx is diluted by the OFA injected. In the area above the OFA nozzle the NOx concentration rises slowly with the increase in furnace height owing to the good oxidizing atmosphere, and finally tends to be stable. When the excess air coefficient is larger, the NOx concentration in the burning-out zone increases greatly.
3.3.2. Effects of OFA Ratio
The effect of OFA ratio on NOx is that it reduces the amount of oxygen in the main combustion zone and makes the pulverized coal burn in stages in the main combustion zone and the burning-out zone. The air staged combustion can effectively reduce the NOx formation during coal combustion. In this section, under the boiler load of 600, 500, 400 and 250 MW, respectively, the total air amount and the air distribution temperature are kept unchanged and the OFA ratio is set as 15%, 20%, 25%, 30% and 35%, respectively. The numerical simulations of different OFA ratios are carried out, there being a total of 20 working conditions.
Effects of OFA Ratio on NOx Concentration at Economizer Outlet
Under different boiler loads, the variation in NOx concentration at the economizer outlet with the OFA ratio is shown in
Figure 12. It can be seen from
Figure 12 that the NOx concentration at the economizer outlet decreases with the increase in the OFA ratio. This is because the increase in the OFA ratio can enhance the air staging effect and reduce the oxygen content in the combustion zone, which can inhibit the formation of NOx. At the boiler loads of 600, 500, 400 and 250 MW, when the OFA ratio is increased from 15% to 35%, the NOx concentration at the economizer outlet decreases by 36, 41, 46 and 57 mg/m
3, respectively. This indicates that the variation in NOx concentration with the OFA ratio is more obvious under the low boiler load. The reason is that the NOx generated in the furnace under the low boiler load is almost the fuel NOx, which is more sensitive to the oxygen content.
Effects of OFA Ratio on NOx Distribution in the Furnace
The curves of NOx concentration varying with the furnace height are illustrated in
Figure 13 under different OFA ratios.
Figure 13a–d separately corresponds to four different boiler loads. It can be seen from
Figure 13 that the NOx concentration in the furnace increases with the increase in furnace height on the whole, corresponding to each OFA ratio under four different boiler loads. When the OFA ratio is larger the increase in NOx concentration in the main combustion zone is smaller, meanwhile the air amount in the main combustion zone is small and the fluctuation of NOx concentration in this zone is small. In the area above the OFA nozzles the NOx concentration goes up with the increase in furnace height, and when the OFA ratio is larger the increase in NOx concentration is also larger.
3.3.3. Effects of Primary Air Ratio
The change in primary air ratio can affect the flow field, the temperature field and the combustion process of pulverized coal at the outlet of the burner. In this section, under the boiler load of 600, 500, 400 and 250 MW, respectively, keeping the total air amount and the air temperature unchanged the primary air ratio is adjusted to 20%, 22.5%, 25%, 27.5% and 30%, respectively. The numerical simulations of operating conditions at four primary air ratios are implemented, there being 20 working conditions in total.
Effects of Primary Air Ratio on NOx Concentration at Economizer Outlet
When the boiler operates under different loads, the variation in NOx concentration at the economizer outlet with the primary air ratio is shown in
Figure 14. It can be seen from
Figure 14 that the NOx concentration at the economizer outlet increases with the increase in the primary air ratio in the range of 400–600 MW load, and the NOx concentration varies greatly with the primary air ratio under high boiler loads. The reason is that a large amount of NOx is generated at the initial stage of combustion because the air–coal ratio at the outlet of the burner increases and the oxidizing atmosphere is enhanced with increasing the primary air ratio. Additionally, the amount of CO is reduced owing to the increase in O
2 content, so the reduction in NOx by CO is weakened, which can contribute to NOx formation. At the boiler loads of 400, 500 and 600 MW, when the primary air ratio increases from 20% to 30%, the NOx concentration at the economizer outlet increases by 36, 42 and 49 mg/m
3, respectively. Under the boiler load of 250 MW, when the primary air ratio is raised from 22.5% to 30% the NOx concentration at the economizer outlet rises slightly. However, when the primary air ratio is less than 22.5% a large amount of fuel-type NOx is generated because of the advance ignition of pulverized coal. Hence, the NOx concentration is reduced by means of increasing the primary air ratio to delay the ignition of pulverized coal.
Effects of Primary Air Ratio on NOx Distribution in Furnace
Under the boiler loads of 600, 500, 400 and 250 MW, when the primary air ratio is different, the variation curves of NOx concentration with the furnace height are illustrated in
Figure 15a–d. It can be seen that under different operating conditions the NOx concentration in the main combustion zone increases with the increase in furnace height as a whole. When the primary air ratio is larger the increase in NOx concentration is larger, and the fluctuation of NOx concentration in this area is also larger. In the zone above the OFA nozzles the NOx concentration rises with the furnace height increasing, and when the primary air ratio is small the increase in NOx concentration in the burning-out zone is large.
3.3.4. Effects of Internal Secondary Air Ratio
In this study, the ratio of the internal secondary air to the external secondary air of the burners can be adjusted, which can affect the pulverized coal combustion and the NOx generation. When the internal secondary air ratio is small the recirculation zone is small, which weakens the ability to entrain the high-temperature flue gas. In order to study the influence of internal secondary air on NOx generation under the boiler load of 600, 500, 400 and 250 MW, respectively, and keeping the total air amount and the air temperature unchanged, the numerical simulation calculation has been performed when the internal secondary air ratio is set as 20%, 27.5%, 35%, 42.5% and 50%, respectively. There are 20 working conditions simulated in total.
Effects of Internal Secondary Air Ratio on NOx Concentration at Economizer Outlet
The variation in NOx concentration at the economizer outlet with the internal secondary air ratio when the boiler operates under different loads is shown in
Figure 16. It can be seen from
Figure 16 that the NOx concentration at the economizer outlet decreases first and then increases with the increase in the internal secondary air ratio under four boiler loads, and the NOx concentration varies greatly with the internal secondary air ratio under low boiler loads. When the internal secondary air ratio is small the increase in the internal secondary air amount can enlarge the internal recirculation zone at the outlet of the burners, which delays the mixing of the pulverized coal–air flow and the secondary air and strengthens the combustion classification effect, so the formation of fuel NOx is inhibited. When the internal secondary air ratio is large, the amount of high temperature flue gas entrained by the internal secondary air increases, which enhances the initial stage temperature of the pulverized coal combustion and then increases the amount of thermal NOx generation. In addition, the increment of thermal NOx is greater than the reduction in fuel NOx. Therefore, the NOx concentration at the economizer outlet decreases first and then increases with the increase in the internal secondary air ratio. When the boiler load is low the combustion aerodynamic field is unstable due to the small primary air rate and the small secondary air rate at the burner outlet, so the formation of NOx is more affected by the internal secondary air ratio. At the boiler load of 400 MW, when the internal secondary air ratio is 35%, the minimum NOx emission at the economizer outlet is 280 mg/m
3.
Effects of Internal Secondary Air Ratio on NOx Distribution in Furnace
At the boiler loads of 600, 500, 400 and 250 MW, respectively, when the internal secondary air ratio is different the variation curves of NOx concentration with furnace height are shown in
Figure 17. It can be seen from this figure that the trends of NOx concentration changing with furnace height are basically the same under different working conditions. Due to the low temperature and the low oxygen content in the cold hopper area, the NOx concentration is less than 330 mg/m
3. In the combustion zone and the burning-out zone, with the increase in the supply air rate in the furnace a large amount of NOx is generated. However, from the position of 5 m above the OFA the NOx concentration is basically no longer changed, because the air rate is no longer provided in the furnace and the pulverized coal combustion reaction is also completed. In the main combustion zone, when the internal secondary air ratio varies the increased amplitude of NOx concentration changes with the increase in furnace height, while the increased amplitude of NOx concentration in the burning-out zone is basically unchanged; this indicates the influence of internal secondary air on NOx formation that mainly occurs in the main combustion zone.
3.4. Effects of Supply Air Temperature on NOx Formation
The temperature increase in the supply air can raise the overall temperature in the furnace and make the pulverized coal catch fire in advance, which can affect the formation and the reduction in NOx. To study the effects of supply air temperature on NOx when the primary and secondary air temperatures are changed in turn under the boiler loads of 600, 500, 400 and 250 MW, the combustion and NOx formation processes in the furnace are numerically simulated and analyzed.
3.4.1. Effects of Primary Air Temperature on NOx Concentration at Economizer Outlet
According to the actual operating conditions under the boiler load of 600, 500, 400 and 250 MW, respectively, and keeping the total air amount and the air distribution mode unchanged, the numerical simulation calculation has been carried out when the primary air temperature is set as 335 K, 345 K, 355 K, 365 K and 375 K. There are a total of 20 working conditions.
The variation curves of NOx concentration at the economizer outlet with the primary air temperature under different boiler loads are shown in
Figure 18. It can be seen from the figure that the NOx concentration at the economizer outlet increases when the primary air temperature goes up, and the NOx concentration varies more obviously with the primary air temperature under high boiler load. When increasing the primary air temperature the overall temperature level in furnace increases. Consequently, the thermal NOx increases exponentially, and the fuel NOx generation also increases because the pulverized coal burns ahead of schedule and a large number of volatiles are released. This is why the NOx concentration at the economizer outlet increases. The thermal NOx accounts for a large proportion under high boiler load and the thermal NOx is more affected by the primary air temperature, so the NOx concentration varies more. When the primary air temperature is increased from 335 K to 375 K the NOx concentration at the economizer outlet increases by 55, 33, 22, and 10 mg/m
3 at the boiler load of 600, 500, 400 and 250 MW, respectively.
3.4.2. Effects of the Temperature of Secondary Air and OFA on NOx Concentration at Economizer Outlet
The proportion of the secondary air and the OFA accounting for the total air amount is larger, hence their temperature change can influence the overall temperature field in the furnace, and then the NOx generation. According to the actual operating conditions, under the boiler loads of 600, 500, 400 and 250 MW, respectively, and keeping the total air amount and the air distribution mode unchanged, the numerical simulation calculation has been carried out when the temperature of secondary air and OFA is set as 550 K, 555 K, 560 K, 565 K and 570 K. There are a total of 20 working conditions.
The variation curves of NOx concentration at the economizer outlet with the temperature of secondary air and OFA under different boiler loads are shown in
Figure 19. It can be seen from the figure that the NOx concentration at the economizer outlet increases when the temperature of secondary air and OFA rises. In addition, the concentration of NOx varies more obviously with the temperature of secondary air and OFA under high boiler load. When raising the temperature of secondary air and OFA, the overall temperature level in the furnace increases, which leads to the increase in NOx generation. When the temperature of secondary air and OFA is raised from 550 K to 570 K the NOx concentration at the economizer outlet increases by 83, 53, 30, and 14 mg/m
3 at the boiler loads of 600, 500, 400 and 250 MW, respectively. The above data show that the influence of the temperature change in secondary air and OFA is greater than that of the primary air temperature change.
4. Conclusions
In this work, taking a 600 MW supercritical opposed firing pulverized coal boiler as the research object, the numerical simulation models of pulverized coal combustion and a full-scale three-dimensional physical model of the boiler are established, which are the basis of the simulation research. The simulation data of the base operating conditions are compared with the field test data, which has verified the accuracy and the reliability of the models established. On that basis, the combustion numerical simulation of 128 groups of variable working conditions has been performed. The effects of boiler load, the air rate and the air temperature on the formation and the distribution of NOx in the furnace have been emphatically analyzed.
The simulation results show the NOx concentration goes up with the increase in furnace height when all the parameters discussed are changed, until it tends towards stability in the burning-out zone. However, the NOx concentration is low in the dry bottom hopper, and it fluctuates greatly in the main combustion zone. When the boiler load is reduced from 600 to 250 MW, the NOx concentration at the economizer outlet decreases first and then increases. When the boiler runs at medium and high loads, the increase in excess air coefficient can enhance the NOx concentration at the economizer outlet because of generating much fuel NOx. However, when the excess air coefficient is less than 1.3, the NOx concentration at the economizer outlet increases as the excess air coefficient decreases under the load of 250 MW. Owing to its air staging effect, the increase in OFA ratio not only reduces the NOx concentration at the economizer outlet, but also improves the combustion stability of the boiler. With the decrease in boiler load, the effect of the OFA ratio on NOx concentration at the economizer outlet increases gradually. The increase in primary air can raise the NOx concentration at the economizer outlet at medium and high boiler loads because of the enhanced oxidizing atmosphere in the furnace. The NOx concentration at the economizer outlet decreases first and then increases with the increase in the internal secondary air ratio; especially, the NOx concentration varies greatly under low boiler loads. The above analyses indicate that the effects of the air rate and air distribution on the NOx formation are very different under variable working conditions. Additionally, the temperature increases in the primary air, the secondary air, and the OFA all lead to the increase in NOx concentration in the furnace, and the influence of the secondary air temperature and the OFA temperature is greater than that of the primary air temperature. Compared with the burning-out zone, the air temperature has a greater influence on NOx formation in the main combustion zone. At high boiler load, the NOx concentration is more affected by the air temperature.
The pulverized coal combustion and NOx formation in the furnace involve the physical and chemical processes, including a series of parallel and continuous reactions, homogeneous and heterogeneous reactions, free radical reactions and molecular reactions. Hence, they are extremely complex and are simultaneously influenced by many factors in the actual operation, and these factors often interact with each other. Their complex characteristics make the experimental research a challenging task, especially under large quantities of variable operating conditions. The experimental research of pulverized coal combustion and NOx formation is usually restricted by many field operational requirements. The numerical simulation of the pulverized coal combustion and NOx formation based on Fluent Software can provide a lot of detailed information in order to obtain the optimum operating conditions and the optimum control strategy. Furthermore, large amounts of simulation data are a new data source for further research on the NOx prediction model at the economizer outlet. It can improve the prediction ability and the generalization ability of the NOx prediction model.